Structured Cabling Design and Specification Guide
Structured Cabling Design and Specification Guide
<NAME OF PROJET>
1 Version 6.4
CONTENTS
The design, installation, and testing shall conform to the applicable requirements of the
latest edition and supplements of the standards, codes, and recommended practice of
the following organisations:
Includes:
- IEEE 802.1™: LAN/MAN Bridging and Management (Active)
- IEEE 802.2: Logical Link Control (Hibernating)
- IEEE 802.3™: Carrier Sense Multiple Access with Collision Detection (CSMA/CD)
Access Method (Active)
- IEEE 802.11™: Wireless LANs (Active)
- IEEE 802.3af : Power Over Ethernet
- IEEE802.3at : Power Over Ethernet Plus
Each standard organization has is own requirements. For instance, ISO/IES and
CENELEC have chosen to define a generic structured cabling able to support all type of
applications, and the ANSI/TIA/EIA has chosen to apply to the IEEE minimum
recommendations defined (for instance 10GBASE-T)
CABLE TYPE
How to choose?
The new baseline installation selects Category 6, and most new project specifies
Category 6A. Note that when you specify the cables, the corresponding connecting
hardware and patch cords be rated in the same category as, or higher than, the
horizontal cable. The cabling system bottleneck will be the weakest link of the
installation. i.e. if you mix Cat 5e, Cat 6 and Cat 6A components, the overall system
bandwidth will be limited to Cat 5e performances.
SCHNEIDER ELECTRIC does not advise a mixing of categories and our warranties will
only cover single class product installations.
1) A terminal outlet using RJ45 modular jack (access point at the workstation)
2) Consolidation point (used for indirect wiring through raised floor or false ceiling)
3) Horizontal cable, also called capillary cable, made of four twisted pairs
4) Floor Distributor (FD) also called sub distribution frame (SDF)
5) The Building Distributor also called Main distribution Frame (MDF)
6) Multi-pair copper backbone cables linking the FD to the Building Distributor (BD)
for telephone application
7) Cables (FO or copper) linking FD to BD for data network applications
Telecommunication Outlet
All the wiring devices should be taken in the same range as infrastructure cabling
system, no mather which installation method is chosen, the wiring devices will be
compliant to IEC 60364 / and HD384 series international standards.
The protection level following the IEC 60529 or l’EN 60529, should be minimum : IP 20
The shock resistance following the IEC 62262 or l’EN 62262 should be IK 02.
The wiring device should never exceed the local standard (ie : 45mm in France,
Belgium)
The wiring device will be compatible with every outlet without any adaptor or
dismantling.
The wiring device should be mounted next to each other without any space in between.
Every wiring device must have a clipsing mechanism without any tool. All
telecommunication outlet must be trivialized.
A minimum of 2 outlets per work area is recommend in case of use of IP-TELEPHONY.
Otherwise a complementary outlet should be considered.
The telecommunication outlets including or not 1 or 2 RJ45 will be ISO 8877 compliant,
defined by ISO IS11801, and TIA/EIA 568 TSB40, which description is done in (29.1.2
RJ45 Connector)
All the range of connectors have to be compliant with all the last international standards.
A valid certificate must be provided by third party laboratory (type :DELTA).
Each connector of the family is available in UTP or STP one piece device compact and
simple locking termination without any loose part, to avoid the installer to lose pieces ,
and to make it easier to handle.
The connector has to be tooless, U-Shaped cable entry, with a smart bridle with
elastomer insert for cable. Easy access for all cables. Automatic 360° earthing with
spring-loaded locking and earthing bridle.
The STP connector must have integrated earth-drain contact for the drain wire
connection, and double earthing for the STP version at the front.
The U shape entry is the same concept, S/FTP or F/FTP cables to enable them to keep
their structure intact (screens and foils are not damaged) transmission performance is
safe. No risk to tear and roll up the screen.
The U-shaped cable entry should be considered for reducing risk of damaging
connections. For the S/FTP et F/FTP (easy access for all cable)
Insulated plastic IDC housing eliminates short-circuit between conductors and metal
body.
The crossing of pairs is implemented before the cable’s introduction into the connector
for easy, secured and efficient wiring. The pair foil can be as near as possible to the
IDC.
The earth drain wire is inserted in an horizontal groove with entire security and is
terminated vertically down on the side of the connector. Secured integrated guiding parts
to enable reproductive position.
The connector has to be labelled on each side the colour coding from the standard EIA
568 A & B.
The connector has to be smooth design with rounded edges, and touch –friendly
materials to avoid injuries.
Performances :
The level of performance has been certified by an independent laboratory Delta with the
EIA/TIA and ISO 11801:2011 Ed2.2 Class E permanent link and channel. All the
parameters required have been surpassed by far during the test.
The test method « Direct Probing » will warranty the interoperability of the connector at
500Mhz, and met the requirement of the international IEC60512-99-001 ed 1 POEP
standard.
RJ45 WATERPROOF
The RJ Protek faceplate are specially design for industrial or laboraty environment,
surgery rooms where chemical, dust, humidity constraints are usual).
For Heavy steel industry vibration plants this RJ45 has improved resistance against
unplanned disconnexion due to high vibrations.
The Waterproof of the RJ45 is secured by the turn&lock, and this gives a IP55 in
surface mount and up to IP67 in flush mount.
DESIGN CONSIDERATIONS
Guidelines for planning the location of telecommunications outlet boxes in the Work
Area:
1. Each work area shall have a minimum of ONE telecommunications outlet box
location. TWO telecommunications outlet box locations should be provided and located
for future additional telecommunications outlets.
2. Work area telecommunications outlet box size.
ANSI/TIA/EIA-569-B, specifies the following:
3. Telecommunications outlet boxes may require supports for attaching the box and a
suitable faceplate to support the telecommunications outlet/connectors that are housed
by the work area telecommunications outlet box.
• Outlet boxes shall be no smaller than
The work area telecommunications outlet box should be located near an electrical outlet
(e.g., within 1 m [3 ft]) and installed at the same height if appropriate.
Page 12 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
5. Floor-mounted telecommunications outlet boxes and monuments (pedestals), and the
cables extending from them, can present a tripping hazard. The location of these
telecommunications outlet boxes should be coordinated with furniture to minimize such
hazards.
6. Cabling system performance may be sensitive to the arrangement and organization of
cable slack located behind the telecommunications outlet/connector. Sufficient space
must be provided in the telecommunications outlet box or equivalent space so that
minimum cable bend radius requirements are not exceeded.
7. The location, mounting, or strain relief of the telecommunications outlet/connector
should allow pathway covers and trim to be removed without disturbing the cable
termination. Care should be exercised to ensure that telecommunications outlet/
connectors are mounted in such a way that they do not significantly reduce the required
pathway cabling capacity.
8. Open office furniture openings provide for mounting faceplates containing one or
more telecommunications outlet/connectors. Two standard sizes of openings are
specified:
All four pairs in the cable shall be terminated in an 8-position modular outlet/connector at
the work area. These connectors may be x/xTP, as described in the above section.
Two wiring schemes are specified in the ANSI/TIA/EIA 568-B.1 Clause 6.2.1. The
pin/pair assignments for T568A and T568B are shown in Figure 1.19b depicting the front
view of each telecommunications outlet/connector.
T568A is the preferred wiring scheme, and T568B optional if necessary to accommodate
certain pre-existing 8-pin cabling systems.
When selecting a connector, make sure it is specified and tested to meet ANSI/TIA/EIA-
568-B.2.
Connecting hardware should be marked to designate transmission performance at the
discretion of the manufacturer or approval agency. The markings, if any, shall be visible
during installation. It is suggested that such markings consist of:
a) the consolidation point shall be located so that each work area group is served by at
least one consolidation point;
b) the consolidation point should be limited to serving a maximum of twelve work
areas ;
c) a consolidation point should be located in accessible locations ;
d) the consolidation point should be located so that there is at least 15m from it to the
floor distributor ;
e) CP cables are to be of the same type than capillary cable and are to be equipped
with RJ45 plugs recommended by the manufacturer.
• Category 6A (see 3.3 Chapter)
• Optical fiber …………….. (see 3.3 Chapter)
When using adapters (e.g., installing a balun), the adaptors must be external to the
telecommunications outlet/connector or MUTOA. For further information, see Cabling
Adapters in CORE-2: Horizontal Distribution Systems. The cabling infrastructure
designer needs to be aware that these work area equipment-specific adaptors may or
Page 14 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
may not offer the same level of transmission performance as the cabling systems to
which they connect.
• Active adapters (e.g. Fiber Optic transceivers) that may be needed when connecting
devices that use different signalling schemes.
• A special cable or adapter is required when the equipment connector is different from
the telecommunications outlet/connector.
The maximum horizontal cable length of 90 m (295 ft) is based on a maximum length of
5 m (16 ft) of work area cable. The combined length of equipment cables, work area
cords, and patch cords in the telecommunications room (TR) or equipment room (ER)
shall not exceed 10 m (33 ft), with the exception of MUTOA where longer work area
cables are used. In the case of MUTOA’s, the horizontal cable length is reduced when
the work area cords exceed 5m.
CABLE PULLING
The maximum pulling tension for a 4-pair balanced twisted pair cable must not exceed
25 lbf (110N). Exceeding this tension will result in transmission degradation and may
affect the system’s ability to pass certification testing.
STRAIN RELIEF
Cables shall be free of physical stress over the entire length of the run. Use of cable
supports, Velcro ties are recommended for strain relieving. Do not over tighten straps or
tie-wraps to avoid damage to the cable.
Velcro ties shall always be used for bundling cables properly in channels and raceways.
Cables distributed to the same work area zone may be bundled together.
The maximum number of cables per bundle shall not exceed 50 cables.
DEFINITIONS
CP: Consolidation Point - a location for the interconnection between horizontal cables
that extend from building pathways and horizontal cables that extend into work areas.
MUTOA: Multi-user Telecommunications Outlet Assembly - a grouping in one
housing of several telecommunications outlets/connectors.
Open Office - a floor space division provided by furniture, movable partitions, or other
means, instead of building walls.
Design goals
Page 18 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
A good cabling plant design always considers possible changes in user requirements in
the future. The horizontal cabling is often very inaccessible after the building is
completed and can incur high cost of changes and result in disruption to occupants and
their work.
Avoiding EMI
1. Maintain physical separation between possible sources and the telecommunications
cabling.
1. Optical fiber and shielded cable should be used for buildings with high levels of
ambient EMI.
2. Balanced twisted-pair cabling, such as Category 5e or better (Category 6
recommended), can offer a certain degree of noise immunity that ensures reliable
transmission in most environments (e.g., electrical field intensity less than 3 volts per
meter [V/m]).
b) The shield of FTP cables shall be bonded through a conducting path to the
telecommunications grounding bus-bar (TGB) in the telecommunications room.
c) Shielded connections at the work area are accomplished through a FTP patch cord.
d) Grounding at the work area is usually accomplished through the equipment power
connection.
e) At the work area end of the horizontal cabling, the voltage measured between the
shield and the ground wire of the electrical outlet used to supply power to the work
station shall not exceed Vrms.
f) All patch panel and RJ45 connector have to be direct earthing.
Administration
Schneider Electric Network Connectivity requires proper and systematic methods and
procedures for labelling and management of horizontal cabling. The guidelines and
requirements for the administration of horizontal cabling systems comply to and make
references to ANSI/TIE/EIA-606-A.
1) All cabling must be identified at both ends of the run.
