C RS Transducer Installation Guide 916 077A
C RS Transducer Installation Guide 916 077A
Flow Transducer
Installation Guide
April 2004
Table of Contents
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Transducer Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Couplants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Preparing for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Choosing an Installation Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Preparing the Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Obtaining the Transducer Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Determining the Number of Traverses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installing the Universal Clamping Fixture and Transducers - UCF . . . . . . . . . . . . . . . . . . . . . 7
Verify Fixture Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Identifying the UCF Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
The Double-Traverse Method -UCF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
The Single-Traverse Method - UCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mounting Transducers into the UCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installing the General Clamping Fixture and Transducers - GCF . . . . . . . . . . . . . . . . . . . . . 21
The Double-Traverse Method - GCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
The Single-Traverse Method - GCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Mounting Transducers into the GCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Installing the Magnetic Clamping Fixture and Transducers - MCF . . . . . . . . . . . . . . . . . . . . 32
Identifying the MCF Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
The Double-Traverse Method - MCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
The Single-Traverse Method - MCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Mounting Transducers into the MCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Maintaining the C-RS Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
iii
April 2004
The warranties set forth herein are exclusive and are in lieu of
all other warranties whether statutory, express or implied
(including warranties or merchantability and fitness for a
particular purpose, and warranties arising from course of
dealing or usage or trade).
iv
April 2004
Introduction The C-RS ultrasonic flow transducer is used exclusively with the GE
Panametrics line of ultrasonic flowmeters. These transducers measure
the flow rate of sonically-conductive liquids through pipes having
diameters between 2 in. (5 cm) and over 300 in. (7.6 m). Such
measurements are typically independent of the pipe material.
This document provides the following instructions on installing and
maintaining C-RS transducers:
• Transducer Construction - see below
• Couplants - page 2
• Preparing for Installation - 3
• Installing the Universal Clamping Fixture and Transducers -
page 7
• Installing the General Clamping Fixture and Transducers -
page 21
• Installing the Magnetic Clamping Fixture and Transducers -
page 32
• Maintaining Transducers - page 44
• Specifications - page 45
Transducer The C-RS operates in process temperatures from -40 to 302oF (-40 to
Construction 150oC)*. Each C-RS transducer assembly consists of the following
components (see Figure 1 below):
• a stainless steel adapter with 3/4” NPT male thread for
attaching a junction box
• a transducer that consists of a peizoelectric element mounted on
a wedge and wired to the BNC connector
• a BNC style connector for use in connecting the transducer to
the flowmeter.
*This temperature is for ATEX certified designs. Consult factory for
higher temperatures.
BNC Connector
Transducer Body
Adapter
Table 1: Couplants
PART
NO. TYPE TEMP. RANGE USE
CPL-1 Standard -40 to 149oF Semi-Permanent
(-40 to +65oC)
CPL-2 High/Low -256 to 500oF Semi-Permanent
Temperature
(-160 to +260oC)
CPL-3 For Portable -4 to 140oF Temporary
(-20 to +60oC)
CPL-4 Special As Required *Difficult
Applications
CPL-7 Epoxy 14 to 122oF Permanent
(-10 to +50oC)
CPL-8 Solid Sheet -40 to 446oF Permanent
(-40 to +230oC)
* Installations involving hotter or colder temperatures than listed
above, may require special couplants. Consult GE Panametrics for
these applications.
Preparing for Before the clamping fixture and transducers can be properly installed,
Installation you must do the following:
Caution!
A flowmeter’s accuracy and performance
depends on the location, spacing, and alignment
of the transducers. The transducer spacing is
unique to your installation.
Choosing an Installation 2. Place the transducers as close as possible to the horizontal plane.
Location (cont.) (see figure below). Locate the transducers on opposite sides of
the pipe 180o apart, ideally at the 3 and 9 o’clock positions. Do
not place transducers on the top or bottom of the pipe.
Pipe
Transducer
Signal Path
End View
Preparing the Pipe 1. Prepare the pipe for the transducers by clearing rust and paint from
an area 2 in. (5 cm) wide by 4 in. (10 cm) long on one side of the
pipe.
2. Polish the cleared area, taking care to preserve the original
curvature of the pipe.
