Doc No:

META-PLANT1-DD-SWA-
1800-ELE-TDS-2012

Revision : F

EPCC FOR METHANOL EFFLUENT TREATMENT ALLEGIANCE


PROJECT (META) AT PETRONAS CHEMICALS METHANOL Page 1 of 4
SDN. BHD.

PROJECT:
PROVISION OF ENGINEERING, PROCUREMENT, CONSTRUCTION AND
COMMISSIONING (EPCC) FOR METHANOL EFFLUENT TREATMENT
ALLEGIANCE PROJECT (META) AT PETRONAS CHEMICALS METHANOL
SDN. BHD.

COMPANY:
PETRONAS CHEMICALS METHANOL SDN. BHD.

CONTRACT NO.:
RFP-000000059837

DOCUMENT TITLE:
DATASHEET FOR INDUCTION MOTOR
OFFSPEC TRANSFER PUMP MOTOR (GM-18008 A/B)

DOCUMENT REVIEW CLASSIFICATION:


Z

SECURITY CLASSIFICATION:
INTERNAL USE
Digitally signed by Ir.
Devandran P. Nagaiah
Date: 2024.09.06 08:58:34
+08'00'

Issued For AAZ /


F 6-SEP-24 MAD DN
Approval MDS
Issued For MAFZ /
E 19-JUL-24 MAD DN
Approval MDS
Issued For MAFZ /
D 05-JUN-24 MAD DN
Approval MDS
Issued For MAFZ /
C 23-APR-24 MAD DN
Review MDS
Issued For MAFZ /
B 15-FEB-24 MAD DN
Review MDS
Issued For MAFZ /
A 09-JAN-24 MAD DN
Review MDS

© 2024 PETROLIAM NASIONAL BERHAD (PETRONAS). All rights reserved. No part of this document may be reproduced, stored in
a retrieval system or transmitted in any form or by any means (electronic, mechanical, photocopying, recording or otherwise) without
the permission of the copyright OWNER.

Internal Use
For Internal Use - For Internal Distribution Only #

PCMSB META PROJECT


COMMENTS RESPONSE SHEET (CRS)

.
Date: 30-Aug-24
CRS No: META-PLANT1-DD-SWA-1800-ELE-TDS-2012_E-CRS
Rev No: E

Drawing / Document Number, Title and Revision: Transmittal Document Purpose:


Doc. No. META-PLANT1-DD-SWA-1800-ELE-TDS-2012 Title: DATASHEET FOR INDUCTION MOTOR OFFSPEC TRANSFER X CODE 2, ACCEPTED WITH COMMENTS
Rev. No. E PUMP MOTOR (GM-18008 A/B)
Transmittal No META-DD-SWA-PTSSB-TRM-0285

No. Comments Confirmation / Explanation by Contractor

1 Refer Row: 59&60, Reword and dont mentioned VTA. "Certificate of Conformity from IECEx is compulsory" Noted and Incorperated

Prepared by: Approved by:

Name: HAZRUL IZWAN HUSSEIN Name: BADRUNNIZAM B SAIRI


Position: ELECTRICAL Position: PROJECT ENGINEERING

Internal
CLIENT: Requisition No.:
META-PLANT1-DD-SWA-
DATASHEET FOR INDUCTION MOTOR Document No.:
1800-ELE-TDS-2012
Sheet No.: 2 OF 4
Rev. No.: F
ENG BY:
PROVISION OF ENGINEERING, PROCUREMENT, CONSTRUCTION AND Item Tag No.: GM-18008 A/B
COMMISSIONING (EPCC) FOR METHANOL EFFLUENT TREATMENT
ALLEGIANCE PROJECT (META) AT PETRONAS CHEMICALS OFFSPEC TRANSFER
Service:
METHANOL SDN. BHD. PUMP MOTOR