2) Markings on the cable must be:
a) Clearly visible after installation.
b) Easily distinguishable from any manufacturers marking on the cable.
c) Can last the full duration of the warranty
Category Mixture
Multiple-category balanced twisted-pair system can be confusing and costly to maintain.
Schneider Electric endorses the use of single category of cabling components, selected
for use in a cabling system. Schneider Electric system warranty does not recognize the
use of mix and match categories in a installed cabling system.
Crossovers/Polarity
When there is a need to connect a transmitter on one end and a receiver on the other, a
cross over cable is required of the copper pair or fiber cores.
Copper
– If crossover cables are required for copper based cable application, they may be used
only outside of the horizontal cabling system. Active equipment will provide the right
polarity if need (MDI/MDI-X).
Optical Fiber
– The optical fiber cabling link shall be installed in a pair-wise crossover orientation in
which the optical fibers of a pair identified as Position A and Position B at one end are
reversed and identified as Position B and Position A (respectively) at the other end.
– This pair-wise crossover for optical fibers is achieved by using connector polarity and
labelling methodologies that apply to horizontal cables, patch cords, equipment cords,
and duplex optical fiber adapters.
NOTE: The colours indicated are associated with horizontal balanced twisted-pair cable.
Colour coding for equipment cables, work area cords, patch cords, and jumpers may vary.
Length limitation
1) The installation length limit of 300m applies to the interconnection and splice
methods. It is based on the combined length of horizontal cable, backbone cable,
equipment cables, cross-connections, and patch cords.
Within the 300 m limit, multimode cabling system will support gigabit services using
centralized networking devices with appropriate optical fiber cable.
2) The cabling length limitation of 90m is associated with the pull-through method. It is
based on the length of horizontal cable from the MC (CD) to the TO/WA.
The total allowable length of additional equipment cables at the MC (CD) and equipment
cables in the work area is 10m with the pull-through method.
SPECIFIC REQUIREMENTS
2.1.6 ENCLOSURE :
Floor-standing cabinet made of galvanized steel symmetric uprights and following
dimension Height:1200, 1400, 1600, 1800, 2000, 2200, Width: 600/750, 800, Depth: 600/800,1000, 1060,1200.
Cabinet should be coated with epoxy-polyester powder hot polymerized in textured RAL
7035 for better corrosion resistance.
All the side panels must be flush with the framework to avoid surprises during the
installation process. For joined enclosures the total length of the set must be the sum of
the individual enclosures that form it to avoid surprises during the installation.
For easier installation and maintenance the cabinet must allow installation of doors on
front and back sides (without special accessories) and installation of 2 doors in the same
upright.
In case that two or more enclosures are installed together the doors should be able to
open without interfering with the adjacent enclosures.
Doors:
Sheet steel plain / transparent door , provided with foamed-in polyurethane gasket and front
door opening. Door shall be provided of adjustable reinforcement frame for increased
ruggedness and assembly of accessories.
Enclosure should allow door opening change. For safety reasons the door must not fall off when totally open and the
pins are off the axis of the hinge. Door opening of 180º for easy maintenance.
Accessories:
Enclosure shall be supplied with 19” uprights, 100mm / 200mm / no mm base/plinth, with/without document pocket,
earthing straps, with/without 19” profiles, eyebolts / lifting brackets / lifting bars, with/without door switch & lamp.
LOCATION OF THE ER
Consider the following when choosing a location for the ER,
Distance from telecommunications cable pathways
Space required for the equipment.
Expandability
Cater for access for large equipment and cables.
Facilities that serve and are served by the ER.
Service Provider (SP) equipment requirements.
Distance from electrical service and mechanical equipment.
Sources of electromagnetic interference (EMI).
CEILING REQUIREMENTS
The recommended height of the ceiling in an ER is at least 3 m (10 ft). Ceiling protrusions
(e.g., sprinkler heads) must be placed to assure a minimum clear height of 2.4 m (8 ft) that
is clear of obstructions, to provide space over the equipment frames for cables and
suspended cable trays.
Some equipment may require additional ceiling clearance, depending upon the
manufacturer’s specifications.
The ceiling finish must:
• Minimize dust.
• Be light coloured to enhance the room lighting.
For fewer than 200 work areas, the minimum ER size shall be no less than 14 m 2.
ER shall have access to the main HVAC 24 hours per day, 365 days per year.
• Temperature will be controlled to 18°-24°C (64°-7 5°F).
• Humidity shall be in the range of 30 to 50%. Both humidity and temperature will be
measured 1.5m off the floor.
FIRE SAFETY
Appropriate portable fire extinguishers shall be kept in ER near the entry or exit.
Power Conditioning
The sensitivity of telecommunications equipment to electrical power fluctuations is a
significant issue in assuring system reliability and longevity. Assess the need for power
conditioner before telecommunications equipment is installed. Many UPS devices will
provide the required power conditioning.
Telephone backbones :
As these cables are designed to carry only telephone signals at 64 Kbits cat.3
performance level is sufficient. They will consist of VDIC235212 (Schneider-Electric)
Multi-pair cable (128 pairs).
Note : To comply with the principle of standardisation of horizontal links, capillary cables
will address the general performance requirements of the cabling system (cat.5 e of
above).
Data backbones :
copper cable colour: should be either green or blue. A white colour is allowed for
LSFROH (IEC60332-3C) cable only.
- For indoor use, the fiber cable will be non-armoured. An anti-rodent protection may be
included. It should have a tight buffered structure.
- For outdoor use, the fiber cable will be armoured and provide an anti-rodent protection.
It should either have a tight buffered or loose tube structure.
High-end copper LAN cables for performances from category 6 to category 6A 500 Mhz.
While exceeding international standards by 3 dB minimum on NEXT & RL, the cable
should have better resistance to the mechanical constraints.
LAN copper cables for category 6A with a single-foil metallic cross-filler, providing high
performance and reliable shielded installations. While exceeding international standards
by 3 dB minimum on NEXT & RL, the cable must provide superior shielding, faster
installations and increased efficiency.
Also, in order to facilitate cable laying, the cables should be available in dual version.
This will allow only one operation to install two cables.
These cables will be made of halogen free compound and should offer a shielding made
of an Aluminium foil laid longitudinally throughout the cable. The foil (or the foils) should
respect the Snail technology features to improve EMC.
The total length of a single link should not exceed 90 meters.
Cable sheath should be blue, and the NVP should be printed
The CL-MX cable is wrapped in one single foil, this means less cutting and improved
quality of cable preparation.
The Actassi Indoor/Outdoor Loose tube LSZH Cables pass most of the following tests:
1) IEC 60754 part 3, Acidity/Corrosively based on pH and Conductivity Measurements
2) IEC 60332-1, Flame Retardant
3) NES 713, Toxicity Index
4) IEC 61034, Smoke Emissions
Copper
The cable should be a 4 pair or 2x4 pairs categorie 5e , U/UTP.
The screen will be made of aluminium in order to maintain the Electromagnetic Immunity
robustness and to meet the quality and performance criteria for high frequencies during
all the warranty time of the system.
In case of fire, the sheath of the cable shouldn’t produce toxic fumes (HALOGEN FREE)
and flame retardant.
All cables shall be 4-pair unshielded Twisted Pair (UTP) cables meeting or exceeding
the quality and performance requirements for Category 6 UTP cables stipulated in
EIA/TIA-568-B.2-1 standard. Each Category 6 UTP cable shall be terminated on an 8-
conductor Category 6 jack in accordance with the EIA/TIA-568B wiring code;
The cable shall be solid or stranded copper conductors of 23 AWG insulated with high
density, PVC or LSZH sheath. Cross filler with optimized design and micro-blades,
is preferred
The cable shall be accompanied with traceable serial numbers from the manufacturer
indicated on the packaging to assist in quality validation of the installed cables;
Page 37 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
The cable shall provide the guaranteed channel performance specifications of the
Category 6 Channel complies to EIA/TIA-568-B.2-1 standard.
Each pair should have an impedance of 100 Ohms, with+/- 15 Ohms, tolerance.
Geometrical characteristics of fiber optic jumpers are to be the same than fiber optic
links cables.
OM3 and OM4 have an additional laser launch modal bandwidth as OM3 and OM4 are
designed to be laser optimized. The difference between ―Overfilled Launch" and ―Laser
Launch" is the test method. A new test method simulating a VCSEL laser launch (TIA-455-
220A and IEC 60793-1-49) was deemed appropriate for these fibers which are intended for
use with VCSELs at higher speeds.
OM4 fiber is designed to enhance the system cost benefits enabled by 850nm VCSELs for
existing 1 Gb/s and 10 Gb/s applications as well as future 40 Gb/s and 100 Gb/s systems.
OM4 fiber supports Ethernet, Fiber Channel, and OIF applications, allowing extended reach
upwards of 550 meters at 10 Gb/s for ultra long building backbones and medium length
campus backbones.
Redundancy
Fiber
optique
Backbone telephone
Horizontal cable
A workstation will include a minimum of 2 (two) outlets (e.g. one for telephone
application, the other one assigned to the data network).
Terminal outlets are to be made of cat.6A RJ45 8-pin modular jacks, normalised by
ISO 8877 (reference VDIB1772XU12 Schneider-Electric or equivalent).
RJ45 modular jacks are to be mounted on faceplate from the local standards. The
faceplate have to be properly equipped to accept screw-on adapters and splitters (i.e.
have a build-in nut).
Note : The outer size of the faceplate may be different if the screwing feature described
above is respected (e.g. ref. 5034 Schneider-Electric Italian plate).
Bridged taps and splitters shall not be used as part of the backbone cabling. (TIA/EIA-
568-B.1)
A workstation will include a minimum of 2 (two) outlets (e.g. one for telephone
application, the other one assigned to the data network).
Terminal outlets are to be made of cat.6A RJ45 9-pin modular jacks, normalised by
ISO 8877 (reference VDIB1772XB12 Schneider-Electric or equivalent).
RJ45 modular jacks are to be mounted on faceplate from the local standards. The
faceplate have to be properly equipped to accept screw-on adapters and splitters (i.e.
have a build-in nut).
Note : The outer size of the faceplate may be different if the screwing feature described
above is respected (e.g. ref. 5034 Schneider-Electric Italian plate).
Bridged taps and splitters shall not be used as part of the backbone cabling. (TIA/EIA-
568-B.1)
Entrance facility (EF)
The Entrance Facility consists of service entrance to the building including the building wall
Telecommunications rooms :
Dedicated telecommunications room :
LIGHTING
• Provide a minimum equivalent of 500 lux (50 foot-candles) measured 1 m (3 ft) above
finished floors.
• Avoid dimmer switches.
• Coordinate closely with the rack placements.
• Light fixtures mounted min 2.6m (8.5 ft) above finished floor.
• Emergency lighting is recommended. Place emergency lighting to ensure that the loss of
power to normal lights will not hamper an emergency exit from the TR.
• Power for lighting should not come from the power panel inside the TR. At least one light
should be on normal power, and one light should be on emergency power, if available.
DOORS
• Fully open (180 degrees) lockable doors with minimum door size 0.9 m (36 in) wide by 2m
(80 in) high.
• Door sills are not allowed because they impede the movement of equipment.
• Doors that open outward provide additional usable space and reduce constraints on TR
layout.
• Door should have a lock.
POWER SUPPLY
• Branch circuits for equipment power that are protected and cabled for 20 Amp capacity
(240 volts depending on the local utilities regulation)
• Minimum of two dedicated, non-switched, 3-cable, 240 volts (V) alternating current (ac)
duplex electrical outlets for equipment power, each on separate branch circuits.
• Separate duplex 240 Vac convenience electrical outlets (for tools, field test instruments,
located at least 150 mm (6 in) above finished floor and spaced at 1.8 m (6 ft) intervals
around perimeter walls.
