0% found this document useful (0 votes)
302 views96 pages

PTXN 60Hz

Uploaded by

Anonymous qOBFvI
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
302 views96 pages

PTXN 60Hz

Uploaded by

Anonymous qOBFvI
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 96

Light Commercial

Packaged Rooftop
Air Conditioners
Models PTXN022-100
22 TR thru 100 TR
(75 KW thru 341 KW)
60Hz
Company Profile
Zamil Air Conditioners, a sector business of Zamil Industrial, is the largest manufacturer of air conditioners in the Middle East.
The company manufactures and markets the complete range of air conditioners, from room air conditioners to packaged units
to large chillers for residential, commercial and industrial applications.

Founded in 1974, Zamil Air Conditioners was one of the first air conditioning companies to be established in Saudi Arabia. Today,
the company produces about one million air conditioners per year. Aside from its head office and two manufacturing plants in
Dammam, Saudi Arabia, the company also has production facilities in India. The company supplies air conditioning products to
over 55 countries across the world, with its major markets located in the GCC, Middle East, North Africa, Europe and Asia.

Zamil Air Conditioners is the first Middle Eastern company to achieve the prestigious AHRI certification (Air-Conditioning, Heating
and Refrigeration Institute, USA). The company is also 9001:2015 Quality Management System, ISO14001:2015 (Environment
Management) and OHSAS 18001:2007 (Occupational Safety) certified with many of its products tested and approved by
Eurovent, AHRI, SASO, ESMA & UL.

Companies:
• Zamil Air Conditioners & Home Appliances Co. (L.L.C),
• Zamil Central Air Conditioners Co. (L.L.C),
• Zamil Air Conditioning and Refrigeration Services Co. (L.L.C)

Manufacturing Facilities:
The company has two factories in Saudi Arabia located in the 1st and 2nd Industrial Cities of Dammam. The company also has
production facilities in India.

Annual Production Capacity:


• Window Air Conditioners: 700,000
• Mini-Split Systems: 300,000
• Central Air Conditioners: 50,000

Core Values

VISION:
To be the partner-of-choice COMMUNITY &
for environmental control HONESTY &
PROSPERITY
INTEGRITY
solutions that are based We believe in mutual prosperity.
We believe goodwill and good
on lifetime value reputation are core to our business.
We aspire to thrive in business
while bringing progress and
We uphold honesty, integrity, prosperity to our own people and
professionalism and a high level of communities where we operate.
business ethics. We observe prudence Our culture, our ideas, our
and fairness in dealing with our practices, our environmental
MISSION: stakeholders. concern, and our teamwork lead
us to create superior values for
To make air-conditioning people and communities
Affordable, Reliable and around us.

Energy-Efficient
VALUES
LEADERSHIP &
CUSTOMER & PRUDENCE
EXCELLENCE We cultivate talent and leadership
to create sound business
We are diligent about understanding solutions, to best meet our
and fulfilling our customers’ needs. customer needs, and to develop
We strive to please our customers with markets, people and shareholder
excellence in quality and services. We value. We do so by optimizing use
listen to our customers and “go the of funds, resources, materials, and
extra mile” to satisfy them. INNOVATION & technologies. We build prudence
CHANGE and cost-effectiveness in our
leadership culture passing on
We are passionate about
benefits to our customers.
meaningful innovation. We are a
learning organization. We learn
from our experiences and global
best practices, and we innovate to
create leading local solutions
leveraging on world class
knowledge. We embrace positive
change brought forth by innovation
and aspirations to grow our
business.
Research & Development
Zamil Air Conditioners boasts of its state-of-the-art testing facilities – “Ikhtebar” which is a third party air conditioner testing
facility built by Intertek Testing Services (ITS) and certified by Electrical Testing Laboratories (ETL). Equipped to perform a wide
range of tests under many recognized local and international standards including: AHRI 210/240; AHRI 410; AHRI 310/380; AHRI
430; AHRI 440; AHRI 340/360; ASHRAE 116; ASHRAE 37;ASHRAE 41.1; AHRI 365; ISO 5151; SASO 385; SASO 2682; UL 1995
and AHRI 550/590.

Features:
• Performance test of whole range of air conditioners – consumer as well as commercial, in capacities from ½ TR to 600 TR
• Support research and development initiatives through implementation of state of the art computational programs.
• Test products for conformance to local and international certifications and standards such as SASO, AHRI, UL, AHAM etc.

Facility:
• Calorimetric Test Rooms
• Psychrometric Test Rooms
• Chiller Test Facility
• Sound Lab
• Reliability Test Facility

Parent Company
Headquartered in Dammam, Saudi Arabia, Zamil Industrial Investment Company ('Zamil Industrial') is a premier business group
engaged in the design, engineering and manufacturing of innovative products and solutions for the global building and construc-
tion industry.

Zamil Industrial offers a wide range of products and services in four sectors viz. HVAC, Steel, Insulation and Concrete. Zamil
Industrial’s key products and services include: air conditioning systems, pre-engineered steel buildings, steel structures, telecom
and transmission towers, process equipment, precast concrete building products, insulation products, installation and mainte-
nance of HVAC Solutions, and solar power solutions.

The company employs more than 15,500 people and derives about 25% of its revenues from outside Saudi Arabia. Zamil Indus-
trial products are sold in more than 90 countries around the globe, and the company operates manufacturing facilities in Saudi
Arabia, United Arab Emirates, Egypt, India and Vietnam. Zamil Industrial shares are actively traded on the Saudi Stock Exchange
(Tadawul).
INDEX

Contents Page

Model decoding .......................................................................................................... 2-4

Standard feature/options ............................................................................................ 5-8

Standard specification .............................................................................................. 9-15

Optional items ......................................................................................................... 16-20

Physical data ........................................................................................................... 21-23

Performance data ................................................................................................... 24-35

Electrical data ......................................................................................................... 36-60

Filter sheet .................................................................................................................... 61

Dimensions ............................................................................................................. 62-79

Schematic diagram ................................................................................................. 80-81

Power cable entry ......................................................................................................... 82

Installion clearance ................................................................................................. 83-85

Lifting and rigging instruction ..................................................................................86-87

Load distribution & mounting points ....................................................................... 88-91

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

1
MODEL DECODING

1,2,3 4,5,6 7 8 9 10

NOMINAL Version ELECTRICAL REFRIGERATION REFRIGERATION


BASIC COOLING Number SUPPLY CIRCUIT CIRCUIT
CAPACITY (TONS) (V-Ph-Hz) TYPE OPTIONS

PTX 022 N: N Version, H: 230-3-60 D: DUAL SCROLL A: STD OPTIONS


MODULAR 025 high COMPRESSORS
efficiency M: 400-3-60 (PTX022N-PTX035N) B: COMPRESSOR SERVICE
PACKAGE 030 VALVES
rooftop (4-WIRE)
UNITS packaged
035 T: TRIO SCROLL
(R-410A) series F: 460-3-60 COMPRESSORS
040
(PTX060N-PTX070N)
045
050 Q: QUADRUPLE SCROLL
COMPRESSORS
060-RH (PTX040N-PTX050N
060-LH & PTX080N-PTX100N)
070-RH
070-LH
080-RH
080-LH
090-RH
090-LH
100-RH
100-LH

11 12 13 14

CONDENSER COIL EVAPORATOR COIL SUPPLY AIR BLOWER FAN ( 3 )


ARRANGEMENT ( 1,2 )

A: ALUMINIUM FIN A: ALUMINIUM FIN A: 1" SINGLE SKIN- F: FORWARD CURVED


TOP SUPPLY BLOWER
B: PRE COATED ALUMINIUM FIN B: PRE COATED ALUMINIUM FIN
B: 1" SINGLE SKIN- B: BACKWARD CURVED
C: COPPER FIN C: COPPER FIN FRONT SUPPLY BLOWER

D: ALUMINIUM FIN WITH D: ALUMINIUM FIN WITH E: 1" DOUBLE SKIN- C: F +SPRING ISOLATOR
ANTI CORROSIVE COATING ANTI CORROSIVE COATING TOP SUPPLY
D: B +SPRING ISOLATOR
E: COPPER FIN WITH ANTI E: COPPER FIN WITH ANTI F: 1" DOUBLE SKIN-
CORROSIVE COATING CORROSIVE COATING FRONT SUPPLY H: F+ BELT GUARD

M: MICROCHANLE I: B+ BELT GUARD


CONDENSER COIL (MCHX)
M: F+C+ H COMBO
G- MICROCHANLE CONDENSER N: B+ D+I COMBO
COIL WITH ANTI CORROSIVE
COATING

2
MODEL DECODING

15 16 17 18 19

BLOWER BLOWER MOTOR HEATER KITS ELECTRICAL EXTRA ELECTRICAL


MOTOR ELECTRICAL OPTIONS OPTIONS OPTIONS OPTIONS

G: 4.0 KW A- STD OPTIONS N - NO HEATER A-STD OPTIONS(5) A-STD OPTIONS


H: 5.5 KW B- MOTOR CIRCUIT A: 10 K- FAN CYCLING SWITCHES. B-CIRCUIT BREAKER
BREAKER B: 15 V- VOLT FREE CONTACT(6) FOR COND. FAN
I: 7.5 KW
C :20 C: COMP CIRCUIT BREAKER. C- EXTERNAL
J: 11 KW E- EXTERNAL OVEROAD
PROTECTION D: 30 D: NON FUSED DISCONNECT SWITCH OVERLOAD FOR
K: 15.0 KW EACH COND. FAN
E: 37.5 P- PUMP DOWN SOLENOID VALVE
L: 18.5 KW V- VARIBALE FRQNACY E- EXTERNAL
DRIVE (4) F :40 B - K + V COMBO OVERLOAD FOR
M: 22.0 KW G :45 E - K + C COMBO EACH COMPRESSOR
N: 30.0 KW Q- B &E COMBO H: 50 G - K + P COMBO F- B & C COMBO
O: 37.0 KW I: 52.5 H: K+D COMBO
H- B & E COMBO
P: 45.0 KW J : 60 T - K + V + C COMBO
K: 80 M - K + V + P COMBO J- C & E COMBO
L: 100 N - V + C + P COMBO
L- B, C & E COMBO
Q: V+C+D COMBO
U: V+D+P COMBO
L- K+V+C+P COMBO
O:K+V+C+P+D COMBO

20 21 22 23

KITS MECHANICAL KITS FILTER EXTRA SECTIONS UNITS


OPTIONS (7) OPTIONS (8) OPTIONS ENCLOSURE

A-STD OPTIONS A: FILTER RACK WITH 2'' INCH A: STANDARD A: STANDARD


DISPOSABLE FILTERS. (WITHOUT SECTION)
M- REPLACEABLE CORE FILTER
DRIER & SHUT-OFF VALVE B: 4" MINI PLEATED FINAL F: UNIT FULL GUARD
F: FILTER RACK WITH 2'' INCH FILTER
P- PRESSURE GAUGES THICK PLEATED FILTERS.
(SUCTION & DISCHARGE) C: BAG FILTER SECTION

H- HOT GAS BYPASS M: FILTER RACK WITH 2'' INCH D: MIXING BOX SECTION -
THICK ALUMINIUM FILTERS. TOP RETURN
R- CONDENSER PRESSURE E: MIXING BOX SECTION -
RELIEF VALVE W: FILTER RACK WITH 2'' INCH FRONT RETURN
J- M + P COMBO THICK WASHABLE PLEATED H: B +D COMBO
HIGH EFFECINCY FILTERS.
N- M + H COMBO
I: B+ E COMBO
K- M + R COMBO
O: P+ H COMBO J: B +F COMBO
F: H+ R COMBO K: B+G COMBO
Q- M + H +R COMBO L: C + D COMBO
T- M + P +H COMBO M: C+E COMBO
L- P +H +R COMBO
N: C+F COMBO
U- M +P+R COMBO
W- M+P+ H+ R COMBO O: C+G COMBO

3
MODEL DECODING

24 25 26 & 27

DRAIN PAN & DRIP DAMPERS SPECIAL OPTIONS


ELIMINATOR

A: STD DRAIN PAN A: STD AA: STD


AB: UV LAMP
D: STAINLESS STEEL DRAIN PAN (304) B: MANUAL FRESH AIR DAMPER
AC: ELECTRONICTHERMOSTAE
E: STD DRAIN PAN WITH DRIP C: MANUAL FRESH AIR DAMPER & AD: ANTICE THERMOSTAT
ELIMINATOR RETURN AIR DAMPER
AE: DIFFERNATIL PRESSURE SWITCH
F: STAINLESS STEEL DRAIN PAN WITH FOR PRE FILTER
F: ECONOMIZER CONTROL WITH
DRIP ELMINATOR (304) OUTSIDE AIR THERMOSTAE TYPE
AF: DIFFERNATIL PRESSURE SWITCH
FOR PRE FILTER & FINAL FILTER
G: ECONOMIZER CONTROL WITH
ENTHALPY SENSOR TYPE AH: HINGED DOOR FOR BLOWER FAN
& MOTOR SECTION
H: ECONOMIZER CONTROL WITH AI :AC+AD
ENTHALPY SENSOR TYPE & CO2
MOINTOR AJ:AC+AD+AE COMBO

AK::AC+AD+AF COMBO

AL::AC+AD+AE+AH COMBO

AM::AC+AD+AF+AH COMBO

1- Top supply is standard for all PTXN models.


2- 1" THK Fiber glass insulation is standard for all models.
3- Alll units are supplied with forward curved blower as standard, while backward curved blower is option.
4- VFD option includes motor circuite brekaer , while EOL is not applicable.
5- Standerd electrical options contain Under Voltage Mointor( UVM) & fixed low/ high pressure switches.
6- A combination of volt free contact option: 1. Unit on/off indication, 2. Compressor run & Unit trip indication, 3.Blower run & trip
indication, 4.Unit trip indication.
7- Standerd options contain sealed type filter drier and sight glass.
8- 2" disposable filter is standard for all models

4
STANDARD FEATURES/OPTIONS

DESCRIPTION STANDARD OPTIONS (FACTORY


FEATURES INSTALLED)
Scroll compressors
Compressor circuit breakers
Compressor with external overload protection
Compressor with serivce valves
Condenser fan - direct drive, propeller type & fan Guard
Condenser motor circuit breakers
Condenser motor with external overload protection
Forward curved blower
Backward curved blower
Blower motor -TEFC & IP55
Blower motor circuit breaker
Blower motor with External overlaod protection
Aluminum fin evaporator coils
Pre-coated aluminum fin evaporator coils
Copper fin evaporator coils
Aluminum fin condenser coils
Copper fin condenser coils
Microchannel condenser Coils-MCHX
Anti-corrosive coating on evpaorator coils or condenser Coils
1'' single skin construction for Air Side Section
1'' double skin construction for Air Side Section
Disposable filters , 2" Thikness
Aluminum filters , 2" Thikness
Pleated filters, 2" Thikness
High efficiency washbale pleated filters- 2" Thikness
Bag filter section,15" Depth
Mini Pleated Filter ,4" Thikness
Mixing box section (up to 30 % Fresh air )
Manual volume dampers ( fresh and return air )
Economizer control with outside air temperature sensor
Economizer control with enthalpy sensor
Economizer control with outside air temperature sensor & CO2 monitor
Economizer control with enthalpy sensor & CO2 monitor
Unit full guard
Drip eliminator
Stainless steel drain pan ( SS-304 )
UV light ( not appliable with drip eleminaotr)
Anti-ice thermostat
Sight glass (moisture indicator)
Sealed type filter drier
Replaceable core filter drier
Hot gas bypass for main circuit
Condenser pressure relief valve
Pressure gauges
Pump down solenoid valve
Differential pressure switch for Filters
Belt guard
High/low pressure switch (Fixed type)
Fan cycling switch ( Fixed type)
UVM (Under Voltage Monitor)
Volt free contact
Bulk head light
Non-fused disconnect switch
Electric heater
Multiple stage thermostat

5
FEATURES AND BENEFITS

* R-410A environmentally friendly refrigerant (HFC refrigerant).


* Nominal gross cooling capacity from 22 TR up to 100 TR for 60 Hz.
* Independent refrigeration circuits with scroll compressors for efficient cooling process.
* Unit’s cooling operating range from 55ºF (12.7ºC) up to (52ºC) 125.6ºF ambient temperature.
* Thermal expansion valve, filter drier kit and moisture indicator as standard.
* Copper tubes and aluminum fins for evaporator coils & condenser coils.
* Microchannel condenser coil is available as an option for all models.
* Compact unit design with smaller unit footprint at lower installation cost.
* Single wall evaporator section with 1" fiberglass insulation.
* Access panels with easy opened 'C' clamp and no screw features in all access panels.
* 2" (50 mm) thick disposable pre-filter applicable to all models.
* Available in Top & front supply duct configuration.
* Belt driven blower fan motor with adjustable motor pulley applicable for all models.
* Rigging holes in base rail for easy lifting & Installation.
* High-pressure switch and low-pressure switch protection.
* Single power point connection to reduce filed wiring cost.
* Easy access to all components for excellent serviceability.
* Condenser coil is provided with Integral sub-cooling circuits to increase overall unit efficiency.
* High efficient permanently lubricated condenser fan motors (TEAO) with class 'F' insulation.
* Smart microprocessor controller with 220V control voltage protected with control fuse.
* Quality assurance according to ISO 9001:2015, which guarantees high and constant product quality.

COOLING RATING TABLE

MODEL No. COOLING STAGES EER


PTX022N 2 10.0
PTX025N 2 10.0
PTX030N 2 10.0
PTX035N 2 10.0
PTX040N 4 10.0
PTX045N 4 10.0
PTX050N 4 10.0
PTX060N 3 10.0
PTX070N 3 10.0
PTX080N 4 9.70
PTX090N 4 9.70
PTX100N 4 9.70

NOTES:
1. Rated in accordance with AHRI 340/360 & SASO2874 Standards.
2. Ratings are based on:95OF DB Outdoor (Ambient) Temperature.
3. EER: Energy Efficiency Ratio.

6
ZAMIL PACKAGED ROOFTOP SYSTEMS

The PTXN Series air-cooled modular packaged rooftop units from Zamil Air Conditioners are produced in an ISO 9001:2015
certified facility. They are designed to provide engineering excellence on comfort air conditioning and industrial cooling with
a superior combination of high-energy efficiency & energy saving, high performance, application flexibility, ease of service &
maintenance and the ability to withstand extreme ambient temperatures found in the climate of the Gulf region.

The PTXN series are modular packaged units with a design that consists of scroll compressor(s), cooling coil, condenser coil,
fans, control wiring and inter connecting piping. These units are shipped in single packaged, fully charged with R-410A refrig-
erant, and are suitable for mounting on the roof or ground with easy installation and excellent serviceability. The unit features
an integral weather resistant control panel, ready for field connection to utilities and ducts.

PTX025N

The PTXN series units are designed to use ozone friendly HFC R-410A refrigerant. HFC R-410A is highly efficient thermody-
namic proprieties, created to serve as one of the key substitutes for HCFC based refrigerants. R-410A is environmentally
safer for long-term use, no chlorine and does not contribute to Ozone depletion. There is no phasing out and no replacement
costs for the life of the equipment.

