RE 517RP Manual
RE 517RP Manual
Analogue Addressable
Fire Alarm Repeater Panel
Alarm System Limitations
Smoke detectors may not sense fire where smoke cannot reach the detectors such as
in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second-
floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing
chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit
particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the celing or upper
walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detectors.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density
levels are not created by a developing fire at the location of detectors, the detectors
will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photoelectronic sensing chambers tend to detect smoldering fires better than
flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing
chambers tend to detect fast-flaming fires better than smoldering fires. Because fires
develop in different ways and are often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detector may not provide adequate
warning of a fire.
1 RE / DD / UM / 517 - RP V 1.0- 00
Smoke detectors cannot be expected to provide adequate warning of fires caused
by arson, children playing with matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper storage of flammable materials,
etc.).
While a fire alarm system may lower insurance rates, it is not a substitute
for fire insurance!
Heat detectors do not sense particles of combustion and alarm only when heat on
their sensors increases at a predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel
and in rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a
developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication.
A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time and only if the
batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is
essential to use only equipment listed for service with your control panel.
2 RE / DD / UM / 517 - RP V 1.0- 00
required per the manufacturer's recommendations, and UL and NFPA standards. At a
minimum, the requirements of NFPA 72 shall be followed. Environments with large
amounts of dust, dirt or high air velocity require more frequent maintenance. A
maintenance agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as required by National
and/or local fire codes and should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections should be kept.
WARNING – Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and / or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit this manual is read and under stood.
CAUTION – System Reacceptance Test after software changes. To ensure proper
system operation, this product must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software. Re-acceptance testing is
required after any change, addition or deletion of the system components or after any
modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating device that are not
directly affected by the change, upto maximum of 50 devices, must also be tested
and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F
and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer
to manual Specifications section for maximum allowable I.R. drop from the specified
device voltage.
Like all solid state electronic devices, this system may operate erratically or can be
damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences,
proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not
recommended, due to an increased susceptibility to nearby lightning strikes. Consult
with the Technical Services Department if any problems are anticipated or
encountered.
3 RE / DD / UM / 517 - RP V 1.0- 00
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of
the enclosure. When possible, make all cable entries from the sides or rear. Before
making modifications, verify that they will not interfere with battery, transformer, and
printed circuit board location.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon proper installation by
authorized personnel.
DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your
equipment, inspect the contents of the carton for shipping damage. If damage is apparent,
immediately file a claim with the carrier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal
adjustments or repairs. Servicing should be performed by qualified personnel.
follows:
STATIC HAZARD - Static electricity can damage components. Therefore, handle as
• Ground yourself before opening or installing components
• Prior to installation, keep components wrapped in anti-static material at all times.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may cause
interference to radio communications. It has been tested and found to comply with the limits
for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a
commercial environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take whatever
measures may be required to correct the interference.
4 RE / DD / UM / 517 - RP V 1.0- 00
Table of Contents
Chapter 1: Product Description..................................................................7
1.1: Feature ..............................................................................................7
1.2: Specification ………………………………………………………9
1.3: Control and Indication …………………………………………….10
1.3.1: Controls …………………………………………………………10
1.3.2: Indication ………………………………………………………..11
1.3.2.1: LED Indication ………………………………………………..11
1.3.2.2: LCD Indication ………………………………………………..11
1.3.2.3: Local Buzzer …………………………………………………..11
1.4: Circuits …………………………………………………………….12
1.4.1: Main Circuit Board ………………………………………………12
1.4.2: RS 485 IOPort……. ……………………………………………..12
1.4.3: Output Circuit ……………………………………………………12
1.4.4: Relays ……………………………………………………………12
1.5: Components ………………………………………………………..13
1.6: Mechanical Construction ………………………………………….14
5 RE / DD / UM / 517 - RP V 1.0- 00
3.2.1.3: About …………………………………………………………. 35
6 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 1: Product Description
1.1 Features.
32 bit processor Arm Cortex M3.
160 (40X4) character LCD display.
Real Time Clock.
2000 events log.
Network options:
RS 485 Communication for Network/Repeater.
USB 2.0 Interface for PC Connectivity.
GSM Module (Optional).
Printer Interface Module (Optional).