• Light switch locations should be easily access upon entry.
• Electrical outlets must be on non-switched circuits (electrical outlet power must not be
controlled by a wall switch or other device that may lead to inadvertent loss of service).
• Consider providing emergency power or UPS backup to the TR with automatic switchover
capability, to ensure continuous operation of any active equipment located in the TR.
• Distribution panels that serve telecommunications equipment should be separate from
those that serve lighting fixtures.
Flood Prevention
Do not locate TRs in areas prone to flooding. Avoid locations that are below or adjacent to
areas of potential water hazard (e.g., areas below water table, restrooms and kitchens).
Clearances
• Minimum m (3 ft) of clear working space from equipment and cross-connect fields.
• 150 mm (6 in) depth off wall for wall-mounted equipment.
• Allocate a space of at least 1000 mm wide, 1000 mm deep, and 2.3 m high for each
PATCH PANELS
Patch panels will be pre-equipped with RJ45 cat.6A shielded (ref. VDIG118241BX0
ACTASSI S-ONE with a 360° shielding), or RJ45 cat.6A unshielded (ref.
VDIG118241UX0 Schneider-Electric).
Alternatively vertical patch cord routing rings (ref. VDIM189111 FOR 600X600 or
VDIM189112 for 800X800 Schneider-Electric) will be placed on the 19" uprights at each
side of the cabinet (4 rings per uprights is to be forecasted).
Shielded panels should include shutters removable from the panel for dust proof.
Optional coloured shutters should be supported to increase port identification.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
telecom panels
The sliding function does permit the use of the punch down tool for LSA contacts with
the panel in a sliding-out position. The telecom panel must have a cable identification to
avoid the need trying to figure out which cable goes where. The cable identification is
very clear on the clever fixing guides. Out of this identification a clear marking with pre-
printed labels and openable label holders will be part of the patch panel.
Finally, the panel has to have two earthing connection points for both shielded cables
and for the rack, easily accessible at the rear.
Page 46 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
Sliding Fiber optic panel 1U:
They will have a capacity of 4 positions equipped with 3 blank plates. Each plates will
have 3 SC/ST/LC or 6 ST SIMPLEX/LC DUPLEX.
The fiber patch panel will have a 0U cable management at the front with integrated clear
marking number in order to identify the cables. At the rear of the sliding fiber panel, a
rear quick fixation to use with a cable gland provide with the panel.
The patch panel has to be equipped with a transparent cover protection at the front, and
on the top of the panel. Finally, the panel will have one or two coiling wheels to avoid
tension on the connectors, and to respect the fiber bend radius. Labelling has to be
integrated on each side of the QUICKFIX system.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
Cable management:
In between each patch panel a patch cord guiding panel should be inserted. This patch
cord guiding panel should have 1 U height and be fixed with ONLY 2 screws. This
guiding panel must have 4 OPENABLE rings for ease of use, and as they have
OPENABLE, they also have to be able to be CLOSED.
Vertical rings :
Cable ties to bundle the cable are forbidden. Velcro should be used instead.
Multipair backbones cables coming from the Telephone Building Distributor will either be
terminated on 8-pairs modules or dedicated patch panels offering 50 RJ45 cat.3 ports on
1U (ref. VDIP141501 Schneider-Electric).
50 ports in 2 rows RJ45 patch panels will be given priority as it suits the universality
feature of a cabling system. Cable organizer and label holders is mandatory.
A cross connection from the telephone backbone to the horizontal cables will allocate an
extension number to the chosen telecommunication outlet.
Page 47 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
A quickfix function on both sides to allow simple fixing and sliding feature.
Telecommunication Outlet
All the wiring devices should be taken in the same range as infrastructure cabling
system, no Mather which installation method is chosen, the wiring devices will be
compliant to IEC 60364 / and HD384 series international standards.
The protection level following the IEC 60529 or l’EN 60529, should be minimum : IP 20
The shock resistance following the IEC 62262 or l’EN 62262 should be IK 02.
The wiring device should never exceed the local standard (ie : 45mm in France,
Belgium)
The wiring device will be compatible with every outlet without any adaptor or
dismantling.
The wiring device should be mounted next to each other without any space in between.
Every wiring device must have a clipsing mechanism without any tool. All
telecommunication outlet must be trivialized.
A minimum of 2 outlets per work area is recommend in case of use of IP-TELEPHONY.
Otherwise a complementary outlet should be considered.
The telecommunication outlets including or not 1 or 2 RJ45 will be ISO 8877 compliant,
defined by ISO IS11801, and TIA/EIA 568 TSB40, which description is done in (29.1.2
RJ45 Connector)
All the range of connectors have to be compliant with all the last international standards.
A valid certificate must be provided by third party laboratory (type :DELTA).
Each connector of the family is available in UTP or STP one piece device compact and
simple locking termination without any loose part, to avoid the installer to lose pieces ,
and to make it easier to handle.
The connector has to be tooless, U-Shaped cable entry, with a smart bridle with
elastomer insert for cable. Easy access for all cables. Automatic 360° earthing with
spring-loaded locking and earthing bridle.
The STP connector must have integrated earth-drain contact for the drain wire
connection, and double earthing for the STP version at the front.
The U shape entry is the same concept, S/FTP or F/FTP cables to enable them to keep
their structure intact (screens and foils are not damaged) transmission performance is
safe. No risk to tear and roll up the screen.
The U-shaped cable entry should be considered for reducing risk of damaging
connections. For the S/FTP et F/FTP (easy access for all cable)
Insulated plastic IDC housing eliminates short-circuit between conductors and metal
body.
The crossing of pairs is implemented before the cable’s introduction into the connector
for easy, secured and efficient wiring. The pair foil can be as near as possible to the
IDC.
The earth drain wire is inserted in an horizontal groove with entire security and is
terminated vertically down on the side of the connector. Secured integrated guiding parts
to enable reproductive position.
The connector has to be labelled on each side the colour coding from the standard EIA
568 A & B.
The connector has to be smooth design with rounded edges, and touch –friendly
materials to avoid injuries.
Performances :
The level of performance has been certified by an independent laboratory Delta with the
EIA/TIA and ISO 11801:2011 Ed2.2 Class E permanent link and channel. All the
parameters required have been surpassed by far during the test.
The test method « Direct Probing » will warranty the interoperability of the connector at
500Mhz, and met the requirement of the international IEC60512-99-001 ed 1 POEP
standard.
RJ45 WATERPROOF
The RJ Protek faceplate are specially design for industrial or laboraty environment,
surgery rooms where chemical, dust, humidity constraints are usual).
For Heavy steel industry vibration plants this RJ45 has improved resistance against
unplanned disconnexion due to high vibrations.
The Waterproof of the RJ45 is secured by the turn&lock, and this gives a IP55 in
surface mount and up to IP67 in flush mount.
Design considerations
Guidelines for planning the location of telecommunications outlet boxes in the Work
Area:
1. Each work area shall have a minimum of ONE telecommunications outlet box
location. TWO telecommunications outlet box locations should be provided and located
for future additional telecommunications outlets.
2. Work area telecommunications outlet box size.
ANSI/TIA/EIA-569-B, specifies the following:
3. Telecommunications outlet boxes may require supports for attaching the box and a
suitable faceplate to support the telecommunications outlet/connectors that are housed
by the work area telecommunications outlet box.
• Outlet boxes shall be no smaller than
The work area telecommunications outlet box should be located near an electrical outlet
(e.g., within 1 m [3 ft]) and installed at the same height if appropriate.
Page 52 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
5. Floor-mounted telecommunications outlet boxes and monuments (pedestals), and the
cables extending from them, can present a tripping hazard. The location of these
telecommunications outlet boxes should be coordinated with furniture to minimize such
hazards.
6. Cabling system performance may be sensitive to the arrangement and organization of
cable slack located behind the telecommunications outlet/connector. Sufficient space
must be provided in the telecommunications outlet box or equivalent space so that
minimum cable bend radius requirements are not exceeded.
7. The location, mounting, or strain relief of the telecommunications outlet/connector
should allow pathway covers and trim to be removed without disturbing the cable
termination. Care should be exercised to ensure that telecommunications outlet/
connectors are mounted in such a way that they do not significantly reduce the required
pathway cabling capacity.
8. Open office furniture openings provide for mounting faceplates containing one or
more telecommunications outlet/connectors. Two standard sizes of openings are
specified:
All four pairs in the cable shall be terminated in an 8-position modular outlet/connector at
the work area. These connectors may be x/xTP, as described in the above section.
Two wiring schemes are specified in the ANSI/TIA/EIA 568-B.1 Clause 6.2.1. The
pin/pair assignments for T568A and T568B are shown in Figure 1.19b depicting the front
view of each telecommunications outlet/connector.
T568A is the preferred wiring scheme, and T568B optional if necessary to accommodate
certain pre-existing 8-pin cabling systems.
When selecting a connector, make sure it is specified and tested to meet ANSI/TIA/EIA-
568-B.2.
Connecting hardware should be marked to designate transmission performance at the
discretion of the manufacturer or approval agency. The markings, if any, shall be visible
during installation. It is suggested that such markings consist of:
f) the consolidation point shall be located so that each work area group is served by at
least one consolidation point;
g) the consolidation point should be limited to serving a maximum of twelve work
areas ;
h) a consolidation point should be located in accessible locations ;
i) the consolidation point should be located so that there is at least 15m from it to the
floor distributor ;
j) CP cables are to be of the same type than capillary cable and are to be equipped
with RJ45 plugs recommended by the manufacturer.
• Category 6 , (see 3.3 Chapter)
• Optical fiber ……………..(see 3.3 Chapter)
When using adapters (e.g., installing a balun), the adaptors must be external to the
telecommunications outlet/connector or MUTOA. For further information, see Cabling
Adapters in CORE-2: Horizontal Distribution Systems. The cabling infrastructure
designer needs to be aware that these work area equipment-specific adaptors may or
may not offer the same level of transmission performance as the cabling systems to
which they connect.
• A special cable or adapter is required when the equipment connector is different from
the telecommunications outlet/connector.
The maximum horizontal cable length of 90 m (295 ft) is based on a maximum length of
5 m (16 ft) of work area cable. The combined length of equipment cables, work area
cords, and patch cords in the telecommunications room (TR) or equipment room (ER)
shall not exceed 10 m (33 ft), with the exception of MUTOA where longer work area
cables are used. In the case of MUTOA’s, the horizontal cable length is reduced when
the work area cords exceed 5m.
Cable Pulling
The maximum pulling tension for a 4-pair balanced twisted pair cable must not exceed
25 lbf (110N). Exceeding this tension will result in transmission degradation and may
affect the system’s ability to pass certification testing.
STRAIN RELIEF
Cables shall be free of physical stress over the entire length of the run. Use of cable
supports, Velcro ties are recommended for strain relieving. Do not over tighten straps or
tie-wraps to avoid damage to the cable.
Velcro ties shall always be used for bundling cables properly in channels and raceways.
Cables distributed to the same work area zone may be bundled together.
The maximum number of cables per bundle shall not exceed 50 cables.
DEFINITIONS
CP: Consolidation Point - a location for the interconnection between horizontal cables
that extend from building pathways and horizontal cables that extend into work areas.
MUTOA: Multi-user Telecommunications Outlet Assembly - a grouping in one
housing of several telecommunications outlets/connectors.
Open Office - a floor space division provided by furniture, movable partitions, or other
means, instead of building walls.
