Hoe Opman en
Hoe Opman en
X EN Door control
BK 150 FUE - 1 / AK 500 FUE - 1
FR Commande de porte
BK 150 FUE - 1 / AK 500 FUE - 1
NL Deurbesturing
BK 150 FUE - 1 / AK 500 FUE - 1
PT Comando do portão
BK 150 FUE - 1 / AK 500 FUE - 1
2.1 General description and intended use 2.2 Qualification of personnel 2.4 General safety instructions 2.5 Safety instructions for operation
The device described below consists of an electronic control for Only qualified and instructed personnel may fit, operate and • In addition, also observe the generally applicable statutory • Before actuating the door, make sure that no persons or
motor-operated doors used for industrial or commercial purposes maintain the industrial door. regulations and other binding regulations for accident objects are located in the door‘s area of travel.
in accordance with EN 13241. The control was designed for the prevention and environmental protection, country-specific • Do not reach into the guide or guide area while the door is in
Before commencing work the assigned personnel must have read
operation of an asynchronous motor with a performance range of regulations, and the recognised specialist technical rules for operation.
these instructions, particularly section 2.
up to 1.5 kW with a 230 V power supply. Due to the complete safe and competent working must be observed. Before • Only actuate the industrial door if it is safe and functional. All
integration of a frequency converter power amplifier, the door can For safety reasons, specify distinct responsibilities for operation, beginning work, instruct personnel in accordance with these protective devices and safety-related devices (e.g. detachable
be operated with variable opening and closing speeds without maintenance and repairs to ensure that there are no unclear rules and regulations. protective devices and emergency-off devices) must be
strain on the mechanics. assignments. • Always keep these instructions ready at hand at the location present and functioning.
In addition to the control of the motor that operates the door, where the industrial door is used. • Do not modify or put the safety devices out of operation.
depending on the intended purpose the control unit can be used for 2.3 Standards and regulations • Without the supplier‘s prior approval, do not carry out any
the following additional tasks: As the operator or owner of the door system, you are responsible modification, attachment or conversion work on the industrial
door which might compromise safety. 2.6 Safety instructions for maintenance
• Positioning the door on and between its travel limits (open, for ensuring that the following regulations are observed and
close and intermediate positions) complied with (without any claim to completeness). • Do not make any modifications to the software of and troubleshooting
programmable control systems. • Perform the described inspection and maintenance work.
• Movement of the operator with different speeds (integrated
frequency converter) European Standards • The location and operation of fire extinguishers must be Comply with the maintenance intervals and note the
indicated by appropriate information signs. Observe the information on the replacement of parts / partial equipment.
• Evaluation of safety sensors on the door (e.g. closing edge EN 12445 Doors – Safety in use of power operated doors:
statutory fire alarm and fire-fighting regulations. • Maintenance and troubleshooting may only be carried out by
monitoring, lintel trap guard, etc.) Test methods
• All work on the industrial door (such as maintenance, cleaning specialist personnel.
• Evaluation of additional safety mechanisms on the door (e.g. EN 12453 Doors – Safety in use of power operated doors:
work and inspections) may only be performed during an • Only use spare parts that comply with the technical
photocells, light grilles, etc.) Requirements
operational shutdown. requirements specified by the manufacturer. This is always
• Evaluation of command units on the door (e.g. pull switches, EN 12604 Doors – Mechanical Aspects – Requirements
• Only qualified electricians may work on the electrical guaranteed when original spare parts are used.
radio, induction loops, etc.) EN 12978 Doors – Protective Devices for Power-Operated connections.
• Evaluation of emergency stop command units Doors – Requirements and Test Methods
• Before undertaking any work, disconnect the system from
• Supply of sensors and command units with electronically EN 13849 Safety of machinery – Safety-related parts the mains supply and ensure that it cannot be
secure 24 V safety low voltage of control systems inadvertently turned on. If any, deactivate the emergency
• Supply of external devices with 230 V EN 60335-1 Safety of electrical equipment for domestic use opening lever.
