IEEE POWER ENGINEERING SOCIETY

Power System Analysis, Computing and Economics Committee

Chair Vice Chair Secretary


MARTIN L. BAUGHMAN CHEN-CHING LIU ROGER C. DUGAN
Professor Emeritus Dept. of Electrical Eng. Sr. Consultant
The University of Texas at Austin University of Washington Electrotek Concepts, Inc.
5703 Painted Valley Drive Box 352500 408 N Cedar Bluff Rd
Austin, TX 78759 Seattle, WA 98195 Knoxville, TN 37923
Vox: 512-345-8255 Vox: 206-543-2198 Vox: 865-470-9222
Subcommittee Chairs Fax: 512-345-9880 Fax: 206-543-3842 Fax: 865-470-9223
Computer & Analytical Methods [email protected] [email protected] [email protected]
EDWIN LIU, Chair
Nexant, Inc.
101, 2nd street, 11F
San Francisco CA 94105
Vox: 415-369-1088
Fax: 415-369-0894
[email protected]

Distribution Systems Analysis


Distribution System Analysis Subcommittee
SANDOVAL CARNEIRO, JR, Chair
Dept. of Electrical Engineering
Federal Univ. of Rio de Janeiro
Rio de Janeiro, RJ, Brazil
Vox: 55-21-25628025
Fax: 55-21-25628628
[email protected]

Intelligent System Applications


DAGMAR NIEBUR, Chair
Department of ECE
Drexel University

IEEE 4 Node Test


3141 Chestnut Street
Philadelphia, PA 19104
Vox: (215) 895 6749
Fax: (215) 895 1695
[email protected]

Reliability, Risk & Probability


Applications
JAMES D. MCCALLEY, Chair
Iowa State University
Feeder
Room 2210 Coover Hall
Ames, Iowa 50011
Vox: 515-294-4844
Fax: 515-294-4263
[email protected]

Systems Economics
ROSS BALDICK, Chair
ECE Dept. , ENS 502
The University of Texas at Austin
Austin, TX 78712
Vox: 512-471-5879
Fax: 512-471-5532
[email protected]

Past Chair
JOANN V. STARON
Nexant Inc/ PCA
1921 S. Alma School Road
Suite 207
Mesa, AZ 85210
Vox: 480-345-7600
Fax: 480-345-7601
[email protected]

The Institute of Electrical and Electronics Engineers, Inc.


IEEE 4 Node Test Feeder

The system to be use in testing transformer models is shown in Figure 1:

Figure 1 – IEEE 4 Node Test Feeder

Both the primary line (Node1-Node 2) and the secondary line (Node 3-node4) will be
constructed using the pole configuration shown in Figure 2.

Figure 2 – Pole Configuration

Phase Conductor: 336,400 26/7


GMR = 0.0244 ft., Resistance = 0.306 Ω/mile, Diameter = 0.721 inch

Neutral Conductor: 4/0 6/1 ACSR


GMR = 0.00814 ft., Resistance = 0.492 Ω/mile, Diameter = 0.563 inch

The Institute of Electrical and Electronics Engineers, Inc.


The source is a 12.47 kV line-to-line infinite bus.

Three-Phase Transformer Data:

Connection kVA kVLL- kVLL-low R - X-


high % %
Step-Down 6,000 12.47 4.16 1.0 6.0
Step-Up 6,000 12.47 24.9 1.0 6.0

Open Wye – Open Delta:


(Two Single Phase Transformers Each Rated)

Connection kVA kV-high kV-low R- X-


% %
Step-Down 2000 7.2 4.16 1.0 6.0
Step-Up 2000 7.2 24.9 1.0 6.0

Closed Connections Load Data:

Balanced Unbalanced
Phase-a
kW 1800 1275
Power Factor 0.9 lag 0.85 lag
Phase-b
kW 1800 1800
Power Factor 0.9 lag 0.9 lag
Phase-c
kW 1800 2375
Power Factor 0.9 lag 0.95 lag

Open Connection Load Data:

Balanced Unbalanced
Phase-a
kW 1200 850
Power Factor 0.9 lag 0.85 lag
Phase-b
kW 1200 1200
Power Factor 0.9 lag 0.9 lag
Phase-c
kW 1200 1583.33
Power Factor 0.9 lag 0.95 lag
Line Impedances