Design goals
Page 58 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
A good cabling plant design always considers possible changes in user requirements in
the future. The horizontal cabling is often very inaccessible after the building is
completed and can incur high cost of changes and result in disruption to occupants and
their work.
Avoiding EMI
1. Maintain physical separation between possible sources and the telecommunications
cabling.
1. Optical fiber and shielded cable should be used for buildings with high levels of
ambient EMI.
2. Balanced twisted-pair cabling, such as Category 5e or better (Category 6
recommended), can offer a certain degree of noise immunity that ensures reliable
transmission in most environments (e.g., electrical field intensity less than 3 volts per
meter [V/m]).
b) The shield of FTP cables shall be bonded through a conducting path to the
telecommunications grounding bus-bar (TGB) in the telecommunications room.
c) Shielded connections at the work area are accomplished through a FTP patch cord.
d) Grounding at the work area is usually accomplished through the equipment power
connection.
e) At the work area end of the horizontal cabling, the voltage measured between the
shield and the ground wire of the electrical outlet used to supply power to the work
station shall not exceed Vrms.
f) All patch panel and RJ45 connector have to be direct earthing.
Administration
Schneider Electric Network Connectivity requires proper and systematic methods and
procedures for labelling and management of horizontal cabling. The guidelines and
requirements for the administration of horizontal cabling systems comply to and make
references to ANSI/TIE/EIA-606-A.
1) All cabling must be identified at both ends of the run.
2) Markings on the cable must be:
a) Clearly visible after installation.
b) Easily distinguishable from any manufacturers marking on the cable.
c) Can last the full duration of the warranty
Category Mixture
Multiple-category balanced twisted-pair system can be confusing and costly to maintain.
Schneider Electric endorses the use of single category of cabling components, selected
for use in a cabling system. Schneider Electric system warranty does not recognize the
use of mix and match categories in a installed cabling system.
Crossovers/Polarity
When there is a need to connect a transmitter on one end and a receiver on the other, a
cross over cable is required of the copper pair or fiber cores.
Copper
– If crossover cables are required for copper based cable application, they may be used
only outside of the horizontal cabling system. Active equipment will provide the right
polarity if need (MDI/MDI-X).
Optical Fiber
– The optical fiber cabling link shall be installed in a pair-wise crossover orientation in
which the optical fibers of a pair identified as Position A and Position B at one end are
reversed and identified as Position B and Position A (respectively) at the other end.
– This pair-wise crossover for optical fibers is achieved by using connector polarity and
labelling methodologies that apply to horizontal cables, patch cords, equipment cords,
and duplex optical fiber adapters.
NOTE: The colours indicated are associated with horizontal balanced twisted-pair cable.
Colour coding for equipment cables, work area cords, patch cords, and jumpers may vary.
Length limitation
1) The installation length limit of 300m applies to the interconnection and splice
methods. It is based on the combined length of horizontal cable, backbone cable,
equipment cables, cross-connections, and patch cords.
Within the 300 m limit, multimode cabling system will support gigabit services using
centralized networking devices with appropriate optical fiber cable.
2) The cabling length limitation of 90m is associated with the pull-through method. It is
based on the length of horizontal cable from the MC (CD) to the TO/WA.
The total allowable length of additional equipment cables at the MC (CD) and equipment
cables in the work area is 10m with the pull-through method.
SPECIFIC REQUIREMENTS
3.1.7 ENCLOSURE :
Floor-standing cabinet made of galvanized steel symmetric uprights and following
dimension Height:1200, 1400, 1600, 1800, 2000, 2200, Width: 600/750, 800, Depth:
600/800,1000, 1060,1200. Cabinet should be coated with epoxy-polyester powder hot
polymerized in textured RAL 7035 for better corrosion resistance.
All the side panels must be flush with the framework to avoid surprises during the
installation process. For joined enclosures the total length of the set must be the sum of
the individual enclosures that form it to avoid surprises during the installation.
For easier installation and maintenance the cabinet must allow installation of doors on
front and back sides (without special accessories) and installation of 2 doors in the same
upright.
In case that two or more enclosures are installed together the doors should be able to
open without interfering with the adjacent enclosures.
Doors:
Sheet steel plain / transparent door , provided with foamed-in polyurethane gasket and
front door opening. Door shall be provided of adjustable reinforcement frame for
increased ruggedness and assembly of accessories.
The impact strength as per IEC 62262 shall be IK10. For enclosures with transparent
door must not have any effect on IP degree however, IK08 is acceptable.
Enclosure should allow door opening change. For safety reasons the door must not fall
off when totally open and the pins are off the axis of the hinge. Door opening of 180º for
easy maintenance.
Accessories:
Enclosure shall be supplied with 19‖ uprights, 100mm / 200mm / no mm base/plinth,
with/without document pocket, earthing straps, with/without 19‖ profiles, eyebolts / lifting
brackets / lifting bars, with/without door switch & lamp.
LOCATION OF THE ER
Consider the following when choosing a location for the ER,
Distance from telecommunications cable pathways
Space required for the equipment.
Expandability
Cater for access for large equipment and cables.
Facilities that serve and are served by the ER.
Service Provider (SP) equipment requirements.
Distance from electrical service and mechanical equipment.
Sources of electromagnetic interference (EMI).
Ceiling Requirements
The recommended height of the ceiling in an ER is at least 3 m (10 ft). Ceiling protrusions
(e.g., sprinkler heads) must be placed to assure a minimum clear height of 2.4 m (8 ft) that
For fewer than 200 work areas, the minimum ER size shall be no less than 14 m 2.
ER shall have access to the main HVAC 24 hours per day, 365 days per year.
• Temperature will be controlled to 18°-24°C (64°-7 5°F).
• Humidity shall be in the range of 30 to 50%. Both humidity and temperature will be
measured 1.5m off the floor.
LIGHTING
• Provide a minimum equivalent of 500 lux (50 foot-candles) measured 1 m above finished
floors.
• Avoid dimmer switches.
• Coordinate closely with the rack placements.
• Light fixtures mounted min 2.6m above finished floor.
• Emergency lighting is recommended. Place emergency lighting to ensure that the loss of
power to normal lights will not hamper an emergency exit from the ER.
• Power for lighting should not come from the power panel inside the ER. At least one light
should be on normal power, and one light should be on emergency power, if available.
FIRE SAFETY
Appropriate portable fire extinguishers shall be kept in ER near the entry or exit.
Power Conditioning
The sensitivity of telecommunications equipment to electrical power fluctuations is a
significant issue in assuring system reliability and longevity. Assess the need for power
conditioner before telecommunications equipment is installed. Many UPS devices will
provide the required power conditioning.
3.1.13 BACKBONES :
Telephone building distributor (TBD)
It is the link between the Private Block Exchange (PBX) and the telephone network, it
permit the allocation of telephone extensions to any floor distributor by the only mean of
cross connections.
Telephone lines within building distributor can be either terminated on 8 pairs modules
or dedicated RJ45 patch panel (ref. VDIG141501 Schneider-Electric). The TBD is to be
located next to the PBX in an area with no electromagnetic disturbances.
Telephone backbones :
As these cables are designed to carry only telephone signals at 64 Kbits cat.3
performance level is sufficient. They will consist of VDIC235212 (Schneider-Electric)
Multi-pair cable (128 pairs).
Note : To comply with the principle of standardisation of horizontal links, capillary cables
will address the general performance requirements of the cabling system (cat.5 e of
above).
Data backbones :
- For indoor use, the fiber cable will be non-armoured. An anti-rodent protection may be
included. It should have a tight buffered structure.
- For outdoor use, the fiber cable will be armoured and provide an anti-rodent protection.
It should either have a tight buffered or loose tube structure.
LAN fiber optic cables are multimode 50/125 µm type OM3 or OM 4 in a tight buffer
structure, connected to SC, ST or LC connectors. For greater sites, the use of dedicated
fiber cables (12 or 24 cores) is advisable (ref. VDIC52412T or VDIC52424T)
Cable types
High-end copper LAN cables for performances from category 6 to category 6A 500 Mhz.
While exceeding international standards by 3 dB minimum on NEXT & RL, the cable
should have better resistance to the mechanical constraints.
LAN copper cables for category 6A with a single-foil metallic cross-filler, providing high
performance and reliable shielded installations. While exceeding international standards
by 3 dB minimum on NEXT & RL, the cable must provide superior shielding, faster
installations and increased efficiency.
Certificates
All LAN cables from Category 6 have to be certified at a component level by the
independent third-party laboratory Delta. Certificates are regularly updated to be
compliant to the latest and highest international standards.
Horizontal cables will be made of 4 twisted copper pairs cable cat.6 UTP. They will
consist of CL-MNC cable (100 ohms) from Schneider-Electric or equivalent.
These cables will be made of halogen free compound. A central cross has to be
included in the cable. Among other features, this cross has to be asymmetric and should
have an integrated pair blocking system (DCBS technology).
The total length of a single link should not exceed 90 meters.
Cable sheath should be blue or green, and the NVP should be printed.
LSZH
LSZH (Low Smoke Zero Halogen) sheath according to test methods IEC 61034 (smoke
density), IEC 60754-1 (gas toxicity), IEC 60754-2 (gas corrosiveness) for Tight buffered
and Loose tube cables.
Flame retardant
Flame retardant (self extinguishing) according to IEC 60332-1 for Tight buffered and
Loose tube cables.
Page 73 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
Fire retardant
Fire retardant (no fire propagation along the cable) according to IEC 60332-3C for Tight
buffered cables.
The CL-MX cable is wrapped in one single foil, this means less cutting and improved
quality of cable preparation.
The Actassi Indoor/Outdoor Loose tube LSZH Cables pass most of the following tests:
1) IEC 60754 part 3, Acidity/Corrosively based on pH and Conductivity Measurements
2) IEC 60332-1, Flame Retardant
3) NES 713, Toxicity Index
4) IEC 61034, Smoke Emissions
All cables shall be 4-pair unshielded Twisted Pair (UTP) cables meeting or exceeding
the quality and performance requirements for Category 6 UTP cables stipulated in
EIA/TIA-568-B.2-1 standard. Each Category 6 UTP cable shall be terminated on an 8-
conductor Category 6 jack in accordance with the EIA/TIA-568B wiring code;
The cable shall be solid or stranded copper conductors of 23 AWG insulated with high
density, PVC or LSZH sheath. Cross filler with optimized design and micro-blades,
is preferred
The cable shall be accompanied with traceable serial numbers from the manufacturer
indicated on the packaging to assist in quality validation of the installed cables;
The cable shall provide the guaranteed channel performance specifications of the
Category 6 Channel complies to EIA/TIA-568-B.2-1 standard.
Each pair should have an impedance of 100 Ohms, with+/- 15 Ohms, tolerance.
Copper :
Geometrical characteristics of fiber optic jumpers are to be the same than fiber optic
links cables.
OM3 and OM4 have an additional laser launch modal bandwidth as OM3 and OM4 are
designed to be laser optimized. The difference between ―Overfilled Launch" and ―Laser
Launch" is the test method. A new test method simulating a VCSEL laser launch (TIA-455-
220A and IEC 60793-1-49) was deemed appropriate for these fibers which are intended for
use with VCSELs at higher speeds.
OM4 fiber is a laser-optimized, high bandwidth 50um multimode fiber. Formerly, it was
called OM3-550 fiber. TIA approved EIA/TIA 492AAAD (OM4) on August 5, 2009
OM4 fiber is designed to enhance the system cost benefits enabled by 850nm VCSELs for
existing 1 Gb/s and 10 Gb/s applications as well as future 40 Gb/s and 100 Gb/s systems.