3. With an ultrasonic thickness gage, measure the pipe thickness at a
minimum of six spots on the cleared area. Take at least three
measurements at each spot to ensure accuracy. The thickness
should not vary by more than 5% at each spot. If you encounter
more than a 5% variation at each spot, move to another section of
the pipe. Verify that the wall thickness at both transducer locations
has less than the 5% variation.
4. Measure the outside diameter (OD) of the pipe using a tape
measure or the supplied pipe wrap.
Obtaining the Before installing the clamping fixture, you must obtain the transducer
Transducer Spacing spacing from the flowmeter. You will need to know the transducer
spacing later in this procedure.
To obtain the spacing, you must enter the measured OD and the pipe
wall thickness into the flowmeter’s user program (Pipe Parameters) to
determine the transducer spacing. Refer to your User’s Manual or
Startup Guide for more details.
Determining the Number The next step in installation is determine the number of traverses. The
of Traverses transducers can be mounted using one of two methods (see Figure 2
on the next page):
• Double-traverse method (“V” method) - transducers are mounted
on the same side of the pipe and the ultrasonic signal is bounced
from one transducer to the other, off the opposite pipe wall.
Transducers
Transducer
Transducer
TOP VIEW
Figure 2: Double- and Single-Traverse Installations
Installing the Universal The Universal Clamping Fixture (UCF) acts as a spacing device and a
Clamping Fixture and transducer holder. The UCF is available in two lengths and consists of
Transducers - UCF a number of components. Before you begin installation, you should
verify your fixture is the correct length and familiarize yourself with
the fixture components.
Verify Fixture Length Make sure you note the following restrictions for your clamping
fixture. The UCF is available in two lengths, 12- and 24-in.
(~30.5- and ~61-cm). Each size fixture can be installed for a single-
or double-traverse method. However, depending on the method used,
there are pipe size restrictions that are outlined in Table 2 below.
Identifying the UCF The UCF has two adjustable short blocks that are used for the double-
Components traverse method. Two slide tracks connect the blocks. A ruler attached
to one of the tracks helps set the transducer spacing. For single-
traverse methods, a long block is also used.
The blocks are used to hold the transducers in position for accurate
measurement. The UCF is chained or strapped around the pipe. The
blocks are positioned using the spacing dimension calculated by the
flowmeter. Then the transducers are mounted into the blocks. Figure
3 on the next page shows the short and long blocks.
The transducer installation consists of mounting the UCF to the pipe
and then mounting the transducers into the fixture. Refer to the
appropriate section that follows for instructions:
Chain
Long Block
2 Screw Hooks
The Double-Traverse Note: The instructions in this section can also be used for a
Method -UCF multiple-traverse method. However, you must use an EVEN
number of traverses. The distance the signal travels from one
side of the pipe wall to the opposite side of the pipe wall is
considered one traverse. For more than two traverses, consult
the GE Panametrics factory.
3. Prepare the pipe where you intend to place the clamping fixture
by making sure it is clean and free of loose material. Sanding,
though usually not required, may be necessary to take off any
high spots. When sanding, be careful to preserve the original
curvature of the pipe.
The Double-Traverse 4. Using the attached ruler, move the blocks so they are a distance
Method -UCF (cont.) S from each other. Use the pressure bolt or the ends of the blocks
as reference points.
.
Centerline Centerline
S = Spacing
S = Spacing
S = Spacing
Side View
6. Wrap the chain around the pipe and fasten the chain on the J
screw hook on the opposite side of the block. Do this for both
blocks.
Top View
The Double-Traverse 7. Using the screw hook on the blocks, tighten the chains until the
Method -UCF (cont.) fixture is secured snugly to the side of the pipe.
Side View
Top View
The Single-Traverse Note: The instructions in this section can also be used for a
Method - UCF multiple-traverse method. However, you must use an ODD
number of traverses. The distance the signal travels from one
side of the pipe wall to the opposite side of the pipe wall is
considered one traverse.
The procedure for mounting the UCF for the single-traverse method
requires a long block and two short blocks. The long block is fastened
to the pipe first and then the short block assembly is properly aligned
and fastened at 180° from the long block.