• Control of application-specific outputs (e.g. relays for door and similar purposes – part 1: General
position reporting) requirements
• Creation and output of diagnosis reports EN 61000-6-2 Interference immunity, industrial sector
• Setting of application-specific parameters at various access EN 61000-6-3 Interference emission, residential area 3 Fitting the control
levels for different user groups EN 61000-6-4 Interference emission, industrial sector
• Control of input / output extension modules EN 61508 Functional safety of electrical / electronic /
• TST SFFE: Radio remote control plug-in module programmable electronic safety-related systems
• TST SUVEK: Induction loop evaluator plug-in module
• TST RFUxCom: Interface module for dock applications, etc.. VDE Regulations min. 100 mm
• TST RFUxK: Universal display and input / output module
• TST LCD / Plain text: Plain text displays with 2x16 characters
VDE 0113 Electrical installations with electronic equipment A B
VDE 0700 Safety of electronic devices for domestic use and
• Evaluation of interface signals for the remote control of the similar purposes
door
• Diagnosis, parameterisation and programme update via an
integrated USB interface Accident prevention regulations
+ 40°C
BGV A3 Electrical installations and equipment
The intended use also includes paying attention to these
ASR A1.7 Technical Rules for Workplaces
instructions and observing inspection and maintenance conditions.
Any other or further use is regarded as non-intended use. The 0°C
manufacturer / supplier is not liable for any damage resulting from Type test
this. The risk is borne solely by the user. Confirmed by TÜV certificate and manufacturer’s CE.
The standard version available at the time of the type test applies. C
min. 100 mm
ATTENTION
0
19 ▶ Touching the electronic components, especially those of the processor circuit, is prohibited. Electronic components may be
damaged or destroyed by electrostatic discharge.
B ▶ Before opening the housing cover, make sure that no bore chips or similar objects, lying on the cover for example, can fall into the
housing.
A ▶ Fit the control without distortion.
▶ Close unused cable entries by suitable measures to maintain the housing's IP 54 protection category. Do not subject the cable
C entry points to any loads, particularly tensile loads.
▶ Operating the control with a dismantled CEE plug is only permitted if the mains supply can be disconnected from the control at all
poles via a suitable switch. The mains plug or the replacement switch used must be easily accessible.
4 90 6 ▶ To avoid danger, the connecting cable of the unit, if damaged, must be replaced by the manufacturer or a similarly qualified person
Ø
(in line with connection type Y according to EN 60335-1).
▶ When the door is moving in press-and-hold operation, ensure that the door area can be monitored by the operator. In this operating
mode, safety equipment such as safety strips and photocells may not be functional. If this is not possible for constructional
reasons, ensure that this operating mode is only accessible to staff that has been instructed accordingly or disable the function
entirely.
WARNING
▶ The control may only be opened if the supply is disconnected at all poles. It is prohibited to connect or operate the control when it
is open.
▶ Switch off all power supply circuits before accessing the connecting terminals.
5 ▶ Before fitting, check the control for shipping damage or other damage. In some cases, damage inside the control may cause
24 considerable consequential damage to the control and even endanger the health and safety of the user.
B
A
4 Electrical connection
C
ATTENTION
0 6
42 Ø ▶ After completing the wiring and before switching on the control for the first time, check whether all motor connections on the control
side and on the motor side are tightened and the motor is correctly connected in star or triangle. Loose motor connections cause
damage to the converter. If the 24 V control voltage is short-circuited or extremely overloaded, the power supply unit will not switch
on even though the intermediate circuit capacitors are charged. The displays remain unlit. The power supply unit can only be
switched on after the short-circuit or extreme overload has been remedied.
▶ For compliance with EMC directives, only shielded, separate motor cables may be used. The shield must be connected on both
sides (motor and control) and no additional connections may be led in the cable. Maximum cable length: 20 m.
▶ If the control is covered in condensation, do not connect or operate it. This can destroy the control.
▶ Before connecting the control supply for the first time, ensure that the evaluator cards (plug-in modules) are plugged in the correct
position. The control may be damaged if the cards are not plugged correctly or are twisted, or if non‑approved cards from other
manufacturers are used.
▶ Do not operate a control with damaged keypad or display. Damaged keypads and display must be replaced. To prevent damage to
0
19 the keypad, do not operate it with sharp objects. The keypad is designed for finger operation only.
▶ Maximum connection cross-sections of the circuit board terminals:
ON
ON
L PE N
16 A / K-Typ
PE
N
CEE – plug / 3 pole Fuse
230 V / 16 A blue 16 A, K-characteristic
The mains plug must be visible and accessible from the control.
