TOKY SD8 Sensor Meter
TOKY SD8 Sensor Meter
SD Series controller.
I. Safety Caution
Warning
1)If the fault of the product or abnormal system lead to a serious accident, please set the appropriate circuit protection outside.
Caution
1)This product should not be used in a nuclear plant and medical equipment which associated with human life.
2)Some time,it will happen radio interference when the product uses in home environment.It should take adequate
countermeasures.
3)This product has electric shock protection through improved insulation.And when using the product and connecting,it
subject to compliance with specifications.
4)In order to avoid lighting surge,it should set appropriate surge suppression circuits when the product uses in the
environment where the total cable lengh more than 30 metre.
5)The product uses in disk,and avoid to touch the part of high voltage,please take the necessary measure on the final product.
6)Please observe the precautions in this manual, otherwise there is risk of causing significant harm or accident.
7)Please abserve the regulation when wiring.
8)To prevent to damage the machine and prevent to machine failure, the product is connected with power lines or large capacity input and
output lines and other methods please install proper capacity fuse or other methods of protection circuit.
9)Please don't put metal and wire clastic mixed with this product,otherwise it may lead to electric shock, fire, fault.
10)Please tighten screw torque according to the rules.If not,it may lead to electric shock and fire.
11)In order not to interfere with this products to dissipate heat, please don't plug casing around the cooling vent hole and equipment.
12)Please don`t knock or rub the panel with rigid thing.
13)The readers of this manual should have basic knowledge of electrical,control, computer and communications.
14)The illustration, example of data and screen in this manual is convenient to understand,instead of guaranteeing the result of
the operation.
15)In order to use this product with safety for long-term,regular maintenance is necessary. The life of some parts of the equipments
are by some restrictions, but the performance of some will change for using many years.
16)Without prior notice, the contents of this manual will be change. We hope these is no any loopholes, if you have questions or objections,
please contact us.
2.Cable caution: Current output DC 4 ~ 20mA load < 500Ω,Temperature drift 250PPM
1)Please use specified compensation wire in the place of TC input;Please use insulated TC if the measured device is heated metal.
Communication port RS485 port Modbus-RTU procotol, maximum input:30 units
2)Please use the cable of lesser resistance in the place of RTD input,and the cable(3 wire) must be no resistance difference,but the total
Insulation impedance Input,output,power cabinet>20MΩ
length is within 5m.
ESD IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
3)In order to avoid the effect of noise,please put the input dignal away from meter cable,power cable,load cable to wiring.
4)In order to reduce the power cables and the load power cables on the effect of this product,please use noise filter in the place Pulse traip anti-interference IEC/EN61000-4-4 ±2KV perf.Criteria B
where easy to effect.You must install it on the grounding of the disk if you use the noise filter,and make the wiring to be shortest Lightning surge IEC/EN61000-4-5 ±2KV perf.Criteria B
between noise filter output side and power connectors.Don`t install fuse and switch on the wiring of noice filter output side,otherwise it
Frequency drop IEC/EN61000-4-29 0% ~ 70% perf.Criteria B
will reduce the effect of noise filter.
5)It takes 5s from input power to output.If there is a place with interlocking actions circuit signal,please use timer relay.
Dielectric strength Signal input & output & power 1500VAC 1min,below 60V Low voltage circuit between DC500V,1min
6)Please use twisted pair with a shield for analog output line,to ensure the reliabilty of signal.
Total weight About 400g
7)Please use twisted pair with a shield for remote RS485 communication cable,and deal with the shield on the host side earth,
Material of case The case and panel frame PC/ABS (Flame Class UL94V-0)
otherwise it will reduce the effect of noise filter.
8)This product is not the fuse;please set according to rated voltage 250V,rated current 1A if you need;fuse type:relay fuse. Material of mark PET(F150/F200)
9)Please use the suitable screw force and crimp terminal. Power-off data protection 10 years,times of writing:1 million times
The screw terminal size: M3X8 (with 6.8X6.8 square base) Protection level of panel IP65(IEC60529)
Recommended tightening torque: 0.4N.m Safety Standard IEC61010-1 Overvoltage category Ⅱ,pollution level 2,levelⅡ(Enhanced insulation)
Proper cables:0.25~1.65mm single cable/multiple core cable
10)Please don`t put the Crimp terminal or bare wire part contact with adjacent connector.