Operates on 120 to 220V AC, 60/50 Hz.
Battery Backup 24VDC with built in Charger.
One programmable form C relay for Fire & Fault, supervisory.
Extensive, built-in transient protection.
Notification appliance Circuits (NACS):
One onboard Class B Style Y NACs.
Programmable Auto Silence.
Programmable Silence Inhibit.
Programmable Synchronized, Temporal, 120 BPM, Steady output.
Programming and Software:
Programmable trouble reminder.
Programmable AC loss delay.
Lamp test.
7 RE / DD / UM / 517 - RP V 1.0- 00
Programmable Relay
NC NO C
Non-supervised Power Limited Primary Source
Power Limited 24V NAC 120/ 220 AC 60/50 Hz
Output
RS 485
Communication
Port
Power Limited
Power Limited
USB 2.0 Port
Figure - 1
8 RE / DD / UM / 517 - RP V 1.0- 00
1.2 Specifications.
Primary Power
120 / 220VAC + 10% -15%, 60 / 50 Hz, Amps.
Standby Power
24V D.C (2 Nos of 12v, 12Ah (Max.) Sealed Lead acid battery)
Operating Condition
Operating Temperature – 0 - 49° C/32-120° F.
Relative Humidity – 93 ± 2% RH (non-condensing) at 32 ±2° C/96 ±3° F.
Charging Circuit
Charging Voltage – 28V, ± 2% Nominal
Charging Current – 0.8A (Max.).
9 RE / DD / UM / 517 - RP V 1.0- 00
1.3 Control and Indications
ANALOGUE ADDRESSABLE
FIRE ALARM REPEATER PANEL RE - 517RP
Control Keys [
Figure – 2
1.3.1. Controls:
ACK. Key:
To mute local buzzer in alarm condition.
To mute local buzzer in Supervisory or fault condition.
User or Admin password protected.
SILENCE Key:
To silence the external NACs in Fire Condition.
User or Admin password protected.
RESET Key:
To reset the Fire alarm or Latched Supervisory condition.
User or Admin password protected.
Possible to access only after silence in alarm condition.
EVACUATE:
To activate External NACs Manually.
User or Admin password protected.
10 RE / DD / UM / 517 - RP V 1.0- 00
CURSOR KEYS:
To move the curse point in the LCD as required.
ENTER Key:
To accept the programmed or edited menu, mode or value in the LCD.
MENU Key:
To enter into the programming Main Menu through the LCD.
TEST Key:
To enter into the Lamp Test mode.
To enter into the self test for individual loop.
ALPHANUMERIC KEYS:
These keys are used for entering the names etc. and numbers.
‘*’ Key is used to go back the previous screen in programming mode.
‘#’ is used for the Back Space / Delete the content.
1.3.2. Indications:
1.3.2.1 LED indication
System On – Green
Mains On – Green
Battery On – Green
NAC Fault – Yellow
System Fault – Yellow
Silenced – Yellow
Fire – Red
Fault – Yellow
Supervisory – Yellow
Alarm – Continuous
Fault – pulse 0.5sec ON and 5sec OFF
Supervisory – pulse 0.25sec ON and 0.25sec OFF
11 RE / DD / UM / 517 - RP V 1.0- 00
1.4 Circuits
The main circuit board provides system control and visual indication control and
contains the system microcontroller, programming part (USB-2.0), non-volatile memory
for system events storages. The main circuit board is used for the critical functions like
programmable logic and timing functions and non critical functions.
The visual display board consists of a series LED’s for common indication of
power, alarm, fault and supervisory. The display board has 40 X 4 characters LCD,
which describes for the system information with real time clock and it helps the user to
program the system options easily. It also contains matrix touch key pad, which helps
the user friendly access.
1.4.4 Relay
One programmable Form-C dry contact relays are provided. This
programmable relay is factory default programmed for alarm. Contacts are rated 2
amps @ 30 VDC and 2 Amps @ 30 VAC.
12 RE / DD / UM / 517 - RP V 1.0- 00
1.5 Components
The main circuit board contains the system CPU, other primary components
wiring interface terminal outputs and RS 485 communication port for networking.
