Distance Protection of TL - 2024
Distance Protection of TL - 2024
Transmission Lines
By : Dr. Atul R. Phadke
Associate Professor in Electrical Engineering
COEP Technological University Pune (Maharashtra)
DRAWBACKS OF OVERCURRENT PROTECTION:
Overcurrent relay with
pick-up setting = Ipu gives
a reach up to bus B for
L-L-G fault.
Reach for L-G fault is
only up to point B1.
Whereas the reach for
three-phase fault is up to
point B2.
Thus, the relay may
under-reach or over-
reach depending upon
the type of fault.
Or
𝑉𝑅
However, = the magnitude of the impedance seen by the relay. Therefore, the
𝐼𝑅
trip law can be written as -
SIMPLE IMPEDANCE RELAY WITH BALANCED BEAM STRUCTURE:
The current coil exerts a torque in such a way that it tends to close the trip contact
(operating torque).
The voltage coil tends to keep the trip contacts open (restraining torque).
The control spring keeps the contacts open when the relay is in unenergized
condition.
SIMPLE DIFFERENTIAL (BASIC) PROTECTION:
The operating torque is proportional to 𝐼𝑅 2 .
The restraining torque is proportional to 𝑉𝑅 2 .
If the effect of spring is neglected, the relay operates when-
2 2
𝑘1 𝐼𝑅 > 𝑘2 𝑉𝑅
Where, 𝑘1 and 𝑘2 are proportionality constants.
2 2
∴ 𝑘2 𝑉𝑅 < 𝑘1 𝐼𝑅
𝑉𝑅 2 𝑘1
∴ 2
<
𝐼𝑅 𝑘2
𝑉𝑅 𝑘1
∴ <
𝐼𝑅 𝑘2
𝑉𝑅 2 𝑘1
∴ 2
<
𝐼𝑅 𝑘2
𝑉𝑅 𝑘1
∴ <
𝐼𝑅 𝑘2
UNIVERSAL TORQUE EQUATION (SIMPLE IMPEDANCE RELAY):
𝑉𝑅 𝑘1
∴ <
𝐼𝑅 𝑘2
𝑉𝑅
= 𝑍𝑠𝑒𝑒𝑛
𝐼𝑅
𝑍𝑠𝑒𝑒𝑛 = the magnitude of impedance seen by the relay
𝑘1
= 𝑍𝑠𝑒𝑡
𝑘2
The reach of the simple impedance relay is independent of the phase angle between voltage and
current at the relay location.
Therefore, the simple impedance relay is not useful where selectivity between the forward and
reverse faults has to be maintained.
However, we can get the desired selectivity using a directional element with simple impedance
relay.
EFFECT OF POWER SWING ON SIMPLE IMPEDANCE RELAY:
When a power system is operating in steady state, all the rotor or machine angles are
constant.
Whenever there are sudden and large changes of power in the system, (say due to
outage of a major tie-line), the rotor angles undergo oscillations till the system reaches a
new stable state.
This phenomenon is known as power swing.
At some point during the power swing, the apparent impedance enters the trip region of
the relay operating characteristic.
This causes the relay to trip, putting the line out of service, adding to the disturbance
already present in the system.
Therefore, tripping because of power swing has to be normally blocked.
The simple impedance relay occupies substantial area in all the four quadrants of the R-X
plane.
Therefore, it is very much vulnerable to maloperation during power swing.
REACTANCE RELAY:
Universal torque equation -
2 2
𝑇 = 𝑘1 𝐼𝑅 + 𝑘2 𝑉𝑅 + 𝑘3 𝑉𝑅 𝐼𝑅 cos 𝜃 − 𝜏 + 𝑘4
𝑘1 be positive, 𝑘2 = 0, 𝑘3 be negative and 𝑘4 is neglected
Therefore, the trip law can be written as –
𝐼𝑓 𝑘1 𝐼𝑅 2 > 𝑘3 𝑉𝑅 𝐼𝑅 cos 𝜃 − 𝜏 𝑡ℎ𝑒𝑛 𝑡𝑟𝑖𝑝; 𝑒𝑙𝑠𝑒 𝑟𝑒𝑠𝑡𝑟𝑎𝑖𝑛
Which can be written as –
𝑘3 𝑉𝑅 𝐼𝑅 cos 𝜃 − 𝜏 < 𝑘1 𝐼𝑅 2
Or
𝑉𝑅 𝐼𝑅 𝑘1
2
cos 𝜃 − 𝜏 <
𝐼𝑅 𝑘3
REACTANCE RELAY:
𝑉𝑅 𝐼𝑅 𝑘1
2
cos 𝜃 − 𝜏 <
𝐼𝑅 𝑘3
𝑉𝑅 𝑘1
∴ cos 𝜃 − 𝜏 <
𝐼𝑅 𝑘3
𝑉𝑅
= 𝑍𝑠𝑒𝑒𝑛 = the apparent impedance seen by the relay.