2.Signal parameters
2 3
3.Isolation diagram .Operation and Menu Direction
Power supply
1.Operation of normal menu and shielding menu
PRE SET
7 2 3 4 5 PRE SET PRE SET PRE SET PRE SET
SET
No. Symbol Name Function SET
AL1 Alarm 1 indicator light 1st loop alarm output indication,alarm output with light,no alarm output without light PRE PRE
AL2 Alarm 2 indicator light 2nd loop alarm output indication,alarm output with light,no alarm output without light PRE SET PRE SET PRE SET PRE SET
AL3 Alamr 3 indicator light 3rd loop alarm output indication,alarm output with light,no alarm output without light SET
1 PRE
MAX Light of max value when the MAX value indicator light,PV display the max value
PRE
MIN Light of min value when the MIN value indicator light,PV display min value. SET
PRE SET PRE SET PRE SET PRE SET
HOLD Light of hold value when HOLD value indicator light,PV display hold value.
2 SET key Menu/ensure key,switch max/min/current value.
3 Shift key Parameters modify and activate,left shift
4 Add/hold key Increase the flashing value, hold measuring the instantaneous value PRE SET PRE SET PRE SET PRE SET
5 Reduce/reverse key Reduce the flashing value,reverse to browse menu.
6 PV Upper display window Display current/max/min value and parameter symbol,error indication
7 SV Lower display window Display measure unit,parameter and alarm value
PRE SET PRE SET PRE SET PRE SET
.Unit symbol comparision
No. Symbol Unit No. Symbol Unit No. Symbol Unit
0 No 11 N 22 KV PRE SET PRE SET PRE SET PRE SET
1 M 12 W 23 mA SET
2 cm 13 KW 24 A
PRE
3 mm 14 RPM 25 KA
PRE SET PRE SET
4 kg 15 RPS 26 Ω
5 g 16 MPM 27 KΩ
6 mg 17 MPS 28 ℃
7 Mpa 18 Hz 29 ℉ PRE SET PRE SET
8 pa 19 KHz 30 K PRE
9 ba 20 mV
10 mba 21 V SET
4 5
LCK=66 SET SET SET Measured high limit,the setting value must more than
20 FH measured low limit Refer signal sheet page 3 1000/1200
SET 21 PS Display translation correction value -1999~9999 0
PRE PRE PRE
SET PRE PRE SET Displayed value of low-input point, setting corresponding
PRE PRE 22 CAS value of low-input point, press to decrease CAS OFF,FL ~ FH OFF
until CAS= OFF , this function is disabled.
SET SET Displayed value of high-input point, setting corresponding
Press SET key for 3s
23 CAK value of high-input point, press to decrease CAK OFF,FL ~ FH OFF
until CAK= OFF , this function is disabled.
Menu shield function,the specification of function symbol as below:
AL1:AD1,AL1,HY1,AE1,DL1A,DL1B; COMM:BAUD,ADDR,DTC; Password, LCK=01,unit lock; LCK=10,menu lock;
AL2:AD2,AL2,HY2,AE2,DL2A,DL2B; SF1:CAS , CAK , SQRT; 24 LCK LCK=11, unit & menu lock; LCK=33, it can enter class 2 0~9999 0
AL3:AD3,AL3,HY3,AE3,DL3A,DL3B; SF2:DREF,STEP,CJC,RLMR; menu; LCK=5555, it will restore factory setting.
BS:BRL,BRH,OLL,OLH,TEST;
25 SCUT Small Signal Elimination,please refer description of o_SL for details -1999~9999 5
When it display one of function symbol,bottom row will display “Y” or “N” (Y means start the function;N means stop the function)
For example:if the meter have no first alarm circuit,please set the AL1 to “N” and then exit menu. Display of choice.o_SL=0, no function , o_SL=1, measured
But now,the menu and submenu will not display AL1,AD1,HY1,AE1,DL1A,DL1B and the alarm function stop to work. value<FL, display FL; measured value>FH, display FH.
1) In the normal measurement mode and when the MME=Y, press “ ” key can switch the max/min/current value circularly. o_SL=2, measured value< SCUT/FL and display FL;
2) Enter MME, and when it displays “Y” , press “ ” key to restart recording max/min value. 26 o_SL measured value>FH,display FH. o_SL=3,measured 0~3 0
3) In the normal measurement mode,press “ ” key can lock current value,and press again to unlock. value<SCUT, display the min value between FL & SCUT;
4) Before CAS, CAK calibration functions are used, long press “SET” + “ ” (make sure PSB=0). measured value>FH, display FH.