4.2 Connecting the supply voltage AK/AS 500 FUE-1 4.3 Motor connection
L1 L2 L3
N 33 34 33 34
X13
X13 X10 X14 X15 X16
X10 X14 X15 X16
L L N N PE T1 T2 T3 10 11 12 20 21 22 30 31 32
L L N N PE T1 T2 T3 10 11 12 20 21 22 30 31 32
WH PE U V W
L1
L2
PE
L3
N
PE
WH
3 16 A / K-Typ
L1
L2 PE
L3 PE U V W
PE M
N 3~
3 2 1
6 5 4
X14: Output relay – Function as ordered – Standard: Door in upper travel limit
X15: Output relay – Function as ordered – Standard: Door in lower travel limit
X16: Output relay – Function as ordered – Standard: no function
E201
X27
+ 24 V
E101
E102
E103
+ 24 V
E104
GND
+ 24 V
E105
GND
+ 24 V
E110
E109
GND
E108
+ 24 V
E107
+ 24 V
E106
+ 24 V
E212
E360
GND
+ 12 V
5 Control replacement 5.2 Control replacement for BS 150 FUE-1 / AS 500 FUE-1
Observe all safety regulations when performing any work on the electrical systems. The control may only be replaced by trained specialists.
ON
1
ON
ON
ON
Additionally activate OPEN button and hold wait approx. 2 seconds: in parameterisation Illustration: 1234567 ➜ 1234. ▼-actuate .567
r
2. mode Illustration: 67 ➜ 67
n Maintenance counter The content of this parameter specifies the number of door
Selecting parameters in open parameterisation mode cycles still to be run until the maintenance is due.
Select desired parameter The parameter value can be viewed or r
modified (see below), display varies with The setting -1 means that the maintenance counter has not been
ATTENTION: selection activated yet.
Not all parameters are directly visible or Crash counter The content of this parameter specifies the number of crashes
modifiable, depending on the password and counted so far. In case of an activated crash input the crash
the positioning type setting counter will be increased by a value of 1 and only press-and-hold
r
operation is possible. The crash or the error caused by it has to
Parameter processing with selected parameter be acknowledged.
1. Control is in parameterisation mode Name of desired parameter displays
7.2 Hold-open phase
2. Opening the parameter The current parameter value is displayed: P. Function Description / notes
0 ... 9999 s Hold-open phase 1 door The door is held in the travel limit for the set time. Then, the
OPEN closing is carried out automatically.
3. Use the OPEN button to increase the If the currently valid parameter value is w
parameter value modified, the decimal points will flash 0 ... 9999 s Hold-open phase 2
intermediate stop / partial
w opening
or Use the CLOSE button to decrease the
parameter value 0 ... 200 s Minimum hold-open phase Deviating from the hold-open phase 1 or 2, the door is held open
for the minimum period of the set time. Then, the closing is
4. Save set parameter value The parameter is saved when all dots have w carried out automatically.
stopped flashing 0 ... 20 s Pre-warning phase Door closing will be delayed by the time indicated in this
before closing parameter if a CLOSE command is received or after the
3s hold‑open phase has elapsed (forced closure).
w
or Discard set parameter value Abort, the original parameter value is
displayed The hold-open phase that runs depends on the travel limit approached and the OPEN command used. You can separately set for each
OPEN command whether a hold-open phase is started and if, which one.
5. Change to display of parameter name Display of parameter name
7.4 Error memory 10. Press the ● und ▲ buttons to skip to parameterisation mode. Select parameter P.980 “Service mode”, open it, and set the parameter
value “2” to “0” (automatic mode).
P. Function Description / notes 11. If required, correct the door OPEN and door CLOSED limit switch positions by fine-tuning the end positions in automatic mode.
1 ... 8 Error memory The control stores the last eight errors that have occurred in the To prevent door from moving unintentionally, only adjust the limit switches if EMERGENCY OFF is activated or control is
error memory. disconnected!
r 12. Now, door may be moved in automatic mode.
After jumping to parameter P.920:
• Switch level using membrane key ▲ and membrane key ▼ 8.3 Requesting new teach-in for limit stops
• Open the error memory using the ● button If electronic limit switches are used and the end-of-travel position teach-in was done in advance, but are not suitable for the door, a new
• Close the error memory using the ● button end-of-travel position teach-in can be requested.
