This set of Refrigeration MCQs focuses on “Effect of Various Parameters on VCR System – 2”.
Answer: c
Explanation: Flash chamber is used to separate vapour and liquid refrigerant. It is an insulated
container and separates both forms by using the centrifugal effect.
2. What is the amount of mass of vapour refrigerant flowing directly from flash chamber to
suction of the compressor?
https://www.sanfoundry.com/refrigeration-mcqs/ 1/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
a) m1
b) m2
c) m1 + m2
d) m2 – m1
View Answer
Answer: d
Explanation: As, m1 = Mass of the liquid refrigerant supplied to the evaporator
m2 = Mass of refrigerant (liquid and vapour) circulating through the condenser
Hence, the amount of mass flowing through the flash chamber to the compressor is given by,
= m 2 – m 1.
3. What is the ratio of the mass of refrigerant supplied to evaporator and mass of refrigerant
circulating through condenser i.e., m1 / m2?
https://www.sanfoundry.com/refrigeration-mcqs/ 2/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
a) h1 – h2 / h1 – h4
b) h1 – h4 / h1 – hf4’
c) h2 – h1 / h4 – h1
d) h1 – hf4’ / h1 – h4
View Answer
Answer: b
Explanation: As flash chamber is an insulated cylinder. Heat transfer between flash chamber
and surroundings is zero. So, by considering thermal equilibrium of flash chamber,
Heat taken by the flash chamber = Heat given out by the flash chamber
m2 h4 = m1 hf4’ + (m2 – m1) h1
m2 (h1 – h4) = m1 (h1 – hf4’)
m1 / m2 = [h1 – h4 / h1 – hf4’].
advertisement
https://www.sanfoundry.com/refrigeration-mcqs/ 3/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
Answer: a
Explanation: Accumulator or pre-cooler does almost the same work as a flash chamber. It
receives the discharge of a mixture of liquid and vapour refrigerant from expansion valve and
supplies liquid refrigerant only to the evaporator. This discharge again sent to the
accumulator, and only dry saturated vapour refrigerant is further sent to the compressor.
5. What is the use of a liquid pump in the VCR system containing accumulator?
Answer: a
Explanation: Accumulator separates the mixture of refrigerants, and provides dry saturated
vapour to the compressor and pure liquid refrigerant to the evaporator. So, to maintain the
circulation of the liquid refrigerant in the evaporator, a liquid pump is used.
Check this: Mechanical Engineering MCQs | Refrigeration & Air Conditioning Books
6. What is the ratio of the mass of refrigerant supplied to evaporator and mass of refrigerant
circulating through condenser i.e., m1 / m2?
a) h1 − h2 / h1 − h4
b) h1 − h4 / h1’ − hf4’
c) h2 − h1 / h4 − h1
d) h1’ − hf4’ / h1 − h4
View Answer
Answer: b
Explanation: As accumulator is an insulated vessel. Heat transfer between flash chamber and
surroundings is zero. So, by considering thermal equilibrium of flash chamber,
Heat taken by the accumulator = Heat given out by the accumulator
m2 h4 + m1 h1’ = m2 h1 + m1 hf4’
m1 (h1’ − hf4’) = m2 (h1 − h4)
m1 / m2 = [h1 − h4 / h1’ − hf4’].
https://www.sanfoundry.com/refrigeration-mcqs/ 5/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
a) Compression
b) Expansion
c) Subcooling of liquid by vapour refrigerant
d) Subcooling of vapour by liquid refrigerant
View Answer
Answer: c
Explanation: Liquid leaves condenser at a higher temperature than vapour leaving the
evaporator. So, liquid refrigerant leaving the condenser is able to be subcooled by passing it
through a heat exchanger which is supplied with the vapour refrigerant from the evaporator.
Hence, this heat exchanger is used to do the subcooling of liquid refrigerant by the vapour
refrigerant.
advertisement
https://www.sanfoundry.com/refrigeration-mcqs/ 6/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
8. What is the ratio of the mass of the vapour refrigerant and mass of the liquid refrigerant i.e.,
m1 / m 2?
a) 1
b) h1 − h4 / h1’ − hf4’
c) 0
d) h1’ − hf4’ / h1 − h4
View Answer
Answer: a
Explanation: In the case of this kind of heat exchanger, heat transfer takes place between
vapour and liquid refrigerant due to the change of temperature and specific heat. As the mass
flowing through condenser and evaporator is same. Due to heat transfer, mass does not get
affected. Hence,
m1 = m2 or m1 / m2 = 1.