7
SCROLL COMPRESSORS
The scroll compressors are consists of two involutes or Archimedean spirals. One spiral is positioned inside the other to form
a series of crescent-shaped pockets. During compression the upper spiral remains stationary and the lower one, being eccen-
trically mounted on the drive shaft, describes an orbital rather than a simple rotary motion.

Compressor working principle Scroll compressor

1. Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. A refrigerant enters the
outer openings as one of the spirals orbits.

2. The open passages are sealed off as gas is drawn into the spiral.

3. As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets.

4. By the time the gas arrives at the center port, discharge pressure has been reached.

5. During operation, all six gas passages are in various stages of compression at all times, resulting in nearly continuous suction
and discharge.

Refrigerant enters the compressor at the suction connection and flows around the motor’s housing and enters at the bottom
side through the openings and oil droplets separate from the refrigerant and fall into the oil sump. All suction refrigerant passes
through the electrical motor, ensuring full motor cooling, after that the refrigerant enters the scroll elements.

Scroll compressor involutes Pockets arrangement

8
STANDARD SPECIFICATION

* UNIT CONSTRUCTION
A. BASE: The base rail is constructed of heavy gauge galvanized steel with lifting holes for ease in rigging and lifting. It also
includes mounting holes suitable to affix with neoprene pads or spring isolators.

* CABINET: The unit cabinet is a modular construction design with a base frame and panels made of heavy gauge galvanized
steel. All panels, top and bottom base pan, vertical posts, cross channels and supporting brackets are joined together and
bolted. The steel sheet panels are zinc-coated and galvanized by the hot dip process of lock-forming quality conforming to
ASTM A 653 commercial weight G-90, followed by a baked on electrostatic polyester dry powder coat, capable of withstanding
1500 hours of salt spray test in accordance with ASTM B-117.

B. COMPRESSOR Cooling Capacity Stage Table


All compressors used in the PTXN series are hermetically
scroll design type with a high energy efficiency ratio, low COOLING NO. OF
MODEL CAPACITY STAGE COMPRESSORS
noise and quite operation. All compressors conform to
AHRI 540 standard and are equipped with internal motor PTX022N 0-50-100% 2
protection, factory installed crankcase heaters and rubber
PTX025N 0-50-100% 2
vibration isolators for quiet and efficient operation. Each
compressor has lockout devices to protect it from short PTX030N 0-50-100% 2
cycling when tripped by safety controls. Each compressor PTX035N 0-50-100% 2
has a separate condenser coil with its own safety controls.
PTX040N 0-25-50-75-100% 4
Sight glass, filter drier and under voltage monitor are
standard on all models. PTX045N 0-25-50-75-100% 4
PTX050N 0-25-50-75-100% 4
PTX060N 0-33-66-100% 3
PTX070N 0-33-66-100% 3
PTX080N 0-25-50-75-100% 4
PTX090N 0-25-50-75-100% 4
PTX100N 0-25-50-75-100% 4

C. AIR HANDLING SECTION


OVERVIEW: The air handling section is made to meet the
compact design requirements as seen in the Figure. This
section contains the evaporator coil, drip eliminator (option-
al), blower fan and motor, electric heater (optional) and 2"
(50mm) filter rack.

* AIR HANDLING COMPARTMENT: The air handling


section is provided with 1" (25mm) thick 3 Ibs/ft3 (48
Kg/m3) density fiberglass insulation with single wall as
standard. 1" (25 mm) thick 3 Ibs/ft3 (48 Kg/m3) density
fiberglass insulation. Double wall construction as an option.
This will prevent condensation from forming on the casing.
Insulation meets the requirements of NFPA 90A regulations
for smoke and flame spread ratings and is protected against
deterioration and erosion from air currents. All access
panels, fixed panels, top and bottom panels are made of
galvanized steel, fastened and sealed with a rubber gasket
to prevent air and water leakage. All access panels are fixed
with 'C' clamp and free of screws, creates flexibility and
simple method of removing and re-installation the access
panels during maintenance.

Air Handling Section

9
* PRE FILTER RACK: Filters can be easily accessed through the filter access rack. 2" (50 mm) disposable panel filters are
standard for all models.

As an option, Zamil Air Conditioners can offer the following:


* 2" aluminum filters.
* 2" pleated filter.
* 2” high efficiency washable pleated filter

Disposable Filter Aluminum Filter Pleated Filter Washable Pleated Filter

* EVAPORATOR COIL: The evaporator coil is fin and tube type,


constructed of seamless copper tube mechanically bonded to
enhanced aluminum fins for maximum heat transfer efficiency. The fins
have full self-spacing collars, which completely cover each tube while
the staggered tube design improves the thermal efficiency. Each coil
equipped with a properly sized thermostatic (TXV) expansion valve and
distributor to ensure that equal refrigerant is fed to all circuits as well as
seamless copper headers. The number of circuits is chosen to provide
optimum heat transfer and reasonable refrigerant velocity and pressure
drop. End plates and tube support sheets aremade of 18gauge galva-
nized steel, formed to provide structural strength. Evaporator coils is
leak tested by charging H2N2 tracer gas in the factory at 450 psig.which
conforms to AHRI410. As options, Zamil AirConditioners can offer:

1. Copper Fins
2. Pre-coated Aluminum Fins
3. Anti-Corrosive Coating for Aluminum or Copper fins

Evaporator Coil

* DRAIN PAN: One of the primary functions of an air conditioning system is to remove water from the air it circulates, therefore
in order to remove the condensed water formed during de-humidification, a drain pan should be provided under the evaporator
(cooling) coil. The drain pan is mounted under evaporator coil on a positive sloped with single side coupling connection to
eliminate standing water and minimize bacteria growth. It is fabricated from G-90 galvanized steel, powder coated and the
outer surface is insulated with 1/8'' closed cell insulation to prevent condensation. For additional corrosion protection. As an
option, a stainless steel drain pan can be provided.

10
* SUPPLY AIR FAN:
• Double inlet, double width (DWDI) centrifugal fan.
• Forward fan with high quality and optimum selection.
• Backward fan is applicable to all models.
• All fan assemblies are statically and dynamically balanced and every
unit is vibration tested before shipment from factory.
• Fan drive by adjustable pitch pulleys and V-belt drive are standard.
• All fan and motor assemblies are isolated from the main unit on 1"
deflection rubber isolator mounts while 1" deflection spring isolators is
optional feature.
• Blower motor is mounted on an adjustable base and secured by a
locking device. Alignment and tensioning can be done in the field
without moving the motor from the base frame.

Blower Section

* BLOWER MOTOR:
Fan motors are of the Totally Enclosed Fan Cooled (TEFC) type, 2 poles or 4 poles with class "B" temperature rise for class "F"
insulation at 50OC ambient temperature and continuous duty. The motor’s index of protection is IP55, which protects from dust
and water. It is mounted on an adjustable base for proper alignment and belt tension adjustment. Motors are suitable for use
with a variable frequency drive. For motor sizing, all mechanical losses are considered in relation to the safety factor.

Blower Motor

D. AIR COOLED CONDENSING SECTION


• Open design permits unrestricted condenser airflow, access to
compressors, refrigeration components and piping.
• High efficiency scroll compressors are standard.
• Each compressor has a separate condenser coil.
• Each refrigerant circuit is furnished with an accessible sight glass,
filter drier, high-pressure switch, low-pressure switch and expansion
valve.
• Each compressor has a crankcase heater as standard.
• The compressor motor is provided with built-in thermal protection
during winding.
• Vertical air discharge minimizes condenser fan noise. Three phase
condenser fan motors eliminate reverse rotation failures.

Condeser Section

11
* CONDENSER FAN
Condenser fans are constructed of die cast aluminum blades / hubs with direct driven motors. All fans are statically and dynam-
ically balanced to operate at minimum noise and vibration. Fan blades are designed with appropriate pitch angle which result
in maximum airflow through the condenser coil. Condenser fan, the impeller and motor are constructed to form one integral
unit. All fan motors are equipped with IP55 ingress protection, three phase with class "F" winding insulation and ball bearings
for high ambient application. These fan motors are of the totally enclosed air over type (TEAO) with inherent thermal protection
of the automatic reset type. As options, Zamil Air Conditioners can offer:

1. UL/ETL recognized condenser fan


2. Fan with protective coating

Condenser Fan

* CONDENSER COIL: Condenser coil is of the fin and tube type, constructed of seamless (3/8" OD) inner grooved copper tube,
mechanically bonded to enhanced aluminum fins for maximum heat transfer efficiency. The fins have full self spacing collars,
which completely cover each tube while the staggered tube design improves the thermal efficiency. The number of circuits is
chosen to provide optimum heat transfer and reasonable refrigerant velocity and pressure drop. End plates and tube support
sheets are made of 18 gauge galvanized steel, formed to provide structural strength Condenser coils is leak tested by charging
H2N2 tracer gas in the factory at 650 psig.

As an option, Zamil Air Conditioners can offer:

1. Copper Fins
2. Pre-coated Aluminum Fins
3. Anti-Corrosive Coating for Aluminum & Copper fins

* CRANKCASE HEATERS: Compressors are equipped with crankcase heater. The compressor crankcase heater is always on
when the compressor is de-energized. This protects the system against refrigerant migration, oil dilution and potential
compressor failure.

* FILTER DRIER: Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil contaminating particles by the filter
drier. Sealed type is standard on all models while replaceable core filter drier is optional.

* SIGHT GLASS: The moisture indicating sight glass is installed in the liquid line and its color indicator shows moisture
contents and provides a means for checking the system’s refrigerant charge.

12
E. CONTROL PANEL
The standard control panel design is equivalent to NEMA-4 standard with hinged door for easy access. It’s designed to be
weather proof and to prevent accumulation of dust. Internal power and control wiring is neatly routed, properly anchored and all
wires are identified with cable markers as per NEC standard applicable to HVAC units. Major control devices fixed in the control
panel are UL approved and reliable in operation at high ambient conditions for a long period of time.

1. Controller board
2. Control transformer
3. Auxiliary terminal block
4. Condenser fan motor contactors
5. External overload relay for condenser fan motor (optional)
6. Condenser fan motor circuit breaker (optional)
7. Control fuse
8. High voltage terminal block
9. Earth terminal block
10. Compressor circuit breaker (optional)
11. Compressor contactor
12. Compressor overload relay (optional)
13. Blower motor circuit breaker (optional)
14. Blower motor contactor
15. Control relays Control Panel
16. Voltage monitor relay (UVM)

F. ELECTRICAL SPECIFICATIONS 2. UNIT OPTIONAL FEATURES:


1. UNIT STANDARD FEATURES: • Volt free contacts
• Under voltage monitor (phase failure Relay) • Fan cycling switches
• Ferrules for wires • Compressor circuit breaker
• Labels for wires and components • Unit disconnect switch
• Warning labels • Circuit breaker for each condenser fan
• PVC cable channels • Circuit breaker for blower motor
• Low and high terminal blocks • External overload for each compressor
• Copper ground bus • External overload for each condenser fan
• Crankcase heater for compressors • Discharge temperature sensor
• 220 V- 1 Ph- 50/60 Hz control voltage • Pump down solenoid valve
• Internal protection for compressors and condenser fans • Hot gas bypass valve
• Control fuses • Anti-freeze protection
• 2 or 4 stage thermostat
• Current transformers
• Service lamp
• Dirty filter indications
• Economizer (free cooling system)
• Electric heaters

13
G. MICROPROCESSOR CONTROLLER

These Packaged units are provided with a microprocessor control board incorporating the following features:

A. BALANCE LOADING OF COMPRESSORS: The unit’s electronic control automatically operates lead/lag sequence of
compressors. This is to load the compressors evenly over long periods of operation. If required however, compressor #1 can
also be set to always lead. In this case, compressor #1 always starts first and stops last. (Selectable through dip switch setting
on control board).

B. PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoid’s opening and compressor starting to equalize the pressure in the system necessary for compressor to start-up.
(Selectable through dip switch setting on control board).

C. COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for compressor.
This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat due to load
demand.

D. COMPRESSOR LOCK-OUT FUNCTION: If any of the unit’s safety control trips due to abnormal conditions, the electronic
controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a qualified service
technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.

E. FAULT DIAGNOSTICS: In case of system fault, LED’s on the board emits a flashing signal indicating where the fault is. This
is to guide the service technician in identifying the fault.

F. DIGITAL I/O’s: The unit’s control board is compatible to operate with a DDC controller or any standard 24V a.c. thermostat
commercially available.

Inputs from DDC or thermostat to the controller for 2 stage models:


* G - Indoor fan operates
* Y1 - 1st stage cooling
* Y2 - 2nd stage cooling
* W1- 1st stage heating
* W2- 2nd stage heating

Outputs from controller to the unit’s controlled devices for 2 stage models:
6. Evaporator fan
7. Compressor 1
8. Compressor 2
9. Heater 1
10. Heater 2
11. Condenser fan 1
12. Condenser fan 2
13. Pump down solenoid 1 (P1)
14. Pump down solenoid 2 (P2)
15. Compressor 1 trip (X1)
16. Compressor 2 trip (X2)

14
G. SEQUENTIAL CONTROL: With input signals from the thermostat or DDC, the motors in the equipment is started in sequen-
tial order: supply fan – condenser fan – compressor; at a pre-determined timings.
Cooling starting sequence without Pump down Solenoid:

Cooling starting sequence without Pump down Solenoid:

G energize
Indoor fan ON
2 sec

Y1 energize 2 sec
Outdoor fan 1 ON Compressor 1 ON SYSTEM 1
5 sec
Y2 energize 2 sec
Outdoor fan 2 ON Compressor 2 ON SYSTEM 2
5 sec

Cooling starting sequence with Pump down Solenoid:

G energize
Indoor fan ON
2 sec

Y1 energize 20 sec 2 sec


PDS 1 ON Outdoor fan 1 ON Compressor 1 ON SYSTEM 1
5 sec
Y2 energize 20 sec 2 sec
PDS 1 ON Outdoor fan 2 ON Compressor 2 ON SYSTEM 2
5 sec

Heating starting sequence:

G energize W1 energize W2 energize


Indoor fan ON Heater 1 ON Heater 2 ON
2 sec 40 sec 15 sec

H. VOLTAGE MONITOR RELAY (UVM)


This device protects the motors in the unit from faults such as, under or over voltage, unbalance, phase loss and phase reversal
of the power supply. When the device senses any of these faults, it will cut-off the supply in the control circuit thereby cutting
off power to the motors. The voltage monitor will re-set automatically when power is brought back to normal conditions.

TRIP & RE-SET VOLTAGE (% OF SET POINT)


LINE VOLTAGE
UNDER VOLTAGE OVER VOLTAGE PHASE IMBALANCE
RANGE
TRIP RE-SET TRIP RE-SET TRIP RE-SET
190 - 480 VAC 90% 93% 110% 107% 6% 4.5%

15
OPTIONAL ITEMS

A. Microchannel Condenser Coils (MCHX)


Microchannel coils are an aluminum construction coil and
composed of:
1. Extended flat tubes with many small flow channels.
2. Flat fins that are brazed to adjoining tubes.
3. Two refrigerant manifold headers.

Advantages of MCHX:
1. MCHX coils have more heat transfer per square foot than traditional
coils and require much less refrigerant charge.
2. No galvanic corrosion (100% aluminum).
3. Reduction in refrigerant charge compare to normal finned and tube
coils.
4. Long life alloy for very aggressive environments.
5. Improving the unit energy efficiency ratio (EER).
6. MCHX is lighter in weight, smaller in volume.

As an option, Zamil Air Conditioners can offer:


*Anti-Corrosive Coating is recommended for seacoast or
other corrosive applications and ambient environments.

B. MIXING BOX SECTION


When fresh air and return air mixing is required, mixing box is selected. The mixing box section is constructed of single wall of
heavy gauge galvanized steel with 1" thick (25mm) 3 Ibs/ft3 (48 Kg/m3) density fiberglass insulation. A double skin (inner wall)
made of galvanized steel with 1" (25mm) thick fiberglass insulation can be provided as an option.

C. MANUAL & MOTORIZED DAMPERS


The best way to control the return airflow with fresh air is by adding dampers on the mixing box section. These dampers are
heavy duty, multi-blade, low leakage and of opposed blade design. The dampers are prepared for either manual or motorized
operation (motor can be provided as an option).

Zamil dampers are entirely made of aluminum profiles with reinforced polyamide accessories, the blades of the damper has
airfoil shape and perfectly controlled by gears that are spaced out by special spacers located in the damper frame.

Zamil damper has an excellent anti-corrosion features as it is made of aluminum and polyamide which make it light in weight
and yet extremely strong because of its well-engineered design. The damper’s air tightness is enhanced by special gasket
inserted in both, the blades and the frame itself.

The outdoor air damper is equipped with a rain hood (factory installed) as standard on the side of the unit as seen in Figure
below. The rain hood is constructed from galvanized steel, finished with the same durable paint finish as the main unit and
includes cleanable aluminum filter to drain water away from the entering air stream.

Mixing Box & Dampers

16
D. BAG FILTER SECTION
The bag filter section is constructed of single wall heavy gauge galvanized steel with 1" thick (25mm) 3 Ibs/ft3 (48 Kg/m3) densi-
ty fiberglass insulation. As an option, double skin (inner wall) made of galvanized steel with 1" (25mm) thick fiberglass insulation
can be provided. Per filter media is an aluminum filter or pleated while the bag filter media is synthetic micro-fiber with high
efficiency air cleaning capability. As an option, the filter pressure gauge (Magnehelic manometer) can be ordered with each filter
section to help promote regular servicing and prevent clogging.

Bag Filter

E. 4" MINI PLEATED FILTER:


As alterative solution to bag Fitter, Zamil can offer high efficiency filter with compact design, which is equivalent to bag filter
efficiency 4" mini pleated filter is designed to perform in difficult operating conditions .The filter media is made of ultra-fine wet
laid fibers.

Mini Pleated Filter

F. HOT GAS BYPASS CONTROL


Hot gas bypass control can be provided on the lead circuit to permit operation of the system down to 80% of its unloaded
capacity. Under low ambient conditions, it controls temperature by eliminating the need to cycle the compressor on and off,
ensuring narrow temperature swing and lengthening the life span of the compressor.

G. PUMP DOWN SOLENOID VALVE


A pump down solenoid valve is installed in the liquid line. When the room thermostat is satisfied, the valve closes and the
compressor continues to run until a substantial portion of the refrigerant has been pumped out from the evaporator coil. The
low-pressure switch will cycle off the compressor at a predetermined evaporator pressure.

H. DRIP ELIMINATOR
The drip (moisture) eliminator is required when the velocity across the cooling coil is above 500 FPM (2.54 m/s). Eliminators are
made of plastic material encased within a galvanized steel frame, which is placed between the coil and blower. This arrange-
ment eliminates water carry over with low-pressure drop.