• Exit the parameter P.920 using Eb -
9.2 Phases
8.2 with mechanical limit switches
1. Move door with ▼ approximately 50 cm before the closed position. P. Function Description / notes
If the door does not move, the motor is lacking in power or, if necessary, check if the brake is released. 0 ... 60 s Memory time for OPEN OPEN commands are saved for the time set here
The distance is very dependent on the door type and speed. For fast doors, increase the value. With incorrect direction of commands
door movement: incorrect motor rotating field, switch off the control and swap the 2 motor connections. w
2. Set the lower pre-limit switch so that it just triggers. 0 ... 20 s Pre-warning phase before Door closing is delayed by the time specified by this parameter
3. Move door with ▼ approximately 10 cm before the closed position. CLOSE movement after the input of a CLOSE command or after the hold-open
The distance is very dependent on the door type and speed. For fast doors, increase the value. w phase (forced closing) has elapsed.
4. Set the lower limit switch so that it just triggers.
Hold-open phase see section 7.2
Do not overshoot limit switch in end positions!
5. Move door with ▼ approximately 50 cm before the open position.
The distance is very dependent on the door type and speed. For fast doors, increase the value.
6. Set the upper pre-limit switch so that it just triggers.
7. Move door with ▼ key approximately 10 cm before the open position.
The distance is very dependent on the door type and speed. For fast doors, increase the value.
8. Set the upper limit switch so that it just triggers.
Do not overshoot limit switch in end positions!
9. Set EMERGENCY upper and lower limit switch.
The boost should always be set as low as possible yet as high as needed.
P. Function Description / notes
P. Function Description / notes 6 ... 200 Hz Operating frequency for fast Operating frequency to lower pre-limit switch
CLOSE movement Observe closing force at safety strip!
0 ... 30 % Boost for OPEN movement Increases the voltage output and thus the performance for lower
numbers of revolutions, until the cut-off frequency (P100) is w
w reached. 6 ... 200 Hz Operating frequency for fast Operating frequency to upper pre-limit switch
The voltage is increased by the value entered in the parameter in OPEN movement
percent to the level of the nominal motor voltage (P103).
w
0 ... 30 s Block time detector channel Detector channel 2 and OPEN 2 commands are blocked for the
2 and OPEN 2 time specified in this parameter after activating a cross-traffic
w input.
1) normal characteristic curve
2) boost characteristic curve
on: ______________________________
w 0: OPEN and CLOSE movement in press-and-release Cycle counter 7.1
operation (Automatic)
1: OPEN movement in press-and-release operation, CLOSE
movement in manual mode (Semi‑automatic) Maintenance counter 7.1
2: OPEN and CLOSE movement in manual mode
(press-and-hold mode)
Hold-open phase 1 7.2
3: Press-and-hold-mode emergency run
ATTENTION
In the emergency run mode, the door moves as long Hold-open phase 2 7.2
as a movement command exists and does not stop at
the end-of-travel positions!
4: Fatigue testing with safety devices. Automatic OPEN and Minimum hold-open phase 7.2
CLOSE movement. Before each new movement, a new
hold-open phase P010 is performed.
Memory time for OPEN commands 9.2
Save parameter file 9.10 Contouring error (change in • Door or motor is blocked
position of door is less than • Brake does not release (check connection / check brake rectifier)
expected) • Power too low for starting torque (check voltage supply)
Load parameter file 9.10 • Speed insufficient
• Mechanical limit switch was not passed or is defective
Resetting the maintenance counter 9.11 • Fixing to shaft of absolute encoder is not tightened
• Wrong door profile selected (P991)
Operating mode 9.12 Detected direction of rotation • When using increment encoders: Channel A and B have been swapped
differs from the expected • Rotational direction of the motor was switched relative to the calibration.
direction of rotation Repeat teach-in door with P.210 = 5.
Start software update 9.10 • Too much "sagging" when door starts to move, brake releases too soon, or
torque is too low, boost may need to be adjusted.
Factory setting 9.13 Position sensor logs faulty • The position sensor bus is disrupted
• No position data received over a longer period
Door profile 9.13 Malfunction of photocell's • The photocell's pre-limit switch remains engaged also at centre travel limit
pre‑limit switch or upper travel limit.
• For absolute encoders: Repeat teach-in of end-of-travel positions, distance
Bridging DIP switch 9.14 between Eu and Eo at least 1 m.
Password 9.14
Operator call crash system
Crash recognised • The control was just connected, one-time reset of the error necessary
• The door was crashed
11 Overview of messages
Reset procedure, see:
11.1 General errors • Fitting instructions
• Wiring diagram
If errors do not reset themselves, they may be acknowledged.