4-wire configuration:

Phase impedance matrix:

 0.4576 1.078j 0.1559 0.5017j 0.1535 0.3849j


zy   0.1559 0.5017j 0.4666 1.0482j 0.158  0.4236j  /mile
 
 0.1535 0.3849j 0.158  0.4236j 0.4615 1.0651j

Sequence impedances:
zypos  0.3061 0.627j /mile

zyzero  0.7735 1.9373j /mile

Three wire configuration:

Phase impedance matrix:

 0.4013 1.4133j 0.0953 0.8515j 0.0953 0.7266j


zd   0.0953 0.8515j 0.4013 1.4133j 0.0953 0.7802j /mile
 
 0.0953 0.7266j 0.0953 0.7802j 0.4013 1.4133j

Sequence impedances:

zdpos  0.306  0.6272j /mile

zdzero  0.5919 2.9855j /mile


Solutions
Step-Down with Balanced Loading

Standard 30 degree connections are assumed for wye-delta and delta-wye banks

V1 = Vag for wye connections and Vab for delta connections


V2 = Vbg for wye connections and Vbc for delta connections
V3 = Vcg for wye connections and Vca for delta connections

Connection Gr Y - Gr Y Gr Y -D Y-D D - Gr Y D-D Open Y-D


Node-2
V1 7106.6/-0.3 7117.9/-0.3 7111.6/-0.3 12378.0/30.0 12381.4/30.0 6988.5/0.4
V2 7139.7/-120.3 7137.8/-120.4 7132.1/-120.5 12386.5/-90.2 12392.2/-90.2 7175.7/-121.6
V3 7120.8/119.6 7129.6/119.6 7123.1/119.6 12357.8/149.9 12366.1/149.9 7287.7/120.5
Node-3
V1 2247.3/-3.7 3931.6/-3.6 3905.5/-3.5 2257.8/33.4 3947.9/26.7 3718.1/-1.2
V2 2268.4/-123.5 3940.4/-123.6 3914.6/-123.6 2270.7/-153.1 3952.0/-93.4 4095.9/-126.3
V3 2255.8/116.4 3935.6/116.3 3909.1/116.3 2267.0./86.6 3943.1/146.6 3615.4/110.9
Node-4
V1 1917.7/-9.1 3601.7/-4.5 3437.0/-7.8 1930.0/-38.7 3619.2/25.8 3496.1/-1.6
V2 2061.1/-128.3 3658.6/-125.9 3496.6/-129.3 2062.3/-158.0 3671.4/-95.7 3907.0/-127.8
V3 1980.7/110.9 3555.2/114.0 3388.1/110.1 1995.2/81.2 3564.0/144.4 3366.7/109.0
Current 1-2
Ia 347.9/-34.9 320.5/-31.3 335.8/-34.7 333.4/-35.3 319.3/-31.0 369.4/-62.9
Ib 323.7/-154.2 320.6/-151.3 336.0/-154.6 331.3/-153.7 319.3/-151.0 374.9/-122.9
Ic 336.8/85.0 320.6/88.7 335.9/85.3 339.9/85.9 319.5/89.0 0
Current 3-4
Ia 1042.9/-34.9 960.8/-61.3 1006.7/-64.7 1036.3/-64.6 957.3/-31.0 639.3/-62.9
Ib 970.4/-154.2 960.8/178.7 1006.8/175.4 969.8/176.2 957.3/-151.0 644.8/177.8
Ic 1009.8/85.0 961.2/58.7 1007.3/55.3 1002.4/55.3 957.7/89.0 648.9/57.1

Only the ungrounded wye-delta bank will have a difference between LG and LN voltages

Node-2 Y-D
VAN 7115.2/-0.3
VBN 7130.9/-12.3
VCN 7120.9/119.6

VNG 3.6/169.8
Step-Down with Unbalanced Loading

Standard 30 degree connections are assumed for wye-delta and delta-wye banks

V1 = Vag for wye connections and Vab for delta connections


V2 = Vbg for wye connections and Vbc for delta connections
V3 = Vcg for wye connections and Vca for delta connections