165 mm
USB 2.0 RS 485 O/P RS 485 I/P PROG-RLY3 NAC
AVANI-MB-RP-1.0
A B A B NC NO C _ +
CN 4 +
CN 3 CN 2 CN 1 F1
U7
U6
110 mm
120 mm
AVANI-MB-RP-1.0
F3
RM 1
IN 5
U8
CN 5
F2
CN 8
IN 5 IN 5
CN 6 CN 7
175 mm
Figure - 3
The display board contains the LED display for common indications, zone group
indications and touch key pad.
The power supply gives the power for the main circuit board and for outputs. It is
SMPS type power supply, gives the output for 3 amps max.
13 RE / DD / UM / 517 - RP V 1.0- 00
Figure - 4
1.6 Mechanical Construction
The enclosure of the Panel is constructed by 18 gauge (1.22mm) CRCA sheet
with powder-coated finish. The ∅22.25mm (∅19mm [8No’s] for Indian Std.) 7 no’s of
knockouts are given for cable entry at the top of the cabinet. The lockable hinged
door is provided to access the inside the cabinet. The panel also has sufficient space
to accommodate 2 Nos. of 12v, 12Ah batteries.
Figure - 6
14 RE / DD / UM / 517 - RP V 1.0- 00
TOP SIDE VIEW
Knockout Ø19mm 20.00
90.00
5.00
M4 tapped hole 19.00
30.00
340.00
36.00
20.0 0
10.00
290.00
30.00 30.00
PLAN
Figure - 7
15 RE / DD / UM / 517 - RP V 1.0- 00
Non Power Limited
Cable Entry
CON 2
Power Supply
CON 8
o ntrol Master Board Board
y&C
Displa oa rd
B (AVANI-MB-RP-1.0) (RE-SMPS-4A-R1)
.0)
DI SP-1
I-RP -
( AVAN
Figure – 8
16 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 2: Installation
Verify that wire sizes are adequate for all IDC’s loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device voltage. Adherence to the
following will aid in problem-free installation with long-term reliability:
17 RE / DD / UM / 517 - RP V 1.0- 00
Like all solid-state electronic devices, this system may operate erratically or can be
damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure
to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of
the enclosure. When possible, make all cable entries from the sides or rear. Before
making modifications, verify that they will not interfere with battery, transformer, and
printed circuit board location.
Do not tighten screw terminals more than 1.0168 N-m. Over-tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
Though designed to last many years, system components can fail at any time. This
system contains static-sensitive components. Always ground yourself with a proper
wrist strap before handling any circuits so that static charges are removed from the
body. Use static-suppressive packaging to protect electronic assemblies removed
from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon proper installation by
authorized personnel.
18 RE / DD / UM / 517 - RP V 1.0- 00
2.2 Panel Mounting
Figure – 9
Remove all the Boards before placing the panel in its mounting position. Place
the panel in its mounting position and fix the panel to the wall using the slots of the four
screws. Ensure the enclosure and the inner parts of the panel are given sufficient
protection during installation. Fix the all boards in its position (Refer Figure 24, 25 & 26).
All external cables are to be entered via the 6 numbers of ∅22.25mm and 7 Numbers
of ∅19mm preformed knockouts located at top of the panel.
When the installation of all the cables has been completed, clean the interior of
the enclosure ensuring all masonry debris and drilling swords are removed.
19 RE / DD / UM / 517 - RP V 1.0- 00
2.3 Panel Wiring
20 RE / DD / UM / 517 - RP V 1.0- 00
Power Supply Circuit Board (RE – SMPS – 4A – R1)
Figure – 10
21 RE / DD / UM / 517 - RP V 1.0- 00
Master Board (AVANI – MB – RP-1.0)
RS 485
Communication
Port
Power Limited
Power Limited A B NC NO C +
U7
U6
AVANI-MB-RP
F3
RM 1
IN 5
CN 5
U8 30V D.C
F2
Input
CN 8
IN 5 IN 5
CN 6 CN 7
24V Battery
Input
Figure – 11
22 RE / DD / UM / 517 - RP V 1.0- 00
Field Wiring Diagram
USB 2.0
Connector
RS 485 A
Output B
Programmable Potential Relay
For Fire, Fault, Supervisory Power
Limited outputs.