2.Directions of menu Zero value,long press + key to clear the display value,
now,zero value will save on PSb. If you preset the zero value,
No. 27 PSb -1999~9999 0
Menu name Directions Setting range Factory default please long press + key or modify PSb to zero.
1 MME Max/min value record function activiation. Y:start, N:close ,1(Y)
0(N) N (The function is non-effective on temperature signal )
Optional 4types alarm.0:alarm close;L:low limit alarm; 28 MEMO Max/min power failure protection.Y:open, N:Close ,1(Y)
0(N) N
0、L、H、
2 AD1 H:high limit alarm;Int:interval alarm; L linear signal Square root
Int、Out 29 SQRT ,1(Y)
0(N) N
Out:outside the interval
30 STEP Display jumping interval 1~10 1
3 AL1 1st alarm setting value FL~FH 200
31 BRL Analog output low limit FL~FH FL
4 AH1 Scope of setting value for 1st alarm FL~FH 1000
32 BRH Analog output high limit FL~FH FH
5 HY1 1st alarm backlash value 0~1000 1
6 AD2 Optional 4 types alarm,if it is 0,the alarm close 0、L 、H、Int、Out Adjust analog output low limit
H
33 OLL OLL=(preset analog low limit - actual analog low limit)/ -500~1000 0
7 AL2 2nd alarm setting value FL~FH 600 actual analog range*1000
8 AH2 Scope of setting value for 2nd alarm FL~FH 1000
Adjust analog output high limit adjustment
9 HY2 2nd alarm backlash value 0~1000 1
34 OLH OLH=(preset analog high limited - actual analog high limit)/
0~1050 1000
10 AD3 Optional 4 types alarm,if it is 0,the alarm close 0、L 、H、Int、Out H actual analog range *1000+1000
11 AL3 3rd alarm setting value FL~FH 800
35 BAUD Communication baud rate 4.8K、9.6K、19.2K 9.6K
12 AH3 Scope of setting value for 3rd alarm FL~FH 1000
36 ADDR Meter communication address 1~255 1
13 HY3 3rd alarm backlash value 0~1000 1
37 DTC Communication delay time Refer remarks(page 14) 0
Choice of display on botton row:no display, Non、Unit、AL1、 38 AE1 AL1 extensions 0~11 0
14 LDSP Unit
engineering unit,1loop/2loop/3loop alarm value. AL2、AL3
39 AE2 AL2 extensions 0~11 0
filter coefficient of digital filters.
15 FT 1~255 10 40 AE3 AL3 extensions 0~11 0
The higher of value, the greater the filter effect.
41 DL1A AL1 start delay(unit:s) 0~999.9 0.0
16 DREF Display refresh cycles,unit:s 0~5 0
42 DL1B AL1 close delay(unit:s) 0~999.9 0.0
17 DP Decimal location for linear signal 0~3 0
43 DL2A AL2 start delay(unit:s) 0~999.9 0.0
18 INP Input signal types Refer signal sheet page 3 0~10V/K
Measured low limit,the setting value must less than 44 DL2B AL2 close delay(unit:s) 0~999.9 0.0
19 FL measured high limit Refer signal sheet page 3 0/-50
6 7
Alarm extension function table
45 DL3A AL3 start delay(unit:s) 0~999.9 0.0 Alarm mode when show
AE1/AE2/AE3 value over limit Whether restrain alarm when power on Alarm control fineness
46 DL3B AL3 close delay(unit:s) 0~999.9 0.0
0 State invariant Do not inhibit
Thermocouple cold end compensation method, -1(Auto),0(Off), Forced alarm output (As long as it meets the requirement of
auto-compensation, close compensation, manual 1
47 CJC Auto
compensation 1~50 Forced alarm close alarm, alarm output) Alarm control with
2
linear resistance value, useable when linear resistance is highest resolution of
0 3 State invariant Inhibit
48 RLMR high (Unit: mΩ) 0~9999 the meter
(Forced alarm close when power on;alarm
4 Forced alarm output
49 TEST Analog input test, used to test output function FL~FH OFF does not output until the alarm condition
5 Forced alarm close from noncoincidence to coincidence. )
Enable user’ s self-calibration, this parameter is for
50 CAE linear signal only; Y: use the parameter self-calibrated by 0(N),1(Y) N 6 State invariant
Do not inhibit
user; N: don`t use the parameter self-calibrated by user 7 Forced alarm output (As long as it meets the requirement of
User set the low-limit input by themselves; after input alarm, alarm output)
8 Forced alarm close Alarm control with
the low-limit signal, flash display YES, press “ ” to
51 CAL YES/OK YES 9 State invariant Inhibit display resolution
confirm, when it display OK, the input signal low-limit
is set. Forced alarm output (Forced alarm close when power on;alarm
10 does not output until the alarm condition
User set the high-limit input by themselves; after input 11 Forced alarm close from noncoincidence to coincidence. )
the high-limit signal, flash display YES, press “ ” to
52 CAH confirm, when it display OK, the input signal high-limit YES/OK YES
is set. .Dimension
53 VER Software version Unable to set V1.0 Panel Size Side Face Size Mounting Size
ON HY OFF HY ON
Deviation alarm PV
AL AH (A10B)
8 8
1 Read register(0x03)
For example: Host reads integer AL1(AL1=200)
SD7 SD9
The address code of AL1 is 0x3201, because AL1 is integer( 2 dyte), seizes 1 data register. The memory code of decimal integer
200 is 0x00C8.