OM4 fiber supports Ethernet, Fiber Channel, and OIF applications, allowing extended reach
upwards of 550 meters at 10 Gb/s for ultra long building backbones and medium length
campus backbones.
Redundancy
Fiber
optique
Backbone telephone
Horizontal cable
- Terminal outlet :
A workstation will include a minimum of 2 (two) outlets (e.g. one for telephone
application, the other one assigned to the data network).
Terminal outlets are to be made of cat.6 RJ45 8-pin modular jacks, normalised by ISO
8877 (reference VDIB17726U12 Schneider-Electric or equivalent).
RJ45 modular jacks are to be mounted on faceplate from the local standards. The
faceplate have to be properly equipped to accept screw-on adapters and splitters (i.e.
have a build-in nut).
Note : The outer size of the faceplate may be different if the screwing feature described
above is respected (e.g. ref. 5034 Schneider-Electric Italian plate).
Bridged taps and splitters shall not be used as part of the backbone cabling. (TIA/EIA-
568-B.1)
A workstation will include a minimum of 2 (two) outlets (e.g. one for telephone
application, the other one assigned to the data network).
Terminal outlets are to be made of cat.6 RJ45 9-pin modular jacks, normalised by ISO
8877 (reference VDIB17726U12 Schneider-Electric or equivalent).
RJ45 modular jacks are to be mounted on faceplate from the local standards. The
faceplate have to be properly equipped to accept screw-on adapters and splitters (i.e.
have a build-in nut).
Note : The outer size of the faceplate may be different if the screwing feature described
above is respected (e.g. ref. 5034 Schneider-Electric Italian plate).
Bridged taps and splitters shall not be used as part of the backbone cabling. (TIA/EIA-
568-B.1)
Page 80 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
Entrance facility (EF)
The Entrance Facility consists of service entrance to the building including the building wall
penetration and continuing to the ER. The EF may also contain backbone paths to link other
buildings as well as antenna entrances.
• All carriers and telecommunications providers involved in providing service shall be
contacted to establish their requirements.
• Easements, permits and rights of way may be required.
• A service entrance pathway shall be provided (underground, aerial, buried).
• See standard for specifications defining manholes, penetrations, etc.
• Grounding and bonding to NEC or local code guidelines.
Telecommunications rooms :
Dedicated telecommunications room :
LIGHTING
• Provide a minimum equivalent of 500 lux (50 foot-candles) measured 1 m (3 ft) above
finished floors.
• Avoid dimmer switches.
• Coordinate closely with the rack placements.
• Light fixtures mounted min 2.6m (8.5 ft) above finished floor.
• Emergency lighting is recommended. Place emergency lighting to ensure that the loss of
power to normal lights will not hamper an emergency exit from the TR.
• Power for lighting should not come from the power panel inside the TR. At least one light
should be on normal power, and one light should be on emergency power, if available.
DOORS
• Fully open (180 degrees) lockable doors with minimum door size 0.9 m (36 in) wide by 2m
(80 in) high.
• Door sills are not allowed because they impede the movement of equipment.
• Doors that open outward provide additional usable space and reduce constraints on TR
layout.
• Door should have a lock.
POWER SUPPLY
• Branch circuits for equipment power that are protected and cabled for 20 Amp capacity
(240 volts depending on the local utilities regulation)
• Minimum of two dedicated, non-switched, 3-cable, 240 volts (V) alternating current (ac)
duplex electrical outlets for equipment power, each on separate branch circuits.
• Separate duplex 240 Vac convenience electrical outlets (for tools, field test instruments,
located at least 150 mm (6 in) above finished floor and spaced at 1.8 m (6 ft) intervals
around perimeter walls.
• Light switch locations should be easily access upon entry.
• Electrical outlets must be on non-switched circuits (electrical outlet power must not be
controlled by a wall switch or other device that may lead to inadvertent loss of service).
• Consider providing emergency power or UPS backup to the TR with automatic switchover
capability, to ensure continuous operation of any active equipment located in the TR.
• Distribution panels that serve telecommunications equipment should be separate from
those that serve lighting fixtures.
Flood Prevention
Do not locate TRs in areas prone to flooding. Avoid locations that are below or adjacent to
areas of potential water hazard (e.g., areas below water table, restrooms and kitchens).
Clearances
• Minimum m (3 ft) of clear working space from equipment and cross-connect fields.
• 150 mm (6 in) depth off wall for wall-mounted equipment.
• Allocate a space of at least 1000 mm wide, 1000 mm deep, and 2.3 m high for each
PATCH PANELS
Patch panels will be pre-equipped with RJ45 cat.6 shielded (ref. VDIG118241B60
ACTASSI S-ONE with a 360° shielding), or RJ45 cat.6 unshielded (ref.
VDIG118241U60 Schneider-Electric).
Alternatively vertical patch cord routing rings (ref. VDIM189111 for 600X600 or
VDIM189112 for 800X800 Schneider-Electric) will be placed on the 19" uprights at each
side of the cabinet (4 rings per uprights is to be forecasted).
Shielded panels should include shutters removable from the panel for dust proof.
Optional coloured shutters should be supported to increase port identification.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
telecom panels
The sliding function does permit the use of the punch down tool for LSA contacts with
the panel in a sliding-out position. The telecom panel must have a cable identification to
avoid the need trying to figure out which cable goes where. The cable identification is
very clear on the clever fixing guides. Out of this identification a clear marking with pre-
printed labels and openable label holders will be part of the patch panel.
They will have a capacity of 4 positions equipped with 3 blank plates. Each plates will
have 3 SC/ST/LC or 6 ST SIMPLEX/LC DUPLEX.
The fiber patch panel will have a 0U cable management at the front with integrated clear
marking number in order to identify the cables. At the rear of the sliding fiber panel, a
rear quick fixation to use with a cable gland provide with the panel.
The patch panel has to be equipped with a transparent cover protection at the front, and
on the top of the panel. Finally, the panel will have one or two coiling wheels to avoid
tension on the connectors, and to respect the fiber bend radius. Labelling has to be
integrated on each side of the QUICKFIX system.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
Cable management:
In between each patch panel a patch cord guiding panel should be inserted. This patch
cord guiding panel should have 1 U height and be fixed with ONLY 2 screws. This
guiding panel must have 4 OPENABLE rings for ease of use, and as they have
OPENABLE, they also have to be able to be CLOSED.
Vertical rings :
Cable ties to bundle the cable are forbidden. Velcro should be used instead.
Multipair backbones cables coming from the Telephone Building Distributor will either be
terminated on 8-pairs modules or dedicated patch panels offering 50 RJ45 cat.3 ports on
1U (ref. VDIP141501 Schneider-Electric).
50 ports in 2 rows RJ45 patch panels will be given priority as it suits the universality
feature of a cabling system. Cable organizer and label holders is mandatory.
Page 85 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
A cross connection from the telephone backbone to the horizontal cables will allocate an
extension number to the chosen telecommunication outlet.
A quickfix function on both sides to allow simple fixing and sliding feature.
Telecommunication Outlet
All the wiring devices should be taken in the same range as infrastructure cabling
system, no Mather which installation method is chosen, the wiring devices will be
compliant to IEC 60364 / and HD384 series international standards.
The protection level following the IEC 60529 or l’EN 60529, should be minimum : IP 20
The shock resistance following the IEC 62262 or l’EN 62262 should be IK 02.
The wiring device should never exceed the local standard (ie : 45mm in France,
Belgium)
The wiring device will be compatible with every outlet without any adaptor or
dismantling.
The wiring device should be mounted next to each other without any space in between.
Every wiring device must have a clipsing mechanism without any tool. All
telecommunication outlet must be trivialized.
A minimum of 2 outlets per work area is recommend in case of use of IP-TELEPHONY.
Otherwise a complementary outlet should be considered.
The telecommunication outlets including or not 1 or 2 RJ45 will be ISO 8877 compliant,
defined by ISO IS11801, and TIA/EIA 568 TSB40, which description is done in (29.1.2
RJ45 Connector)
RJ45 Connector
Each connector of the family is available in UTP or STP one piece device compact and
simple locking termination without any loose part, to avoid the installer to lose pieces ,
and to make it easier to handle.
The connector has to be tooless, U-Shaped cable entry, with a smart bridle with
elastomer insert for cable. Easy access for all cables. Automatic 360° earthing with
spring-loaded locking and earthing bridle.
The STP connector must have integrated earth-drain contact for the drain wire
connection, and double earthing for the STP version at the front.
The U shape entry is the same concept, S/FTP or F/FTP cables to enable them to keep
their structure intact (screens and foils are not damaged) transmission performance is
safe. No risk to tear and roll up the screen.
The U-shaped cable entry should be considered for reducing risk of damaging
connections. For the S/FTP et F/FTP (easy access for all cable)
Insulated plastic IDC housing eliminates short-circuit between conductors and metal
body.
The crossing of pairs is implemented before the cable’s introduction into the connector
for easy, secured and efficient wiring. The pair foil can be as near as possible to the
IDC.
The earth drain wire is inserted in an horizontal groove with entire security and is
terminated vertically down on the side of the connector. Secured integrated guiding parts
to enable reproductive position.
The connector has to be labelled on each side the colour coding from the standard EIA
568 A & B.
The connector has to be smooth design with rounded edges, and touch –friendly
materials to avoid injuries.
Performances :
The level of performance has been certified by an independent laboratory Delta with the
EIA/TIA and ISO 11801:2011 Ed2.2 Class E permanent link and channel. All the
parameters required have been surpassed by far during the test.
The test method « Direct Probing » will warranty the interoperability of the connector at
500Mhz, and met the requirement of the international IEC60512-99-001 ed 1 POEP
standard.
RJ45 WATERPROOF
The RJ Protek faceplate are specially design for industrial or laboraty environment,
surgery rooms where chemical, dust, humidity constraints are usual).
For Heavy steel industry vibration plants this RJ45 has improved resistance against
unplanned disconnexion due to high vibrations.
The Waterproof of the RJ45 is secured by the turn&lock, and this gives a IP55 in
surface mount and up to IP67 in flush mount.
Design considerations
Guidelines for planning the location of telecommunications outlet boxes in the Work
Area:
1. Each work area shall have a minimum of ONE telecommunications outlet box
location. TWO telecommunications outlet box locations should be provided and located
for future additional telecommunications outlets.
2. Work area telecommunications outlet box size.
ANSI/TIA/EIA-569-B, specifies the following:
3. Telecommunications outlet boxes may require supports for attaching the box and a
suitable faceplate to support the telecommunications outlet/connectors that are housed
by the work area telecommunications outlet box.
• Outlet boxes shall be no smaller than
The work area telecommunications outlet box should be located near an electrical outlet
(e.g., within 1 m [3 ft]) and installed at the same height if appropriate.
Page 90 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
5. Floor-mounted telecommunications outlet boxes and monuments (pedestals), and the
cables extending from them, can present a tripping hazard. The location of these
telecommunications outlet boxes should be coordinated with furniture to minimize such
hazards.
6. Cabling system performance may be sensitive to the arrangement and organization of
cable slack located behind the telecommunications outlet/connector. Sufficient space
must be provided in the telecommunications outlet box or equivalent space so that
minimum cable bend radius requirements are not exceeded.
7. The location, mounting, or strain relief of the telecommunications outlet/connector
should allow pathway covers and trim to be removed without disturbing the cable
termination. Care should be exercised to ensure that telecommunications outlet/
connectors are mounted in such a way that they do not significantly reduce the required
pathway cabling capacity.
8. Open office furniture openings provide for mounting faceplates containing one or
more telecommunications outlet/connectors. Two standard sizes of openings are
specified:
All four pairs in the cable shall be terminated in an 8-position modular outlet/connector at
the work area. These connectors may be x/xTP, as described in the above section.