I. PRESSURE GAUGES
This option is used for monitoring and inspecting the suction and discharge pressure, it is installed on the condensing section,
which allows inspection of refrigerant system performance.

J. UNIT FULL GUARD


The guard is mounted on the condensing section only, which protects the condenser coil from physical damage.

17
K. BULK HEAD LIGHT
The bulk headlight can be equipped inside the fan section to provide light for servicing purpose.

L.VARIABLE FREQNACY DRIVE FOR BLOWER MOTOR (VFD)


Variable Frequency Drives are installed on blower fan motors to vary the fan speed in applica-
tions where the supply CFM is not constant and must be varied. In applications where Variable
Air Volume (VAV’s), for example, are installed throughout the occupied space, the total CFM
discharged by the packaged unit will depend on the demand requested by the VAV boxes. When
the space is satisfied and the VAV box closes its damper, the total required CFM will be reduced.
To avoid over pressurizing the ducting, a Variable Frequency Drive is installed to reduce the
speed of the fan and hence reduce the total CFM discharged by the unit. A full range of Variable
Frequency Drives 40 (220V-3Phase, 380/480V-3phase).

M. ELECTRIC HEATERS Electric Heating Capacity Table


Electric heaters are of the resistance open-coil type and
conform to the requirements of UL 573 or equivalent. ELECTRIC HEATING NO. OF
MODEL
Electrical characteristics, kW capacities and number of CAPACITY (KW) HEATING STAGE
stages are as indicated. Thermal cutouts, fusible links PTX022N 10, 15, 20, 30, 40 2
and airflow switches are provided to shut-off power to
PTX025N 10, 15, 20, 30, 40 2
heaters in case of airflow failure.
PTX030N 20, 30, 40, 50 2
PTX035N 20, 30, 40, 50 2
PTX040N 30, 40, 50, 60 4
PTX045N 30, 40, 50, 60 4
PTX050N 30, 40, 50, 60 4
PTX060N 37.5,45,52.5,60 3
PTX070N 37.5,45,52.5,60 3
PTX080N 40, 50, 60, 80, 100 4
PTX090N 40, 50, 60, 80, 100 4
Electric Heater
PTX100N 40, 50, 60, 80, 100 4

N.FAN CYCLE SWITCH HEAD PRESSURE CONTROL


The capacity of air-cooled condensers varies with the difference between condensing temperature and condenser entering air
temperature (ambient temperature). It increases as this difference increases. For a given capacity, a drop in the ambient
temperature will lower the condensing temperatures and if the ambient temperature drops below a given limit, head pressure
control is required. Control shall be set for a minimum of 95°F (35°C) saturated refrigerant condensing temperature, or to suit
the specified application.

O.CIRCUIT BREAKER FOR COMPRESSORS OR CONDENSER MOTOR OR BLOWER MOTOR


This feature protects against branch circuit fault. When tripped (manually or automatically), the breaker cut-off the power supply
to the compressor /condenser motor /blower motor and disable its control through the breaker's auxiliary contacts.

P. MOTOR EXTERNAL OVERLOAD PROTECTION


Motors are provided with overload relays or a built-in thermal winding device or both for its overload protection.

18
Q.ECONOMIZER/CO2 MONITORING
The economizer permits low cost operation by utilizing cool outdoor air for free cooling. A damper on the economizer controls
the amount of outdoor air and on closed position it provides a leak proof seal. It can easily be adjusted for 100% outdoor air,
100% return air or any proportions of mixed air.

The economizer is operated either by a dry bulb outdoor air thermostat (OAT) or a solid state enthalpy controller (EC) used to
sense the outdoor air temperature. The unit is equipped with an electronic control board and the economizer uses controller
with a sensitive feedback system that carefully modulates the damper to allow correct percentage of fresh air and return air.
The economizer controller is designed to match with the Zamil electronic thermostat.

1. OUTDOOR AIR THERMOSTAT (OAT) ECONOMIZER CONTROL


Economizer operation is governed by outdoor temperature and unit OAT setting, as follows:

a. Outdoor Temperature > Outdoor Air Thermostat (OAT) setting:


If the thermostat calls for cooling, the economizer damper moves to minimum position, simultaneously blower motor, compres-
sor-1 & fan motors would start. If further cooling is required, compressor-2 also starts with a time delay. After the thermostat is
satisfied the compressors are staged out. The economizer controller moves the damper automatically to closed position simul-
taneously the blower is also shutdown.

b. Outdoor Temperature < Outdoor Air Thermostat (OAT) setting:


As the cooling load would be low, the economizer controller will operate as stage-1 of cooling system first switching ON the
blower motor simultaneously modulating the damper in steps to required position, allowing the cool outside air into indoor side.
If further cooling is required compressor-1 & fan motors will switch ON as stage-2 of the system, whereas compressor-2 is
pulled out of service. As the room temperature is attained, economizer controls will cut-off the compressor, fan motors simulta-
neously closing damper to fully closed position.

2. ENTHALPY SENSOR FOR ECONOMIZER CONTROL


The solid state enthalpy sensor is capable of accurately sensing outdoor air enthalpy content (temperature & humidity) and
controlling the economizer damper for the minimum heat content introduce to the evaporator coil. Thereby, providing an
efficient & economical system operation.

3. CO2 MONITOR
Indoor air quality (IAQ) is becoming more and more important, CO2 monitoring give an indication of the amount of CO2 inside
a facility. Once it is exceeding a certain level it sends a signal to the control system demanding for fresh air to replace the inside
poor quality air. The control is responding in opening the damper and at the same time there is input in the control for an
exhaust relief fan externally connected to the unit as it purge the poor quality air.

19
R.ULTRA VIOLET LIGHT

1. IMPROVED OVERALL INDOOR AIR QUALITY


When used for general IAQ control, UV FLOWTM products can successfully:
• Control fungi in HVAC systems to reduce or eliminate mold-related allergies.
• Prevent the development of different types of bacteria.
• Reduce the spread of cold and flu viruses and other airborne transmitted diseases.
• Eliminate odors and maintain a fresh air smell indoors.

UV FLOWTM Emitters pose no risk to components, equipment or inhabitants. Their


non-chemical energy kills organisms without producing secondary contamination
and costs little to operate.

UV Light

2. SAVE ENERGY AND CUT COSTS


UV FLOWTM can reduce maintenance cost as UVC lights successfully eliminate the bio-film (dirt) that fouls surface of heat
exchangers - completely cleaning and continuously maintaining coils and drain pans to 'as new' conditions. This in turn
improves heat-transfer efficiency, coil pressure drop, and fan performance.

S.DISCONNECT SWITCH
A single non-fused disconnect switch is provided for disconnecting electrical power
at the unit. The disconnect switch is mounted internally on the control panel and
operated by an externally mounted handle. Disconnect Switch

T.ELECTRONIC THERMOSTAT
Electronic thermostat can control up to four cooling stages and four heating stages
depending on the number of compressors and electric heaters.

The thermostat normally displays room temperature and mode of operation. The
temperature can be set by up/down buttons for both cooling and heating cycles. The
thermostat also allows you to select continuous fan operation or have the fan on
intermittent operation with the equipment. The thermostat is best located about 1500
mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should not
be exposed to direct light from lamps, sun etc. It should be in return air stream, away
from supply air registers/diffusers.

Electronic Thermostat

U. ANTI-CORROSIVE COATING
: A single component of aluminum impregnated coating applied on the fins of heat exchanging coils. The product has
been designed for Middle East climate conditions. A high chemical, abrasion and UV resistance has been proven in both
laboratories and on field environment. The coating can be applied at the factory as well as in the field for maintenance or rejuve-
nation purposes.

Multi : A two component coating system that withstands the extreme climate conditions. The coating can be applied
to all metal parts of HVAC equipment; the piping, the compressors and grids might require a different pretreatment and layer
build up. Please check ResisTec product information sheets, the heat exchangers can not be coated using this type. The coating
can be applied at the factory as well as in the field for maintenance or rejuvenation purposes.

20
PHYSICAL DATA

MODEL NUMBER 022N 025N 030N 035N

GROSS CAPACITY (F&T @ 95OF DB AMBIENT & 80/67OF INLET TEMP.)* 20.6 23.2 29.4 34.7
GROSS CAPACITY (MCHX @ 95OF DB AMBIENT & 80/67OF INLET TEMP.)* 21.1 23.9 30.1 35.8
NUMBER OF REFRIGERATION CIRCUIT 2 2 2 2
TYPE HERMETIC SCROLL

OIL TYPE POE OIL

OIL PER SYSTEM (OZ) 110 110 110/114 114


COMPRESSOR
REFRIGERANT R-410A

CHARGE PER SYSTEM ( F&T ) - (IB) 29.7 29.7 29.7/56.6 56.6


CHARGE PER SYSTEM (MCHX) - (IB) 18.8 18.8 18.8/33.4 33.4
TYPE PROPELLER WITH DIRECT DRIVEN MOTOR

QTY. 2 2 3 4
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION & IP55

MOTOR SIZE (KW) 1.35 1.35 1.35 1.35


TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)

CONDENSER COIL FINS SPACING (FPI) 16 16 16 16


TOTAL FACE AREA (SQ. FT.) 48.9 48.9 73.3 97.8
TYPE MICROCHANNEL COIL (MCHX)

CONDENSER COIL FINS SPACING (FPI) 20 20 20 20


TOTAL FACE AREA (SQ. FT.) 48.9 48.9 73.3 97.8
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)

EVAPORATOR COIL FINS SPACING (FPI) 14 14 14 14


TOTAL FACE AREA (SQ. FT.) 24.6 24.6 24.6 24.6
TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN ( FORWARD OR BACKWARD)


EVAPORATOR BLOWER
MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55

NOMINAL AIR FLOW (CFM) 8000 8500 10000 11500


OPEN (PSIG) 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22
OPEN (PSIG) 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7
SOUND PRESSURE LEVEL , ( 1 m /3m / 5m )** dBA 71.7/65.7/62.2 73.5/67.5/64 75.3/69.3/65.8 76.5/70.5/67

*GROSS COOLING CAPACITY (TR)


**BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA

21
PHYSICAL DATA

MODEL NUMBER 040N 045N 050N 060N

GROSS CAPACITY (F&T @ 95OF DB AMBIENT & 80/67OF INLET TEMP.)* 39.6 43.1 47.0 60.7

GROSS CAPACITY (MCHX @ 95OF DB AMBIENT & 80/67OF INLET TEMP.)* 40.8 44.4 48.8 62.5
NUMBER OF REFRIGERATION CIRCUIT 4 4 4 3
TYPE HERMETIC SCROLL

OIL TYPE POE OIL

OIL PER SYSTEM (OZ) 110 110 110 114/152


COMPRESSOR
REFRIGERANT R-410A

CHARGE PER SYSTEM ( F&T ) - (IB) 30.3 30.3 30.3 57.2/60


CHARGE PER SYSTEM (MCHX) - (IB) 19.4 19.4 19.4 34.4/37.8
TYPE PROPELLER WITH DIRECT DRIVEN MOTOR

QTY. 4 4 4 6
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION & IP55

MOTOR SIZE (KW) 1.35 1.35 1.35 1.35


TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)

CONDENSER COIL FINS SPACING (FPI) 16 16 16 16


TOTAL FACE AREA (SQ. FT.) 97.8 97.8 97.8 146.6
TYPE MICROCHANNEL COIL (MCHX)

CONDENSER COIL FINS SPACING (FPI) 20 20 20 20


TOTAL FACE AREA (SQ. FT.) 97.8 97.8 97.8 146.6
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)

EVAPORATOR COIL FINS SPACING (FPI) 14 14 14 14


TOTAL FACE AREA (SQ. FT.) 37.0 37.0 37.0 46.2
TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN ( FORWARD OR BACKWARD)


EVAPORATOR BLOWER
MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55

NOMINAL AIR FLOW (CFM) 14000 14500 16000 17500


OPEN (PSIG) 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22
OPEN (PSIG) 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7
SOUND PRESSURE LEVEL , ( 1 m /3m / 5m )** dBA 74.7/68.7/65.2 75.7/69.7/66.2 76.5/70.5/67 81.9/75.9/72.4

*GROSS COOLING CAPACITY (TR)


**BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA

22
PHYSICAL DATA

MODEL NUMBER 070N 080N 090N 100N

GROSS CAPACITY (F&T @ 95OF DB AMBIENT & 80/67OF INLET TEMP.)* 64.8 78.1 88.6 99.7

GROSS CAPACITY (MCHX @ 95OF DB AMBIENT & 80/67OF INLET TEMP.)* 67.1 80.7 90.6 103.4
NUMBER OF REFRIGERATION CIRCUIT 3 4 4 4
TYPE HERMETIC SCROLL

OIL TYPE POE OIL

OIL PER SYSTEM (OZ) 152 114/152 152 152


COMPRESSOR
REFRIGERANT R-410A

CHARGE PER SYSTEM ( F&T ) - (IB) 60 58.1/62.2 62.2 79.1


CHARGE PER SYSTEM (MCHX) - (IB) 37.8 35.3/39.7 39.7 41.3
TYPE PROPELLER WITH DIRECT DRIVEN MOTOR

QTY. 6 8 8 8
CONDENSER FAN
MOTOR TYPE TOTALLY ENCLOSED AIR OVER TYPE (TEAO) , CLASS F INSULATION & IP55

MOTOR SIZE (KW) 1.35 1.35 1.35 2.4


TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)

CONDENSER COIL FINS SPACING (FPI) 16 16 16 14


TOTAL FACE AREA (SQ. FT.) 146.6 195.5 195.5 195.5
TYPE MICROCHANNEL COIL (MCHX)

CONDENSER COIL FINS SPACING (FPI) 20 20 20 20


TOTAL FACE AREA (SQ. FT.) 146.6 195.5 195.5 195.5
TYPE ENHANCED FINS & INNER GROOVED TUBES (F&T)

EVAPORATOR COIL FINS SPACING (FPI) 14 14 14 14


TOTAL FACE AREA (SQ. FT.) 46.2 55.0 55.0 67.2
TYPE DIDW CENTRIFUGAL FAN WITH V-BELT DRIVE

QTY. SINGLE FAN ( FORWARD OR BACKWARD)


EVAPORATOR BLOWER
MOTOR TYPE TOTALLY ENCLOSED FAN COOLED TYPE (TEFC) , CLASS F INSULATION & IP55

NOMINAL AIR FLOW (CFM) 19000 25500 27000 31000


OPEN (PSIG) 650±15 650±15 650±15 650±15
HIGH PRESSURE SWITCH
CLOSE (PSIG) 500±22 500±22 500±22 500±22
OPEN (PSIG) 50±7 50±7 50±7 50±7
LOW PRESSURE SWITCH
CLOSE (PSIG) 90±7 90±7 90±7 90±7
SOUND PRESSURE LEVEL , ( 1 m /3m / 5m )** dBA 83.1/77.1/73.5 82.5/76.5/73 84.3/78.3/74.7 86.2/80.2/76.6

*GROSS COOLING CAPACITY (TR)


**BASED ON FREE FIELD AREA AT AHRI CONDITION . TOLERANCE: ± 2dBA

23
PERFORMANCE DATA

MODEL: PTX022N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 7000 8000 9200
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 231.5 252.4 269.2 237.0 258.3 275.3 244.0 263.8 280.8
85 SC 216.4 179.2 149.8 231.7 189.4 156.4 244.0 200.6 163.1
KW 14.5 14.8 15.1 14.6 14.9 15.2 14.7 15.0 15.3
TC 221.7 241.8 258.2 226.8 247.2 263.2 235.1 252.2 268.1
95 SC 211.5 174.3 144.9 226.6 184.3 151.1 235.1 195.1 157.4
KW 16.1 16.4 16.7 16.2 16.5 16.8 16.3 16.6 16.9
TC 211.4 230.4 246.1 217.7 235.3 250.7 225.6 240.3 255.5
105 SC 206.5 169.0 139.6 217.7 178.8 145.3 225.6 189.5 151.6
KW 17.9 18.3 18.5 18.0 18.3 18.6 18.1 18.4 18.7
TC 200.4 218.8 233.5 207.9 223.6 237.6 215.1 227.9 241.9
115 SC 200.4 163.5 134.0 207.9 173.2 139.5 215.1 183.5 145.3
KW 20.0 20.2 20.5 20.1 20.3 20.5 20.2 20.4 20.6
TC 190.4 206.1 219.7 197.3 210.4 223.7 203.9 214.1 227.1
125 SC 190.4 157.5 127.9 197.3 166.9 133.1 203.9 176.9 138.3
KW 22.3 22.5 22.7 22.4 22.6 22.7 22.5 22.6 22.8

MODEL: PTX022N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 7000 8000 9200
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 236.8 258.6 276.1 242.5 264.7 282.5 249.2 270.4 288.4
85 SC 219.0 182.1 152.8 234.4 192.5 159.5 249.2 203.8 166.5
KW 13.8 14.1 14.3 13.9 14.2 14.4 14.0 14.3 14.5
TC 226.6 247.2 263.7 231.8 252.8 269.7 239.7 258.1 275.1
95 SC 213.9 176.8 147.4 229.1 187.0 153.9 239.7 198.0 160.5
KW 15.5 15.8 16.0 15.6 15.9 16.1 15.7 15.9 16.2
TC 215.6 235.3 251.7 221.3 240.3 256.5 229.6 245.8 261.1
105 SC 208.5 171.3 142.1 221.3 181.1 148.0 229.6 192.2 154.2
KW 17.4 17.7 17.9 17.5 17.7 18.0 17.6 17.8 18.0
TC 203.4 222.4 237.3 210.8 227.4 242.1 218.3 231.8 246.3
115 SC 202.6 165.2 135.7 210.8 175.0 141.5 218.3 185.4 147.4
KW 19.6 19.8 20.0 19.7 19.9 20.1 19.8 20.0 20.2
TC 192.1 208.6 222.4 199.1 212.7 226.4 205.8 216.9 229.6
125 SC 192.1 158.8 129.0 199.1 168.1 134.4 205.8 178.4 139.6
KW 22.2 22.3 22.5 22.2 22.4 22.6 22.3 22.4 22.6

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

24
PERFORMANCE DATA

MODEL: PTX025N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 7300 8500 10000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 260.8 284.0 302.6 268.5 291.6 310.2 275.7 299.0 317.2
85 SC 234.6 196.1 165.5 253.3 208.7 173.5 274.6 222.8 182.1
KW 17.3 17.7 18.1 17.4 17.9 18.2 17.5 18.0 18.3
TC 249.1 271.6 289.5 256.0 278.9 296.4 264.5 285.9 303.2
95 SC 228.9 190.3 159.8 247.1 202.6 167.5 264.5 216.5 175.8
KW 19.2 19.6 20.0 19.4 19.8 20.1 19.5 19.9 20.3
TC 236.4 258.0 275.1 242.6 264.7 281.6 252.5 271.0 287.8
105 SC 222.6 184.0 153.5 240.5 196.0 161.0 252.5 209.6 169.0
KW 21.5 21.9 22.2 21.6 22.0 22.3 21.8 22.1 22.5
TC 222.9 243.7 259.5 230.3 249.3 265.5 240.0 255.1 270.9
115 SC 216.0 177.3 146.7 230.3 188.8 153.9 240.0 202.0 161.4
KW 23.8 24.2 24.6 24.0 24.4 24.7 24.2 24.5 24.9
TC 208.5 228.3 243.9 217.5 233.8 249.4 226.5 238.9 253.5
125 SC 208.5 170.2 139.8 217.5 181.6 146.6 226.5 194.3 153.1
KW 26.5 26.8 27.1 26.7 26.9 27.2 26.8 27.0 27.4