• Control cabinet door outside
You must first eliminate the source of the error before you acknowledge the related notification.
Number of activations • Parameterised maximum number of activations of safety B during one door
exceeded, safety B cycle has been exceeded
Parameter is not set Number of activations • Parameterised maximum number of activations of safety C during one door
Control is not parameterised • The basic parameters of the control were not set yet. See P990 and P991. exceeded, safety C cycle has been exceeded
Intermediate circuit current is • A one-phase supply has been detected for the AK / AS 500 FUE - 1
too high for one-phase supply and the permitted intermediate circuit current is too high for one-phase Internal error
supply. This error always occurs in conjunction with F.520
Communication not possible • Communication with extension card is disrupted
External 24 V supply missing • Overload, but no short circuit. with the extension card • No extension card inserted
or too low • If the 24 V short circuits, the control supply does not switch on and the
• CAN connection disrupted (cable break or no power supply
V306 glow lamp lights up.
for the extension card)
Overvoltage at the power input • The supply voltage is too high
Communication error • Hardware defects
• The supply voltage has a high fluctuation between main processor • Extremely disruptive environment
• For controls with UPS: UPS in battery operation – restore power supply and I/O processor • Temperature too high
Heat sink temperature is • Load on output stage or brake chopper too high
Emergency stop chain not • Not all EMERGENCY STOP inputs are bridged separately, even though the
outside operating range limit 2 • Clock frequency of output stage too high (P160) complete entire emergency chain is bridged.
• Ambient temperature of control too low • Redundant check of the emergency stop chain activated
Malfunction: Temperature in • Interior temperature too high Braking current is not OK • Braking current is not OK – The expected braking current set with
housing rising above critical parameter P.183 has been exceeded by at least +0.5 A.
80°C
• Incorrect brake
Overload current in • Set voltage increase ("boost") not adjusted
Erroneous input test • Testing of the monitoring function failed
intermediate circuit limit 2 • Motor incorrectly dimensioned for door used
• Check monitoring device connection
• Door is sluggish
Motor wiring test • Damaged motor cable
• Damaged motor
Upper travel limit locked, no closing possible (e.g. safety loop) beyond the permitted upper travel limit
Active opening
Information message during automated operation
Emergency opening message
Centre travel limit (intermediate travel limit)
Open command encoder priority active, close movement only with a command encoder that has the same priority
Emergency operation, press-and-hold operation, ignores all safety devices, etc. (see P5 x 4)
Malfunction of the safety strip NC during the last closing, the message is deleted after the close position has been
reached without malfunctions
Malfunction of the safety strip NO during the last closing, the message is deleted after the close position has been
Lower travel limit reached reached without malfunctions
Information message during automated operation General inputs – for function see wiring diagram
Upper limit switch is being corrected Input 2
Max. speed during the automatic limit switch correction has not been reached. Input 5
The parameter file cannot be written because the storage medium is full External emergency-off 1
External emergency-off 2
Programmer message
Input 1
Induction loop evaluator – plug-in module 12.4 “Traffic light function” application parameters A.710 / A.720
Channel 1
Up to software version FU_H30124
Channel 2 A Function Description / notes
A.710 / A.720 0 Deactivated
A.710 1 “Door OPEN” signal
Channel 3
A.720 1 “Door CLOSED” signal
A.710 / A.720 2 Standard Red / Green traffic • No dependence on direction
Channel 4
light • Pre-warning phase P.025 = 3 s
A.710 / A.720 3 Flashing / rotating warning • No dependence on direction
light • Pre-warning phase P.025 = 3 s
Internal inputs
• Active during door travel and pre-warning phase
Fault signal from drive module
A.710 / A.720 4 “Austria” traffic light • No dependence on direction
• Pre-warning phase P.025 = 3 s
• Active during door travel and pre-warning phase
• Acknowledgement after emergency OFF via STOP
membrane push button
12 Application parameters BK / BS 150 FUE-1 / AK/AS 500 FUE-1 A.710 / A.720 5 Locking • “Door not CLOSED” signal