Two wiring schemes are specified in the ANSI/TIA/EIA 568-B.1 Clause 6.2.1. The
pin/pair assignments for T568A and T568B are shown in Figure 1.19b depicting the front
view of each telecommunications outlet/connector.
T568A is the preferred wiring scheme, and T568B optional if necessary to accommodate
certain pre-existing 8-pin cabling systems.
When selecting a connector, make sure it is specified and tested to meet ANSI/TIA/EIA-
568-B.2.
Connecting hardware should be marked to designate transmission performance at the
discretion of the manufacturer or approval agency. The markings, if any, shall be visible
during installation. It is suggested that such markings consist of:
k) the consolidation point shall be located so that each work area group is served by at
least one consolidation point;
l) the consolidation point should be limited to serving a maximum of twelve work
areas ;
m) a consolidation point should be located in accessible locations ;
n) the consolidation point should be located so that there is at least 15m from it to the
floor distributor ;
o) CP cables are to be of the same type than capillary cable and are to be equipped
with RJ45 plugs recommended by the manufacturer.
• Category 5e ……………...(see 3.3 Chapter)
• Optical fiber ……………..(see 3.3 Chapter)
When using adapters (e.g., installing a balun), the adaptors must be external to the
telecommunications outlet/connector or MUTOA. For further information, see Cabling
Adapters in CORE-2: Horizontal Distribution Systems. The cabling infrastructure
designer needs to be aware that these work area equipment-specific adaptors may or
• Active adapters (e.g. Fiber Optic transceivers) that may be needed when connecting
devices that use different signalling schemes.
• A special cable or adapter is required when the equipment connector is different from
the telecommunications outlet/connector.
The maximum horizontal cable length of 90 m (295 ft) is based on a maximum length of
5 m (16 ft) of work area cable. The combined length of equipment cables, work area
cords, and patch cords in the telecommunications room (TR) or equipment room (ER)
shall not exceed 10 m (33 ft), with the exception of MUTOA where longer work area
cables are used. In the case of MUTOA’s, the horizontal cable length is reduced when
the work area cords exceed 5m.
Cable Pulling
The maximum pulling tension for a 4-pair balanced twisted pair cable must not exceed
25 lbf (110N). Exceeding this tension will result in transmission degradation and may
affect the system’s ability to pass certification testing.
STRAIN RELIEF
Cables shall be free of physical stress over the entire length of the run. Use of cable
supports, Velcro ties are recommended for strain relieving. Do not over tighten straps or
tie-wraps to avoid damage to the cable.
Velcro ties shall always be used for bundling cables properly in channels and raceways.
Cables distributed to the same work area zone may be bundled together.
The maximum number of cables per bundle shall not exceed 50 cables.
DEFINITIONS
CP: Consolidation Point - a location for the interconnection between horizontal cables
that extend from building pathways and horizontal cables that extend into work areas.
MUTOA: Multi-user Telecommunications Outlet Assembly - a grouping in one
housing of several telecommunications outlets/connectors.
Open Office - a floor space division provided by furniture, movable partitions, or other
means, instead of building walls.
Design goals
Page 96 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
A good cabling plant design always considers possible changes in user requirements in
the future. The horizontal cabling is often very inaccessible after the building is
completed and can incur high cost of changes and result in disruption to occupants and
their work.
Avoiding EMI
1. Maintain physical separation between possible sources and the telecommunications
cabling.
1. Optical fiber and shielded cable should be used for buildings with high levels of
ambient EMI.
2. Balanced twisted-pair cabling, such as Category 5e or better (Category 6
recommended), can offer a certain degree of noise immunity that ensures reliable
transmission in most environments (e.g., electrical field intensity less than 3 volts per
meter [V/m]).
b) The shield of FTP cables shall be bonded through a conducting path to the
telecommunications grounding bus-bar (TGB) in the telecommunications room.
c) Shielded connections at the work area are accomplished through a FTP patch cord.
d) Grounding at the work area is usually accomplished through the equipment power
connection.
e) At the work area end of the horizontal cabling, the voltage measured between the
shield and the ground wire of the electrical outlet used to supply power to the work
station shall not exceed Vrms.
f) All patch panel and RJ45 connector have to be direct earthing.
Administration
Schneider Electric Network Connectivity requires proper and systematic methods and
procedures for labelling and management of horizontal cabling. The guidelines and
requirements for the administration of horizontal cabling systems comply to and make
references to ANSI/TIE/EIA-606-A.
1) All cabling must be identified at both ends of the run.
2) Markings on the cable must be:
a) Clearly visible after installation.
b) Easily distinguishable from any manufacturers marking on the cable.
c) Can last the full duration of the warranty
Category Mixture
Multiple-category balanced twisted-pair system can be confusing and costly to maintain.
Schneider Electric endorses the use of single category of cabling components, selected
for use in a cabling system. Schneider Electric system warranty does not recognize the
use of mix and match categories in a installed cabling system.
Crossovers/Polarity
When there is a need to connect a transmitter on one end and a receiver on the other, a
cross over cable is required of the copper pair or fiber cores.
Copper
– If crossover cables are required for copper based cable application, they may be used
only outside of the horizontal cabling system. Active equipment will provide the right
polarity if need (MDI/MDI-X).
Optical Fiber
– The optical fiber cabling link shall be installed in a pair-wise crossover orientation in
which the optical fibers of a pair identified as Position A and Position B at one end are
reversed and identified as Position B and Position A (respectively) at the other end.
– This pair-wise crossover for optical fibers is achieved by using connector polarity and
labelling methodologies that apply to horizontal cables, patch cords, equipment cords,
and duplex optical fiber adapters.
NOTE: The colours indicated are associated with horizontal balanced twisted-pair cable.
Colour coding for equipment cables, work area cords, patch cords, and jumpers may vary.
Length limitation
1) The installation length limit of 300m applies to the interconnection and splice
methods. It is based on the combined length of horizontal cable, backbone cable,
equipment cables, cross-connections, and patch cords.
Within the 300 m limit, multimode cabling system will support gigabit services using
centralized networking devices with appropriate optical fiber cable.
2) The cabling length limitation of 90m is associated with the pull-through method. It is
based on the length of horizontal cable from the MC (CD) to the TO/WA.
The total allowable length of additional equipment cables at the MC (CD) and equipment
cables in the work area is 10m with the pull-through method.
SPECIFIC REQUIREMENTS
4.1.7 ENCLOSURE :
Floor-standing cabinet made of galvanized steel symmetric uprights and following
dimension Height:1200, 1400, 1600, 1800, 2000, 2200, Width: 600/750, 800, Depth:
600/800,1000, 1060,1200. Cabinet should be coated with epoxy-polyester powder hot
polymerized in textured RAL 7035 for better corrosion resistance.
All the side panels must be flush with the framework to avoid surprises during the
installation process. For joined enclosures the total length of the set must be the sum of
the individual enclosures that form it to avoid surprises during the installation.
For easier installation and maintenance the cabinet must allow installation of doors on
front and back sides (without special accessories) and installation of 2 doors in the same
upright.
In case that two or more enclosures are installed together the doors should be able to
open without interfering with the adjacent enclosures.
Doors:
Sheet steel plain / transparent door , provided with foamed-in polyurethane gasket and
front door opening. Door shall be provided of adjustable reinforcement frame for
increased ruggedness and assembly of accessories.
Door shall be supplied with an opening handle to allow easy door managing when
equipped,
and shall be provided with a closing system locked by a key number 333.
Enclosure should allow door opening change. For safety reasons the door must not fall
off when totally open and the pins are off the axis of the hinge. Door opening of 180º for
easy maintenance.
Accessories:
Enclosure shall be supplied with 19‖ uprights, 100mm / 200mm / no mm base/plinth,
with/without document pocket, earthing straps, with/without 19‖ profiles, eyebolts / lifting
brackets / lifting bars, with/without door switch & lamp.
For ED switchboards and Industrial Control boards the supplier must present a thermal
study clearly indicating if thermal management measures are needed, and:
> Highest temperature of the board without temperature management
> Necessary cooling power
> Cooling power offered by the solution
> & the calculations made
LOCATION OF THE ER
Consider the following when choosing a location for the ER,
Distance from telecommunications cable pathways
Space required for the equipment.
Expandability
Cater for access for large equipment and cables.
Facilities that serve and are served by the ER.
Service Provider (SP) equipment requirements.
Distance from electrical service and mechanical equipment.
Sources of electromagnetic interference (EMI).
Ceiling Requirements
The recommended height of the ceiling in an ER is at least 3 m (10 ft). Ceiling protrusions
(e.g., sprinkler heads) must be placed to assure a minimum clear height of 2.4 m (8 ft) that
is clear of obstructions, to provide space over the equipment frames for cables and
suspended cable trays.
Some equipment may require additional ceiling clearance, depending upon the
manufacturer’s specifications.
For fewer than 200 work areas, the minimum ER size shall be no less than 14 m 2.
ER shall have access to the main HVAC 24 hours per day, 365 days per year.
• Temperature will be controlled to 18°-24°C (64°-7 5°F).
• Humidity shall be in the range of 30 to 50%. Both humidity and temperature will be
measured 1.5m off the floor.
LIGHTING
• Provide a minimum equivalent of 500 lux (50 foot-candles) measured 1 m above finished
floors.
• Avoid dimmer switches.
• Coordinate closely with the rack placements.
• Light fixtures mounted min 2.6m above finished floor.
• Emergency lighting is recommended. Place emergency lighting to ensure that the loss of
power to normal lights will not hamper an emergency exit from the ER.
• Power for lighting should not come from the power panel inside the ER. At least one light
should be on normal power, and one light should be on emergency power, if available.
FIRE SAFETY
Appropriate portable fire extinguishers shall be kept in ER near the entry or exit.
Power Conditioning
The sensitivity of telecommunications equipment to electrical power fluctuations is a
significant issue in assuring system reliability and longevity. Assess the need for power
conditioner before telecommunications equipment is installed. Many UPS devices will
provide the required power conditioning.
4.1.13 BACKBONES :
Telephone building distributor (TBD)
It is the link between the Private Block Exchange (PBX) and the telephone network, it
permit the allocation of telephone extensions to any floor distributor by the only mean of
cross connections.
Telephone lines within building distributor can be either terminated on 8 pairs modules
or dedicated RJ45 patch panel (ref. VDIG141501 Schneider-Electric). The TBD is to be
located next to the PBX in an area with no electromagnetic disturbances.
Telephone backbones :
As these cables are designed to carry only telephone signals at 64 Kbits cat.3
performance level is sufficient. They will consist of VDIC235212 (Schneider-Electric)
Multi-pair cable (128 pairs).
Note : To comply with the principle of standardisation of horizontal links, capillary cables
will address the general performance requirements of the cabling system (cat.5 e of
above).
Data backbones :
copper cable colour: should be either green or blue. A white colour is allowed for
LSFROH (IEC60332-3C) cable only.
- For indoor use, the fiber cable will be non-armoured. An anti-rodent protection may be
included. It should have a tight buffered structure.
- For outdoor use, the fiber cable will be armoured and provide an anti-rodent protection.
It should either have a tight buffered or loose tube structure.
High-end copper LAN cables for performances from category 6 to category 6A 500 Mhz.
While exceeding international standards by 3 dB minimum on NEXT & RL, the cable
should have better resistance to the mechanical constraints.
LAN copper cables for category 6A with a single-foil metallic cross-filler, providing high
performance and reliable shielded installations. While exceeding international standards
by 3 dB minimum on NEXT & RL, the cable must provide superior shielding, faster
installations and increased efficiency.