Note:It should read DP value or confirm DP menu value first to ensure the decimal point postion when reading data,and converse
the reading data to get the actual value. On the contrary ,it should converse the data to corresponding ratio first before writing the
data into meter.
Host request(Read multi-register)
1 2 3 4 5 6 7 8
Data byte Data byte
Function Start ADD Start ADD CRC code CRC code
Meter ADD length length
code High bit Low bit low bit high bit
high bit low bit
Meter ADD Function Data byte Data Data CRC code CRC code
SD80
code number high bit low bit low bit high bit
Address error abnormal answer: (For example, host request address is 0x2101)
Meter ADD Function code Error code CRC code CRC code
(A10B)
low bit high bit
Note: If there is any change, please subject to the drawing on the meter 0x01 0x83 0x02 0xC0 0xF1
2 Write multi-register (0x06)
For example: Host writes AL1(First alarm set value 100)
The address code of AL1 is 0x3201, because AL1 is integer ( 2 dyte), seizes 1 data register. The hexadecimal memory code for decimal
XI. Exclusive methods of simple fault integer 100 is 0x0064.
Display Methods Host request(Write single-register)
Checks whether the input signal connects or not, whether the figure of FH/FL value is too small, whether 1 2 3 4 5 6 7 8
HHHH/LLLL input signal is selected correctly, whether working environment is normal.
Meter ADD Function Data ADD Data ADD Data Data CRC code CRC code
code low bit high big
XII. Communication procotol High bit Low bit High bit Low bit
Meter adopt Modbus RTU communication protocol, RS485 half duplex communication.Read function code:0x03,
write function code 0x06 or 0x10. Adopts 16 digit CRC check, the meter does not return for error check. 0x01 0x06 0x32 0x01 0x00 0x64 0xD7 0x59
Data frame format:
Slave normarl answer(Write single-register)
Start bit Data bit Stop bit Check bit
1 2 3 4 5 6 7 8
1 8 1 No
Abnormal communication processing: Meter ADD Function Data ADD Data ADD Data Data CRC code CRC code
When abnormal response,put 1 on the highest bit of function code. For example: when host request function code is 0x03, slave code High bit Low bit High bit Low bit low bit high big
response function code should be 0x83.
0x01 0x06 0x32 0x01 0x00 0x64 0xD7 0x59
Error code:
0x02---Illegal address: the register address designated by host beyond the address range of meter.
Communication cycle:
Communication cycle is the time from host request to slave response data . ie: communication cycle= time of request data sending
+slave preparation time + response delay time + response return time.
Eg: 9600 Baud rate: communication cycle of single measured data ≥ 250ms.