• No delay time
12.1 Intermediate Stop
A. Function Description / notes
From software version FU_H30124
0 No intermediate stop
A Function Description / notes
1 Intermediate stop See wiring diagram for connection A.710 / A.720 0 Deactivated
selection switch A.710 / A.720 1 “Door OPEN” signal • No switching delay
2 Impulse generator “Opening See wiring diagram for connection A.710 / A.720 2 Standard Red / Green traffic • No dependence on direction
height requested by user” light • Pre-warning phase P.025 = 3 s
A.710 / A.720 3 Flashing / rotating warning • No dependence on direction
light • Pre-warning phase P.025 = 3 s
12.2 UPS emergency opening • Active during door travel and pre-warning phase
A.710 / A.720 4 “Austria” traffic light • No dependence on direction
A. Function Description / notes
• Pre-warning phase P.025 = 3 s
0 No UPS emergency opening
• Active during door travel and pre-warning phase
• Acknowledgement after emergency OFF via STOP
1 UPS emergency opening with See wiring diagram for connection; self-test activated membrane push button
self-test, locking priority A.710 / A.720 5 Release • “Door CLOSED” signal
2 UPS emergency opening with See wiring diagram for connection, self-test active • Power on delay 1 s
self-test, emergency opening • NO contact
test priority A.710 / A.720 6 Locking • “Door not CLOSED” signal
3 UPS emergency opening with UPS emergency opening with self-test, only with RW kit • Power off delay 1 s
self-test, only with RW kit • NO contact
A.710 / A.720 7 “Door CLOSED” signal • No switching delay
Keypad (X400) 3 buttons “Open-Stop-Close” USB host (X403) Low-power USB memory stick with FAT32 file structure.
Malfunction if incorrectly inserted without destroying component. USB profile “Mass Storage Device” (8), Sub Class Code “SCSI transparent command
Connected via 4-pin uncoded plug connector. Switching to plus! set” (6), Interface log “Bulk-only transfer” (0×50), Logical Unit Number (LUN 0), SCSI
Without lighting / without warning lights! “Request Sense” < 2.5 s, USB-Request-Time < 2.5 s, USB-NAK < 36684x,
Voltage supply (wire black (L1…3) / blue (N)) Variant BK / BS 150 FUE - 1 AK / AS 500 FUE - 1 no Hubs / Compounds possible!
Plug: USB type A
Nominal voltage 1 N ~ 230 V 3 (N) ~ / 2~ 400 V Max. supply: 100 mA
Voltage range 110 to 240 V ± 10% 200 to 480 V ± 10% Max. cable length: 2 m
Safeguarding on-site 16 A, slow-acting 16 A, slow-acting Typical data record size per door cycle (log storage function): approx. 2 KByte
The temperature range must be taken into account if the USB stick is used
Nominal frequency 50 to 60 Hz continually within the control, e.g. as a log memory. Recommendation:
Connections on the circuit board are not plug-in type! • “Industrial grade” (typ.): 0°C ... + 70°C
Control without operator Max. 140 W at full use of the 24 V supply • “Extended industrial grade” (typ.): – 40 °C ... + 85°C.
External supply 1 (X10: L‘/N‘) Transfer of phase L1 and N. (typical nominal voltage L‘ to N‘: 230 V AC) Alternatively as a USB device (X401) PC communication with HÖRMANN service protocol
L‘ is fused on the printed circuit board: 4 AT “Communication device ➜ virtual serial port”
Not with UL variants! Plug USB-type B (mini USB)
Max. cable length: 2 m
Control voltage / external supply 2 24 V DC ± 5 % max. 3,500 mA low safety voltage acc. to EN 60335-1
(among others, terminal “+ 24 V”: • Incl. all external consumers, such as plug-in modules, I/O modules, 24 V Only one USB participant may be operated on the interface!
40, 44, 47, 50, 55, 57, 59 brakes, switched transistor outputs and additional control voltages
.“GND”: 36, 46, 49, 53, 73, 83) Security chain / emergency off All inputs must have a volt-free connection.
• Fused and short-circuit-proof thanks to a self-resetting central
(X24a-70/71, X26-90/91, Contact load: ± 26 V DC / ≤ 120 mA
switching regulator.
X23-60/61 or X25b If the security chain is disrupted, the operator can no longer move,
• GND potential internally earthed to PE (protective earth potential) even in press‑and-hold operation.
Control voltage / external supply 3 For electronic limit switches and safety strip ATTENTION: No parallel connection between X25 and X25b!)
(tml. 74, 80) Nominal value 11.5 V / max. 130 mA Input safety strip 1 – “Si-Lei” For electrical safety strips with 8.2 kΩ terminating resistor and for dynamic
Control inputs “Digital” IN 1 ... 10 24 V DC / typ. 15 mA, max. 26 V DC / 20 mA (X24b – tml. 72 or X27) optical systems.
