Allied Engineering & Services (Pvt.) Ltd.

21/2, Sector No. 22, korangi Industrial Area, Karachi-74900, G.P.O. Box 940, Karachi-74200

UAN: 111 250 250 Tel: 35066901-13 Fax: 35066915, 35066916

Email: [email protected] Website:www.aesl.com.pk

FIELD SERVICE REPORT


CUSTOMER RELIANCE WEAVING MILLS LTD. SITE ADDRESS C-1 FIRST FLOOR HASSAN ARCADE MULTAN

2024-09-19 FIELD REPAIR SHOP REPAIR

Hour Millage Time Travel


Time Time on Time off Hour
Service Men Worked Time On Time Off
Depart Site Site Out Return Worked
HH:MM Out Return
HH:MM HH:MM
MUHAMMAD
09:37 AM 10:20 AM 05:25 PM 07:01 36 KM 36 KM 00:33
ANSAR ALI
Shymayam
09:37 AM 10:20 AM 05:25 PM 07:01 36 KM 36 KM 00:33
Tariq

THE FOLLOWING SMS DETAILS ARE REQUIRED FOR EACH SEPARATE INCIDENT

WORK ORDER No. REPORT DATE MODEL SERIAL NO. HOURS

FO5844 2024-09-19 G3520H GFP00180 23727

PART CAUSING FAILURE QTY DC GROUP NO. OPERATIONAL COMMENTS

1- CUSTOMER COMPLAINT

Maintenance and service (2000 Hrs)

2- DETAILS OF FAILURE INCLUDING CONSEQUENTLY DAMAGE

Genset is overdue for Topend Overhauling.


Advised customer to please follow CAT recommended preventive maintenance schedule for safe operation.

3- BRIEF DETAILS OF REPAIR METHOD

1- Visited site genset found stopped as standby.


2- Carried out walk around inspection, started for warmup & saved ET parameters.
3- Stopped genset & performed 2000 hrs PMS as per CAT specs.
4- Removed tappet covers & ignition Transformers.
5- Checked/adjusted valve Bridges,valve lash & HLA settings of all intake and exhaust valves as per CAT specs.
6- Recorded valve recession of all intake and exhaust valves.
7- Inpected engine air intake & exhaust system found satisfactory.
08- Cleaned main alternator, breathers & inspected couplings (generator + PMG) found normal.
09- Greased ( CAT Grease) main alternator both end bearings.
*Electrical Activity*
10- Checked Exciter stator- rotor Gap up. 0.036", Dn. 0.029", L. 0.035", R. 0.037".
11-Perform Insulation Resistance test of main stator(250V): 740 M ohm (30 sec) and 1724M ohm (60sec).
12-Checked ignition transformers resistance found 35K ohm. Cleaned with contact cleaner.
13- Checked/cleaned all harnesses and connectors found ok.
14- Checked/cleaned bus bar, CT condition, and connection wire.
15- Checked rectifier assembly found ok.
16- Checked control breakers and wire condition found ok.
17- Checked starting motor connection, SMR, and SMR fuses found ok.
18- After completed all jobs, the genset tested only offload due to load unavailability found normal parameters.
19- Nox sensor couldn't be calibrated due to load unavailability.

4- CAUSE OF FAILURE

5- CUSTOMER COMMENTS

Please rectify the parameters issue on Enercon HMI after last flasfile activity by AESL.
We will share load data as load available in couple of days.

JOB COMPLETED: Yes

CUSTOMER SIGNATURE SIGNATURE (FIELD. SERVICEMAN)


Distribution: 1. Original (White) Region

Blue- Customer
NAME: Hammad Mustafa
Pink- G.O. Service
DESIGNATION: Plant Manager