3. Prepare the pipe where you intend to place the UCF by making
sure it is clean and free of loose material. Sanding, though
usually not required, may be necessary to take off any high
spots. However, be careful to preserve the original curvature of
the pipe and not to eradicate the marks on the pipe.
4. Find the top of the pipe and use a level to draw a line parallel to
the pipe’s axis.
Side View
The Single-Traverse 5. Make two marks on the line equal to the transducer spacing
Method -UCF (cont.) distance S, as calculated by the meter.
Spacing
Mark Mark
Side View
Spacing
Crossmark
Side View
7. From the other mark, go in the other direction around the pipe
for one quarter the circumference and make another crossmark.
Spacing
Crossmark
Side View
The Single-Traverse 8. Center the long block over one of the crosssmarks on the pipe.
Method -UCF (cont.) Align the long block so that the pressure bolt is over the center of
the crossmark. Fasten the block by wrapping both chains around
the pipe and fastening the chains to the screw hooks on the
opposite side of the block.
.
Fasten Chains
Top View
9. Use the wing nuts to tighten the chains on the long block until it
is secured snugly to the pipe.
Note: Make sure both chains are perpendicular to the bottom of the
block and are not twisted. If the chains are slanted, the slack
will cause the block to slide.
Tighten Screw
Hooks
Top View
The Single-Traverse 10. Position the clamping fixture rails so that one of the short blocks
Method -UCF (cont.) is placed over the remaining crossmark on the opposite side of
the pipe and the pressure bolt is over the center of the crossmark.
Make sure the block does not lie on top of the chains of the long
block.
Short Block
Crossmark (One of two)
Crossmark
Top View
11. Wrap the chain around the pipe and fasten the chain to the screw
hook on the opposite side of the block. Do this for both short
blocks.
Note: Make sure the chains on both blocks are on the same side of
the fixture and are opposite the ruler.
Top View
12. Tighten the pressure bolt all the way down on the short block
that is NOT positioned over the crossmark. This will act as a
reminder to not install the transducer in that block.
The Single-Traverse 13. Use the screw hooks to tighten the chains on the fixed and
Method - UCF (cont.) adjustable blocks until the blocks are secured snugly to the pipe.
Side View
Top View
Mounting Transducers The last step of installation is mounting the transducers into the
into the UCF clamping fixture. C-RS transducers are manufactured with a V-notch
on top of the transducer body.
IMPORTANT: To maintain ATEX certification the transducer face
must be protected against impact. This is provided by
properly installing the transducer into the clamping
fixture. All care must be taken during installation to
ensure all protection is afforded.
Procedure for Mounting Transducers
To mount the transducers into the UCF, use the following steps:
1. Apply a thread sealant to the transducer threads. A sealant is not
required within the US, however, a sealant must be used in
European Communities.
2. Before mounting the transducers, thread the junction box onto
the end of the transducer with the BNC connector. Ensure that at
least five full threads are engaged. Make sure to orient the cover
of the junction box so it is accessible to make cable connections
once the box is installed.
Mounting Transducers 4. Place the transducers into the blocks. Make sure the junction box
into the UCF (cont.) faces away from the block as shown below.
Flow
Top View
Flow
Top View
Mounting Transducers 6. Tighten the locking nut on the pressure bolt (see Figure 3 on
into the UCF (cont.) page 8).
!WARNING!
Before performing the next step make
sure power to the flowmeter electronics
has been disconnected.
Mounting Transducers
into the UCF (cont.)
Note: If you have mounted the transducers into the UCF properly,
the two transducer cable connectors will face away from each
other as shown in the above figure.
Installing the General The General Clamping Fixture (GCF) acts as a permanent transducer
Clamping Fixture and holder. The fixture has two blocks that are used for double- and
Transducers - GCF single-traverse methods. Steel straps secure the blocks to the pipe for
a permanent installation.
The Double-Traverse Note: The instructions in this section can also be used for a
Method - GCF multiple-traverse method. However, you must use an EVEN
number of traverses. The distance the signal travels from one
side of the pipe wall to the opposite side of the pipe wall is
considered one traverse. For more than two traverses, consult
the GE Panametrics factory.