NC
Program. Contact Rating: Notification Appliance Circuit
Relay NO 2.0A @ 30VDC Class B Style Y
2.0A @ 30VAC End of Line - 4K7 1/2W
Power Factor: 0.6 PN: RE4K7
_
NAC - 2
EOL
(1A) +
Note:
All the field wiring circuits are supervised
All the field wiring circuits are Power limited
except Battery.
Figure – 12
23 RE / DD / UM / 517 - RP V 1.0- 00
2.4 Relays
The one Form – C programmable relay is provided in this FACRP with the contact
rating for 2 Amps @ 24 VDC or 1 Amps @ 120 VAC. The default options for the
Programmable Relay as Fire.
Relay Relay
Relay contacts shown with power applied to Relay contacts shown with power applied to
the panel no active Fire or Gas Release the panel active Fire or Supervisory
If the relay is configured as fault, then it will reverse If the relay is configured as fault, then it will reverse
Figure - 13
Note: The relay connections may be power limited or non – power limited, provided
that 0.25” spacing is maintained between conductors of power limited and non –
power limited circuits.
2.5 NACs
The one programmable, Class B Style Y, supervised NAC is provided with the current
rating of 1 Amps. This NAC (Notification Appliance Circuit) is programmable for the
following options like Continuous, Synchronized, Temporal and 60 BPM.
EOL
Non Polarized
+ Sounder
Polarized
+ Sounder
NAC 1
Figure – 14
24 RE / DD / UM / 517 - RP V 1.0- 00
2.6 UL Power-limited wiring requirements
The power limited and non-power limited circuit wiring must remain separated in
the cabinet. All power limited circuit wiring must remain at least 0.25” (6.35mm) away
from any other non- power limited circuit wiring and non-power limited circuit wiring
must enter and exit the cabinet through different knockouts and/or conduits as shown
in the figure - 8.
Chapter 3: Programming
1. All applicable codes and standards should be considered when the programming
the control unit.
2. The Control Unit continues to monitor inputs circuits and devices and acts according
to the current program settings if and alarm is received wile it is being programmed.
3. Loading a new database erases the current database before loading the new
database. If the new database is not loaded after the erase, the panel will not
operate.
4. The Database must be completely loaded fro it to be considered valid. The
program keeps track if the last database load was valid/complete or not. An invalid
database load disables the panel until a valid database load is done.
The system all normal screen will be displayed in a programmed system with no
active alarms, troubles or supervisory, as illustrated below.
To access the programming or view the status & history, press menu key, which is
shown in LCD as below.
From this menu screen by pressing ‘1’, the panel enters into status/history view
mode. It allows user to view the event and program setting of the control panel. The
password is not required for this feature.
From this menu screen by pressing ‘2’, the panel enters into programming mode
which only can access by the authorized persons. After pressing ‘2’, LCD screen will be
in password prompt. After pressing correct password and by pressing enter key, user
can select the programming options to change it.
From this menu screen by pressing ‘3’, the panel enters into the loop test mode.
In this mode the detectors connected in the loop can check from the panel. It
required admin password.
From this menu screen by pressing ‘4’, the panel shows the about the version
and revision levels.
After completing the wiring of the addressable devices to the SLC, apply power
to the control panel. If the addressable devices are not programmed in the Fire Alarm
Panel, the following trouble message will be displayed.
26 RE / DD / UM / 517 - RP V 1.0- 00
3.1.4 Programming Description
By pressing menu key, the view and program options have multiple functions or
features which may be chosen. To view all of the choices, it is necessary that the
programmer scroll through a number of the additional screen and cursor keys. Refer
“Programming Instruction”, for additional information of the various screens.
The title of the main option screen will always be displayed at bottom right of the sub-
screens. To select the one of the choices in a screen, the programmer presses the
keypad numerical key corresponding to the desired choice.
Note: That sub-screen may also have multiple options which require viewing more
than one screen. The same process, as detailed in the previous paragraph is followed
to view all options.