MODEL: PTX025N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 7300 8500 10000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 268.6 292.7 312.0 276.7 300.9 320.1 284.1 308.7 328.3
85 SC 238.4 200.2 169.6 257.3 213.1 177.8 278.8 227.3 187.0
KW 16.4 16.7 17.0 16.5 16.8 17.1 16.6 16.9 17.2
TC 256.1 279.5 298.0 263.6 287.3 305.7 271.1 294.5 312.7
95 SC 232.3 194.0 163.5 250.8 206.6 171.5 271.1 220.5 180.1
KW 18.4 18.8 19.0 18.5 18.9 19.2 18.6 19.0 19.3
TC 242.8 265.1 283.1 249.4 272.2 289.8 258.7 278.8 296.5
105 SC 225.7 187.4 157.0 243.9 199.6 164.5 258.7 213.3 172.9
KW 20.7 21.1 21.3 20.8 21.2 21.4 21.0 21.3 21.5
TC 227.6 249.1 266.0 234.6 255.5 272.4 244.7 261.5 278.1
115 SC 218.2 179.9 149.5 234.6 191.7 156.9 244.7 205.2 164.6
KW 23.4 23.7 24.0 23.5 23.8 24.1 23.6 23.9 24.2
TC 211.3 231.6 247.3 220.0 237.3 252.8 229.2 242.5 258.0
125 SC 210.3 171.8 141.3 220.0 183.3 148.2 229.2 196.1 155.4
KW 26.4 26.7 26.9 26.5 26.8 27.0 26.7 26.9 27.1

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

25
PERFORMANCE DATA

MODEL: PTX030N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 8500 10000 11500
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 327.2 356.8 380.5 338.1 368.0 391.6 346.7 376.7 400.2
85 SC 288.9 243.0 206.4 314.2 260.4 217.5 337.9 275.9 227.3
KW 21.0 21.6 22.0 21.2 21.8 22.2 21.3 21.9 22.4
TC 313.6 342.0 364.7 323.5 352.4 375.1 331.9 360.7 383.2
95 SC 282.2 236.2 199.5 307.1 253.1 210.3 329.2 268.5 219.8
KW 23.2 23.7 24.2 23.4 23.9 24.4 23.5 24.1 24.6
TC 298.4 325.9 347.5 307.7 335.4 357.2 317.1 343.0 364.3
105 SC 274.7 228.7 192.0 299.2 245.2 202.4 317.1 260.1 211.5
KW 25.7 26.2 26.6 25.8 26.4 26.8 26.0 26.5 27.0
TC 282.4 308.7 329.0 291.2 317.2 337.4 302.1 324.1 344.5
115 SC 266.8 220.6 183.9 289.7 236.7 193.7 302.1 251.3 202.5
KW 28.4 28.9 29.4 28.6 29.1 29.6 28.8 29.3 29.7
TC 265.0 289.9 309.1 275.6 297.9 317.1 285.9 303.7 322.8
125 SC 258.2 212.0 175.1 275.6 227.7 184.5 285.9 241.7 192.5
KW 31.5 31.9 32.3 31.7 32.1 32.5 31.9 32.2 32.7

MODEL: PTX030N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 8500 10000 11500
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 334.8 365.4 390.1 346.3 377.1 401.9 355.2 386.5 411.2
85 SC 292.8 247.0 210.6 318.4 264.5 222.0 342.1 280.6 232.1
KW 20.1 20.6 21.0 20.3 20.8 21.2 20.4 21.0 21.4
TC 320.6 349.9 373.5 331.1 360.8 384.4 339.4 369.4 392.8
95 SC 285.7 239.9 203.3 310.8 257.0 214.4 334.3 272.5 224.1
KW 22.4 22.9 23.3 22.5 23.0 23.5 22.7 23.2 23.6
TC 304.8 332.9 355.2 314.5 343.1 365.3 323.5 350.8 372.9
105 SC 277.9 232.0 195.3 302.7 248.7 206.0 322.6 263.9 215.2
KW 24.9 25.4 25.8 25.1 25.6 26.0 25.3 25.7 26.2
TC 287.3 314.1 335.3 296.0 323.1 344.3 306.8 330.1 351.1
115 SC 269.2 223.1 186.6 293.2 239.4 196.7 306.8 254.2 205.5
KW 27.9 28.4 28.8 28.1 28.5 28.9 28.3 28.7 29.1
TC 268.2 293.3 313.1 278.3 301.5 321.2 288.9 307.8 327.2
125 SC 259.9 213.5 176.8 278.3 229.3 186.5 288.9 243.7 194.6
KW 31.3 31.8 32.1 31.5 31.9 32.3 31.7 32.0 32.4

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

26
PERFORMANCE DATA

MODEL: PTX035N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 9800 11500 13000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 385.8 420.5 448.7 398.9 434.5 462.2 407.8 443.7 471.4
85 SC 334.2 282.0 240.6 361.8 301.0 252.8 384.7 316.0 262.1
KW 24.6 25.3 25.8 24.8 25.5 26.1 25.0 25.7 26.3
TC 370.4 404.0 430.3 382.2 416.3 442.7 390.5 425.1 451.4
95 SC 326.3 274.1 232.3 353.6 292.4 244.2 376.0 307.2 253.1
KW 27.0 27.7 28.2 27.3 28.0 28.5 27.4 28.1 28.7
TC 353.2 385.7 411.0 364.0 396.9 421.9 372.4 404.8 430.1
105 SC 317.9 265.4 223.9 344.4 283.1 235.0 366.9 297.4 243.8
KW 29.8 30.4 30.9 30.0 30.6 31.2 30.2 30.8 31.3
TC 334.3 365.0 389.1 344.8 375.8 399.3 352.8 383.2 406.1
115 SC 308.4 255.6 214.3 334.8 273.2 224.9 352.8 287.3 232.8
KW 32.9 33.5 34.0 33.1 33.7 34.2 33.3 33.9 34.4
TC 314.8 343.7 365.8 323.8 352.8 374.7 334.6 359.5 380.9
125 SC 298.7 245.6 203.7 323.8 262.2 213.6 334.6 275.7 221.3
KW 36.3 36.9 37.4 36.5 37.2 37.7 36.7 37.3 37.8

MODEL: PTX035N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 9800 11500 13000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 398.1 433.6 462.5 411.5 447.9 476.5 420.9 457.8 486.3
85 SC 340.4 288.2 246.7 368.3 307.4 259.1 391.1 322.6 268.8
KW 23.8 24.4 24.9 24.0 24.6 25.2 24.1 24.8 25.4
TC 381.9 416.2 443.4 394.4 429.5 456.4 403.2 438.6 465.4
95 SC 332.2 279.9 238.2 359.7 298.6 250.3 382.2 313.6 259.4
KW 26.2 26.8 27.4 26.4 27.1 27.6 26.6 27.3 27.8
TC 364.0 397.0 422.8 375.4 408.8 434.9 383.4 417.5 442.5
105 SC 323.3 270.7 229.1 350.2 288.8 240.7 372.4 303.6 249.2
KW 29.1 29.7 30.2 29.3 29.9 30.4 29.4 30.1 30.6
TC 344.2 375.3 399.9 354.5 386.3 410.4 362.2 393.9 417.7
115 SC 313.4 260.5 218.9 339.7 278.2 229.7 361.8 292.2 238.1
KW 32.4 33.0 33.5 32.6 33.2 33.7 32.7 33.3 33.8
TC 322.6 352.1 374.5 331.8 361.6 383.9 341.7 368.3 389.9
125 SC 302.6 249.6 207.6 328.3 266.5 217.7 341.7 280.1 225.4
KW 36.1 36.7 37.2 36.3 36.9 37.4 36.5 37.0 37.5

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

27
PERFORMANCE DATA

MODEL: PTX040N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 12000 14000 16200
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 441.1 481.8 513.4 454.6 495.5 527.3 466.0 507.9 539.6
85 SC 388.1 326.3 277.0 418.3 346.7 290.1 448.3 366.7 302.7
KW 28.6 29.3 29.8 28.8 29.5 30.0 29.0 29.7 30.2
TC 423.1 461.7 492.2 435.8 474.6 505.7 446.6 485.9 516.1
95 SC 379.0 316.8 267.7 408.9 336.7 280.4 438.6 356.2 292.0
KW 31.9 32.5 33.0 32.1 32.7 33.3 32.3 32.9 33.4
TC 404.2 441.2 469.5 415.8 453.1 481.0 426.3 462.9 490.9
105 SC 369.6 307.3 257.4 398.8 326.5 269.4 426.3 345.0 280.6
KW 35.6 36.1 36.7 35.7 36.3 36.9 35.9 36.6 37.0
TC 383.2 418.4 445.8 393.8 429.6 456.4 406.7 438.5 465.2
115 SC 359.2 296.4 247.0 387.7 315.3 258.4 406.7 333.4 268.9
KW 39.7 40.2 40.6 39.9 40.4 40.8 40.1 40.5 40.9
TC 360.8 394.5 420.3 371.9 404.4 429.6 386.0 412.9 437.5
125 SC 348.1 285.0 235.7 371.9 303.2 246.3 386.0 321.0 255.9
KW 44.4 44.8 45.1 44.5 44.9 45.3 44.7 45.0 45.4

MODEL: PTX040N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 12000 14000 16200
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 455.6 497.9 530.8 469.8 512.5 546.0 482.3 525.4 558.4
85 SC 395.2 334.0 284.6 425.6 354.6 298.4 456.5 375.1 311.0
KW 27.3 27.8 28.3 27.5 28.0 28.5 27.6 28.2 28.7
TC 437.3 476.6 508.0 449.8 490.1 521.6 461.2 502.3 533.8
95 SC 386.2 323.8 274.7 415.9 344.0 287.3 446.1 364.2 300.1
KW 30.7 31.2 31.7 30.9 31.4 31.9 31.0 31.6 32.1
TC 416.4 454.4 484.3 428.2 467.2 497.0 439.2 478.1 507.4
105 SC 375.7 313.4 264.0 405.0 333.2 276.6 435.0 352.5 288.2
KW 34.6 35.1 35.5 34.7 35.2 35.6 34.9 35.4 35.8
TC 393.9 430.2 458.2 405.0 441.5 469.7 416.9 451.4 479.2
115 SC 364.5 302.0 252.5 393.5 320.9 264.3 416.9 339.6 275.3
KW 39.0 39.4 39.8 39.1 39.6 39.9 39.3 39.7 40.1
TC 369.5 403.2 429.8 379.5 413.8 439.4 393.8 422.3 447.6
125 SC 352.3 289.2 239.8 379.5 307.5 250.6 393.8 325.5 260.5
KW 44.1 44.5 44.8 44.2 44.6 44.9 44.4 44.7 45.0

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

28
PERFORMANCE DATA

MODEL: PTX045N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 12400 14500 16600
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 480.4 524.1 559.1 495.7 540.1 575.5 508.2 553.1 588.1
85 SC 423.6 356.6 303.0 459.3 381.0 319.0 492.8 403.6 333.0
KW 31.5 32.2 32.9 31.8 32.5 33.2 32.0 32.8 33.4
TC 459.5 501.8 536.0 474.1 517.0 550.8 487.1 529.0 563.0
95 SC 413.2 346.2 292.9 448.6 370.2 308.2 477.9 392.3 321.9
KW 35.1 35.8 36.4 35.3 36.1 36.7 35.6 36.3 36.9
TC 437.4 478.2 510.6 451.0 492.1 524.2 464.5 502.7 535.0
105 SC 402.3 335.3 281.9 437.1 358.7 296.5 462.3 380.0 309.5
KW 39.1 39.8 40.5 39.4 40.1 40.7 39.6 40.3 40.9
TC 414.0 453.1 483.5 427.8 465.7 496.6 442.0 475.2 505.8
115 SC 390.8 323.5 270.1 421.6 346.3 284.3 442.0 367.1 296.3
KW 43.6 44.2 44.9 43.8 44.5 45.1 44.1 44.7 45.3
TC 388.6 425.9 455.5 403.4 437.4 466.7 418.5 446.7 475.1
125 SC 378.3 311.0 257.7 403.4 333.0 270.9 418.5 353.4 282.4
KW 48.6 49.2 49.6 48.8 49.3 49.8 49.0 49.5 50.0

MODEL: PTX045N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 12400 14500 16600
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 495.1 540.6 577.1 511.5 557.8 594.3 524.7 571.3 608.1
85 SC 431.0 364.3 310.8 467.1 389.2 327.3 500.9 412.0 341.8
KW 30.0 30.6 31.1 30.2 30.9 31.4 30.4 31.1 31.6
TC 473.2 516.9 551.9 488.2 533.0 568.2 501.1 545.6 580.6
95 SC 420.0 353.2 299.8 455.5 377.6 315.8 488.0 400.0 329.7
KW 33.7 34.4 34.9 33.9 34.6 35.1 34.1 34.8 35.3
TC 449.7 491.9 525.3 464.0 506.4 539.9 477.1 518.0 551.8
105 SC 408.4 341.6 288.2 443.6 365.3 303.4 471.1 387.1 316.8
KW 38.0 38.6 39.0 38.2 38.8 39.3 38.3 38.9 39.5
TC 424.0 464.1 495.8 437.4 477.5 508.8 451.4 487.7 519.5
115 SC 395.8 328.6 275.3 428.4 352.0 289.7 451.4 372.8 302.5
KW 42.9 43.4 43.9 43.0 43.6 44.1 43.2 43.7 44.2
TC 395.5 433.7 463.2 409.7 445.2 475.4 425.0 454.9 484.0
125 SC 381.6 314.5 261.1 409.1 336.7 274.8 425.0 357.4 286.4
KW 48.5 48.9 49.3 48.6 49.1 49.5 48.8 49.2 49.6

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

29
PERFORMANCE DATA

MODEL: PTX050N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 14000 16000 18600
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 528.3 575.0 612.5 542.2 589.7 627.3 556.3 604.9 642.4
85 SC 476.3 397.6 335.2 511.5 421.7 350.6 554.4 449.9 367.9
KW 34.8 35.7 36.4 35.1 36.0 36.7 35.4 36.3 37.0
TC 504.0 550.1 586.6 517.5 563.6 600.1 533.9 577.6 613.8
95 SC 464.3 386.1 324.0 499.3 409.3 338.7 533.9 437.0 354.9
KW 38.8 39.6 40.3 39.0 39.9 40.6 39.3 40.1 40.8
TC 478.1 522.2 557.2 490.1 534.9 570.5 510.3 548.4 582.1
105 SC 451.5 373.1 310.9 485.5 396.0 325.1 510.3 423.5 340.6
KW 43.2 44.0 44.7 43.4 44.3 45.0 43.8 44.5 45.3
TC 451.4 493.1 526.2 465.1 504.2 537.3 484.3 516.9 548.7
115 SC 438.3 359.6 297.1 465.1 381.4 310.5 484.3 408.1 325.5
KW 48.0 48.9 49.6 48.2 49.1 49.8 48.8 49.4 50.0
TC 422.7 462.9 493.8 439.9 473.7 503.5 457.9 484.7 513.0
125 SC 422.7 345.3 283.0 439.9 366.8 295.0 457.9 392.8 308.6
KW 53.3 54.0 54.7 53.6 54.2 54.9 53.9 54.4 55.1

MODEL: PTX050N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 14000 16000 18600
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 548.2 597.5 636.6 563.1 612.8 652.0 578.9 629.2 668.2
85 SC 486.2 408.3 345.8 521.8 432.4 361.4 565.7 461.5 379.5
KW 32.9 33.5 34.1 33.1 33.8 34.3 33.3 34.0 34.5
TC 522.8 570.4 608.0 537.1 585.2 622.7 551.5 600.5 637.3
95 SC 473.5 395.4 333.2 509.1 419.4 348.4 551.5 447.9 365.6
KW 36.9 37.6 38.2 37.1 37.8 38.4 37.3 38.1 38.6
TC 495.4 541.4 577.5 508.5 555.3 591.4 526.4 568.9 605.1
105 SC 460.1 382.0 319.9 494.8 405.3 334.6 526.4 433.1 351.3
KW 41.5 42.2 42.8 41.7 42.4 43.0 42.0 42.6 43.2
TC 465.2 509.3 543.9 477.5 521.6 556.4 498.7 534.0 568.0
115 SC 445.0 367.1 305.0 477.5 389.6 318.9 498.7 416.3 334.2
KW 46.8 47.5 48.0 47.0 47.7 48.2 47.3 47.9 48.4
TC 431.9 473.5 506.6 448.8 484.4 516.9 467.6 496.7 527.6
125 SC 428.7 350.3 288.6 448.8 372.1 301.3 467.6 398.3 315.6
KW 52.9 53.5 54.0 53.1 53.6 54.1 53.4 53.8 54.3

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

30
PERFORMANCE DATA

MODEL: PTX060N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 15000 17500 20000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 670.9 732.6 783.5 695.7 758.9 810.2 715.5 780.4 830.3
85 SC 565.1 482.1 415.7 613.0 515.9 438.5 658.0 547.2 458.1
KW 45.9 47.0 48.0 46.3 47.5 48.6 46.7 47.9 49.0
TC 644.5 704.3 752.6 667.4 728.6 777.1 686.5 747.6 795.8
95 SC 551.7 468.9 402.1 599.1 501.7 424.0 643.3 531.7 443.0
KW 50.6 51.7 52.7 51.0 52.2 53.2 51.4 52.6 53.6
TC 616.7 673.7 719.9 637.4 696.2 742.3 656.2 713.6 759.4
105 SC 538.0 454.5 387.8 584.1 486.5 408.7 624.1 515.7 427.0
KW 55.8 57.0 57.9 56.3 57.5 58.4 56.7 57.8 58.8
TC 586.5 641.3 684.9 606.4 661.5 705.4 624.5 677.9 720.1
115 SC 523.0 439.4 372.5 567.9 470.3 392.4 604.0 499.0 409.5
KW 61.7 62.8 63.7 62.1 63.2 64.2 62.5 63.6 64.6
TC 553.8 606.0 647.5 573.7 624.7 665.9 590.5 639.2 680.2
125 SC 506.6 422.8 356.1 547.1 453.1 374.9 582.2 480.9 391.5
KW 68.2 69.3 70.2 68.7 69.7 70.6 69.0 70.0 70.9