There are three advantages in using the double-traverse method:
The Double-Traverse The procedure for mounting the GCF involves marking the pipe for
Method - GCF (cont.) the desired spacing, fastening the clamping fixture on the pipe and
then mounting the transducers into the fixture.
3. Prepare the pipe where you intend to place the clamping fixture
by making sure it is clean and free of loose material. Sanding,
though usually not required, may be necessary to take off any
high spots. Be careful to preserve the original curvature of the
pipe.
4. Find the top of the pipe and use a level to draw a line parallel to
the pipe’s axis.
Side View
The Double-Traverse 5. Make two marks on the line equal to the transducer spacing
Method - GCF (cont.) distance S, as calculated by the meter.
Spacing
Mark Mark
Side View
Spacing
Side View
Crossmarks
7. Center one of the blocks over one of the crossmarks on the pipe.
Align the block so that the pressure bolt is over the center of the
mark. Secure the block by wrapping the two straps around the
block and pipe and tightening them. Make sure the turnbuckles
are at least 1/2 pipe diameter away from the block.
Turnbuckles
Top View
The Double-Traverse 8. Repeat Step 7 to install the other block over the other crossmark.
Method - GCF (cont.)
Note: Make sure both straps are perpendicular to the bottom of the
block. If the straps are slanted, the slack will cause the block
to slide. The slack may also change the transducer spacing
after the transducers are mounted.
Top View
Top View
End View
The Single-Traverse Note: The instructions in this section can also be used for a
Method - GCF multiple-traverse method. However, you must use an ODD
number of traverses. The distance the signal travels from one
side of the pipe wall to the opposite side of the pipe wall is
considered one traverse.
The procedure for mounting the GCF involves marking the pipe for
the desired spacing, fastening the fixture to the pipe and then
mounting the transducers into the fixture.
3. Prepare the pipe where you intend to place the GCF by making
sure it is clean and free of loose material. Sanding, though
usually not required, may be necessary to take off any high
spots. Be careful to preserve the original curvature of the pipe
and not to eradicate the marks on the pipe.
4. Find the top of the pipe and use a level to draw a line parallel to
the pipe’s axis.
Side View
The Single-Traverse 5. Make two marks on the line equal to the transducer spacing
Method - GCF (cont.) distance S, as calculated by the meter.
Spacing
Mark Mark
Side View
Spacing
Crossmark
Side View
Spacing
Crossmark
Side View
The Single-Traverse 8. Center one of the blocks over one of the crossmarks on the pipe.
Method -GCF (cont.) Align the block so that the pressure bolt is over the center of the
crossmark. Secure the block by wrapping two straps around the
block and pipe and tightening them. Make sure the turnbuckles
are at least 1/2 pipe diameter away from the block.
Turnbuckles
Top View
9. Repeat Step 8 to install the other block over the other punch
mark.
Note: Make sure both straps are perpendicular to the bottom of the
block. If the straps are slanted, the slack will cause the block
to slide. The slack may also change the transducer spacing
after the transducers are mounted.
Top View
Top View
End View
Mounting Transducers The last step of installation is mounting the transducers into the
into the GCF clamping fixture. C-RS transducers are manufactured with a dimple
on top of the transducer body. In addition, there are scribe marks on
each side.
IMPORTANT: To maintain ATEX certification the transducer face
must be protected against impact. This is provided by
properly installing the transducer into the clamping
fixture. All care must be taken during installation to
ensure all protection is afforded.
Procedure for Mounting Transducers
To mount the transducers into the GCF, use the following steps:
Mounting Transducers 4. Place the transducers in the appropriate blocks. Make sure the
into the GCF (cont.) transducers are oriented as shown below.
Note: If the transducer cables are already connected, you must
determine the upstream and downstream directions of the pipe
and place the transducers into the appropriate blocks.
Locking Nut
Top View
Note: If you have mounted the transducers into GCF properly, the
two transducer cable connectors will face away from each
other as shown in the above figure.
Installing the Magnetic The Magnetic Clamping Fixture (MCF) is used to fasten transducers
Clamping Fixture and to the pipe at the proper spacing without chains or straps. The MCF is
Transducers - MCF used on ferrous pipe materials only.