Also, in order to facilitate cable laying, the cables should be available in dual version.
This will allow only one operation to install two cables.
Certificates
All LAN cables from Category 6 have to be certified at a component level by the
independent third-party laboratory Delta. Certificates are regularly updated to be
compliant to the latest and highest international standards.
Specifications
Horizontal cables will be made of 4 twisted copper pairs cable cat.5E UTP. They will
consist of CL-C UTP cable (100 ohms) AWG24, 4 pairs or 2x4 twisted pairs without
screen from Schneider-Electric or equivalent.
These cables will be made of halogen free compound.
The total length of a single link should not exceed 90 meters (it is admitted that an
average length of 40m per link is a maximum).
The cable should support the compatibility of PoE standards (Power over Ethernet) and
PoEP (Power over Ethernet Plus) which allow to supply equipments (IP phone, camera,
WIFI hotspot…) until 13W or 25W (IEEE 802.3AF and IEEE802.3AT)
Performances
Compliant to EN50173-1, ISO/IEC 11801:2011 Ed2.2, IEC61156-5 Ed2 and
TIA/EIA-568-C.2 standards
Cable sheath should be green and the NVP should be printed
Page 111 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
Category 5E F/UTP 155Mhz cabling :
Horizontal cables will be made of 4 or 2x4 twisted copper pairs cable cat.5E UTP. They
will consist of CL-C cable (100 ohms) from Schneider-Electric or equivalent.
These cables will be made of halogen free compound and should offer a shielding made
of an Aluminium foil laid longitudinally throughout the cable. The foil (or the foils) should
respect the Snail technology features to improve EMC.
The total length of a single link should not exceed 90 meters.
Cable sheath should be green and the NVP should be printed.
The cable should have superior headroom and bandwidth, exceeding international and
local standards.
Improved safety in case of fire
The outer-sheath of the CL-MX should be available in LSFRZH to comply with IEC
60332-1 and 60332-3c standards. This means reduction of the emissions of opaque
smoke and acid gases. Thus helps reducing damages to equipment and allows people
to escape from the building more easily.
LSZH
LSZH (Low Smoke Zero Halogen) sheath according to test methods IEC 61034 (smoke
density), IEC 60754-1 (gas toxicity), IEC 60754-2 (gas corrosiveness) for Tight buffered
and Loose tube cables.
Flame retardant
Flame retardant (self extinguishing) according to IEC 60332-1 for Tight buffered and
Loose tube cables.
Fire retardant
Fire retardant (no fire propagation along the cable) according to IEC 60332-3C for Tight
buffered cables.
The CL-MX cable is wrapped in one single foil, this means less cutting and improved
quality of cable preparation.
The Actassi Indoor/Outdoor Loose tube LSZH Cables pass most of the following tests:
1) IEC 60754 part 3, Acidity/Corrosively based on pH and Conductivity Measurements
2) IEC 60332-1, Flame Retardant
3) NES 713, Toxicity Index
4) IEC 61034, Smoke Emissions
All cables shall be 4-pair unshielded Twisted Pair (UTP) cables meeting or exceeding
the quality and performance requirements for Category 6 UTP cables stipulated in
EIA/TIA-568-B.2-1 standard. Each Category 6 UTP cable shall be terminated on an 8-
conductor Category 6 jack in accordance with the EIA/TIA-568B wiring code;
The cable shall be solid or stranded copper conductors of 23 AWG insulated with high
density, PVC or LSZH sheath. Cross filler with optimized design and micro-blades,
is preferred
The cable shall be accompanied with traceable serial numbers from the manufacturer
indicated on the packaging to assist in quality validation of the installed cables;
The cable shall provide the guaranteed channel performance specifications of the
Category 6 Channel complies to EIA/TIA-568-B.2-1 standard.
Copper :
Patch cords or work area cords, category 5E U/UTP 155Mhz:
Cords are to be of the same manufacturer than cables and connectors used in horizontal
links to obtain optimised performances. They will be unshielded and have an impedance
of 100 Ohms (ref. VDIP181546020 Schneider-Electric for a 2m length).
Cords must always be as short as possible to ease their management inside cabinets
and higher the global performances of the horizontal links.
Cords have to be compliant with : ISO / IEC 11801 Ed 2.2 and third part, updated Delta
certified - EN50173ed.3. , EIA/TIA 568 - C.2, IEC 61935-2
Specifications Low Smoke Zero Halogen (LSZH), 4 pairs, 100 ohms, pre-wired and
tested in factory, with light grey colour design (RAL7035)
Connectors with grey over-moulding, Snag-free connection to protect the plug-clip from
breakage. In order to identify, a pair of COLOR clips Covering either shielded or
unshielded will be provided. Each patch cord will be delivered in individual packaging.
Geometrical characteristics of fiber optic jumpers are to be the same than fiber optic
links cables.
OM3 and OM4 have an additional laser launch modal bandwidth as OM3 and OM4 are
designed to be laser optimized. The difference between ―Overfilled Launch" and ―Laser
Launch" is the test method. A new test method simulating a VCSEL laser launch (TIA-455-
220A and IEC 60793-1-49) was deemed appropriate for these fibers which are intended for
use with VCSELs at higher speeds.
OM4 fiber is designed to enhance the system cost benefits enabled by 850nm VCSELs for
existing 1 Gb/s and 10 Gb/s applications as well as future 40 Gb/s and 100 Gb/s systems.
OM4 fiber supports Ethernet, Fiber Channel, and OIF applications, allowing extended reach
upwards of 550 meters at 10 Gb/s for ultra long building backbones and medium length
campus backbones.
The basis of a cabling system organisation is shown by the following diagram. It shows a
star organisation model of FD around the BD. It is to notice that the redundant backbone
links shown are not compulsory but offer a higher security margin against breaks.
Redundancy
Fiber
optique
Backbone telephone
Horizontal cable
- Terminal outlet :
A workstation will include a minimum of 2 (two) outlets (e.g. one for telephone
application, the other one assigned to the data network).
Terminal outlets are to be made of cat.5E RJ45 8-pin modular jacks, normalised by
ISO 8877 (reference VDIB17725U12 Schneider-Electric or equivalent).
RJ45 modular jacks are to be mounted on faceplate from the local standards. The
faceplate have to be properly equipped to accept screw-on adapters and splitters (i.e.
have a build-in nut).
Note : The outer size of the faceplate may be different if the screwing feature described
above is respected (e.g. ref. 5034 Schneider-Electric Italian plate).
Bridged taps and splitters shall not be used as part of the backbone cabling. (TIA/EIA-
568-B.1)
A workstation will include a minimum of 2 (two) outlets (e.g. one for telephone
application, the other one assigned to the data network).
Terminal outlets are to be made of cat.5E RJ45 8-pin modular jacks, normalised by
ISO 8877 (reference VDIB17725B12 Schneider-Electric or equivalent).
RJ45 modular jacks are to be mounted on faceplate from the local standards. The
faceplate have to be properly equipped to accept screw-on adapters and splitters (i.e.
have a build-in nut).
Note : The outer size of the faceplate may be different if the screwing feature described
above is respected (e.g. ref. 5034 Schneider-Electric Italian plate).
Bridged taps and splitters shall not be used as part of the backbone cabling. (TIA/EIA-
568-B.1)
The Entrance Facility consists of service entrance to the building including the building wall
penetration and continuing to the ER. The EF may also contain backbone paths to link other
buildings as well as antenna entrances.
• All carriers and telecommunications providers involved in providing service shall be
contacted to establish their requirements.
• Easements, permits and rights of way may be required.
• A service entrance pathway shall be provided (underground, aerial, buried).
• See standard for specifications defining manholes, penetrations, etc.
• Grounding and bonding to NEC or local code guidelines.
7 TELECOMMUNICATIONS ROOMS :
TR SPECIFICATIONS
LIGHTING
• Provide a minimum equivalent of 500 lux (50 foot-candles) measured 1 m (3 ft) above
finished floors.
• Avoid dimmer switches.
• Coordinate closely with the rack placements.
• Light fixtures mounted min 2.6m (8.5 ft) above finished floor.
• Emergency lighting is recommended. Place emergency lighting to ensure that the loss of
power to normal lights will not hamper an emergency exit from the TR.
• Power for lighting should not come from the power panel inside the TR. At least one light
should be on normal power, and one light should be on emergency power, if available.
DOORS
• Fully open (180 degrees) lockable doors with minimum door size 0.9 m (36 in) wide by 2m
(80 in) high.
• Door sills are not allowed because they impede the movement of equipment.
• Doors that open outward provide additional usable space and reduce constraints on TR
layout.
• Door should have a lock.
POWER SUPPLY
• Branch circuits for equipment power that are protected and cabled for 20 Amp capacity
(240 volts depending on the local utilities regulation)
• Minimum of two dedicated, non-switched, 3-cable, 240 volts (V) alternating current (ac)
duplex electrical outlets for equipment power, each on separate branch circuits.
• Separate duplex 240 Vac convenience electrical outlets (for tools, field test instruments,
located at least 150 mm (6 in) above finished floor and spaced at 1.8 m (6 ft) intervals
around perimeter walls.
• Light switch locations should be easily access upon entry.
• Electrical outlets must be on non-switched circuits (electrical outlet power must not be
controlled by a wall switch or other device that may lead to inadvertent loss of service).
Flood Prevention
Do not locate TRs in areas prone to flooding. Avoid locations that are below or adjacent to
areas of potential water hazard (e.g., areas below water table, restrooms and kitchens).
PATCH PANELS
Patch panels will be equipped with RJ45 cat.5e shielded (ref. VDIB118241F50 ACTASSI
S-ONE with a 360° shielding), or RJ45 cat.5e unshielded (ref. VDIB118241U50
Schneider-Electric).
Alternatively vertical patch cord routing rings (ref. VDIM189111 FOR 600X600 OR
VDIM189112 FOR 800X800 Schneider-Electric) will be placed on the 19" uprights at
each side of the cabinet (4 rings per uprights is to be forecasted).
Shielded panels should include shutters removable from the panel for dust proof.
Optional colouredearthing shutters should be supported to increase port identification.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
Patch panels will be pre-equipped with RJ45 cat.5e shielded (ref. VDIG17725B12
ACTASSI S-ONE with a 360° shielding), or RJ45 cat.5e unshielded (ref.
VDIG17725U12 Schneider-Electric).
Alternatively vertical patch cord routing rings (ref. VDIM189111 for 600X600 or
VDIM189112 for 800X800 Schneider-Electric) will be placed on the 19" uprights at each
side of the cabinet (4 rings per uprights is to be forecasted).
Shielded panels should include shutters removable from the panel for dust proof.
Optional coloured shutters should be supported to increase port identification.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
Patch panels will be pre-equipped with RJ45 cat.6A shielded (ref. VDIG118241BX0
ACTASSI S-ONE with a 360° shielding), or RJ45 cat.6A unshielded (ref.
VDIG118241UX0 Schneider-Electric).
Shielded panels should include shutters removable from the panel for dust proof.
Optional coloured shutters should be supported to increase port identification.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
telecom panels
The sliding function does permit the use of the punch down tool for LSA contacts with
the panel in a sliding-out position. The telecom panel must have a cable identification to
avoid the need trying to figure out which cable goes where. The cable identification is
very clear on the clever fixing guides. Out of this identification a clear marking with pre-
printed labels and openable label holders will be part of the patch panel.
Finally, the panel has to have two earthing connection points for both shielded cables
and for the rack, easily accessible at the rear.