(tml. 41, 42, 43, 45, 48, 49, 58, 56, 54, 52, 51) All inputs must have a volt-free connection or: ATTENTION: No parallel connection between X24b and X27!)
< 5 V : inactive ➜ logically 0 Transistor output – Out 26 Main function: “Test”
> 7 V : active ➜ logically 1 (TML. 75) 24 V DC / min. 10 mA / max. 100 mA
Min. signal duration for input control commands: > 100 ms Normally open, + 24 V switching!
Galvanic separation via optoelectronic coupler on the printed circuit board. Only resistive loads! Fused!
Communication interfaces Transistor outputs – Out 28 / 29 24 V DC / min. 10 mA / max. 200 mA
Serial interface 1 “DoorCom” For electronic limit switches DES or TST PD/PE or other communication partners (X18 – tml. 35 / 37) Normally open, + 24 V switching!
RS485-0 (X25 / 25b) approved by HÖRMANN Only resistive loads! Fused!
RS485 level (A, B), terminated by 120 Ω Brake 24 V – Out 4 24 V DC / min. 100 mA / max. 2500 mA
Recommended cable: shielded twisted-pair cable in disruptive environment, (X17 – 33 / 34) Fused!
twisted pair in normal environment Incl. monitoring of switching behaviour!
If using HÖRMANN limit switches TST PD / PE in parallel also e.g. for future I / O NOTE:
extensions If the security chain is disrupted, the output is switched to a voltage-free state!
Serial interface 2 “AdvDoorCom” For operating unit TST UTH, external operation of extension PCB TST RFUxK Relay outputs Out 1 / 2 “Malfunction / door position signals / traffic light functions”
CAN-2 (X28 / 28b) or another communication partner approved by HÖRMANN (X14 / 15) If inductive loads are switched (e.g. additional relays or brakes), they must
CAN level (CH, CL), terminated by 120 Ω be equipped with the appropriate suppression measures (free-wheeling diodes,
Recommended cable: shielded twisted-pair cable in disruptive environment, varistors, RC circuits)!
twisted pair in normal environment
Volt-free change-over contact Contacts used once for power switching
Serial interface 3 For module TST RFUHCom or other communication partners approved by • Min. 10 mA can no longer switch small currents.
CAN-1 for communication module HÖRMANN NOTE:
• Max. 230 V AC / 3 A
TST RFUHCom TTL level (Tx, Rx) Flash functions limit the mechanical
(use fused phase L‘!)
Max. cable length: 10 cm for internal wiring to module service life!
Serial interface 4 For module TST RFUHCom or another communication partner approved Alternative use as a brake relay Change-over contact to release electromechanical brakes
RS485-1 for communication module by HÖRMANN (Out 1 or 2 / X14 / 15) with upstream brake rectifier.
TST RFUHCom Typical for communication between two doors (loading house/locking) ATTENTION: no safety function
TTL level (Tx, Rx, DDR) Max. 230 V AC / 3 A (use fuse phase from L‘!)
Max. cable length: 10 cm for internal wiring to module
Serial interface 5 Suitable for operation of the module TST RFUxK or another communication
CAN-0 (X701) for extension PCB TST RFUxK partner approved by HÖRMANN in the housing!
TTL level (Cx, Rx)
Max. cable length: 10 cm for internal wiring to module
Operator output (X13): Variant BK / BS 150 FUE-1 AK / AS 500 FUE-1 14 Plug-in type traffic detector
Nominal voltage 3 ~ 230 V 3 ~ 400 V SUVEK1 – Simple detector
Voltage range 110 to 240 V ± 10% 200 to 480 V ± 10% SUVEK2 – Double detector
RoHS/WEEE/REACH Europe
By adjusting the sensitivity, it is determined for each channel which inductivity change must be caused by a vehicle to cause the
respective output of the detector.
Adjustment of the sensitivity is implemented separately for each channel via 2 DIL switches each.
14.2.3 Frequency setting and repeat adjustment 14.4.3 Output of the loop frequency
Frequency Channel 1: DIL switch 4 Approx. 1 second after the matching of the detector, the loop frequency is displayed via flashing signals of the green LED.