10 11
Address error abnormal answer:( for example, host request address is 0x2101) 10 0x3104 UNIT Unit setting 2 R/W Refer to symbol table (Page 4)
Collocate with DP value to
Slave answer error code 11 0x3105 PS Translation correct 2 R/W read value
1 2 3 4 5 12 0x3106 CAS limit point display value Set the low input point
setting 2 R/W
corresponding display value
Function CRC code CRC code 13 0x3107 CAK high point display value 2 R/W Set the high input point
Meter ADD Error code setting corresponding display value
code low bit high big
14 0x3108 FT Filter constants 2 R/W 1~255
0x01 0x86 0x02 0xC3 0xA1
15 0x3109 DREF Display refresh cycle 2 R/W Unit: second
3、Write register(0x10)
2 Collocate with DP value to
For example: host writes AL1 (First alarm set value 100) 16 0x310A SCUT Small Signal Elimination R/W read value
Host request(Write register) 17 0x310B Collocate with DP value to
PSb Zero clearing value 2 R/W read value
1 2 3 4 5 6 7 8 9 10 11
18 0x310C oSL Display method option 2 R/W Refer to menu illustration (Page 7)
Meter Function Start ADD Start ADD Data byte Data byte Data byte Data Data CRC code CRC code
code High bit Low bit length length low bit high bit 2 R/W Non(0)、Unit(1)、AL1(2)、
ADD length high bit low bit 19 0x310D LDSP Lower line display content option AL2(3)、AL3(4)
high bit low bit
STEP Display jumping interval Set the minimum step value of
0x01 0x10 0x32 0x01 0x00 0x01 0x02 0x00 0x64 0xB5 0xA9 20 0x310E 2 R/W display change
21 0x310F MME Maximum/minimum value
record function 2 R/W 0:N;1:Y
Slave normarl answer(Write register)
22 0x3110 MEMO Enable power failure memory 2 R/W 0:N;1:Y
1 2 7 4 5 6 7 8
Data byte Data byte 23 0x3111 SQRT Enable linear signal square root 2 R/W 0:N;1:Y
Meter Function Start ADD Start ADD CRC code CRC code
code High bit Low bit length length -1: Auto compensation、0: No
ADD low bit high bit CJC Thermocouple cold end compensation、(1~50) Manual
high bit low bit 24 0x3112 2 R/W
compensation method input cold end temperature
0x01 0x10 0x32 0x01 0x00 0x01 0x5E 0xB1
25 0x3113 RLMR linear resistance value 2 R/W Unit: mOhm
Data location error response:(For example:Host request write ADD index is 0x2100)
Reserve
Slave answer error code
26 AD1 1st loop alarm type 0:no alarm、1:L、2:H、
1 2 3 4 5 0x3200 2 R/W 3:Int、4:Out
27 FL~FH Collocate with DP value
0x3201 AL1 1st loop alarm value 2 R/W to read value
Meter ADD Function Error code CRC code CRC code
code low bit AH1 1st alarm interval high limit value FL~FH Collocate with DP value
high bit 28 0x3202 2 R/W to read value
0x01 0x90 0x02 0xCD 0xC1 29 0x3203 HY1 1st loop alarm backlash value 2 R/W 0~1000 配合 DP 值读数
MAX Maximum measure value 2 R Collocate with DP value to read value AD2 2nd loop alarm type 0:no alarm、1:L、2:H、
2 0x3001 33 0x3207 2 R/W 3:Int、4:Out
3 0x3002 MIN Minimum measure value 2 R Collocate with DP value to read value 2 R/W FL~FH Collocate with DP value
34 0x3208 AL2 2nd loop alarm value to read value
4 0x3003 HOLD Hold measured value 2 R Collocate with DP value to read value 35 2 R/W FL~FH Collocate with DP value
0x3209 AH2 2nd alarm interval high limit value to read value
5 0x3004 STA Output status word 2 R Note①(Page 15) 36 0x320A HY2 2nd loop alarm backlash value 2 R/W 0~1000 Collocate with DP value
to read value
Reserve AE2 2nd loop alarm extended function 2 R/W Refer to alarm extention table
37 0x320B
(Page 9)
6 0x3100 FL Measuring range low limit 2 R/W Collocate with DP value to read
value 38 0x320C DL2A 2nd loop alarm start delay 2 R/W 10 corresponding to 1.0 second
7 0x3101 FH Measuring range high limit 2 R/W Collocate with DP value to read
value 39 0x320D DL2B 2nd loop alarm close delay 2 R/W 10 corresponding to 1.0 second
8 Refer to measure signal parameter
0x3102 INP Input signal type 2 R/W AD3 3rd loop alarm type 2 R/W 0:no alarm、1:L、2:H
table(Page 3) 40 0x320E
Effective for all quantities-related FL~FH Collocate with DP value
9 0x3103 DP Decimal point 2 R/W 41 0x320F AL3 3rd loop alarm value 2 R/W to read value
parameter
12 13
45 0x3213 DL3A 3rd loop alarm start delay 2 R/W 10 corresponding to 1.0 second Note②:DTC communication configuration byte illustration
14 15