MODEL: PTX060N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 15000 17500 20000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 690.4 754.2 806.6 716.4 781.9 834.8 737.3 804.0 857.0
85 SC 574.8 492.2 426.0 623.4 526.6 449.2 669.0 558.1 470.0
KW 43.9 44.9 45.8 44.3 45.4 46.3 44.6 45.8 46.7
TC 662.9 724.1 774.0 686.8 749.4 800.0 706.1 770.3 820.4
95 SC 561.1 478.2 411.4 608.5 511.6 434.2 653.4 542.3 454.0
KW 48.8 49.8 50.7 49.1 50.2 51.1 49.5 50.6 51.5
TC 633.4 692.1 739.5 655.2 715.3 763.0 673.5 734.2 781.8
105 SC 546.4 463.1 396.5 592.9 495.4 417.9 636.0 525.5 436.8
KW 54.3 55.3 56.1 54.6 55.7 56.5 55.0 56.0 56.9
TC 600.6 656.5 701.5 621.2 677.6 723.3 639.1 694.7 739.4
115 SC 529.9 446.5 379.6 575.9 477.9 400.4 614.1 507.1 418.2
KW 60.6 61.6 62.4 61.0 62.0 62.8 61.3 62.3 63.1
TC 564.9 617.7 659.5 583.7 636.7 678.6 600.9 651.8 693.6
125 SC 512.1 428.3 361.3 554.5 458.8 380.7 590.0 486.7 397.6
KW 67.8 68.8 69.6 68.2 69.2 70.0 68.5 69.5 70.3

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

31
PERFORMANCE DATA

MODEL: PTX070N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 16000 19000 22000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 714.3 780.1 834.0 742.5 810.7 864.1 765.9 834.2 888.0
85 SC 601.3 512.9 442.4 657.4 552.7 468.6 710.4 588.7 492.1
KW 50.4 51.6 52.7 50.9 52.2 53.3 51.3 52.7 53.8
TC 685.9 749.4 800.8 713.0 777.8 829.9 734.1 799.7 851.6
95 SC 586.9 498.3 427.8 642.9 537.4 453.8 694.9 572.6 476.2
KW 55.6 56.8 57.8 56.1 57.4 58.4 56.5 57.8 58.9
TC 656.4 717.0 765.6 681.4 742.8 792.3 700.2 763.1 811.6
105 SC 572.2 483.2 412.3 627.0 521.2 437.3 678.1 555.5 458.5
KW 61.4 62.7 63.7 62.0 63.3 64.3 62.4 63.7 64.7
TC 625.0 683.0 729.2 647.7 707.0 752.5 665.7 725.3 771.5
115 SC 556.4 467.3 396.2 610.6 504.3 419.9 660.8 537.7 440.9
KW 67.9 69.1 70.2 68.4 69.6 70.8 68.8 70.1 71.2
TC 590.7 646.6 690.7 611.9 668.0 712.3 632.2 684.7 728.6
125 SC 539.5 450.5 379.5 592.9 486.0 402.0 632.2 518.5 421.5
KW 75.1 76.3 77.2 75.6 76.7 77.7 76.0 77.1 78.0

MODEL: PTX070N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 16000 19000 22000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 739.3 807.8 864.3 770.4 840.9 897.7 794.5 866.3 924.0
85 SC 613.4 525.9 455.7 671.3 566.8 483.3 724.9 603.7 508.1
KW 48.1 49.1 50.0 48.5 49.6 50.6 48.9 50.1 51.0
TC 709.9 775.4 828.7 738.1 805.3 859.6 760.6 828.9 882.8
95 SC 598.8 510.6 439.8 655.1 550.0 466.8 707.8 586.3 489.8
KW 53.5 54.5 55.4 53.9 55.1 56.0 54.3 55.4 56.4
TC 678.3 740.9 791.7 705.1 768.7 820.3 725.5 790.6 841.7
105 SC 583.0 494.4 423.6 638.6 533.0 449.5 690.4 568.4 471.9
KW 59.6 60.7 61.5 60.1 61.1 62.0 60.4 61.5 62.4
TC 643.6 703.4 751.6 668.1 728.7 777.3 686.4 748.5 796.4
115 SC 565.8 476.7 405.9 620.6 514.5 430.8 671.1 548.8 451.6
KW 66.7 67.7 68.5 67.1 68.1 69.0 67.4 68.5 69.3
TC 606.3 662.7 707.5 627.6 685.2 730.1 646.2 702.8 747.3
125 SC 547.1 458.0 386.7 600.7 494.2 409.9 646.2 527.3 430.1
KW 74.7 75.7 76.6 75.1 76.2 77.0 75.4 76.5 77.3

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

32
PERFORMANCE DATA

MODEL: PTX080N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 22500 25500 29000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 875.7 954.1 1017.3 897.9 977.6 1040.6 919.5 1000.7 1063.3
85 SC 762.7 642.7 547.4 811.3 676.4 569.3 865.3 712.9 592.3
KW 58.5 60.0 61.2 58.9 60.4 61.8 59.3 60.9 62.3
TC 839.5 915.2 976.0 860.6 937.5 997.7 882.0 958.7 1018.2
95 SC 744.5 624.6 529.3 792.9 657.4 550.5 844.4 693.0 572.1
KW 64.4 65.9 67.1 64.8 66.3 67.6 65.2 66.8 68.0
TC 801.9 875.1 932.4 821.6 895.1 952.7 843.5 914.7 970.7
105 SC 725.6 605.6 510.1 773.5 637.5 530.4 817.1 671.9 550.9
KW 71.1 72.5 73.7 71.5 72.9 74.1 71.9 73.3 74.5
TC 761.0 831.0 885.4 780.8 849.7 903.6 802.7 867.2 919.8
115 SC 705.3 584.8 489.4 749.1 616.2 508.5 787.6 649.5 527.9
KW 78.5 79.9 81.0 78.9 80.3 81.4 79.3 80.6 81.9
TC 718.4 783.8 834.8 738.8 800.6 851.1 758.9 816.4 866.5
125 SC 684.1 563.0 466.8 718.9 592.9 485.0 756.4 625.2 503.7
KW 86.7 88.1 89.2 87.1 88.5 89.5 87.6 88.8 89.9

MODEL: PTX080N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 22500 25500 29000
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 903.3 984.7 1050.7 927.3 1010.2 1076.3 950.5 1034.3 1100.7
85 SC 776.4 657.1 562.2 826.0 691.9 585.0 880.8 728.8 608.7
KW 56.0 57.3 58.5 56.3 57.7 58.9 56.7 58.2 59.4
TC 866.5 944.2 1007.5 888.7 967.8 1030.2 910.3 990.9 1052.8
95 SC 758.0 638.3 543.2 806.9 671.9 564.5 860.7 708.2 587.6
KW 62.1 63.4 64.5 62.4 63.8 64.9 62.8 64.2 65.4
TC 826.6 901.0 960.8 847.1 923.0 982.7 868.7 943.4 1002.4
105 SC 737.9 618.0 522.6 786.1 650.6 543.5 835.1 685.7 565.1
KW 69.0 70.3 71.4 69.3 70.7 71.7 69.7 71.0 72.1
TC 782.7 854.3 910.3 801.7 873.8 929.1 824.5 892.1 947.5
115 SC 716.0 595.7 500.3 763.5 627.6 519.8 803.6 661.4 540.6
KW 77.0 78.2 79.3 77.3 78.6 79.7 77.7 78.9 80.0
TC 735.4 802.1 854.5 754.9 819.3 871.3 775.6 836.4 887.3
125 SC 692.5 571.1 475.4 731.0 601.6 494.2 768.6 635.0 513.2
KW 86.0 87.3 88.3 86.4 87.6 88.7 86.8 88.0 89.0

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

33
PERFORMANCE DATA

MODEL: PTX90N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 24500 27000 30500
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 996.7 1085.2 1155.8 1017.9 1107.0 1178.1 1042.6 1131.7 1204.3
85 SC 863.5 728.6 620.5 908.4 759.0 640.9 967.7 798.1 666.1
KW 67.7 69.4 70.9 68.1 69.8 71.3 68.6 70.4 71.9
TC 957.6 1042.2 1110.2 977.1 1062.9 1132.1 999.2 1086.2 1154.7
95 SC 843.8 708.3 600.5 888.1 737.9 620.5 945.7 776.9 644.1
KW 74.7 76.4 77.7 75.1 76.7 78.1 75.5 77.2 78.6
TC 915.3 996.2 1061.5 932.8 1014.9 1080.9 954.0 1036.7 1102.0
105 SC 822.7 686.5 579.2 865.7 715.3 597.9 923.5 753.2 620.4
KW 82.6 84.2 85.5 82.9 84.6 86.0 83.4 85.0 86.4
TC 872.1 950.3 1010.2 888.3 966.3 1027.6 907.7 986.3 1046.6
115 SC 801.3 665.3 556.2 843.9 692.7 573.9 900.3 729.1 595.8
KW 91.1 92.7 94.3 91.4 93.1 94.6 91.8 93.5 95.0
TC 824.4 898.5 958.0 839.1 914.6 973.4 862.0 933.4 990.2
125 SC 777.6 640.9 533.3 819.1 668.5 550.0 862.0 704.1 570.2
KW 100.7 102.2 103.5 101.0 102.5 103.8 101.4 103.0 104.2

MODEL: PTX90N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 24500 27000 30500
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 1019.0 1111.5 1185.4 1041.3 1134.7 1209.4 1067.7 1161.8 1235.8
85 SC 875.1 740.8 633.7 920.1 772.1 654.6 979.8 812.3 680.2
KW 64.5 66.0 67.2 64.9 66.4 67.6 65.3 66.8 68.1
TC 977.3 1064.8 1135.3 997.7 1086.9 1156.7 1021.2 1111.5 1182.7
95 SC 853.8 718.7 611.3 898.1 749.4 631.2 956.5 788.8 656.6
KW 71.8 73.2 74.4 72.1 73.6 74.8 72.5 74.0 75.3
TC 933.2 1016.9 1084.0 951.5 1036.5 1103.3 973.8 1059.9 1127.3
105 SC 831.9 696.1 589.0 875.4 725.5 607.9 933.4 764.2 631.6
KW 79.9 81.3 82.5 80.2 81.7 82.8 80.6 82.0 83.2
TC 884.7 965.5 1027.4 901.4 981.8 1046.6 921.1 1003.4 1067.2
115 SC 807.4 672.3 563.8 850.2 700.0 582.1 907.0 737.3 605.2
KW 89.3 90.7 91.8 89.6 91.0 92.1 90.0 91.4 92.5
TC 831.0 906.8 966.7 846.4 922.7 982.8 868.6 945.6 1001.2
125 SC 780.8 644.5 536.9 822.6 671.9 553.9 868.6 709.8 575.3
KW 100.0 101.4 102.5 100.3 101.7 102.8 100.7 102.1 103.1

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

34
PERFORMANCE DATA

MODEL: PTX100N
EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 26400 31000 35500
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 1104.0 1206.2 1286.8 1143.3 1247.1 1329.3 1174.7 1278.8 1361.2
85 SC 950.5 805.4 688.8 1033.2 862.5 727.1 1110.1 913.6 759.4
KW 74.2 76.2 77.8 75.0 77.0 78.7 75.6 77.7 79.4
TC 1060.5 1158.1 1237.0 1096.6 1196.6 1276.1 1126.4 1227.2 1305.3
95 SC 928.5 783.0 666.7 1010.3 838.9 703.7 1084.1 889.6 734.6
KW 81.8 83.7 85.3 82.6 84.5 86.1 83.1 85.1 86.8
TC 1013.2 1107.4 1182.8 1048.3 1144.0 1219.3 1078.6 1172.4 1244.9
105 SC 904.9 759.1 643.1 986.4 814.2 678.3 1050.2 863.5 707.4
KW 90.6 92.4 93.9 91.2 93.1 94.6 91.8 93.7 95.2
TC 963.2 1053.2 1124.4 995.8 1086.8 1157.3 1026.6 1112.0 1181.6
115 SC 880.3 733.5 617.4 958.5 787.4 650.8 1012.9 835.0 679.0
KW 100.4 102.2 103.7 101.0 102.9 104.4 101.7 103.4 104.9
TC 910.1 996.4 1063.7 942.9 1026.6 1092.0 972.9 1050.0 1113.6
125 SC 853.8 707.2 590.4 921.2 758.7 621.6 972.9 805.4 648.3
KW 111.4 113.1 114.5 112.0 113.7 115.2 112.6 114.2 115.7

MODEL: PTX100N (MCHX)


EVAPORATOR AIRFLOW, CFM
Condenser Entering Air 26400 31000 35500
Temp (OF) WB WB WB WB WB WB WB WB WB
62 67 71 62 67 71 62 67 71
TC 1144.8 1249.0 1334.6 1187.0 1294.3 1380.9 1219.9 1329.1 1415.0
85 SC 970.8 825.6 709.9 1055.0 884.9 749.5 1132.7 937.5 782.9
KW 71.1 72.8 74.3 71.7 73.5 75.1 72.3 74.2 75.7
TC 1098.0 1199.9 1280.4 1137.6 1240.2 1322.3 1168.4 1272.4 1354.3
95 SC 947.4 802.7 686.0 1030.6 859.4 723.8 1106.8 910.8 756.5
KW 79.0 80.6 82.0 79.6 81.3 82.8 80.1 81.9 83.4
TC 1048.9 1145.5 1222.8 1085.2 1183.5 1261.5 1114.7 1213.8 1290.5
105 SC 922.7 776.9 660.4 1004.4 832.9 697.2 1076.0 883.3 727.9
KW 88.1 89.7 91.0 88.7 90.3 91.7 89.2 90.8 92.2
TC 995.0 1086.9 1160.9 1027.9 1121.8 1195.2 1058.8 1148.7 1222.0
115 SC 896.0 749.3 633.3 976.3 803.8 667.5 1036.6 852.4 697.6
KW 98.7 100.2 101.5 99.3 100.8 102.1 99.8 101.3 102.6
TC 935.2 1023.2 1092.3 967.7 1055.0 1123.7 998.0 1078.3 1147.1
125 SC 866.0 719.5 603.0 939.3 772.2 635.8 993.4 818.9 663.4
KW 110.9 112.4 113.6 111.5 112.9 114.2 112.0 113.4 114.6

TC - Total Capacity (1000 Btuh) Gross kW - Compressor Power Input


SC - Sensible Heat Capacity (1000 Btuh) Gross CFM - Cubic feet per minute
DBE- Dry Bulb Temp.(OF) of Air Entering Coil WBE - Wet Bulb Temp. (OF) of Air Entering Coil

NOTES: 1, Direct interpolation is permissible - Do not extrapolate

35
ELECTRICAL DATA
DESCRIPTION PTX022N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (2 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 99.6 110
10 14.4 99.6 110
15 21.7 99.6 110
4 14
20 28.9 99.6 110
30 43.3 111.6 125
40 57.7 143.0 150
0 0.0 103.5 125
10 14.4 103.5 125
15 21.7 103.5 125
5.5 17.9
20 28.9 103.5 125
30 43.3 116.5 125
40 57.7 147.9 150
230-3-60 207 253 5 33.6 225
0 0.0 109.8 125
10 14.4 109.8 125
15 21.7 109.8 125
7.5 24.2
20 28.9 109.8 125
30 43.3 124.4 150
40 57.7 155.8 175
0 0.0 122.2 150
10 25.1 122.2 150
15 37.7 122.2 150
11 36
20 50.2 122.2 150
30 75.3 139.1 150
40 100.4 170.5 175
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

36
ELECTRICAL DATA
DESCRIPTION PTX022N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (2 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 63.6 80
10 14.4 63.6 80
15 21.7 63.6 80
4 9.1
20 28.9 63.6 80
30 43.3 65.5 80
40 57.7 83.5 90
0 0.0 64.3 90
10 14.4 64.3 90
15 21.7 64.3 90
5.5 10.1
20 28.9 64.3 90
30 43.3 66.8 90
380/400-3-60 40 57.7 84.8 90
(4 WIRE) 342 418 3 21.4 140
0 0.0 67.8 90
10 14.4 67.8 90
15 21.7 67.8 90
7.5 13.6
20 28.9 67.8 90
30 43.3 71.1 90
40 57.7 89.2 90
0 0.0 74.9 100
10 14.4 74.9 100
15 21.7 74.9 100
11 20.7
20 28.9 74.9 100
30 43.3 80.0 100
40 57.7 98.0 100
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

37
ELECTRICAL DATA
DESCRIPTION PTX022N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (2 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 56.5 80
10 12.6 56.5 80
15 18.8 56.5 80
4 9
20 25.1 56.5 80
30 37.7 58.3 80
40 50.2 74.0 80
0 0.0 56.9 80
10 12.6 56.9 80
15 18.8 56.9 80
5.5 9.4
20 25.1 56.9 80
30 37.7 58.8 80
40 50.2 74.5 80
460-3-60 414 506 2.8 18.6 114
0 0.0 60.2 80
10 12.6 60.2 80
15 18.8 60.2 80
7.5 12.7
20 25.1 60.2 80
30 37.7 62.9 80
40 50.2 78.6 80
0 0.0 67.4 90
10 12.6 67.4 90
15 18.8 67.4 90
11 19.7
20 25.1 67.4 90
30 37.7 71.7 90
40 50.2 87.4 90
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

38
ELECTRICAL DATA
DESCRIPTION PTX025N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (2 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 99.6 125
10 14.4 99.6 125
15 21.7 99.6 125
4 14
20 28.9 99.6 125
30 43.3 111.6 125
40 57.7 143.0 150
0 0.0 103.5 125
10 14.4 103.5 125
15 21.7 103.5 125
5.5 17.9
20 28.9 103.5 125
30 43.3 116.5 150
40 57.7 147.9 175
0 0.0 109.8 125
10 14.4 109.8 125
15 21.7 109.8 125
230-3-60 207 253 5 33.6 225 7.5 24.2
20 28.9 109.8 125
30 43.3 124.4 150
40 57.7 155.8 175
0 0.0 129.5 150
10 25.1 129.5 150
15 37.7 129.5 150
11 36
20 50.2 129.5 150
30 75.3 139.1 150
40 100.4 170.5 175
0 0.0 145.2 175
10 25.1 145.2 175
15 37.7 145.2 175
15 48.8
20 50.2 145.2 175
30 75.3 155.1 175
40 100.4 186.5 200

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

39
ELECTRICAL DATA
DESCRIPTION PTX025N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (2 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 74.5 100
10 14.4 74.5 100
15 21.7 74.5 100
4 9.1
20 28.9 74.5 100
30 43.3 74.5 100
40 57.7 83.5 100
0 0.0 75.5 100
10 14.4 75.5 100
15 21.7 75.5 100
5.5 10.1
20 28.9 75.5 100
30 43.3 75.5 100
40 57.7 84.8 100
0 0.0 79.0 110
10 14.4 79.0 110
380/400-3-60 15 21.7 79.0 110
(4 WIRE) 342 418 3 21.4 140 7.5 13.6
20 28.9 79.0 110
30 43.3 79.0 110
40 57.7 79.0 110
0 0.0 86.1 110
10 14.4 86.1 110
15 21.7 86.1 110
11 20.7
20 28.9 86.1 110
30 43.3 86.1 110
40 57.7 98.0 110
0 0.0 94.3 110
10 14.4 94.3 110
15 21.7 94.3 110
15 28.4
20 28.9 94.3 110
30 43.3 94.3 110
40 57.7 107.7 125