27 RE / DD / UM / 517 - RP V 1.0- 00
3.2 Programming Instruction
3.2.1 Menu Key Flow Diagram
M ENU USER - 1 to 5
ADM IN - 6
Installer - 9
ADM IN
PASSWORD REQUIRED
1 2 (Default: 6) 3
DD/MM/Y Y <Pane l Sta tus > HH:MM: SS DD/MM/Y Y < Pan el Statu s> HH:MM:SS
1. Suppressed Events 1. Syste m
Ad dr ess able Fir e A lar m Cont ro l Pane l
[Progr am] Rav el, A van i 1. 0 [A bo ut]
1
DD/MM/Y Y <Pane l Sta tus > HH:MM: SS
DD/ MM/Y Y < Pan el Statu s> HH:MM:SS 1 1. Settings
1 . PreA lar m 2. Ad van ced A
2 . Sup ervisory
3 . Fa ults
[Sy stem]
2
DD/MM/Y Y <Pa nel Stat us> HH: MM:SS 1 DD/MM/ YY <Pa nel Sta tus> HH: MM:SS DD/MM/ YY <Pane l Sta tus> H H:MM:SS
1. A ll 1. Da te & Time 1
2. A la rm 2. Ca ption Date : DD / MM / Y Y ( #.Edit )
3. De lete 3. Pass w or d [Se ttin gs] Time : HH : MM : SS [Date / Time]
DD/MM/ YY < Pan el Status > HH:MM:SS DD/ MM/Y Y <Pa nel Statu s> HH:MM:SS
X = 6 - [Ch g AdmPass] X= 1 - 6
DD/MM/ YY <Pa nel Stat us> HH: MM:SS DD/ MM/Y Y <Pa nel Statu s> HH:MM:SS
28 RE / DD / UM / 517 - RP V 1.0- 00
MENU KEY - FLOW DIAGRAM
A
2 Configuration
Password required
Pa ssw ord?
[Pas sw o rd ]
2
Same a s do ne in Us er an d
A d min pa ssw ord c han ge
29 RE / DD / UM / 517 - RP V 1.0- 00
Main Menu
The MENU key navigates the user to view & edit system settings, Features
settings, etc. It also possesses help menu for lamp test and About. By Selecting
Menu key the display shows the options as like below,
3.2.1.1 View
View Option can be accessible by User. By this option user can view
the past history and exiting configuration, however they cannot change
preserved settings. By selecting ‘1’ when in Main menu, the system enters
into View mode and shows the viewing category options as like below,
[View]
30 RE / DD / UM / 517 - RP V 1.0- 00
3.2.1.2 Program
By selecting the number 2 from the main menu screen, the system
enters into program mode. This mode is protected by password and it
requires admin password (Default – 6). In this mode, the panel loop card
configuration, RTC & password settings, to alter the optional features and
to reset the panel for factory setting. After entering into the view mode,
screen will be as below.
3.2.1.2.1 System
By selecting the number 1 from the program screen, the system
enters into panels configuration mode. In this mode, panel settings (RTC,
Caption, and Password), Advanced. After entering into this mode, screen
will be as below.
3.2.1.2.1.1 Settings
By selecting the number 1 from the System screen, the system
enters into panel settings mode. In this mode, Date & Time, caption
and Password are changed by entering into the corresponding
menu. After entering into this mode, screen will be as below.
31 RE / DD / UM / 517 - RP V 1.0- 00
By selecting a number from the list in the system menu,
respected subject relevant configuration alone displayed.
3.2.1.2.1.1.1 Date&Time
By selecting the number 1 from the setting screen, the system
enters into Date & Time settings mode. In this mode, time and date
settings are changed by using ‘#’ key. After entering into this mode,
screen will be as below.
Date : DD/MM/YY
Time : HH/MM/SS [System]
3.2.1.2.1.1.2 Caption
By selecting the number 2 from the system screen, the system
enters into Caption editing mode. In this mode, caption is changed
by using ‘#’ key, maximum 20 characters can entered which will be
display in front screen in system healthy mode. After entering into
this mode, screen will be as below.
3.2.1.2.1.1.3 Password
By selecting the number 3 from the system screen, the system
enters into password change mode. In this mode, the user 1 to 5
and admin password can be changed by selecting corresponding
number, after entering into this mode, screen will be as below.
32 RE / DD / UM / 517 - RP V 1.0- 00
DD/MM/YY <Panel Status> HH:MM:SS
Old Password?
[Chg XXX Pass]
New Password?
[Chg XXX Pass]
Re-New Password?