S-703D Data Sheet for


Low Voltage Three Phase Cage Induction Motors
2 Tag No. : GM-18008 A/B
3 Service : OFFSPEC TRANSFER PUMP MOTOR
4 Ref. Cl. IOGP Ref. META SPC Characteristics Additional notes
5 General
6 Manufacturer : VTA
7 Model number : VTA
8 Serial number : VTA
9 Order status : for enquiry
10 Conformity Assessment System (CAS) level : D
11 7.9 Frame size : In accordance with IEC 60072-1
12 and IEC 60072-2
13 Duty
14 4.1, 4.2.1, Duty type : S1 Refer META-PLANT1-DD-SWA-1800-
15 4.2.10, 4.2.2, ROT-TDS-2012
16 4.2.3, 4.2.4,
17 4.2.5, 4.2.6,
18 4.2.7, 4.2.8,
19 4.2.9, 5.1, 5.3,
20 5.5.2
21 Number of poles : VTA
22 Duty point shaft power : VTA kW
23 Direction of rotation : VTA
24 Load drive : VTA
25 11.3.5.3, External radial loading on the motor shaft end : VTA N
26 11.3.5.4
27 11.3.5.3, External axial loading on the motor shaft end : VTA N
28 11.3.5.4
29 Moment of inertia of the load (Jext) : VTA kg·m²
30 Rating
31 11.8.2, 5.5.3, Rated power output : 11 kW
32 5.8
33 Full load current (FLC) : VTA A
34 Site conditions
35 6.1 7.2 Location environment :
36 6.1, 6.2 7.2 Altitude : other m <100m above sea level
37 6.1, 6.3 Maximum ambient air temperature : other °C 34°C
38 6.1, 6.4 Minimum ambient air temperature : other °C 24°C
39 6.6 Transport and storage conditions : within defined site conditions
40 6.6 Standstill period :
41 6.1, 6.3 Maximum relative humidity : other % Design 98%
42 6.8.1 7.7 Motor enclosure ingress protection : IP68
43 6.9 Impact protection : IK08
44 Electrical operating conditions
45 7.4 Motor rated voltage : 380 V
46 7.4 Motor rated frequency : 50 Hz
47 7.3, 9.12.1.3, Maximum operating voltage limit : other % +5 - Note 11
48 7.3, 9.12.1.3, Minimum operating voltage limit : other % -5 - Note 11
49 7.3, Figure 12 Maximum operating frequency limit : other % +2 - Note 11
50 7.3, Figure 12 Minimum operating frequency limit : other % -2 - Note 11
51 7.2.1.1 Power supply quality : as per IEC 60034-1-sect. 7.2.1
52 Thermal performance
53 8.1 7.10 Thermal class : F
54 8.1 7.10 Temperature rise class : B
55 Starting performance
56 9.12.1.1 7.18 Starting designation : N
57 9.5 Pull-up torque : VTA pu of FLT

58 9.12.1.2 Declared locked rotor current tolerance : 20 %


59 9.12.1.2 Declared locked-rotor current at 100% rated voltage : VTA pu of FLC

60 9.12.1.2 Declared locked-rotor current at 80% rated voltage : VTA pu of FLC

61 Table 21 Declared locked-rotor torque at 100% rated voltage : VTA N·m


62 Table 21 Declared locked-rotor torque at 80% rated voltage : VTA N·m
63 Declared locked-rotor power factor at 100% rated voltage : VTA
64 Moment of inertia of the motor (Jm) : VTA kg·m²
65 Maximum permissible starting time at 100% rated voltage : VTA s
66 Maximum permissible starting time at 80% rated voltage : VTA s
67 Data for protection setting/power modelling : Not required
68 Operating performance
69 9.6, Table 18 Rated full load speed : VTA r/min
70 Rated full load torque : VTA N·m
71 Rated breakdown torque : VTA pu of FLT

72 9.14.1, 9.14.2 7.5 Efficiency : IE3


73 9.14.1, 9.14.2 Efficiency at 100% rated output : VTA %
74 Efficiency at 75% rated output : VTA %
75 Efficiency at 50% rated output : VTA %
76 Power factor at 100% rated output : VTA pu
77 Power factor at 75% rated output : VTA pu
78 Power factor at 50% rated output : VTA pu
CLIENT: Requisition No.:
META-PLANT1-DD-SWA-
DATASHEET FOR INDUCTION MOTOR Document No.:
1800-ELE-TDS-2012
Sheet No.: 3 OF 4
Rev. No.: F
ENG BY:
PROVISION OF ENGINEERING, PROCUREMENT, CONSTRUCTION AND Item Tag No.: GM-18008 A/B
COMMISSIONING (EPCC) FOR METHANOL EFFLUENT TREATMENT
ALLEGIANCE PROJECT (META) AT PETRONAS CHEMICALS OFFSPEC TRANSFER
Service:
METHANOL SDN. BHD. PUMP MOTOR