https://www.sanfoundry.com/refrigeration-mcqs/ 7/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
a) Compression
b) Subcooling of liquid by liquid refrigerant
c) Subcooling of liquid by vapour refrigerant
d) Subcooling of vapour by liquid refrigerant
View Answer
Answer: b
Explanation: Liquid leaves the condenser at a higher temperature than liquid leaving the
expansion valve. So, the liquid refrigerant leaving the condenser is able to be subcooled by
passing through the heat exchanger which is supplied with the liquid refrigerant from the
expansion valve. Hence, a heat exchanger is used to do the subcooling of liquid refrigerant at a
higher temperature by the liquid refrigerant at a lower temperature.
advertisement
https://www.sanfoundry.com/refrigeration-mcqs/ 8/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
a) m2 − m1
b) m1 − m3
c) m2 + m3
d) m2 − m3
View Answer
Answer: d
Explanation: As, m1 = Mass of refrigerant leaving the evaporator
m2 = Mass of liquid refrigerant passing through the condenser
m3 = Mass of liquid refrigerant supplied to the heat exchanger from the expansion valve
By taking the help of schematic,
Mass of refrigerator leaving the evaporator, m1 = m2 − m3.
11. What is the ratio of the mass of liquid refrigerant passing through the condenser and mass of
liquid refrigerant supplied to the heat exchanger i.e., m3 / m2?
https://www.sanfoundry.com/refrigeration-mcqs/ 9/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
a) h1 − h2 / h1 − h4
b) h1 − h4 / h1’ − hf4’
c) hf3 − hf3’ / h1 − hf4’
d) h1 − hf4’ / hf3 − hf3’
View Answer
Answer: c
Explanation: Considering the thermal equilibrium of the heat exchanger,
Heat lost by liquid refrigerant from condenser = Heat gained by liquid refrigerant from
expansion valve
m2 hf3 + m3 hf4’ = m3 h1 + m2 hf3’
m2 (hf3 − hf3’) = m3 (h1 − hf4’)
m3 / m2 = [hf3 − hf3’ / h1 − hf4’].
Sanfoundry Global Education & Learning Series – Refrigeration & Air Conditioning.
To practice MCQs on all areas of Refrigeration, here is complete set of 1000+ Multiple Choice
Questions and Answers.
« Prev - Refrigeration Questions and Answers » Next - Refrigeration Questions and Answers –
– Effect of Various Parameters on VCR Simple VCR System – Pressure – Enthalpy Chart
System – 1
Related Posts:
advertisement
Recommended Articles:
1. Refrigeration Questions and Answers – Effect of Various Parameters on VCR System – 1
2. Refrigeration Questions and Answers – Two/Multi Stage Compression with Water
Intercooling, Liquid Subcooling and Flash Chamber – 2
3. Refrigeration Questions and Answers – Two/Multi Stage Compression with Water
Intercooling, Liquid Subcooling and Flash Chamber – 1
4. Refrigeration Questions and Answers – Two/Multi Stage Compression with Water
Intercooling, Liquid Subcooling and Flash Intercooler
5. Refrigeration Questions and Answers – Simple VCR System – Pressure – Enthalpy Chart
6. Refrigeration Questions and Answers – Domestic Electrolux and Lithium Bromide
Refrigeration System – 2
7. Refrigeration Questions and Answers – Coefficient of Performance of Ideal VAR System – 1
8. Refrigeration Questions and Answers – Two/Multi Stage Compression with Liquid
Intercooling – 1
9. Refrigeration Questions and Answers – Two/Multi Stage Compression with Water
Intercooling and Liquid Subcooling – 2
10. Refrigeration Questions and Answers – Domestic Electrolux and Lithium Bromide
Refrigeration System – 1
advertisement
https://www.sanfoundry.com/refrigeration-mcqs/ 11/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
Additional Resources:
Popular Pages:
https://www.sanfoundry.com/refrigeration-mcqs/ 12/13
2/16/23, 5:45 PM VCR System Parameters Effect - Refrigeration Multiple Choice Questions 2 - Sanfoundry
Name
Subscribe
Manish Bhojasia, a technology veteran with 20+ years @ Cisco & Wipro, is
Founder and CTO at Sanfoundry. He lives in Bangalore, and focuses on
development of Linux Kernel, SAN Technologies, Advanced C, Data
Structures & Alogrithms. Stay connected with him at LinkedIn.
https://www.sanfoundry.com/refrigeration-mcqs/ 13/13