[Chg XXX Pass]
3.2.1.2.1.2 Advanced
By selecting the number ‘2’ from the system screen, the
system enters into advanced settings mode. It required the
Configuration password. In this mode, the system up gradation like
changing the network address, changing the configuration
password and factory resetting can be done. The default
Configuration password is “9”. After entering into this mode, screen
will be as below.
33 RE / DD / UM / 517 - RP V 1.0- 00
DD/MM/YY <Panel Status> HH:MM:SS
1. Network
2. Chg AdvPass
3. Factory Default [Advanced]
3.2.1.2.1.2.1Network:
By selecting the number 1 from the advanced screen,
the system enters into the network mode. In this mode using
alpha numeric keys the panel address shall be entered. After
entering into this mode, screen will be as shown below.
[ N/W PN L *]
Use Key to go the
Feature
34 RE / DD / UM / 517 - RP V 1.0- 00
3.2.1.2.1.2.3 Factory Default:
By selecting the number 3 from the advanced screen, the
system enters into the factory default setting mode. In this
mode, it gives the warning screen before changing
configuration. After entering into this mode, screen will be as
below.
3.2.1.3 About
It shows the details of the panel by pressing number 4 from the
menu screen. The LCD will show as below. In this screen the model and
software version has shown.
35 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 4 Operating Instruction
4.3 Indications
SYSTEM ON: This LED will glow when the panel is energized by primary and standby
power. This is the only LED glowing in the normal monitoring condition. The LCD Display
as shown below.
DD/MM/YY HH:MM:SS
System Healthy
Ravel Electronics
MAINS ON: It indicates that panel is operated through the mains supply (120 /
220VAC). Whenever the Main Supply (220v A.C) fails, the Mains ON LED will goes to off
condition and it also indicated in LCD with toggle Buzzer tone.
BATTERY ON: It indicates that the battery is connected with the panels and it under
charging. Whenever the backup battery fails, the battery fault LED will goes to off
condition and it also indicated in LCD with toggle Buzzer tone. Similarly the same LED
will blink when the battery voltage goes down below the 21.6v (Battery Low).
SYSTEM FAULT: Glowing of this LED indicates the failure of the CPU.
SILENCED: This LED will glow when the silence key is pressed in fire condition only.
NAC FAULT: Whenever there is any fault in Notification Appliances Circuits like NAC
loop Open / Short / Earth fault, it will be identified by COMMON NAC FAULT LED.
FIRE: This twin fire LED will glow when any one or more of the zones are in fire
condition.
36 RE / DD / UM / 517 - RP V 1.0- 00
SUPERVISORY: This supervisory LED will glow when any one or more of the zones are
in supervisory condition.
FAULT: This fault LED will glow when any one or more of the zones are in fault
condition.
4.4 Buzzer
A piezo buzzer provides separate and distinct sounds for alarm, trouble and
supervisory conditions:
Alarm – Continuous
Fault – pulse 0.5sec ON and 5sec OFF
Supervisory – pulse 0.25sec ON and 0.25sec OFF
Operating Keys
The control keys are located at center of the front sticker and these keys are
touch pad. They are as follows:
SILENCE Key: When the silence key is pressed, after entering the user or admin
password the following will occur:
The silenceable Notification Appliance Circuits will be turned OFF
The Silence LED will be turned ON
Upon the occurrence of a subsequent fire event, Signal Silence is overridden and
the control panel will respond to the new event. The panels connected in the
network shall be silenced from the repeater panel.
RESET Key: When the Reset key is pressed, after entering user or admin password,
the control panel will:
The Reset key is accessible only after silencing in alarm condition. The panels
connected in the network shall be reset from the repeater panel. Any alarm,
supervisory or trouble condition that exists after a system reset, will resound the
system, reactivating normal system activity.
ACK. Key: This key is used to acknowledge the buzzer tone during the fault and fire
condition. This key can be operated with user or admin password. The panels
connected in the network shall be acknowledged from the repeater panel.
37 RE / DD / UM / 517 - RP V 1.0- 00
EVACUATE Key: This key is used to energize the all-external NAC’s without actual
fire, It will operate at user or admin level. Using the silence key NAC output can be
silenced.
ENTER KEY: This key is used to accept the password during silence, reset in Fire
Condition And also used for the Evacuate and wherever requires.
CURSOR KEYS: The cursor keys (Right / Left arrows) are used to move the cursor
point wherever required.