Connection Gr Y - Gr Y Gr Y -D Y-D D - Gr Y D-D Open Y-D


Node-2
V1 7163.7/-0.1 7116.8/-0.2 7111.1/-0.2 12377.8/29.9 12385.8/30.0 6957.4/0.6
V2 7110.5/-120.2 7149.3/-120.4 7143.6/-120.4 12365.0/-90.1 12403.1/-90.2 7184.1/-121.9
V3 7082.1/119.3 7119.0/119.5 7111.1/119.5 12370.3/149.9 12353.3/149.8 7304.9/120.6
Node-3
V1 2305.4/-2.3 3920.4/-2.9 2896.0/-2.8 2297.8/-32.2 3938.6/27.3 3652.0/-0.3
V2 2256.5/-123.6 3996.0/-123.8 3971.8/-123.6 2267.1/-153.5 4004.6/-93.6 4145.5/-127.2
V3 2202.8/114.8 3907.1/115.7 3874.8/115.7 2225.9/85.5 3916.7/146.0 3513.2/109.0
Node-4
V1 2174.8/-4.1 3604.3/-3.2 3425.1/-5.8 2163.6/-34.0 3623.5/27.1 3437.8/-0.2
V2 1929.6/-126.8 3760.8/-126.8 3646.0/-130.3 1941.6/-156.8 3770.7/-96.6 3984.9/-129.3
V3 1832.7/102.8 3483.9/112.7 3297.3/108.6 1867.2/73.9 3494.9/143.1 3227.3/106.5
Current 1-2
Ia 230.1/-35.9 296.2/-38.1 309.8/-41.7 284.8/-27.3 343.6/-37.1 409.6/-71.0
Ib 345.8/-152.6 301.0/-141.8 315.6/-145.2 399.5/-149.3 270.3/-149.3 422.0/-115.9
Ic 455.0/84.7 368.6/89.5 387.2/85.9 346.8/74.9 347.5/96.9 0
Current 3-4
Ia 689.7/-35.9 1033.6/-67.4 1083.9/-71.0 693.3/-65.8 1030.0/-37.1 708.9/-71.0
Ib 1036.5/-152.6 813.2/-179.6 850.0/177.0 1030.1/177.4 810.4/-149.3 550.5/178.6
Ic 1364.0/84.7 1045.9/66.6 1098.8/63.1 1338.9/55.7 1041.8/96.9 730.3/64.1

Only the ungrounded wye-delta bank will have a difference between LG and LN voltages

Node-2
VAG 7115.4/-0.3
VBG 7142.0/-120.4
VCG 7108.5/119.5

VNG 7.3/171.8
Step-Up with Balanced Loading

Standard 30 degree connections are assumed for wye-delta and delta-wye banks

V1 = Vag for wye connections and Vab for delta connections


V2 = Vbg for wye connections and Vbc for delta connections
V3 = Vcg for wye connections and Vca for delta connections

Connection Gr Y - Gr Y Gr Y -D Y-D D - Gr Y D-D Open Y-D


Node-2
V1 7126.2/-0.3 7126.1/-0.3 7126.3/-0.3 12389.4/29.9 12389.5/29.9 7000.7/0.3
V2 7145.0/-120.3 7144.7/-120.3 7144.6/-120.3 12400.1/-90.2 12400.2/-90.2 7182.7/-121.5
V3 7137.2/119.6 7137.5/119.6 7137.4/119.6 12376.2/149.9 12376.3/149.9 7280.3/120.5
Node-3
V1 13674.5/-3.3 23748.2/56.7 23696.7/-3.3 13730.6/26.9 23783.5/26.9 22433.8/-1.3
V2 13714.3/-123.4 23723.7/-63.4 23744.8/-123.3 13743.8/-93.2 23807.0/-93.2 24604.6/-125.9
V3 13697.5/-3.3 23700.1/176.7 23720.3/116.6 13714.6/146.8 23759.1/146.8 21942.1/111.4
Node-4
V1 13630.0/-3.5 23698.1/56.6 23630.8/-3.4 13686.4/26.8 23733.6/26.9 22399.2/-1.3
V2 13681.7/-123.5 23681.1/-63.5 23686.3/-123.5 13711.3/-93.3 23764.5/-93.2 24575.2/-125.9
V3 13660.3/116.5 23642.4/176.6 23646.8/116.4 13677.4/146.7 23701.7/146.8 21903.3/111.3
Current 1-2
Ia 293.0/-29.3 292.2/-29.3 292.4/-29.3 291.7/-29.1 291.4/-29.0 346.5/-61.2
Ib 291.9/-149.3 292.2/-149.3 292.4/-149.3 291.7/-149.1 291.4/-149.0 349.6/-121.3
Ic 292.3/90.6 292.2/90.7 292.4/90.7 291.6/90.9 291.4/91.0 0
Current 3-4
Ia 146.7/-29.3 146.3/0.7 146.4/-59.3 146.1/1.0 146.0/-29.0 1002./-61.2
Ib 146.2/-149.3 146.3/-119.3 146.4/-179.3 145.9/-119.1 146.0/-149.0 100.8/179.2
Ic 146.4/90.6 146.3/120.7 146.4/60.7 146.2/120.9 146.0/91.0 101.1/58.7