To properly mount the MCF, you should become familiar with the
components of each type of fixture.
Identifying the MCF Refer to Figure 11 below to identify these components, then refer to
Components one of the following sections to install the clamping fixture:
Pressure Bolt
Optional Safety Chain
Locking Nut ON/OFF Switch
Thumbscrews
Rails
Figure 11: Transducer Block and Magnetic Block
The Double-Traverse The Double-Traverse MCF consists of two blocks connected by two
Method - MCF rods (one of the two rods acts as a scale or ruler to help you properly
space transducers). Both blocks are adjustable. This type of fixture
has two transducer blocks and like the magnetic blocks, both are
adjustable.
The procedure for mounting the MCF involves setting the transducer
spacing and then securing the fixture to the pipe.
!WARNING!
Do not use the MCF at temperatures that exceed
120°F (49°C), or the fixture will fall off the pipe.
3. Prepare the pipe where you intend to place the clamping fixture
by making sure it is clean and free of loose material. Sanding,
though usually not required, may be necessary to take off any
high spots. Be careful to preserve the original curvature of the
pipe.
The Double-Traverse 4. Using the scale on the rod, move the blocks so they are located a
Method - MCF (cont.) distance equal to the spacing dimension from each other. To
move the block, loosen the red thumb screws, slide the block to
the desired location and tighten the thumb screws. Use the
pressure bolt or the edge of the block as the measuring point for
the block.
At least 4”
Top View
The Single-Traverse The Single-Traverse MCF consists of two parts. Each part is made up
Method - MCF of two magnetic blocks which are connected by two rods. In addition,
a sliding transducer block, which is used to hold the transducer in
proper alignment, is positioned on the two rods. Each part is
positioned on the pipe to face 180o opposite each other.
The procedure for mounting the MCF involves marking the pipe and
then securing the fixtures to the pipe.
!WARNING!
Do not use magnetic fixtures
at temperatures that exceed 120°F (49°C),
or the fixture will fall off the pipe.
3. Prepare the pipe where you intend to place the MCF by making
sure it is clean and free of loose material. Sanding, though
usually not required, may be necessary to take off any high
spots. Be careful to preserve the original curvature of the pipe
and not to eradicate the marks on the pipe.
The Single-Traverse 4. Find the top of the pipe and use a level to draw a line parallel to
Method - MCF (cont.) the pipe’s axis.
Side View
Spacing
Mark Mark
Side View
Spacing
Crossmark
Side View
The Single-Traverse 7. From the other mark, go in the opposite direction around the
Method - MCF (cont.) pipe for one quarter the circumference and make another
crossmark.
Spacing
Crossmark
Side View
Thumbscrew
9. Center the block over one of the marks on the pipe. Align it such
that the pressure bolt on the transducer block is right over the
center of the crossmark.
.
Pressure Bolt
Top View
The Single-Traverse 10. Turn the switches on each magnet to the ON position.
Method - MCF (cont.)
11. Repeat Steps 9 and 10 for the other fixture on the opposite pipe
marking.
Top View
12. If provided, secure the safety chain. The safety chain prevents
the fixture from falling of the pipe in the event the magnet
releases.
Mounting Transducers The last step of installation is mounting the transducers into the
into the MCF clamping fixture. C-RS transducers are manufactured with a dimple
on top of the transducer body. In addition, it also has scribe marks on
each side.
IMPORTANT: To maintain ATEX certification the transducer face
must be protected against impact. This is provided by
properly installing the transducer into the clamping
fixture. All care must be taken during installation to
ensure all protection is afforded.
Procedure for Mounting Transducers
To mount the transducers into the MCF, use the following steps:
Mounting Transducers 4. Place the transducers in the appropriate blocks. Make sure the
into the MCF (cont.) transducers are oriented as shown below.
Note: If the transducer cables are already connected, you must
determine the upstream and downstream directions of the pipe
and place the transducers into the appropriate blocks.
Downstream Transducer
Flow
Top View
!WARNING!
Do not tighten the pressure bolt so that
the magnet separates from the pipe.