ALPHANUMERIC KEYS: These keys are used for entering the names etc. and
numbers. ‘*’ Key is used to go back the previous screen in programming mode. ‘#’
key is used for the Lamp test in system healthy condition.
MENU KEYS: The menu key is used to get into the program menu to change the
required configurations. It requires password to change the configurations.
To change the other indexed fire event zones which are suppressed use right / left
arrow keys.
Restoral: Silence the NAC’s by appropriate user or admin password. after silencing
the panel will perform the following;
38 RE / DD / UM / 517 - RP V 1.0- 00
When the Fire condition is cleared and Reset key has been pressed after
entering the user or admin password. The Reset is accessed only after silencing the
panel in alarm condition and it also accessed from the repeater panel. The panel
will perform the following after clearing fire and resetting:
DD/MM/YY HH:MM:SS
System Healthy
Ravel Electronics
To change the other indexed supervisory event zones which are suppressed use
right / left arrow keys.
Restoral: When the supervisory condition is cleared and Reset key has been pressed
after entering the user or admin password if the zones are programmed for
latching, the panel will perform the following:
DD/MM/YY HH:MM:SS
System Healthy
Ravel Electronics
39 RE / DD / UM / 517 - RP V 1.0- 00
Note:
If the supervisory mode is selected as resettable, the resetting the zone / SLC
is not required. The zone / SLC is retrieved automatically after clearing the
supervisory condition.
Restoral: When the fault condition is cleared, the panel will perform the following
automatically:
DD/MM/YY HH:MM:SS
System Healthy
Ravel Electronics
Note: The Fault occurred will not affect the other normal functions of
the panel
40 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 5: Networking:
The AVANI can be incorporated into a network including other AVANI panels and
AVANI RP annunciators. Though up to 8 panels and 8 annunciators (Repeater) can
be supported by the network. The network can be setup for single building or
multiple building operations.
AVANI AVANI AVANI
AVANI AVANI
ADD 5 ADD 4
Figure – 20
The basic layout of the network is a single loop (see figure 20). Each panel and
annunciator has a unique ID. The panels work in a peer to peer fashion using token
pass method. This means panel having a lower address takes the token first and it is
broadcast its status. Then token is passed to next addressed panel and so on. The
Information is exchanged over the network by two basic means: a - specific frames
(token pass) which are from one panel to another and 2 – broadcast frame, which
are from one panel to all other.
Note:
1. For correct operation of the network, all panels and annunciators
need to be loaded with same version.
2. When the panels and annunciators are first installed, the panel ID
should not repeat.
Network communication
Information is sent across the network in frames. There are two types of frames:
specific and broadcast. Specific frames are sent from one unit to another.
Broadcast frames are sent from one unit all other.
Specific Frames: Specific frames deal with information generated at one panel and
required at another. It is passed from panel to panel until reaches its destination.
Each panel has a list as to which port to send frames from to reach all other panels
through the fewest number of panels. Since networks will generally have all
communications links running at the same baud rate, this is generally the shortest
time as well.
41 RE / DD / UM / 517 - RP V 1.0- 00
AVANI AVANI AVANI
AVANI AVANI
ADD 5 ADD 4
Figure – 21
If there is a break in the communication (see Figure 21), the panel that can not
back the way it came. If there is single open as shown in the figure 21, the network
would not affect the intended application. If there is more than one open will
affect the network communication, the panels in between two open will not be in
network.
Broadcast Frames
Broadcast frames deal with information that affects the entire network. When a
broadcast frame is created by a panel or annunciator, it is sent out both network
communications port. Each unit in turn will receive the broadcast in one port, act
upon it and pass it on out the other port. Upon reaching the unit that generated
the broadcast frame, that unit then disposes of it. This means that under normal
circumstances, all units will receive a broadcast twice and act upon it twice.
42 RE / DD / UM / 517 - RP V 1.0- 00
RS485 RS485
RS485
Network topology:
FARP-1
RS485
FAP-1 FAP-2 FAP-3
RS485
43
Figure – 23
RS485 RS485 RS485
FARP-2
FAP-4
FAP-6 FAP-5
NOTE:
For Every 1.2Km Cable length RS 485 Repeater should be provided.
RS485 Communication cable should be CAT5E or equivalent.