S-703D Data Sheet for


Low Voltage Three Phase Cage Induction Motors
2 Tag No. : GM-18008 A/B
3 Service : OFFSPEC TRANSFER PUMP MOTOR
4 Ref. Cl. IOGP Ref. META SPC Characteristics Additional notes
5 Noise
6 9.13.1, 9.13.2 Purchaser maximum permissible noise limit : as per IEC 60034-9 db(A)
7 9.13.1, 9.13.2 Maximum declared motor sound power level at no-load : VTA db(A)
8 9.13.1, 9.13.2 7.11 Maximum expected motor sound power level at full load : 77 db(A)
9 9.13.1, 9.13.2 Noise level test of one motor from this order batch : No
10 Machine construction
11 Motor weight : VTA kg
12 Stainless steel fixings : VTA
13 Rotor
14 11.3.2.2 Maximum vibration magnitude : grade A
15 Fan
16 11.3.3.1 8.3.2 Fan impeller material : steel fan Note 13
17 11.3.3.2 8.2, 8.3.2 Fan direction of rotation : VTA In the direction of the driven equipment -
18 Note 4
19 Terminal box
20 8.1 Location : Top Rotatable in 90 deg. Increments
21 6.8.1 7.7 Ingress protection of all terminal box(es) : IP68
22 11.3.4.3, Line conductor terminal box cable gland entries : TBC Suitable for Zone 2 Area
23 11.3.4.5
24 Line conductor cross-section area : TBC mm²
25 8.1 Large terminal box : not required unless advised by VENDOR - Note 7
26 Bearings
27 11.3.5.1, D-end bearing type : VTA
28 11.3.5.3
29 11.3.5.1, N-end bearing type : VTA
30 11.3.5.3
31 11.3.5.2 Internal clearance : C3
32 11.3.5.1 Lubrication specification : VTA
33 Space heaters
34 11.3.6.1 8.4 Heater requirement : Space Heater is required for motor rated
Not Required
35 75kW and above
36 11.3.6.2 Supply voltage : 200-240 V
37 11.7.2 8.4 Separate terminal box : required
38 11.3.6.5 14.0 Warning label language : English
39 Mounting
40 11.4.1, 11.4.2 7.9 Mounting arrangement : VTA
41 Cooling
42 11.5 7.8 Cooling method : VTA
43 Vibration
44 11.3.5.5 Vibration monitoring : none
45 11.3.2.1, Vibration level test report : required
46 11.3.2.2
47 Shock pulse monitoring connection : VTA
48 Surface protection
49 11.6.1, 11.6.2 Surface protection corrosivity category : C4
50 11.6.3 Surface protection durability category : medium (M) 7 to 15 years, high
51 (H) 15 to 25 years
52 Surface finish : manufacturer's standard Note 12
53 7.22 Paint colour : other Standard Mid Green (14E 53) - Note 7
54 Temperature monitoring
55 11.7.1, 11.7.2 7.23 Winding temperature detection : PTC - see comment VENDOR may propose his standard
56 protection elements
57 Motors intended for use in potentially explosive atmospheres
58 7.12 Motor to be rated for use in potentially explosive atmosphere: no Note 10
59 15.1.1, 15.1.2 7.3, 14.0 Hazardous area equipment certifying body : IECEx Certificate of conformity is required - To
60 accept IECEx certificate ONLY
61 15.1.1, 15.1.3 Temperature group : T3 VTA - Note 10 F
62 15.1.1, 15.1.3 Gas group : IIA VTA - Note 10
63 15.1.2, 15.1.3 Equipment protection level : EPL Gc VTA - Note 10
64 15.1.4, 15.2.1 Motor classification : Ex ec VTA - Note 10
65 Miscellaneous
66 Provision for IoT hardware installation : not required
67 Area Classification non-hazardous Note 10
68 Origin VTA
69
70
71
72
73
74
75
76
77
78
CLIENT: Requisition No.:
META-PLANT1-DD-SWA-
DATASHEET FOR INDUCTION MOTOR Document No.:
1800-ELE-TDS-2012
Sheet No.: 4 OF 4
Rev. No.: F
ENG BY:
PROVISION OF ENGINEERING, PROCUREMENT, CONSTRUCTION AND Item Tag No.: GM-18008 A/B
COMMISSIONING (EPCC) FOR METHANOL EFFLUENT TREATMENT
ALLEGIANCE PROJECT (META) AT PETRONAS CHEMICALS OFFSPEC TRANSFER
Service:
METHANOL SDN. BHD. PUMP MOTOR

S-703D Data Sheet for


Low Voltage Three Phase Cage Induction Motors
2 Tag No. : GM-18008 A/B
3 Service : OFFSPEC TRANSFER PUMP MOTOR
4 Notes
5 1. This data sheet shall be used in conjunction with IEC-60034, the supplementary requirements specification IOGP S-703, information requirements specification IOGP S-703L and
6 quality requirements specification IOGP S-703Q which together comprise the full set of specification documents.
7 2. VTA - VENDOR to advise
8 3. TBC - To be confirmed
9 4. Unidirectional fans shall have an engraved arrow for permanent indication on the direction of rotation.
10 5. The internal and external surface finish of the machines shall provide adequate protection against corrosion under the specified site conditions. Additional and special treatments such
11 as tropical treatment, etc. may be required and specified in the requisition.
6. Refer Datasheet for Offspec Transfer Pump (G-18008 A/B), Doc No: META-PLANT1-DD-SWA-1800-ROT-TDS-2012.
12
7. Refer Specifications for Induction Motor, Doc No: META-PLANT1-DD-SWA-1800-ELE-SPC-0005.
13
8. Refer Specification for Submersible Pump (CWA12), Doc No: META-PLANT1-DD-SWA-1800-ROT-SPC-2006.
14
9. Refer Specification for VSD, Doc No: META-PLANT1-DD-SWA-1800-ELE-SPC-0006.
15 10. Refer Hazardous Area Classification, Doc No: META-GEN-DD-SWA-0-PSM-HZA-0001.
16 11. Refer Electrical Design Basis, Doc No: META-GEN-DD-SWA-0-ELE-DES-0001.
17 12. The internal and external surface finish of the machines shall provide adequate protection against corrosion under the specified site conditions. Additional and special treatments
18 such as tropical treatment, etc. may be required and specified in the requisition.
19 13. Treated with a corrosion resistance coating. Aluminum material not accepted.
20 14. IECEx Certification is required for any Ex Equipment.
21
22 F
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78

You might also like