Sliding Fiber optic panel 1U:
They will have a capacity of 4 positions equipped with 3 blank plates. Each plates will
have 3 SC/ST/LC or 6 ST SIMPLEX/LC DUPLEX.
The fiber patch panel will have a 0U cable management at the front with integrated clear
marking number in order to identify the cables. At the rear of the sliding fiber panel, a
rear quick fixation to use with a cable gland provide with the panel.
The patch panel has to be equipped with a transparent cover protection at the front, and
on the top of the panel. Finally, the panel will have one or two coiling wheels to avoid
tension on the connectors, and to respect the fiber bend radius. Labelling has to be
integrated on each side of the QUICKFIX system.
The preferred colour of the patch panel is RAL 7016 (dark grey) in order to be
homogeneous with all the RACK and other patch panels.
Cable management:
In between each patch panel a patch cord guiding panel should be inserted. This patch
cord guiding panel should have 1 U height and be fixed with ONLY 2 screws. This
Vertical rings :
Cable ties to bundle the cable are forbidden. Velcro should be used instead.
Multipair backbones cables coming from the Telephone Building Distributor will either be
terminated on 8-pairs modules or dedicated patch panels offering 50 RJ45 cat.3 ports on
1U (ref. VDIP141501 Schneider-Electric).
50 ports in 2 rows RJ45 patch panels will be given priority as it suits the universality
feature of a cabling system. Cable organizer and label holders is mandatory.
A cross connection from the telephone backbone to the horizontal cables will allocate an
extension number to the chosen telecommunication outlet.
A quickfix function on both sides to allow simple fixing and sliding feature.
Transmission performances :
The performance of a horizontal cabling is specified for channels and permanent links.
The channel is the end-to-end transmission path connecting any two pieces of
application specific equipment. It includes both work area and equipment cords which
are inserted into the tester and remote equipment.
The permanent link is the transmission path between the telecommunication outlet and
the floor distributor. The permanent link does not include work area cords, equipment
cords and jumpers, but includes the connection at each end. It can include a CP link. In
this case, the test cords to be used are the one of the testing equipment.
Interpreting test results should always take into account that the ultimate goal is "to be
sure that any application will run on the cabling".
If NEXT and PS NEXT values are above standards and insertion loss is below 4 dB,
ACR and PS ACR values are to be used as reference.
Dry risers should offer 50% available space to enable the re-cabling of a complete area.
Between two floors, cable-through have to be sealed off (fire protection).
Workstations supply :
In theory, a workstation is designed for the connection of all the equipment of a user in a
space measuring approximately 10m². The faculty of doubling applications to allow two
users to be connected instead of one is particularly interesting but should remain an
exceptional measure.
Distribution modes will be designed to directly receive high power and data connectors
to the 45x45mm standard shape. The chosen distribution modes according to the
building layout are described here after :
- Open spaces : PVC trunking system with 3 compartments ref. 64560 Schneider-
Electric, which allow to easily move outlets within the central compartment and also
insures an optimal distance between power supply cables and data cables.
- Offices with trays in false ceiling : distribution poles ref. Schneider-Electric 64543
(basic), 64541 (1 box) or 64542 (2 boxes).
- Offices with trays in raised floor : under carpet latch (ref. 6510 Schneider-Electric)
and low profile boxes or multifunctional boxes (Schneider-Electric or equivalent).
- Refurbishment : individual wall mounted boxes housing both high voltage and data
cables.
The purpose of this standard is to standardize design and construction practices intra-and
interbuildings (commercial premises) related to pathways and spaces for supporting
telecommunications media and equipment.
Standards are given for different types of rooms found in a commercial premise and the
cabling pathways leading into the rooms. The following are the different type of spaces and
pathways found in a typical commercial building shown in diagram 4.2.
Horizontal pathways and related spaces: Those facilities that serve as pathways for the
installation of telecommunications media from the telecommunications room (TR) to the
work area (WA).
Intrabuilding backbone pathways and related spaces: Those facilities that may exist in a
building that are usually formed by vertically stacking TRs with floor openings between
them. Tie pathways may also exist to permit installation of backbone media between
multiple TRs on the same floor.
In most designs:
• The front panel is removable.
• Telecommunications outlet/connectors may be placed at any point along the run and may
be moved or added after initial installation
Page 133 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
• In a perimeter raceway, electrical power and telecommunications services must be run in
SEPERATE compartments and must comply with applicable electrical codes.
• When a metallic barrier is provided, it must be bonded to ground.
8.3 Conduits
Enclosed metallic raceways or conduits can be used as backbone pathways. Due to its
limited capacity, it is not effective for backbone distribution. Conduits can only be used to
run cables point-to-point when intermediate splices or terminations are not required.
However due to its high degree of shielding effectiveness and the security and physical
protection, many military installations prefer enclosed metallic raceways or conduits to be
used as backbone pathways.
Conduit Fill for Backbone Cable
NOTES:
1) Column A is used when one cable is to be placed in conduit.
2) Column B is used when two cables are to be placed together. The percentage fill of
conduit is applied to straight runs with nominal offset equivalent to no more than two 90º
bends.
3) Column C is used when three or more cables are to be placed in a conduit.
BEST PRACTISE
Sleeves to extend a minimum of 25 mm above the floor level
BEST PRACTICES
1. Slots are typically located flush against the wall within a space
2. Slots SHALL BE constructed with a minimum 25 mm high curb.
3. Shall be designed at a depth (the dimension perpendicular to the wall) of 150–600 mm.
4. The location and configuration of the slot(s) shall be approved by a structural engineer.
9 Field Testing
If a test fails because of a non-relevant parameter, functional qualities of the link are to
be taken into account (e.g. on a very short link, the NEXT parameter could issue a fail
result but insertion loss and ACR are, however, excellent)
10 Warranties :
Contractor must also justify their technical skills on the installed cabling system by
presenting certificates of attendance to specific training and manufacturer approval.
Ingress Protection (IP) ratings are developed by the European Committee for Electro
Technical Standardization (CENELEC) (NEMA IEC 60529 Degrees of Protection
Provided by Enclosures - IP Code), specifying the environmental protection the
enclosure provides.
Example - IP Rating
With the IP rating IP 54, 5 describes the level of protection from solid objects and 4
describes the level of protection from liquids.
An "X" can used for one of the digits if there is only one class of protection, i.e. IPX1
which addresses protection against vertically falling drops of water e.g. condensation..
0 No special protection
Protected against solid objects over 50 mm, e.g. accidental touch by persons
1
hands.
0 No protection.
4 Protection against water sprayed from all directions - limited ingress permitted.
5 Protected against low pressure jets of water from all directions - limited ingress.
Protected against temporary flooding of water, e.g. for use on ship decks -
6
limited ingress permitted.
10 Gigabit Ethernet IEEE 802.3 is the installed on aerial supporting structures such
standard specifying 10 Gb/s transmission for as poles, sides of buildings, and other
single-mode fiber or 50 μm multimode fiber structures
ACR see Attenuation to Crosstalk Ratio Air Handling Plenum a compartment or
ADM see Add/Drop Multiplexing chamber with one or more air ducts
ANSI see American National Standards connected and that forms part of the
Institute environmental air distribution system
APD see Avalanche Photodiode All-Dielectric Self-Supporting refers to an
ASTM see American Society for Testing aerial cable design that is intended for long
and Materials spans where electric fields from lightning or
ATM see Asynchronous Transfer Mode nearby high-voltage cabled could cause
AWG see American Wire Gauge elevated temperatures or other unwanted
Acceptance Angle largest possible angle for effects in cables with metallic elements; it is
launching light into an optical fiber; this used as an alternative to OPGW on electric
angle is used to determine the numerical power company aerial high-voltage
aperture (NA) of a fiber transmission routes
Access Connection the physical connection Alternate Entrance a supplemental
at a central office connecting a local channel entrance facility into a building using a
to an interoffice channel different routing to provide diversity of
Access Floor a system of raised flooring that service and assurance of service continuity
has removable and interchangeable floor Ambient Temperature the temperature of a
panels medium (gas or liquid) surrounding an
Adapter a mechanical media termination object American National Standards Institute
device designed to align and join fiber optic (ANSI) refers to a standards organization
connectors; often referred to as a coupling, that organizes committees and oversees the
bulkhead or interconnect sleeve development and publication of standards,
Add/Drop (ADM) multiplexers used at a including standards for network interfaces,
network node to separate a signal from a communication protocols, and other
multiplexed signal or to combine a communication technologies
lowerspeed local signal into a higher-speed American Society for Testing and
transport signal Materials(ASTM) a nonprofit industry-wide
Administration the method for labeling, organization which publishes standards,
identification, documentation and usage methods of test, recommended practices,
needed to implement moves, adds and definitions and other related material
changes to the telecommunications American Wire Gauge (AWG) a standard
infrastructure; TIA/EIA 606 system for designation wire diameter; also
Aerial a type of cable installation where the referred to as the Brown and Sharpe (B&S)
cable is connected to poles or towers by wire gauge
means of cable clamps or other pole Ampere the unit of current; one ampere is
attachment hardware; refer to lashed, the current flowing through one ohm of
messenger, figure-eight or self-support resistance at one volt potential
Aerial cable telecommunication cable
Page 147 sur 167
Technical specifications LAN cabling system requirements
12/05/2013
Analog a continuously varying signal; Asynchronous Transfer Mode (ATM)
analog signals may have an unlimited standard for cell switching to route packets
number of values, as amplitude and/or of digital information, designed to
frequency may vary accommodate burst data transmission; an
ANSI/TIA/EIA 568 Commercial Building ATM cell has fixed length of 53 bytes: 5
Telecommunications Standard; it gives operation at bit rates from 1.544 Mbps up to
guidelines on implementing structured 2 Gbps; the standard defines both the
cabling within a building; it also defines the multiplexing and cell relay protocols
minimum mechanical and transmission Attenuation loss of signal in a length of
performance criteria for U/UTP, F/UTP, cable (in dB)
S/FTP, coax, and fiber optic cabling Attenuation Coefficient attenuation
ANSI X3T9.5 the ANSI committee expressed as a function of distance (dB/km);
responsible for FDDI sometimes listed as the Greek letter alpha
Approved Ground a grounding bus or strap (aor α)
approved for use as a telecommunications Attenuation to Crosstalk Ratio (ACR)
ground; refer to EIA/TIA 607 and the calculated as the crosstalk value (dB) minus
National Electric Code the attenuation value (dB); typically, ACR
Aramid Yarn a non-conductive strength may be given for a cable, link or channel and
element used in cable to provide support and is a key indicator of performance for U/UTP
additional protection of fiber bundles systems
Armor the protective element added to Backboard a panel, wood or metal, used for
cables; it is usually made of steel, but can mounting equipment
also be heavy plastic or aluminum Backbone the part of the distribution system
Armored additional protection between that include the main cable routing from the
jacketing layers to provide protection against equipment room to remote locations; this
severe outdoor elements; usually made of may include distribution to the same or
plastic-coated steel, corrugated for different floors within a building.
flexibility; may also be called armoring Backbone Raceway the portion of the
ASCII American Standard Code for pathway system that permits the placing of
Information Interchange main or high-volume cables between the
Asynchronous (or Async) a transmission entrance location and all cross-connect
and switching technology that relies on the points within a building or between
use of bits or strings of bits at the beginning buildings
and the end of the data payload; these are Backfill materials used to fill an excavation;
called “farming bits”; this technology differs may be crushed stone, sand or soil
from synchronous transmission, where the Backscattering the scattering of a fiber
data payload is referenced to a clock optic signal in the opposite direction from its
intended course