Pressure Bolt
Locking Nut
Top View
Mounting Transducers 6. Tighten the locking nut on the pressure bolt (see drawing in step
into the MCF (cont.) 5 on previous page).
!WARNING!
Before performing the next step make
sure power to the flowmeter electronics
has been disconnected.
!WARNING!
If your fixture is installed at an elevated location, GE
Panametrics recommends securing the fixture with
the optional safety chain or a tether/leash to
prevent injury if the fixture falls off the pipe.
Mounting Transducers
into the MCF (cont.)
Note: If you have mounted the transducers into the MCF properly,
the two transducer cable connectors will face away from each
other as shown in the above figure.
Maintaining the C-RS Transducers, couplant, the clamping fixture and dampening material
Transducers are provided by GE Panametrics. Once you have completed
installation little maintenance is required. Refer to Table 3 below for
maintenance information.
Specifications
Table 4: C-RS Transducer Specifications
Transducer # 401 402 403
Designation Large pipes; ductile Mid-size pipes, high Small pipes; high per-
iron pipes, lined performance formance
pipes; high levels of
two-phase liquid;
high performance
Installation Type Clamp-on for liquid applications
Material 316 Stainless Steel or plastic
Pipes Sizes 2” to 300” (5 cm to 2” to 300” (5 cm to 2” to 6” (5 to 15 cm)
7.6 m) diameter 7.6 m) diameter diameter
Operating Frequency 0.5 MHz 1.0 MHz 2.0 MHz
Electrical Rating 200 V peak-to-peak, 5 mA
Ambient Temperature -40 to +167°F (-40 to +75°C)
Range
Process Temperature -40 to +302°F (-40 to +150°C)
Range
North American Class I, Division 1, Group B, C & D
Certification - Explosion
proof (Pending)
European Certification - II 2 GD, EEx md IIC T6 80°C
Flameproof Tam -40 to 75oC (-40 to 167oF)
KEMA 02ATEX2337 X
North American IP66, TYPE 4X
Certification - 200Vpp, 5mA
Weatherproof
European Certification - IP 66
Weatherproof
IMPORTANT: The transducer is protected by a suitable fuse located in the flowmeter electronics.
The fuse has a breaking capacity in accordance with the short circuit current of the
supply.
We, GE Panametrics
Shannon Industrial Estate
Shannon, Co. Clare
Ireland
to which this declaration relates, are in conformity with the following standards:
• EN 50014:1997+A1+A2:1999
• EN 50018:2000
• EN 50028:1987
• EN 50281-1-1:1998 (CRL, CRS and CRW only)
• II 2 G EEx d IIC T6
CRL, CRS: KEMA02ATEX2337 X
C-PT-N, -M, -H: KEMA03ATEX1147 X
CRW: KEMA03ARTEX1540 X
CXL: KEMA03ATEX1459 X
KEMA, Ultrechtseweg, 310 Arnhem, The Netherlands
• EN 61326:1998, Class A, Annex A, Continuous Unmonitored Operation
following the provisions of the 89/336/EEC EMC Directive and the 94/9/EC ATEX Directive.
The units listed above and any ancillary sample handling systems supplied with them do not bear CE
marking for the Pressure Equipment Directive, as they are supplied in accordance with Article 3, Section 3
(sound engineering practices and codes of good workmanship) of the Pressure Equipment Directive
97/23/EC for DN<25.
TÜV
TÜV ESSEN
ISO 9001
U.S.
Nous, GE Panametrics
Shannon Industrial Estate
Shannon, Co. Clare
Ireland
• EN 50014:1997+A1+A2:1999
• EN 50018:2000
• EN 50028:1987
• EN 50281-1-1:1998 (CRL, CRS and CRW only)
• II 2 G EEx d IIC T6
CRL, CRS: KEMA02ATEX2337 X
C-PT-N, -M, -H: KEMA03ATEX1147 X
CRW: KEMA03ARTEX1540 X
CXL: KEMA03ATEX1459 X
KEMA, Ultrechtseweg, 310 Arnhem, The Netherlands
• EN 61326:1998, Class A, Annex A, Continuous Unmonitored Operation
Les matériels listés ci-dessus ainsi que les systèmes d'échantillonnages pouvant être livrés avec, ne portent
pas le marquage CE de la directive des équipements sous pression, car ils sont fournis en accord avec la
directive 97/23/EC des équipements sous pression pour les DN<25, Article 3, section 3 qui concerne les
pratiques et les codes de bonne fabrication pour l'ingénierie du son.