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

40
ELECTRICAL DATA
DESCRIPTION PTX025N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (2 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 59.6 80
10 12.6 59.6 80
15 18.8 59.6 80
4 9
20 25.1 59.6 80
30 37.7 59.6 80
40 50.2 74.0 80
0 0.0 60.0 80
10 12.6 60.0 80
15 18.8 60.0 80
5.5 9.4
20 25.1 60.0 80
30 37.7 60.0 80
40 50.2 74.5 80
0 0.0 63.3 80
10 12.6 63.3 80
15 18.8 63.3 80
460-3-60 414 506 2.8 18.6 114 7.5 12.7
20 25.1 63.3 80
30 37.7 63.3 80
40 50.2 78.6 80
0 0.0 70.3 90
10 12.6 70.3 90
15 18.8 70.3 90
11 19.7
20 25.1 70.3 90
30 37.7 71.7 90
40 50.2 87.4 90
0 0.0 79.4 100
10 12.6 79.4 100
15 18.8 79.4 100
15 27
20 25.1 79.4 100
30 37.7 80.8 100
40 50.2 96.5 100

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

41
ELECTRICAL DATA
DESCRIPTION PTX030N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (3 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 147.6 200
20 50.2 147.6 200
5.5 17.9 30 75.3 147.6 200
40 100.4 147.9 200
50 125.5 179.3 200
0 0.0 153.9 200
20 50.2 153.9 200
7.5 24.2 30 75.3 153.9 200
40 100.4 155.8 200
62.1 340 50 125.5 187.1 200
230-3-60 207 253 5 & &
37.1 239 0 0.0 165.7 200
20 50.2 165.7 200
11 36 30 75.3 165.7 200
40 100.4 170.5 200
50 125.5 201.9 225
0 0.0 178.5 200
20 50.2 178.5 200
15 48.8 30 75.3 178.5 200
40 100.4 186.5 200
50 125.5 125.5 225
0 0.0 92.9 125
20 28.9 92.9 125
5.5 10.1 30 43.3 92.9 125
40 57.7 92.9 125
50 72.2 102.8 125
0 0.0 96.4 125
20 28.9 96.4 125
7.5 13.6 30 43.3 96.4 125
40 57.7 96.4 125
380/400-3-60 37.9 196 50 72.2 107.2 125
342 418 3 & &
(4 WIRE) 0 0.0
26.4 145 103.5 125
20 28.9 103.5 125
11 20.7 30 43.3 103.5 125
40 57.7 103.5 125
50 72.2 116.1 125
0 0.0 111.2 150
20 28.9 111.2 150
15 28.4 30 43.3 111.2 150
40 57.7 111.2 150
50 72.2 125.7 150
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

42
ELECTRICAL DATA
DESCRIPTION PTX030N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (3 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 75.3 110
20 25.1 75.3 110
5.5 9.4 30 37.7 75.3 110
40 50.2 75.3 110
50 62.8 90.2 110
0 0.0 78.6 110
20 25.1 78.6 110
7.5 12.7 30 37.7 78.6 110
40 50.2 78.6 110
30 173
460-3-60 414 506 2.8 & & 50 62.8 94.3 110
20 125 0 0.0 85.6 110
20 25.1 85.6 110
11 19.7 30 37.7 85.6 110
40 50.2 87.4 110
50 62.8 103.1 110
0 0.0 92.9 110
20 25.1 92.9 110
15 27 30 37.7 92.9 110
40 50.2 96.5 110
50 62.8 112.2 125

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

43
ELECTRICAL DATA
DESCRIPTION PTX035N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 159.8 200
20 50.2 159.8 200
7.5 24.2 30 75.3 159.8 200
40 100.4 159.8 200
50 125.5 187.1 200
0 0.0 171.6 200
20 50.2 171.6 200
11 36 30 75.3 171.6 200
40 100.4 171.6 200

230-3-60 207 253 5 37.1 239 50 125.5 201.9 225


0 0.0 187.3 225
20 50.2 187.3 225
15 48.8 30 75.3 187.3 225
40 100.4 187.3 225
50 125.5 217.9 225
0 0.0 200.2 225
20 50.2 200.2 225
18.5 59.1 30 75.3 200.2 225
40 100.4 200.2 225
50 125.5 230.8 250
0 0.0 108.4 125
20 28.9 108.4 125
7.5 13.6 30 43.3 108.4 125
40 57.7 108.4 125
50 72.2 108.4 125
0 0.0 115.5 125
20 28.9 115.5 125
11 20.7 30 43.3 115.5 125
40 57.7 115.5 125
380/400-3-60 50 72.2 116.1 125
342 418 3 26.4 145
(4 WIRE)
0 0.0 123.7 150
20 28.9 123.7 150
15 28.4 30 43.3 123.7 150
40 57.7 123.7 150
50 72.2 125.7 150
0 0.0 130.7 150
20 28.9 130.7 150
18.5 34 30 43.3 130.7 150
40 57.7 130.7 150
50 72.2 132.7 150
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

44
ELECTRICAL DATA
DESCRIPTION PTX035N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 86.1 110
20 25.1 86.1 110
7.5 12.7 30 37.7 86.1 110
40 50.2 86.1 110
50 62.8 94.3 110
0 0.0 93.1 110
20 25.1 93.1 110
11 19.7 30 37.7 93.1 110
40 50.2 93.1 110
460-3-60 414 506 2.8 20 125 50 62.8 103.1 110
0 0.0 102.2 110
20 25.1 102.2 110
15 27 30 37.7 102.2 110
40 50.2 102.2 110
50 62.8 112.2 125
0 0.0 107.2 125
20 25.1 107.2 125
18.5 31 30 37.7 107.2 125
40 50.2 107.2 125
50 62.8 117.2 125

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

45
ELECTRICAL DATA
DESCRIPTION PTX040N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 187.0 200
30 75.3 187.0 200
7.5 24.2 40 100.4 187.0 200
50 125.5 187.1 200
60 150.6 218.5 225
0 0.0 199.4 225
30 75.3 199.4 225
11 36 40 100.4 199.4 225
50 125.5 201.9 225

230-3-60 207 253 5 33.6 225 60 150.6 233.3 250


0 0.0 215.4 225
30 75.3 215.4 225
15 48.8 40 100.4 215.4 225
50 125.5 217.9 225
60 150.6 249.3 300
0 0.0 228.3 250
30 75.3 228.3 250
18.5 59.1 40 100.4 228.3 250
50 125.5 230.8 250
60 150.6 262.1 300
0 0.0 116.6 125
30 43.3 116.6 125
7.5 13.6 40 57.7 116.6 125
50 72.2 116.6 125
60 86.6 125.3 150
0 0.0 123.7 150
30 43.3 123.7 150
11 20.7 40 57.7 123.7 150
50 72.2 123.7 150
380/400-3-60 60 86.6 134.1 150
342 418 3 21.4 140
(4 WIRE)
0 0.0 133.1 150
30 43.3 133.1 150
15 28.4 40 57.7 133.1 150
50 72.2 133.1 150
60 86.6 143.8 150
0 0.0 140.1 150
30 43.3 140.1 150
18.5 34 40 57.7 140.1 150
50 72.2 140.1 150
60 86.6 150.8 175
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

46
ELECTRICAL DATA
DESCRIPTION PTX040N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 103.0 110
30 37.7 103.0 110
7.5 12.7 40 50.2 103.0 110
50 62.8 103.0 110
60 75.3 110.0 125
0 0.0 110.2 125
30 37.7 110.2 125
11 19.7 40 50.2 110.2 125
50 62.8 110.2 125
460-3-60 414 506 2.8 18.6 114 60 75.3 118.8 125
0 0.0 119.4 125
30 37.7 119.4 125
15 27 40 50.2 119.4 125
50 62.8 119.4 125
60 75.3 127.9 150
0 0.0 124.4 150
30 37.7 124.4 150
18.5 31 40 50.2 124.4 150
50 62.8 124.4 150
60 75.3 132.9 150

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

47
ELECTRICAL DATA
DESCRIPTION PTX045N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 194.9 225
30 75.3 194.9 225
7.5 24.2 40 100.4 194.9 225
50 125.5 194.9 225
60 150.6 218.5 225
0 0.0 206.7 225
30 75.3 206.7 225
11 36 40 100.4 206.7 225
50 125.5 206.7 225
60 150.6 233.3 250
0 0.0 222.4 250
37.1 239 30 75.3 222.4 250
230-3-60 207 253 5 & & 15 48.8 40 100.4 222.4 250
33.6 225 50 125.5 222.4 250
60 150.6 249.3 300
0 0.0 235.3 250
30 75.3 235.3 250
18.5 59.1 40 100.4 235.3 250
50 125.5 235.3 250
60 150.6 262.1 300
0 0.0 249.2 300
30 75.3 249.2 300
22 70.2 40 100.4 249.2 300
50 125.5 249.2 300
60 150.6 276.0 300
0 0.0 127.8 150
30 43.3 127.8 150
7.5 13.6 40 57.7 127.8 150
50 72.2 127.8 150
60 86.6 127.8 150
0 0.0 134.9 150
30 43.3 134.9 150
11 20.7 40 57.7 134.9 150
50 72.2 134.9 150
60 86.6 134.9 150
0 0.0 143.1 150
380/400-3-60 26.4 145 30 43.3 143.1 150
(4 WIRE) 342 418 3 & & 15 28.4 40 57.7 143.1 150
21.4 140 50 72.2 143.1 150
60 86.6 143.8 150
0 0.0 150.1 175
30 43.3 150.1 175
18.5 34 40 57.7 150.1 175
50 72.2 150.1 175
60 86.6 150.8 175
0 0.0 158.1 175
30 43.3 158.1 175
22 40.4 40 57.7 158.1 175
50 72.2 158.1 175
60 86.6 158.8 175
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

48
ELECTRICAL DATA
DESCRIPTION PTX045N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 106.1 125
30 37.7 106.1 125
7.5 12.7 40 50.2 106.1 125
50 62.8 106.1 125
60 75.3 110.0 125
0 0.0 113.1 125
30 37.7 113.1 125
11 19.7 40 50.2 113.1 125
50 62.8 113.1 125
60 75.3 118.8 125
0 0.0 122.2 125
20 125 30 37.7 122.2 125
460-3-60 414 506 2.8 & & 15 27 40 50.2 122.2 125
18.6 114 50 62.8 122.2 125
60 75.3 127.9 150
0 0.0 127.2 150
30 37.7 127.2 150
18.5 31 40 50.2 127.2 150
50 62.8 127.2 150
60 75.3 132.9 150
0 0.0 136.3 150
30 37.7 136.3 150
22 38.3 40 50.2 136.3 150
50 62.8 136.3 150
60 75.3 142.0 150

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

49
ELECTRICAL DATA
DESCRIPTION PTX050N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 213.7 250
30 75.3 213.7 250
11 36 40 100.4 213.7 250
50 125.5 213.7 250
60 150.6 233.3 250
0 0.0 229.4 250
30 75.3 229.4 250
15 48.8 40 100.4 229.4 250
50 125.5 229.4 250
60 150.6 249.3 250
0 0.0 242.3 250
30 75.3 242.3 250
230-3-60 207 253 5 37.1 239 18.5 59.1 40 100.4 242.3 250
50 125.5 242.3 250
60 150.6 262.1 250
0 0.0 256.2 250
30 75.3 256.2 250
22 70.2 40 100.4 256.2 250
50 125.5 256.2 250
60 150.6 276.0 300
0 0.0 288.9 300
30 75.3 288.9 300
30 96.4 40 100.4 288.9 300
50 125.5 288.9 300
60 150.6 308.8 350
0 0.0 144.9 150
30 43.3 144.9 150
11 20.7 40 57.7 144.9 150
50 72.2 144.9 150
60 86.6 144.9 150
0 0.0 153.1 175
30 43.3 153.1 175
15 28.4 40 57.7 153.1 175
50 72.2 153.1 175
60 86.6 153.1 175
0 0.0 160.1 175
380/400-3-60 30 43.3 160.1 175
(4 WIRE) 342 418 3 26.4 145 18.5 34 40 57.7 160.1 175
50 72.2 160.1 175
60 86.6 160.1 175
0 0.0 168.1 175
30 43.3 168.1 175
22 40.4 40 57.7 168.1 175
50 72.2 168.1 175
60 86.6 168.1 175
0 0.0 186.1 200
30 43.3 186.1 200
30 54.8 40 57.7 186.1 200
50 72.2 186.1 200
60 86.6 186.1 200
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

50
ELECTRICAL DATA
DESCRIPTION PTX050N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (4 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 115.9 125
30 37.7 115.9 125
11 19.7 40 50.2 115.9 125
50 62.8 115.9 125
60 75.3 118.8 125
0 0.0 125.0 150
30 37.7 125.0 150
15 27 40 50.2 125.0 150
50 62.8 125.0 150
60 75.3 127.9 150
0 0.0 130.0 150
30 37.7 130.0 150
460-3-60 414 506 2.8 20 125 18.5 31 40 50.2 130.0 150
50 62.8 130.0 150
60 75.3 132.9 150
0 0.0 139.1 150
30 37.7 139.1 150
22 38.3 40 50.2 139.1 150
50 62.8 139.1 150
60 75.3 142.0 150
0 0.0 156.2 175
30 37.7 156.2 175
30 52 40 50.2 156.2 175
50 62.8 156.2 175
60 75.3 159.1 175

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

51
ELECTRICAL DATA
DESCRIPTION PTX060N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (6 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 291.1 350
37.5 94.1 291.1 350
11 36 45 113.0 291.1 350
52.5 131.8 291.1 350
60 150.6 291.1 350
0 0.0 303.9 350
37.5 94.1 303.9 350
15 48.8 45 113.0 303.9 350
52.5 131.8 303.9 350
60 150.6 303.9 350
0 0.0 314.2 350
80.7 538 37.5 94.1 314.2 350
230-3-60 207 253 5 & & 18.5 59.1 45 113.0 314.2 350
62.1 340 52.5 131.8 314.2 350
60 150.6 314.2 350
0 0.0 325.3 400
37.5 94.1 325.3 400
22 70.2 45 113.0 325.3 400
52.5 131.8 325.3 400
60 150.6 325.3 400
0 0.0 355.4 400
37.5 94.1 355.4 400
30 96.4 45 113.0 355.4 400
52.5 131.8 355.4 400
60 150.6 355.4 400
0 0.0 163.6 200
37.5 54.1 163.6 200
11 20.7 45 65.0 163.6 200
52.5 75.8 163.6 200
60 86.6 163.6 200
0 0.0 171.3 200
37.5 54.1 171.3 200
15 28.4 45 65.0 171.3 200
52.5 75.8 171.3 200
60 86.6 171.3 200
0 0.0 176.9 200
380/400-3-60 39.3 290 37.5 54.1 176.9 200
(4 WIRE) 342 418 3 & & 18.5 34 45 65.0 176.9 200
37.9 196 52.5 75.8 176.9 200
60 86.6 176.9 200
0 0.0 183.6 200
37.5 54.1 183.6 200
22 40.4 45 65.0 183.6 200
52.5 75.8 183.6 200
60 86.6 183.6 200
0 0.0 201.6 225
37.5 54.1 201.6 225
30 54.8 45 65.0 201.6 225
52.5 75.8 201.6 225
60 86.6 201.6 225
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

52
ELECTRICAL DATA
DESCRIPTION PTX060N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (6 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 139.4 150
37.5 47.1 139.4 150
11 19.7 45 56.5 139.4 150
52.5 65.9 139.4 150
60 75.3 139.4 150
0 0.0 146.7 150
37.5 47.1 146.7 150
15 27 45 56.5 146.7 150
52.5 65.9 146.7 150
60 75.3 146.7 150
0 0.0 150.7 175
34.3 229 37.5 47.1 150.7 175
460-3-60 414 506 2.8 & & 18.5 31 45 56.5 150.7 175
30 173 52.5 65.9 150.7 175
60 75.3 150.7 175
0 0.0 159.0 175
37.5 47.1 159.0 175
22 38.3 45 56.5 159.0 175
52.5 65.9 159.0 175
60 75.3 159.0 175
0 0.0 176.1 200
37.5 47.1 176.1 200
30 52 45 56.5 176.1 200
52.5 65.9 176.1 200
60 75.3 176.1 200

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

53
ELECTRICAL DATA
DESCRIPTION PTX070N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (6 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 328.3 400
37.5 94.1 328.3 400
11 36 45 113.0 328.3 400
52.5 131.8 328.3 400
60 150.6 328.3 400
0 0.0 341.1 400
37.5 94.1 341.1 400
15 48.8 45 113.0 341.1 400
52.5 131.8 341.1 400
60 150.6 341.1 400
0 0.0 351.4 400
37.5 94.1 351.4 400
230-3-60 207 253 5 80.7 538 18.5 59.1 45 113.0 351.4 400
52.5 131.8 351.4 400
60 150.6 351.4 400
0 0.0 362.5 400
37.5 94.1 362.5 400
22 70.2 45 113.0 362.5 400
52.5 131.8 362.5 400
60 150.6 362.5 400
0 0.0 392.6 450
37.5 94.1 392.6 450
30 96.4 45 113.0 392.6 450
52.5 131.8 392.6 450
60 150.6 392.6 450
0 0.0 166.4 200
37.5 54.1 166.4 200
11 20.7 45 65.0 166.4 200
52.5 75.8 166.4 200
60 86.6 166.4 200
0 0.0 174.1 200
37.5 54.1 174.1 200
15 28.4 45 65.0 174.1 200
52.5 75.8 174.1 200
60 86.6 174.1 200
0 0.0 179.7 200
380/400-3-60 37.5 54.1 179.7 200
(4 WIRE) 342 418 3 39.3 290 18.5 34 45 65.0 179.7 200
52.5 75.8 179.7 200
60 86.6 179.7 200
0 0.0 186.4 225
37.5 54.1 186.4 225
22 40.4 45 65.0 186.4 225
52.5 75.8 186.4 225
60 86.6 186.4 225
0 0.0 204.4 225
37.5 54.1 204.4 225
30 54.8 45 65.0 204.4 225
52.5 75.8 204.4 225
60 86.6 204.4 225
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

