Short Circuit Fault Calculation
Short Circuit Fault Calculation
SELECT:
BASE MVA = 0.075 MVA
BASE KV = 0.240 kV
BASE CURRENT = 0.3125 kA
FROM TABLE 9.1.1.9, PEC 2009,R & X OF 80mm2 THW COPPER WIRE IN PVC CONDUIT:
FROM TABLE 9.1.1.9, PEC 2009,R & X OF 5.5mm2 THHN COPPER WIRE IN PVC CONDUIT:
FROM TABLE 9.1.1.9, PEC 2009,R & X OF 5.5mm2 THHN COPPER WIRE IN PVC CONDUIT:
8.) WASHING MACHINE BRANCH CIRCUIT CONDUCTOR (C14) PER-UNIT IMPEDANCE, ZC14pu
FROM TABLE 9.1.1.9, PEC 2009,R & X OF 5.5mm2 THHN COPPER WIRE IN PVC CONDUIT:
FROM TABLE 9.1.1.9, PEC 2009,R & X OF 5.5mm2 THHN COPPER WIRE IN PVC CONDUIT:
10.) WATER PUMP BRANCH CIRCUIT CONDUCTOR (C18) PER-UNIT IMPEDANCE, ZC18pu
FROM TABLE 9.1.1.9, PEC 2009,R & X OF 5.5mm2 THHN COPPER WIRE IN PVC CONDUIT:
WHERE 25% IS THE AVERAGE INDUCTION MOTOR IMPEDANCE PER IEEE STD 141 (PEC 2009)
M5-REFRIGERATOR MOTOR
ZM5pu = (25%/100)X(0.075MVA/0.0015MVA) = 12.5 pu
1
1 1 1 1 1
+ + + +
(0.063164+ j 0.036947) (0.1763+ j 10.197544) (0.2398+ j 10.20019) (0.2131+ j12.50888) (0.2193+ j12.5
1
ZTOTAL pu = = 0.06063799935 + j0.03750972966
(11.92734738− j7.378072834)
=√ ¿ ¿
=0.070130180071 pu
ISC L-L@ “F3” =(PU VOLTAGE/ZTOTAL PU)X(BASE CURRENT)
= (1.0/0.07014908514)X(0.3125kA)
= 4.382778512 kA
= 4,382.8 A RMS SYMMETRICAL
ASSUMING FAULT CURRENTS IN ALL BRANCH CIRCUITS IS EQUAL TO THE VALUE TAKEN FROM
THE FAULT CURRENT AT “F3”:
ISC L-L@ “F3”=ISC L-L@ “F4”=ISC L-L@ “F5”=ISC L-L@ “F6”=ISC L-L@ “F7”=ISC L-L@ “F8”=ISC L-L@ “F9”=ISC L-L@
“F10”=ISC L-L@ “F11”=ISC L-L@ “F12”=ISC L-L@ “F13”=ISC L-L@ “F14”=ISC L-L@ “F15”=ISC L-L@ “F16”=ISC L-L@
“F17”=ISC L-L@ “F18”=ISC L-L@ “F19”=ISC L-L@ “F20”=ISC L-L@ “F21”=ISC L-L@ “F22”= ISC L-L@ “F23” =ISC L-L@
“F24”=ISC L-L@ “F25”=ISC L-L@ “F26”=ISC L-L@ “F27”=ISC L-L@ “F28”.