Controller Modes
Controller Modes
1 Introduction
Two-Position (ON/OFF) Controller
Introduction
The relation shows that when the measured value is less than the
setpoint (i.e. ep > 0), the controller output will be full (i.e. 100%)
when the measured value is more than the setpoint (i.e. ep < 0),
the controller output will be zero (i.e. 0%).
Introduction
Two-Position (ON/OFF) Controller
Temperature control
Neutral Zone
Neutral Zone: In practical implementation of the two-position con-
troller, there is an overlap as ep increases through zero or decreases
through zero. In this span, no change in the controller output occurs
which is illustrated in the Fig. below.
Introduction
Two-Position (ON/OFF) Controller
Implementation
we can design an electronic controller for two position (On-OFF)
controller using both comparator and schmitt trigger
Continuous Controller Modes
For some range of errors about the setpoint, each value of error has
unique value of controller output in one-to-one correspondence.
Low gain (G2) leads to slow response, but wide band of errors within
which output is not saturated.
Continuous Controller Modes
Proportional Control Mode
PB = 100/Kp
Offset: The characteristic of the proportional control mode is that
it produces a permanent residual error in the operating point of the
controlled variable when a load change occurs and is referred to as
offset.
Implementation
If the error makes random excursions above and below zero, the net
sum will be zero, so the integral action will not contribute.
where p(0) = controller output when the integral action starts (%)
KI = Integral gain (s −1 )
The derivative mode must be used with great care and usually with
a small gain, because a rapid rate of change of error can cause very
large, sudden changes of controller output and lead to instability.
Continuous Controller Modes
Derivative Control Mode
Implementation