𝐼𝑅
𝑘1
∴ 𝑍𝑠𝑒𝑒𝑛 cos 𝜃 − 𝜏 <
𝑘3
If the maximum torque angle of the directional element (𝜏) is set 900, and let
𝑘1
= 𝑋𝑛
𝑘3
The first quadrant represents the forward faults whereas the third quadrant
represents the reverse faults.
The trip characteristic of the reactance relay occupies areas in both these
quadrants.
Reactance relay does not exhibit any directional property.
EFFECT OF POWER SWING ON REACTANCE RELAY:
The reactance relay occupies a large area on the R-X plane.
It operates even during normal load flow.
Therefore, the reactance relay operates on power swing as well.
This is not desirable.
MHO RELAY:
Universal torque equation -
2 2
𝑇 = 𝑘1 𝐼𝑅 + 𝑘2 𝑉𝑅 + 𝑘3 𝑉𝑅 𝐼𝑅 cos 𝜃 − 𝜏 + 𝑘4
If we set 𝑘1 = 0, 𝑘2 negative, and 𝑘3 positive, and 𝑘4 is negligible
Voltage provides restraining torque, and the directional element provides the
operating torque.
Therefore, the trip law can be written as –
𝑘3 𝑉𝑅 𝐼𝑅 cos 𝜃 − 𝜏 > 𝑘2 𝑉𝑅 2
Consider an arcing fault at point B and let the fault resistance is BC.
The impedance seen by the relay considering the fault resistance lies on the verge of the trip
region.
The relay will restrain for any fault beyond point B.
The reach of relay reduces from OA to OB.
DIRECTIONAL PROPERTY OF MHO RELAY:
Magnitude of impedance
= 32 + 42 = 5 . Trip
The circle with ‘𝑂’ as a
center and radius equal
to 5 on 𝑅 − 𝑋 plane, 𝑂 𝑅
represents the
characteristics of an
impedance relay.
NUMERICAL PROBLEM:
−1 4
Phase angle = tan = 53.13°
3
𝑂𝐴 = 5 Restrain
𝑋 𝐴
𝑂𝐵 = 3
𝐶 𝐷
𝐴𝐵 = 4
Trip
Let
53.13°
𝐶𝐷 = 1 , which represents the resistance
of the arcing fault. 𝑂 𝐵 𝑅
𝑂𝐴 = 𝑂𝐷 = 5 Restrain
2 2
∴ 𝑂𝐷2 = 𝑂𝐶 cos(53.13° ) +1 + 𝑂𝐶 sin 53.13° 𝑋 𝐴
∴ 52 = 0.6 𝑂𝐶 + 1 2
+ 0.8 𝑂𝐶 2 𝐶 𝐷
∴ 25 = 0.36𝑂𝐶 2 + 1.2 𝑂𝐶 + 1 + 0.64𝑂𝐶 2 Trip
∴ 𝑂𝐶 2 + 1.2 𝑂𝐶 − 24 = 0 53.13°
∴ 𝑂𝐶 =4.25 𝑂 𝐵 𝑅
% of line protected by impedance relay
4.25
= × 100 = 85%
5
𝐴𝐶 0.75
% Under-reach × 100 = × 100 = 15%
𝑂𝐴 5
NUMERICAL PROBLEM:
Draw reactance relay characteristics to protect 100% of the line having an
impedance of 3 + 𝑗4 . If an arcing fault having an arc impedance 1 + 𝑗0 occurs
anywhere on the line find the maximum portion of the line that can be protected by
reactance relay.
𝑋 Restrain
Trip
Ans:
Magnitude of reactance = 4 .
The line parallel to the
resistance axis at a distance of 𝑂 𝑅
4 (reactance), represents
the characteristics of a
reactance relay.
NUMERICAL PROBLEM:
𝑋 Restrain
= 2.6968.2°
NUMERICAL PROBLEM:
The impedance of line section 𝐴𝐵 is 3 + 𝑗7.5 (primary side). CT ratio: 400/1 A and
PT ratio: 132000/110 V.
First zone covers 80% of the first line. Second zone covers 150% of line section 𝐴𝐵,
and third zone covers 220% of 𝐴𝐵. Find the first, second and third zone setting of
an impedance relay at A.
Ans:
Impedance of line section on relay side (secondary side) = 2.6968.2°
Setting of impedance relay used for first zone protection = 0.8 × 2.69 = 2.152
Setting of second zone = 1.5 × 2.69 = 4.035
Setting of zone 3 = 2.2 × 2.69 = 5.918