54
ELECTRICAL DATA
DESCRIPTION PTX070N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (6 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 148.0 175
37.5 47.1 148.0 175
11 19.7 45 56.5 148.0 175
52.5 65.9 148.0 175
60 75.3 148.0 175
0 0.0 155.3 175
37.5 47.1 155.3 175
15 27 45 56.5 155.3 175
52.5 65.9 155.3 175
60 75.3 155.3 175
0 0.0 159.3 175
37.5 47.1 159.3 175
460-3-60 414 506 2.8 34.3 229 18.5 31 45 56.5 159.3 175
52.5 65.9 159.3 175
60 75.3 159.3 175
0 0.0 167.6 175
37.5 47.1 167.6 175
22 38.3 45 56.5 167.6 175
52.5 65.9 167.6 175
60 75.3 167.6 175
0 0.0 184.7 200
37.5 47.1 184.7 200
30 52 45 56.5 184.7 200
52.5 65.9 184.7 200
60 75.3 184.7 200

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

55
ELECTRICAL DATA
DESCRIPTION PTX080N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (8 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 394.6 450
40 100.4 394.6 450
50 125.5 394.6 450
15 48.8
60 150.6 394.6 450
80 200.8 394.6 450
100 251.0 394.6 450
0 0.0 404.9 450
40 100.4 404.9 450
50 125.5 404.9 450
18.5 59.1
60 150.6 404.9 450
80 200.8 404.9 450
100 251.0 404.9 450
0 0.0 416.0 500
80.7 538 40 100.4 416.0 500
50 125.5 416.0 500
230-3-60 207 253 5 & & 22 70.2
60 150.6 416.0 500
62.1 340 80 200.8 416.0 500
100 251.0 416.0 500
0 0.0 446.1 500
40 100.4 446.1 500
50 125.5 446.1 500
30 96.4
60 150.6 446.1 500
80 200.8 446.1 500
100 251.0 446.1 500
0 0.0 473.1 500
40 100.4 473.1 500
50 125.5 473.1 500
37 118
60 150.6 473.1 500
80 200.8 473.1 500
100 251.0 473.1 500
0 0.0 216.6 250
40 57.7 216.6 250
50 72.2 216.6 250
15 28.4
60 86.6 216.6 250
80 115.5 216.6 250
100 144.3 216.6 250
0 0.0 222.2 250
40 57.7 222.2 250
50 72.2 222.2 250
18.5 34
60 86.6 222.2 250
80 115.5 222.2 250
100 144.3 222.9 250
0 0.0 228.9 250
39.3 290 40 57.7 228.9 250
380/400-3-60 50 72.2 228.9 250
(4 WIRE) 342 418 3 & & 22 40.4
60 86.6 228.9 250
37.9 196 80 115.5 228.9 250
100 144.3 230.9 250
0 0.0 246.9 250
40 57.7 246.9 250
50 72.2 246.9 250
30 54.8
60 86.6 246.9 250
80 115.5 246.9 250
100 144.3 248.9 300
0 0.0 259.7 300
40 57.7 259.7 300
50 72.2 259.7 300
37 65 60 86.6 259.7 300
80 115.5 259.7 300
100 144.3 261.7 300
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

56
ELECTRICAL DATA
DESCRIPTION PTX080N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (8 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 186.6 200
40 50.2 186.6 200
15 27 50 62.8 186.6 200
60 75.3 186.6 200
80 100.4 186.6 200
100 125.5 190.6 200
0 0.0 190.6 200
40 50.2 190.6 200
18.5 31 50 62.8 190.6 200
60 75.3 190.6 200
80 100.4 190.6 200
100 125.5 195.6 200
34.3 229 0 0.0 198.9 225
460-3-60 414 506 2.8 & & 40 50.2 198.9 225
30 173 22 38.3 50 62.8 198.9 225
60 75.3 198.9 225
80 100.4 198.9 225
100 125.5 204.8 225
0 0.0 216.0 250
40 50.2 216.0 250
30 52 50 62.8 216.0 250
60 75.3 216.0 250
80 100.4 216.0 250
100 125.5 221.9 250
0 0.0 224.1 250
40 50.2 224.1 250
37 58.5 50 62.8 224.1 250
60 75.3 224.1 250
80 100.4 224.1 250
100 125.5 230.0 250
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

56
ELECTRICAL DATA
DESCRIPTION PTX090N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (8 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 442.1 500
40 100.4 442.1 500
50 125.5 442.1 500
18.5 59.1
60 150.6 442.1 500
80 200.8 442.1 500
100 251.0 442.1 500
0 0.0 453.2 500
40 100.4 453.2 500
50 125.5 453.2 500
22 70.2
60 150.6 453.2 500
80 200.8 453.2 500
80.7 538 100 251.0 453.2 500
230-3-60 207 253 5
0 0.0 483.3 500
40 100.4 483.3 500
50 125.5 483.3 500
30 96.4
60 150.6 483.3 500
80 200.8 483.3 500
100 251.0 483.3 500
0 0.0 510.3 600
40 100.4 510.3 600
50 125.5 510.3 600
37 118
60 150.6 510.3 600
80 200.8 510.3 600
100 251.0 510.3 600
0 0.0 225.0 250
40 57.7 225.0 250
50 72.2 225.0 250
18.5 34
60 86.6 225.0 250
80 115.5 225.0 250
100 144.3 225.0 250
0 0.0 231.7 250
40 57.7 231.7 250
50 72.2 231.7 250
22 40.4
60 86.6 231.7 250
80 115.5 231.7 250
380/400-3-60 100 144.3 231.7 250
(4 WIRE) 342 418 3 39.3 290
0 0.0 249.7 300
40 57.7 249.7 300
50 72.2 249.7 300
30 54.8
60 86.6 249.7 300
80 115.5 249.7 300
100 144.3 249.7 300
0 0.0 262.5 300
40 57.7 262.5 300
50 72.2 262.5 300
37 65
60 86.6 262.5 300
80 115.5 262.5 300
100 144.3 262.5 300
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

57
ELECTRICAL DATA
DESCRIPTION PTX090N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (8 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 199.2 225
40 50.2 199.2 225
50 62.8 199.2 225
18.5 31
60 75.3 199.2 225
80 100.4 199.2 225
100 125.5 199.2 225
0 0.0 207.5 225
40 50.2 207.5 225
50 62.8 207.5 225
22 38.3
60 75.3 207.5 225
80 100.4 207.5 225
100 125.5 207.5 225
460-3-60 414 506 2.8 34.3 229
0 0.0 224.6 250
40 50.2 224.6 250
50 62.8 224.6 250
30 52
60 75.3 224.6 250
80 100.4 224.6 250
100 125.5 224.6 250
0 0.0 232.7 250
40 50.2 232.7 250
50 62.8 232.7 250
37 58.5
60 75.3 232.7 250
80 100.4 232.7 250
100 125.5 232.7 250

LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

58
ELECTRICAL DATA
DESCRIPTION PTX100N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (8 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 488.7 500
40 100.4 488.7 500
50 125.5 488.7 500
18.5 59.1
60 150.6 488.7 500
80 200.8 488.7 500
100 251.0 488.7 500
0 0.0 499.8 600
40 100.4 499.8 600
50 125.5 499.8 600
22 70.2
60 150.6 499.8 600
80 200.8 499.8 600
100 251.0 499.8 600
0 0.0 526.3 600
95 605 40 100.4 526.3 600
50 125.5 526.3 600
230-3-60 207 253 6.8 & & 30 96.4
60 150.6 526.3 600
80.7 538 80 200.8 526.3 600
100 251.0 526.3 600
0 0.0 553.3 600
40 100.4 553.3 600
50 125.5 553.3 600
37 118
60 150.6 553.3 600
80 200.8 553.3 600
100 251.0 553.3 600
0 0.0 584.6 600
40 100.4 584.6 600
50 125.5 584.6 600
45 143
60 150.6 584.6 600
80 200.8 584.6 600
100 251.0 584.6 600
0 0.0 274.1 300
40 57.7 274.1 300
50 72.2 274.1 300
18.5 34
60 86.6 274.1 300
80 115.5 274.1 300
100 144.3 274.1 300
0 0.0 280.5 300
40 57.7 280.5 300
50 72.2 280.5 300
22 40.4
60 86.6 280.5 300
80 115.5 280.5 300
100 144.3 280.5 300
0 0.0 294.9 350
57.9 380 40 57.7 294.9 350
380/400-3-60 50 72.2 294.9 350
(4 WIRE) 342 418 3.9 & & 30 54.8
60 86.6 294.9 350
39.3 290 80 115.5 294.9 350
100 144.3 294.9 350
0 0.0 306.9 350
40 57.7 306.9 350
50 72.2 306.9 350
37 65 60 86.6 306.9 350
80 115.5 306.9 350
100 144.3 306.9 350
0 0.0 328.6 350
40 57.7 328.6 350
50 72.2 328.6 350
45 82.4 60 86.6 328.6 350
80 115.5 328.6 350
100 144.3 328.6 350
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

59
ELECTRICAL DATA
DESCRIPTION PTX100N
VOLTAGE RANGE FM ELECTRIC
POWER SUPPLY (see Note) (8 each) COMPRESSOR BM HEATER
(V-Ph-Hz) MCA MOCP
Min. Max. FLA RLA LRA kW FLA Nom. kW FLA
0 0.0 224.7 250
40 50.2 224.7 250
18.5 31 50 62.8 224.7 250
60 75.3 224.7 250
80 100.4 224.7 250
100 125.5 224.7 250
0 0.0 232 250
40 50.2 232 250
22 38.3 50 62.8 232 250
60 75.3 232 250
80 100.4 232 250
100 125.5 232 250
0 0.0 248.2 275
42.1 320 40 50.2 248.2 275
460-3-60 414 506 3.8 & & 30 52 50 62.8 248.2 275
34.3 229 60 75.3 248.2 275
80 100.4 248.2 275
100 125.5 248.2 275
0 0.0 256.3 275
40 50.2 256.3 275
37 58.5 50 62.8 256.3 275
60 75.3 256.3 275
80 100.4 256.3 275
100 125.5 256.3 275
0 0.0 276.1 300
40 50.2 276.1 300
45 74.3 50 62.8 276.1 300
60 75.3 276.1 300
80 100.4 276.1 300
100 125.5 276.1 300
LEGEND:
kW - Kilo Watt BM - Blower Motor FM - Fan Motor (Condenser)
FLA - Full Load Amps LRA - Locked Rotor Amps RLA - Rated Load Amps
MCA - Minimum Circuit Ampacity MOCP - Maximum Over Current Protection

NOTE:
The equipment is guaranteed to operate continuously at ±5% of nominal power supply rating. Although equipment can still
operate beyond this value, it should be limited in extent, frequency and duration. Corrective measures should be undertaken
to improve voltages to within ±5% of nominal voltage supply rating.

60
FILTER SHEET

PRE-FILTER BAG FILTER MINI PLEATED


MODEL
LXH W QTY. LXH W QTY. LXH W QTY
PTX022N 20X24 2 8 20X24 15 8 20X24 4 8
PTX025N 20X24 2 8 20X24 15 8 20X24 4 8
PTX030N 20X24 2 8 20X24 15 8 20X24 4 8
PTX035N 20X24 2 8 20X24 15 8 20X24 4 8
PTX040N 20X24 2 12 20X24 15 12 20X24 4 12
PTX045N 20X24 2 12 20X24 15 12 20X24 4 12
PTX050N 20X24 2 12 20X24 15 12 20X24 4 12
PTX060N 20X24 2 16 20X24 15 16 20X24 4 16
PTX070N 20X24 2 16 20X24 15 16 20X24 4 16
PTX080N 24X24 2 16 24X24 15 16 24X24 4 16
PTX090N 24X24 2 16 24X24 15 16 24X24 4 16
PTX100N 24X24 2 20 24X24 15 20 24X24 4 20

NOTE: Filter Nominal Dimensions are in (INCH).

L W

Filter Efficiency Table


PRE-FILTER H Thickness
Filter Type MERV Rating
(INCH)
Disposable
Filter 2 MERV 2

Aluminum 2 MERV 3

L W Pleated Filter 2 MERV 7


Washable
Pleated Filter 2 MERV 8

Bag Filter 15 MERV 15


BAG FILTER
H Mini pleated
Filter 4 MERV 15

L W

MINI PLATED
FILTER H

61
DIMENSIONS

PTX 022N, 025N (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 022N, 025N (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

62
DIMENSIONS

PTX 030N (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 0305N (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

63
DIMENSIONS

PTX 035N (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 035N (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

64
DIMENSIONS

PTX 040N, 045N, 050N (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 040N, 045N, 050N (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

65
DIMENSIONS

PTX 060N, 070N - LH (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 060N, 070N - LH (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

66
DIMENSIONS

PTX 060N, 070N - RH (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 060N, 070N - RH (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

67
DIMENSIONS

PTX 080N, 090N - LH (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 080N, 090N - LH (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

68
DIMENSIONS

PTX 080N, 090N - RH (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 080N, 090N - RH (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

69
DIMENSIONS

PTX 100N - RH (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 100N - RH (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

70
DIMENSIONS

PTX 100N - LH (VERTICAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

PTX 100N - LH (HORIZONTAL SUPPLY)

TOP VIEW

SIDE VIEW FRONT VIEW

71
OPTIONAL SECTION - MIXING BOX - FRONT RETURN

72
OPTIONAL SECTION - MIXING BOX - TOP RETURN

73
OPTIONAL SECTION - BAG FILTER

74
OPTIONAL SECTION - BAG FILTER & MIXING BOX (STD) - FRONT RETURN

75
OPTIONAL SECTION - BAG FILTER & MIXING BOX - TOP RETURN

76
OPTIONAL SECTION - 4” MINI PLEATED & MIXING BOX (STD) - FRONT RETURN

77
OPTIONAL SECTION - 4” MINI PLEATED & MIXING BOX (STD) - FRONT RETURN

78
RAINHOOD ASSEMBLY FOR FRESH AIR & ECONOMIZER

HOOD ACCESSORIES FRESH AIR DAMPER WITH RAIN HOOD (2" ALU FILTER)
1. HOOD TOP PANEL MODEL DIMENSION QTY MODEL DIMENSION QTY
2. RIGHT HAND SIDE PANEL PTX022N 12"X24" 2 PTX050N 12"X24" 3
3. LEFT HAND SIDE PANEL PTX025N 12"X24" 2 PTX060N 24"X24" 2
PTX030N 12"X24" 2 PTX070N 24"X24" 2
4. SHEETMETAL SCREW
PTX035N 12"X24" 2 PTX0B0N 24"X24" 2
5. BOTTOM PANEL
PTX040N 12"X24" 3 PTX090N 24"X24" 2
6. LOCK BRACKET 3
PTX045N 12"X24" PTX100N 24"X24" 2
7. BIRD SCREEN

ECONOMIZER DAMPER WITH RAIN HOOD (2" ALU FILTER)


MODEL DIMENSION QTY MODEL DIMENSION QTY
PTX022N 16"X24" 2 PTX050N 24"X24" 3
12"X24" 2 12"X24" 3
PTX025N 16"X24" 2 PTX060N 24"X20" 4
12"X24" 2 12"X20" 4
PTX030N 24"X24" 2 PTX070N 24"X20" 4
12"X24" 2 12"X20" 4
PTX035N 24"X24" 2 PTX0B0N 24"X20" 4
12"X24" 2 20"X20" 4
PTX040N 24"X24" 3 PTX090N 24"X20" 4
12"X24" 3 20"X20" 4
24"X24" 3 PTX100N 24"X20" 4
PTX045N 20"X20" 4
12"X24" 3

79
SCHEMATIC DIAGRAM
PACKAGE UNIT
POWER SUPPLY

380~400V-3PH-60HZ & NEUTRAL

SHEET 2 OF 2 FOR
CONDENSER FAN MOTOR
PLEASE REFER TO
POWER CONNECTIONS.
HVTB
TO FUSED L1
DISCONNECT L2
SWITCH OR CB
L3
(SEE NOTE-4)

LUG

NTB
NEUTRAL CC1 CC2 CC3 CC4

L1
L2
L3
OLR1 OLR2 OLR3 OLR4
UVM CONNECTION BMC
HC1 HC2 HC3 HC4
L1 L2 L3

T1C
T2C
T3C

T1D
T2D
T3D
T1A
T2A
T3A

T1B
T2B
T3B

68
69
70

T1F
T2F
T3F

T1G

T2G
T3G
T1H
T2H

T3H

T1I

T2I
T3I
L1 L2 L3 UVM
1 UVM-1 8 COMP COMP COMP COMP HEATER1 HEATER2 HEATER3 HEATER4
BM
1 2 3 4 (Stg. 1 Heating) (Stg. 2 Heating) (Stg. 3 Heating) (Stg. 4 Heating)

TO ATB 1
(REMOVE JP1)
TO ATB 1A
TO HVTB TO NTB
SMOKE DETECTOR L1 N

ATB ATB
F1
1 JP1 1A JP2 1B

PLEASE REFER TO FAN MOTOR


CONTROL CONNECTION, (SHEET 2 OF 2) BMC

OPTIONAL OPTIONAL BMR


VFC CONNECTION PDS CONNECTION
(SHEET 2 OF 2) (SHEET 2 OF 2)
TO TO TO TO CC2
FR2 FR1 PDS1 PDS2
CC1
JP ( NOTE 7)
SWITCHING CONTACTS
41B

41A

3B

3A
14

4A

FROM T'STAT CONTROLLER OR DDC


4B

(by others)
TB1 LVTB
OUTFAN2

OUTFAN1

HEATER2

HEATER1

COMP1
COMP2

15 R
INFAN

TO ATB
LIVE

R R
X2

X1

P1

P2

17 24Vac
BM
C T.O.P C
G1 G2 BM CONTROL G
G G
FUSE
ECB1
31A STG1 COOLING Y1
Y1 Y1
NEUTRAL

LED 31B STG2 COOLING Y2


POWER INDICATOR LED FAULT INDICATOR Y2 Y2
SQMBO4 ( P 4 ) YR3 32C STG3 COOLING Y3 ( NOTE 6)
W1 Y3
LOCK2 LOCK1 YR4 32D STG4 COOLING Y4
W2 Y4
W1
SYSTEM2 SYSTEM1 W1
STG1 HEATING

STG2 HEATING W2
ON/OFF W2
HR1 W3
PRI

STG3 HEATING
W3
(ON/OFF) HR2 STG4 HEATING W4
W4
OLR1-1 (SSPS1) (OPS1) HPS1
TRANS1 21A
P4_## HP1 24A JP3 25A JP5 26A
P
(HP1) 27A
220~230v
OLR2-1 (SSPS2) (OPS2) HPS2
12v-0-24v 21B
HP2 24B JP4 25B JP6 26B
P
(HP2) 27B
ON DIP

22A LPS1
LP1
DIP SWITCH
SEC

(LP1) 23A P

22B LPS2
J_PROG LP2
LVTB LOCATION 23B
(LP2)
P
6-FAN MOTOR LAYOUT

PLEASE REFER TO FAN MOTOR


CONTROL CONNECTION, (SHEET 2 OF 2)
TO ATB OPTIONAL OPTIONAL TO ATB
VFC CONNECTION PDS CONNECTION
1 (SHEET 2 OF 2) (SHEET 2 OF 2)
2
TO TO TO TO DPS SETTINGS
TO ATB FR4 FR3 PDS3 PDS4 CC4 Name Ratting
2
DPS1 (ALU FILTER) 125Pa
CC3
DPS2 (BAG FILTER) 250Pa
41D