Channel 2: DIL switch 8 (only SUVEK2)
Low OFF Example of 57kHz loop frequency:
High ON
∞
X1 / 3 Optoelectronic coupler GND
Hold time
X1 / 4 Optoelectronic coupler output channel 2 (only SUVEK2)
Loop lead Max. 100 m
X1 / 5 Optoelectronic coupler output channel 1
Loop resistance max. 20 Ω (incl. lead)
X2 / 1 Additional optoelectronic coupler output
Optoelectronic coupler output 45 V / 10 mA / 100 mW
X2 / 2 Additional optoelectronic coupler input
Slow operation 50 ms SUVEK1, 100 ms SUVEK2 > 200 ms
X2 / 3 24 V DC output (connection X1 / 2)
Signal duration slow release 25 ms SUVEK1, 50 ms SUVEK2
X2 / 4 – X2 / 5
Connection 2 × MOLEX socket series 3215, 5-pole
X5 / 1 - X5 / 2 Loop channel 1
1 × plug terminal 4-pole, RM 3.81
X5 / 3 – X5 / 4 Loop channel 2 (only SUVEK2)
14.4 Outputs and LED display 15 Radio remote control 868 MHz
14.4.1 Outputs 15.1 Receiver
Optoelectronic coupler Detector statuses Note:
output channel 1 / 2
When used at the same time, GSM 900 mobile phones can affect the range of the radio remote control.
High Loop free / reset / matching
Low Loop configured / loop malfunction 1. Briefly press the red button (programming button) on the receiver – the red LED begins to flash slowly.
2. Press the hand transmitter button to be programmed at least 1 second. There must be a distance of at least 1 m between the
The signal output takes place via the optoelectronic coupler outputs PIN 4 and 5 to the plug X1. GND reference is X1 Pin 3. transmitter and the receiver.
3. Upon completed programming the red LED on the receiver begins to flash faster.
14.4.2 LED display 4. Release the hand transmitter button.
Green LED loop control Red LED loop status Detector status After the flashing has stopped, the receiver is ready to receive.
Off Off Voltage supply missing To verify, push the programmed button of the transmitter, the red LED of the receiver lights up.
Flashes Off Matching or frequency output
Note:
On Off Detector ready, loop free
If no programming takes place for 30 seconds after the programming button has been pressed, the slowly flashing red LED in the receiver
On On Detector ready, signal output
will be turned off again.
Off On Loop malfunction
The green LED signals that the detector is ready for operation. The red LED indicates the activation of the relay output depending on the Cancelling of the programming
configuration status of the loop. If the programming button is pressed briefly 3 times within 2 seconds, the red LED is turned off and the programming procedure is
abandoned.
16.4 Troubleshooting
Possible cause Troubleshooting
The red status LED in the • Transmitter is inactive, check the wiring, check the test signal
SGT receiver is continually lit • Bottommost beam is interrupted, remove the obstruction
• Extraneous light in the bottommost beam
Yellow output LED flickering • Extraneous light from another system, change the fitting position of the other system, eliminate the
light from the other system
17.3 Function description The concerned crash switch must be replaced immediately in case of this display.
LED Displays
Delivery condition
Transmitter Receiver Note
Transmitter hard coded, receiver not programmed, must be programmed first. After the receiver is switched on, the LED in the receiver
is permanently green. Brief flashing if a signal is received from any compatible transmitter – then permanently in green – transistor output Off Off Resting state
remains open – no door function. Flashes 1 × Flashes 1 × Upon actuation:
Function OK, crash signal is transmitted
Flashes 2 × Continuous flashing Upon actuation:
Battery voltage decreased, crash signal is transmitted, replace transmitter
Flashes 2 × Continuous flashing Upon actuation:
Battery voltage very low, crash signal is transmitted – replace transmitter
— Constant light Unit is not programmed – teach-in 2 transmitters
Programming
Briefly press the programming button, the LED flashes slowly. Within the next 5 minutes, first actuate the first and then the second crash
switch. When the radio signal of the first crash switch is received, the LED flashes 8 × very quickly while the code is being stored. During
this time, you cannot teach in a second code yet. The LED then flashes again slowly and you can teach in the second transmitter. When the
radio signal of the second crash switch is received, the LED flashes again 8 × and goes out. You have to always teach in two different
crash switches on a receiver.
Delete programming
Switch on voltage supply. Push and hold the programming button. LED flashes slowly. Switch off voltage supply. Now no more transmitters
are taught in.