TÜV
TÜV ESSEN
ISO 9001
U.S.
Wir, GE Panametrics
Shannon Industrial Estate
Shannon, Co. Clare
Ireland
• EN 50014:1997+A1+A2:1999
• EN 50018:2000
• EN 50028:1987
• EN 50281-1-1:1998 (CRL, CRS and CRW only)
• II 2 G EEx d IIC T6
CRL, CRS: KEMA02ATEX2337 X
C-PT-N, -M, -H: KEMA03ATEX1147 X
CRW: KEMA03ARTEX1540 X
CXL: KEMA03ATEX1459 X
KEMA, Ultrechtseweg, 310 Arnhem, The Netherlands
• EN 61326:1998, Class A, Annex A, Continuous Unmonitored Operation
Die oben aufgeführten Geräte und zugehörige, mitgelieferte Handhabungssysteme tragen keine CE-
Kennzeichnung gemäß der Druckgeräte-Richtlinie, da sie in Übereinstimmung mit Artikel 3, Absatz 3
(gute Ingenieurpraxis) der Druckgeräte-Richtlinie 97/23/EG für DN<25 geliefert werden.
TÜV
TÜV ESSEN
ISO 9001
U.S.
as the manufacturer, declare under our sole responsibility that the product
to which this document relates, in accordance with the provisions of ATEX Directive 94/9/EC Annex II,
meets the following specifications:
II 2 GD EEx md IIC T6
1180 KEMA02ATEX2337X T80°C, -40°C to +75°C
Furthermore, the following additional requirements and specifications apply to the product:
• Having been designed in accordance with EN 50014, EN 50018, EN 50281 and EN 50028, the
product meets the fault tolerance requirements of electrical apparatus for categories “d” and “m”.
• The product is an electrical apparatus and must be installed in the hazardous area in accordance with
the requirements of the EC Type Examination Certificate. The installation must be carried out in
accordance with all appropriate international, national and local standard codes and practices and site
regulations for flameproof apparatus and in accordance with the instructions contained in the manual.
Access to the circuitry must not be made during operation.
• Only trained, competent personnel may install, operate and maintain the equipment.
• The product has been designed so that the protection afforded will not be reduced due to the effects of
corrosion of materials, electrical conductivity, impact strength, aging resistance or the effects of
temperature variations.
• The product cannot be repaired by the user; it must be replaced by an equivalent certified product.
Repairs should only be carried out by the manufacturer or by an approved repairer.
• The product must not be subjected to mechanical or thermal stresses in excess of those permitted in
the certification documentation and the instruction manual.
• The product contains no exposed parts which produce surface temperature infrared, electromagnetic
ionizing, or non-electrical dangers.
• The product must be protected by a suitable fuse. The breaking capacity of the fuse must be in
accordance with the prospective short circuit current of the supply.
• The product must be installed in such a way that its front face is protected against impact.
• Installation Instructions: The product is provided with a male 3/4” NPT thread. For electrical
connection, the product must be mounted to a certified metal enclosure in type of explosion protection
flameproof enclosure “d”, the assembly complying with the requirements of EN50018 and providing
a degree of protection of IP6X. Measures must be taken to ensure a good bonding connection and to
prevent the connection from self-loosening.
CERT-ATEX-C 7/16/03
WORLDWIDE
OFFICES
July 2003
USA
GE Panametrics
221 Crescent Street, Suite 1
Waltham, MA 02453-3497
Telephone: (781) 899-2719
Toll-free: (800) 833-9438
Fax: (781) 894-8582
E-Mail: [email protected]
Web: www.gepower.com/panametrics
Ireland
GE Panametrics
Shannon Industrial Estate
Shannon, County Clare
Ireland
Telephone: 353-61-470200
Fax: 353-61-471359
E-Mail: [email protected]