Only the ungrounded wye-delta bank will have a difference between LG and LN voltages

Node-2
VAN 7129.4/-0.3
VBN 7143.3/-120.3
VCN 7135.6/119.6

VNG 3.1/174.9
Step-Up with Unbalanced Loading

Standard 30 degree connections are assumed for wye-delta and delta-wye banks

V1 = Vag for wye connections and Vab for delta connections


V2 = Vbg for wye connections and Vbc for delta connections
V3 = Vcg for wye connections and Vca for delta connections

Connection Gr Y - Gr Y Gr Y -D Y-D D - Gr Y D-D Open Y-D


Node-2
V1 7160.9/-0.1 7119.9/-0.4 7125.7/-0.2 12394.1/30.0 12393.5/30.0 6973.6/0.5
V2 7120.2/-120.3 7146.9/-120.3 7155.5/-120.4 12409.3/-90.2 12410.6/-90.2 7193.4/-121.8
V3 7127.5/119.2 7149.8/119.5 7128.9/119.5 12365.2/149.8 12365.8/149.8 7293.9/120.5
Node-3
V1 13838.7/-2.1 23704.7/57.2 23646.6/-2.8 13828.0/27.9 23742.1/27.5 22096.3/-0.6
V2 13662.0/-123.3 24041.5/-63.6 24054.2/-123.5 13754.6/-93.2 24099.9/-93.3 24904.4/-126.6
V3 13654.6/115.1 23578.4/176.1 23591.3/116.0 13678.7/145.7 23639.5/146.3 21477.3/109.7
Node-4
V1 13814.7/-2.2 23656.8/58.2 23580.8/-2.9 13804.1/27.9 23694.4/27.4 22062.9/-0.6
V2 13613.5/-123.4 24006.0/-63.7 24009.0/-123.7 13706.2/-93.3 24064.4/-93.4 24879.7/-126.7
V3 13614.4/114.9 23514.8/176.0 23510.7/115.8 13638.5/145.5 23576.0/146.2 21433.4/109.6
Current 1-2
Ia 216.8/-34.0 333.2/-28.1 269.5/-35.4 308.5/-34.9 31.3/-34.5 379.2/-68.5
Ib 293.3/-149.2 269.4/-155.3 274.4/-139.7 248.9/-146.2 247.3/-146.9 387.8/-114.0
Ic 366.6/96.7 274.1/100.3 333.6/91.7 318.4/98.3 315.4/99.0 0
Current 3-4
Ia 108.6/-34.0 156.3/-4.7 156.4/-64.8 108.7/-3.9 155.9/-34.5 109.7/-68.5
Ib 146.9/-149.2 124.2/-117.1 124.3/-117.2 145.9/-119.1 123.9/-146.9 85.8/-179.7
Ic 183.6/96.7 158.3/128.8 158.5/68.7 183.3/127.3 158.0/99.0 112.1/66.0

Only the ungrounded wye-delta bank will have a difference between LG and LN voltages

Node-2
VAN 7129.3/-0.2
VBN 7156.8/-120.4
VCN 7126.9/119.5

VNG 3.7/177.3