H
H
12
13
Magnetization curve
𝟐𝝅𝒇𝑻ɸ
RMS voltage
EA = =√𝟐𝝅𝒇Tɸ =4.44𝒇Tɸ
√𝟐
Vector Diagrams of a Loaded Alternato
2
0
21
Voltage Regulation
Value of Ra
Can be measured directly by voltmeter and ammeter method or by using Wheatstone bridge
Synchronous
Example 1. A 3-phase, star-connected alternator supplies a load of 10 MW at p.f. 0.85
lagging and at 11 kV (terminal voltage). Its resistance is 0.1 ohm per phase and
synchronous reactance 0.66 ohm per phase. Calculate the line value of e.m.f. generated
Example 2 The effective resistance of a 2200V, 50Hz, 440 KVA, 1-phase, alternator is
0.5 ohm. On short circuit, a field current of 40 A gives the full load current of 200 A. The
electro- motive force on open-circuits with same field excitation is 1160 V. Calculate the
synchronous impedance and reactance
Example3 A60-KVA, 220V, 50-Hz, 1-ϕalternator has effective armature resistance of 0.016
ohm and an armature leakage reactance of 0.07 ohm. Compute the voltage induced in the
armature when the alternator is delivering rated current at a load power factor of (a) unity
(b) 0.7 lagging and (c) 0.7leading
24
Example 4 In a50-kVA,star-connected,440-V,3-phase,50-Hzalternator,theeffective
armature resistance is 0.25 ohm per phase. The synchronous reactance is 3.2 ohm per phase
and leakage reactance is 0.5 ohm per phase. Determine at rated load and unity power
factor:(a) Internal e.m.f. Ea (b) no-load e.m.f. E0 (c) percentage regulation on full-load (d)
value of synchronous reactance which replaces armature reaction.
25
Example 6 From the following test results, determine the voltage regulation of a 2000-V, 1-
phase alternator delivering a current of 100 A at (i) unity p.f. (ii) 0.8 leading p.f. and (iii)
0.71 lagging p.f.
Test results : Full-load current of 100 A is produced on short-circuit by a field excitation of
2.5A.
An e.m.f. of 500 V is produced on open-circuit by the same excitation. The armature
resistance is 0.8Ω
26
Example8. A3.5-MVA,Y-connected a alternator at 4160 volts at 50-Hz has the open- circuit
characteristic given by the following data
Example 10. A 3-phase, 800-kV A, 3,300-V, 50-Hz alternator gave the following results:
The armature leakage reactance drop is 10% and the resistance drop is 2% of the normal
voltage. Determine the excitation at full-load 0.8 power factor lagging by the m.m.f. method
3
0
Field amperes : 14 18 23 30 43
Terminal volts : 4000 5000 6000 7000 8000
With armature short-circuited and full-load current flowing the field current is 17 A and
when the machine is supplying full-load of 2,000 kVA at zero power factor, the field current
is 42.5 A and the terminal voltage is 6,000 V.
Determine the field current required when the machine is supplying the full-load at 0.8 p.f.
lagging
31
32
Output power
Example 12. Derive the condition for the maximum output of a synchronous generator
connected to infinite bus-bars and working at constant excitation. A 3- ϕ, 11-kV, 5-MVA, Y-
connected alternator has a synchronous impedance of (1 + j 10) ohm per phase. Its
excitation is such that the generated line e.m.f.is 14kV.If the a alternator is connected to
infinite bus- bars, determine the maximum output at the given excitation
Synchronous motor
Example 14. A 75-kW, 3-ϕ, Y-connected, 50-Hz, 440-V cylindrical rotor synchronous motor
Operates at rated condition with 0.8 p.f. leading. The motor efficiency excluding field and
stator losses, is 95% and XS = 2.5 Ω. Calculate (i) mechanical power developed (ii) armature
current (iii) back e.m.f. (iv) power angle and (v) maximum or pull-out torque of the motor.
55