41C

4D

3D

3C
4C

PRESSURE SWITCH SETTINGS IN PSIG


TB1 BMR-1
OUTFAN2

OUTFAN1

HEATER2

HEATER1

R410A
COMP1
COMP2

15B 15C
INFAN
LIVE

R
X2

X1

P2
P1

NAME OPEN CLOSE


C
JP LPS1~4 50 ± 5 90 ± 5
G YR3-1
FUSE
ECB2
31C LPS(HGS) 125 105
Y1
NEUTRAL

LED 31D YR4-1 LPS5~8(UL) 130


LED FAULT INDICATOR Y2 140
POWER INDICATOR HR1-1 HPS1~4
SQMBO4 ( P 4 ) W1
31E
650 ± 10 500 ± 15
LOCK2 LOCK1 31F
HR2-1 FCS1~4
W2 310 ± 10 410 ± 15
SYSTEM2 SYSTEM1
ON/OFF
PRI

(ON/OFF) ECB1 & 2 DIP SWITCH SETTINGS & LED INDICATORS


OLR3-1 HPS3 S1 OFF=TEST MODE DISABLE ON= TEST MODE ENABLE
TRANS2 HP1 21C JP7 JP9
P4_## 24C 25C 26C LOAD BALANCE
P S2 OFF= (Comp1&2 Auto Lead Lag) ON= COMPRESSOR 1 LEAD
230v (HP1) 27C
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION
OLR4-1 HPS4
12v-0-12v 21D S4 OFF= SINGLE STAGE ON= DUAL STAGE
HP2 24D JP8 25D JP10 26D FACTORY SETTINGS OF DIP SWITCHES LED INDICATORS
P
(HP2) 27D Green power on/off indicator
ON DIP DIP SWITCH # S1 S2 S3 S4
Red system lock-out due to system fault
22C LPS3 ON system 1 / 3 fault diagnostic
LP1 OFF
DIP SWITCH Yellow blinking slow - LPS1 ckt fault
SEC

(LP1) 23C P note: blinking fast - HPS1 ckt fault


Set dip switch #S3 according to unit's option
(pump down or no pump down) system 2 / 4 fault diagnostic
22D LPS4
J_PROG LP2 Dip switch #S1 should always be OFF during Orange blinking slow - LPS2 ckt fault
LVTB LOCATION operation. blinking fast - HPS2 ckt fault
(LP2) 23D P

80
SCHEMATIC DIAGRAM
PACKAGE UNIT

SWITCHING CONTACTS
CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS FROM T'STAT CONTROLLER OR DDC
(by others)
L1 L2 L3 ( NOTE 7) LVTB ECB
ECB 1 STD CONN BELOW
L1 L2 L3 L1 L2 L3
6-FAN MOTOR LAYOUT R
R R
FM1 FM5 FM3 C 24Vac 24Vac
OUTFAN 1 T.O.P T.O.P C C
FMC1 T.O.P FMC3
12A 13A 12E 13E FMC1A-1 12C 13C G BM CONTROL
JP 2 G G
1 2
Y1 STG1 COOLING
OUTFAN 2 Y1 Y1
Y2 STG2 COOLING
Y2 Y2
ECB 2
103
104
105

Y3 STG3 COOLING
100
101
102

Y3 Y3
FM6
106
107
108

FM2 FM4 Y4 STG4 COOLING


OUTFAN 1 T.O.P T.O.P FMC2 T.O.P Y4 Y4
FMC1 FMC2 12B 13B 12F 13F FMC2A-1 12D
FMC4
JP 2 13D W1 STG1 HEATER
FMC3 FMC4 1 2 W1 W1
OUTFAN 2 W2 STG2 HEATER W2 W2
W3 STG3 HEATER W3 W3
35C
36C
37C

35D
36D
37D
W4 STG4 HEATER W4 W4

FM3 FM4
35B
36B
37B

35F
36F
37F
35A
36A
37A

35E
36E
37E

FM1 FM5 FM2 FM6

OPTIONAL CONNECTIONS

PUMP DOWN SOLENOID CONNECTION BM RUN AND TRIP INDICATION UNIT STATUS (VFC) INDICATION CONNECTION
PDS2 ATB
UNIT ON/OFF
2
PDS1 1 AR1 2
48 BMCA-1A 49
4B

4A

45 AR1-1A 46
BM RUN
P2

P1

ECB1 51 OLR-2 52
PDS4 ATB UNIT ON
2 UNIT TRIP
PDS3 43 FR1-1 44A FR2-1 44B FR3-1 44
44C FR4-1
BM TRIP
4D

4C

LEGEND
UNIT TRIP
P2

P1

HEATER DATA TABLE


ECB2 INDIVIDUAL COMP. RUN/TRIP AR AUXILIARY RELAY
TTL KW STAGE1/3 STAGE2/4 ATB
FR1 AUXILIARY TERMINAL BLOCK BLOWER
TO ECB1 2 BM
30 7.5KW+7.5KW 7.5KW+7.5KW 41A MOTOR
COMP. SSPS CONNECTION X1
40 10KW+10KW 10KW+10KW BMC BLOWER MOTOR CONTACTOR
(SEE NOTE 5)
SSPS1 50 12.5KW+12.5KW 12.5KW+12.5KW FR1-2A BMCA BMC AUXILIARY CONTACT
24A 25A CB CIRCUIT BREAKER
M1/11 M2/14
CC1A-2A
CBA CB AUXILIARY CONTACT COMPRESSOR
1 2
L1/MP/L L2/R/N CC CONTACTOR
CCA CC AUXILIARY CONTACT CRANKCASE
(REMOVE JP3) HEATER BOX CONNECTION TYPES
55 56 58 C.HTR HEATER
SSPS2 TO 3PH POWER SUPPLY TO 3PH POWER SUPPLY
24B 25B COMP/C COMPRESSOR
M1/11 M2/14 T1 T2 T3 T1 T2 T3 COMP1 ON ELECTRONIC CONTROL BOARD
ECB
1 2 COMP1 TRIP F FUSE
L1/MP/L L2/R/N
OHT OHT OHT OHT FCS FAN CYCLING SWITCH
FR2 2
(REMOVE JP4) TO ECB1 41B FMCA FMC AUXILIARY CONTACT
X2 FM FAN MOTOR (CONDENSER)
SSPS3 FL FL
24C 25C FL FR2-2A FMC FAN MOTOR CONTACTOR
M1/11 M2/14 FL
FL FR FAULT RELAY
1 2 CC2A-2A
L1/MP/L L2/R/N TYPE-I TYPE-I I HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
(REMOVE JP7) JP JUMPER
SSPS4 HEATER CONTROL CONNECTION 60 61 63 L1 LINE 1
24D 25D
M1/11 M2/14 L2 LINE 2
ECB1 HC1
1 2 29 28 COMP2 ON L3 LINE 3
L1/MP/L L2/R/N HEATER 1 LOW PRESSURE SWITCH
COMP2 TRIP LPS
HC2 LUG LUG GROUND
(REMOVE JP8) 30
HEATER 2 LVTB LOW VOLTAGE TERMINAL BLOCK
FR3 2
TO ECB2 41C NTB NEUTRAL TERMINAL BLOCK
ECB2 HC3 X1
30A OLR OVER LOAD RELAY
HEATER 1 FR3-2A P PRESSURE
30B HC4 PDS PUMP DOWN SOLENOID
HEATER 2 CC3A-2A S DIP SWITCH (IN ECB)
AFS SSPS SOLID STATE PROTECTION SYSTEM FM
ATB NC T.O.P THERMAL OVERLOAD PROTECTION
2 C
NOTE: 65 66 68 TRANS TRANSFORMER
NO
HC3 AND HC4 CONNECTION IS APPLICABLE ONLY UVM VOLTAGE MONITOR RELAY
FOR HEATER RATINGS 40 TO 100 KW. COMP3 ON FIELD WIRING
COMP3 TRIP SPLICE-CLOSED END
TERMINAL BLOCK OR
FR4 2 TERMINATION POINT
TO ECB2 41D
X2
FR4-2A
NOTES
COMP. CRANKCASE HTR CONNECTION CC4A-2A
( 220V~240V ) 1. ANY WIRE REPLACEMENT, SHOULD BE OF THE 90°C TYPE OR ITS EQUIVALENT.
2. USE COPPER CONDUCTORS ONLY.
1B CC1A-1B C.HTR1 2 3. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR A MINIMUM OF 12 HOURS,
100A
70 71 73 PRIOR TO SYSTEM START UP. IF POWER SUPPLY HAS BEEN INTERRUPTED
FOR A PROLONGED PERIOD, OIL SUMP HEATERS MUST BE ENERGIZED FOR 12 HRS
1B CC2A-1B C.HTR2 2 COMP4 ON MINIMUM,BEFORE STARTING COMPRESSOR.
100B
COMP4 TRIP 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY THE USER,
AS PER ELEC. DATA IN INSTALLATION MAN'L.
1B CC3A-1B C.HTR3 2
100C
5. COMPRESSORS ARE EITHER PROVIDED WITH SSPS OR INTERNAL LINE BREAK
THERMAL OVERLOAD PROTECTION.
1B CC4A-1B C.HTR4 2 6. USE SHIELDED TYPE CABLE, #18AWG (min), FOR LVTB FIELD WIRING.
100D
GROUND CONNECT AT BOTH ENDS.
7. COOLING OUTPUT SIGNAL FROM CONTROLLER SHOULD FOLLOW THE SEQUENCE:
ON SEQUENCE - Y1 - Y2 - Y3 - Y4
HEATER ON INDICATION (OPTIONAL) HEATER ON INDICATION (OPTIONAL) OFF SEQUENCE - Y4 - Y3 - Y2 - Y1

80A HC1A-1A 81A 80B HC2A-1A 81B 80A HC1A-1A 81A 80B HC2A-1A 81B

HTR1 ON HTR2 ON HTR1 ON HTR2 ON


80D HC4A-1A 81D 80C HC3A-1A 81C 80D HC4A-1A 81D
80C HC3A-1A 81C

HTR4 ON HTR3 ON HTR4 ON


HTR3 ON

81
POWER CABLE ENTRY

POWER CABLE ENTRY PACKAGE UNIT


PACKAGE UNIT(2-COMPRESSOR MODEL) (4/6-COMPRESSOR MODEL)
PACKAGE UPTX008-070 PTX080 AND ABOVE

82
INSTALLATION CLEARANCE (SINGLE)

Clearance - mm CLEARANCE
MODEL Top clearance
A B C D
B
DUCT
PTX022N-PTX035N 3000 2800 2800 2200
Unobstructed
PTX040N-PTX050N 3000 2800 2800 2200

DUCT
C
PTX022N - PTX025N

DUCT

A
DUCT

C
PTX030N - PTX050N

A
DUCT

Note:
1. If unit is installed in special pit, please observe same tolerance for walls . Pit height should not exceed unit height.
2. No obstruction above condenser fan.

83
INSTALLATION CLEARANCE (MULTIPLE)

Clearance - mm
MODEL Top clearance
A B C D
PTX022N-PTX035N 3000 2800 2800 2200
Unobstructed
PTX040N-PTX050N 3000 2800 2800 2200

Note:
1. If unit is installed in special pit, please observe same tolerance for walls . Pit height should not exceed unit height.
2. No obstruction above condenser fan.

84
INSTALLATION CLEARANCE (MULTIPLE)

Clearance - mm
MODEL Top clearance
A B C D
PTX060N-PTX070N 3000 3000 3000 3000
Unobstructed
PTX080N-PTX100N 3000 3000 3500 3000

Note:
1. If unit is installed in special pit, please observe same tolerance for walls . Pit height should not exceed unit height.
2. No obstruction above condenser fan.

85
LIFTING AND RIGGING INSTRUCTION

ATTENTION TO RIGGERS
Hook rigging sling thru the holes on the lifting plates, as shown below.
Lifting plates or holes on the base rail are centered around the unit's center of gravity.
Center of gravity is not unit center line.
Ensure center of gravity aligns with the main lifting point before lifting.
Use spreader bar when rigging to prevent the slings from damaging the unit.

CAUTION
All panels should be in place when rigging.
Care must be taken to avoid damage to the coils during handling.
Insert packing material between coils & slings if necessary.

1. STEEL BAR
2. LIFTING CABLE OR CHAIN
3. CHAIN SLING
4. BOLT & NUT
5. SPREADER BAR

NOTE: STEEL BAR MUST BE 2.50" NOMINAL PIPE THROUGH UNIT FOR SLINGS TO AVOID BASE DAMAGE

86
LIFTING AND RIGGING INSTRUCTION

NOTE: STEEL BAR MUST BE 2.50" NOMINAL PIPE THROUGH UNIT FOR SLINGS TO AVOID BASE DAMAGE

87
LOAD DISTRIBUTION (KG) & MOUNTING POINTS (STANDARD UNIT WITHOUT SECTION)

88
LOAD DISTRIBUTION (KG) & MOUNTING POINTS
(STANDARD UNIT WITHOUT SECTION)

MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 TOTAL WT.


PTX022N 244 220 262 239 - - - - - - 965
PTX025N 245 222 268 245 - - - - - - 980
PTX030N 195 193 190 186 270 266 - - - - 1300
PTX035N 209 207 204 202 271 267 - - - - 1360
PTX040N 245 243 240 238 347 342 - - - - 1655
PTX045N 246 244 241 239 357 353 - - - - 1680
PTX050N 261 259 256 254 382 378 - - - - 1790
PTX060N 315 301 280 280 348 334 348 334 - - 2540
PTX070N 329 315 294 294 353 341 353 341 - - 2620
PTX080N 321 321 316 316 307 307 395 376 395 376 3430
PTX090N 342 342 338 338 328 328 415 397 415 397 3640
PTX100N 371 371 366 366 355 355 454 434 454 434 3960

MCHX CONDENSER COIL VERTICAL SUPPLY

MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 TOTAL WT.


PTX022N 244 220 262 239 - - - - - - 965
PTX025N 245 222 268 245 - - - - - - 980
PTX030N 195 193 190 186 270 266 - - - - 1300
PTX035N 209 207 204 202 271 267 - - - - 1360
PTX040N 245 243 250 248 407 402 - - - - 1795
PTX045N 246 244 251 249 417 413 - - - - 1820
PTX050N 261 259 266 264 442 438 - - - - 1930
PTX060N 315 301 285 285 398 384 398 384 - - 2750
PTX070N 329 315 299 299 403 391 403 391 - - 2830
PTX080N 321 321 316 316 312 312 465 446 465 446 3720
PTX090N 342 342 338 338 333 333 485 467 485 467 3930
PTX100N 371 371 366 366 360 360 524 504 524 504 4250

MCHX CONDENSER COIL HORIZONTAL SUPPLY

89
LOAD DISTRIBUTION (KG) & MOUNTING POINTS
(STANDARD UNIT WITHOUT SECTION)

MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 TOTAL WT.


PTX022N 277 252 267 244 - - - - - - 1040
PTX025N 278 254 273 250 - - - - - - 1055
PTX030N 222 220 217 213 274 269 - - - - 1415
PTX035N 244 242 239 237 279 274 - - - - 1515
PTX040N 280 278 275 273 355 349 - - - - 1810
PTX045N 281 279 276 274 365 360 - - - - 1835
PTX050N 296 294 291 289 392 388 - - - - 1950
PTX060N 370 356 335 335 353 339 348 334 - - 2770
PTX070N 384 370 349 349 358 346 353 341 - - 2850
PTX080N 371 371 366 366 357 357 400 381 395 376 3740
PTX090N 392 392 388 388 378 378 420 402 415 397 3950
PTX100N 426 426 421 421 410 410 459 439 454 434 4300

FIN & TUBE CONDERSER COIL (AL/CU) VERTICAL SUPPLY

MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 TOTAL WT.


PTX022N 277 252 267 244 - - - - - - 1040
PTX025N 278 254 273 250 - - - - - - 1055
PTX030N 222 220 217 213 274 269 - - - - 1415
PTX035N 244 242 239 237 279 274 - - - - 1515
PTX040N 280 278 280 278 420 414 - - - - 1950
PTX045N 281 279 281 279 430 425 - - - - 1975
PTX050N 296 294 296 294 457 453 - - - - 2090
PTX060N 370 356 340 340 403 389 398 384 - - 2980
PTX070N 384 370 354 354 408 396 403 391 - - 3060
PTX080N 371 371 366 366 362 362 470 451 465 446 4030
PTX090N 392 392 388 388 383 383 490 472 485 467 4240
PTX100N 426 426 421 421 415 415 529 509 524 504 4590

FIN & TUBE CONDERSER COIL (AL/CU) HORIZONTAL SUPPLY

90
LOAD DISTRIBUTION (KG) & MOUNTING POINTS
(STANDARD UNIT WITHOUT SECTION)

MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 TOTAL WT.


PTX022N 327 302 302 279 - - - - - - 1210
PTX025N 328 304 308 285 - - - - - - 1225
PTX030N 260 257 255 250 319 314 - - - - 1655
PTX035N 295 290 287 285 324 319 - - - - 1800
PTX040N 330 328 324 322 409 402 - - - - 2115
PTX045N 331 329 325 323 431 426 - - - - 2165
PTX050N 346 344 341 339 472 468 - - - - 2310
PTX060N 444 431 408 408 403 389 398 384 - - 3265
PTX070N 459 445 424 424 408 396 403 391 - - 3350
PTX080N 437 437 431 431 422 422 453 431 445 426 4335
PTX090N 458 458 454 454 444 444 480 463 474 456 4585
PTX100N 501 501 496 496 485 485 532 512 526 506 5040

FIN & TUBE CONDERSER COIL (CU/CU) VERTICAL SUPPLY

MODELS R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 TOTAL WT.


PTX022N 327 302 302 279 - - - - - - 1210
PTX025N 328 304 308 285 - - - - - - 1225
PTX030N 260 257 255 250 319 314 - - - - 1655
PTX035N 295 290 287 285 324 319 - - - - 1800
PTX040N 330 328 329 327 474 467 - - - - 2255
PTX045N 331 329 330 328 496 491 - - - - 2305
PTX050N 346 344 346 344 537 533 - - - - 2450
PTX060N 444 431 413 413 453 439 448 434 - - 3475
PTX070N 459 445 429 429 458 446 453 441 - - 3560
PTX080N 437 437 431 431 427 427 523 501 515 496 4625
PTX090N 458 458 454 454 449 449 550 533 544 526 4875
PTX100N 501 501 496 496 490 490 602 582 596 576 5330

FIN & TUBE CONDERSER COIL (CU/CU) HORIZONTAL SUPPLY

91
Zamil Central Air Conditioners
P.O. Box 41015, Dammam 31521, Kingdom of Saudi Arabia
Tel.: +966 13 812 5400 Fax: +966 13 812 1977
Customer Service: 92 0000 468 www.zamilac.com

20Z1 PL-AP-PTXN-60Hz-20-2M-E