RE / DD / UM / 517 - RP V 1.0- 00
Chapter 6: Servicing:
MOV 2 MOV 1
F1
R 11
Br2
C10
C3 MOV 3
U5
C23
L1
C4
R A3 R 3
CN 4 +
CN 3 CN 2 CN 1 F1
U7
U6
AVANI-MB-RP
F3
RM 1
IN 5
U8
CN 5
F2
CN 8
IN 5 IN 5
CN 6 CN 7
Figure – 24
44 RE / DD / UM / 517 - RP V 1.0- 00
Mounting position for Display board (RE – AVANI – RP - DISP):
AVANI-RP-DISP
Figure – 25
45 RE / DD / UM / 517 - RP V 1.0- 00
Mounting position for Power supply unit (RE – SMPS – 4A – R1):
CN 4 +
CN 3 CN 2 CN 1 F1
U7
U6
F3
RM 1
IN 5
U8
CN 5
F2
CN 8
IN 5 IN 5
CN 6 CN 7
MOV 2 MOV 1
F1
R 11
Br2
C10
C3 MOV 3
U5
C23
L1
C21 U3
Br1
U1
C4
R A3 R 3
Figure – 26
46 RE / DD / UM / 517 - RP V 1.0- 00
6.2 Lamp Test
The lamp test function done through the sub menu by pressing ‘Test’ key,
system (Panel) is in normal condition. In this mode, all the LED’s are checked
for good condition by glowing all LED’s.
Primary
(power 3A N/A N/A 0.04A 0.4A N/A 15 Min
supply)
Secondary
1.3A 12Ah 10% 0.2A 1.3A 24 Hrs. 5 Min.
(back up)
47 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 7: Battery Calculation
Use Table 6-1 to calculate the total standby and alarm load in ampere hours (AH).
This total load determines the battery size (in AH), required to support the control
panel under the fail of the AC Power Supply. Complete the table 6-1 as follows:
1. Enter the NFPA standby and alarm times (refer to NFPA requirements below).
2. Calculate the ampere-hours fro standby and Alarm, and then sum the standby
and alarm ampere-hours.
3. Multiply the sum by the derating factor of 1.2 to calculate the proper battery
size (in AH).
4. Write the ampere hour requirements on the protected premises lable located
inside the cabinet door.
48 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 8: Wire Requirements
Compatible NAC’s:
49 RE / DD / UM / 517 - RP V 1.0- 00
Chapter 10: Abbreviations
50 RE / DD / UM / 517 - RP V 1.0- 00
RAVEL ELECTRONICS PVT. LTD
No. 150-A, Elec. Indsl. Estate, Perungudi, chennai – 600 096. India
Tel.: 24961004 / 24960825 Fax: 044-4204 9599
Email: [email protected]
Web: www.ravelfire.com
DATE:
TEST CERTIFICATE
We hereby certify that the items details hereon have been manufactured,
inspected and electrically tested to ensure the compliance with ravel products
Serial No.:
51 RE / DD / UM / 517 - RP V 1.0- 00
RAVEL ELECTRONICS PVT. LTD
No. 150-A, Elec. Indsl. Estate, Perungudi, chennai – 600 096. India
Tel.: 24961004 / 24960825 Fax: 044-4204 9599
Email: [email protected]
Web: www.ravelfire.com
WARRANTY CERTIFICATE
Serial No.:
Ravel Electronics warrants each product to be free from defects in material and workmanship.
This obligation is limited to servicing or part returned to the company for that purpose and making good
any parts thereof which shall be within warranty period, returned to the company under a written
intimation and which to the company’s satisfaction to be found defective. The company reserves the
right to decide the workplace for the repair work. The freight for defective material will have to be borne
by the purchaser, and the transit risk for such material will rest with the purchaser.
This warranty will last for a period of 12 months from the date of Invoice of the product from
the factory. The warranty is applicable only if the product is used within its specifications. The warranty
for the replaced components will lapse along with that of the main product.
Authorised Signatory
52 RE / DD / UM / 517 - RP V 1.0- 00
Ravel Electronics Pvt Ltd.,
150A, Electronic Industrial Estate,
Perungudi, Chennai – 600096, India.
Web: www.ravelfire.com
Email: [email protected]
53 RE / DD / UM / 517 - RP V 1.0- 00