EL - 5036 - V7 - Power Plant Electrical Reference Series - Volume 7 Auxiliary Electrical Equipment
EL - 5036 - V7 - Power Plant Electrical Reference Series - Volume 7 Auxiliary Electrical Equipment
VOLUME 7
Q)
j)
0
j)
en_ ~~
•
- -
Q)
p
rn ••
<Ni
Q)
en@ -
- --
Q)
C
~~
- 11111
J
CS>
am
cf]
..
0)
DD
Q)
VOLUM E7
Written by
Stone & Webster Engineering Corporation
245 Summer Street
Boston, Massachusetts 02107
EL-5036, Volume 7
Project 2334
ISBN 0-8033-5006-6 volume
ISBN 0-8033-5015-5 series
Notice
This series was prepared by Stone &. Webster Engineering
Corporation as an account of work sponsored by the Elec-
tric Power Research Institute, Inc. (EPRil. Neither EPRI,
members of EPRI, Stone &. Webster Engineering Corpora-
tion, nor any person acting on behalf of any of them:
(a) makes any warranty, express or implied, with respect to
the use of any information, apparatus, method, or process
disclosed in this series or that such use may not infringe
privately owned rights, or (b) assumes any liabilities with
respect to the use of, or for damages resulting from the
use of, any information, apparatus, method, or process dis-
closed in this series.
13196308
FORE WORD
In the past, several electrical equipment manufac- well defined before this equipment can be cor-
turers published reference books dealing with rectly specified.
specific technical areas. Many utilities have stated Information about the application of station ser-
that these reference books have been very useful vice electrical equipment is available in the publi-
to them in dealing with plant emergencies and in cations and standards of technical societies, in
making decisions on design, system planning, and engineering handbooks, and in manufacture rs'
preventive maintenance. literature. This volume additionally provides the
Unfortunately, manufacture rs today seldom overall performanc e requirement s of the station
publish or update reference books on electric service auxiliary equipment. It guides the user in
power apparatus, mainly because of tighter bud- applying the industry standards for power plants.
get constraints. Until now, utilities have had no up- The goal of this volume is to describe the tech-
to-date industrywid e practical reference manual nological advances in load~switching and fault-
covering the various electric power apparatus and interrupting equipment. A selection and a review
electrical phenomena commonly encountered in of applicable published literature and industry
power plants. The Power Plant Electrical Refer- standards were performed to guide generating-
ence Series was planned to fill this need. station personnel in the design, procuremen t, test-
EPRI believes that the series will save utilities ing, and maintenance of this equipment. This vol-
time and money. It will aid plant engineers in ume discusses the available types of equipment
■ Prevention of forced outages through proper and delineates the system requirement s and the
installation, application, and protection of diagnostics for problems unique to this type of
station auxiliary equipment equipment.
13196308
13196308
ACK NOW LED GME NTS
13196308
13196308
CONT ENTS
Tables .......... .......... ... 7-xiii Molded-Case Circuit Breakers .... 7-29
7.2 Definition of Terms .......... 7-1 7.9 Generator Circuit Breakers .. 7-30
13196308
FIGURES
7-3 Barriers With an Inverted 7-18 Bimetallic Overload Relay ........ 7-26
V-shaped Slot for Extinguishing
Arcs by Constriction . . . . . . . . . . . . 7-3 7-19 Generati ng Station With Generato r
Circuit Breakers . . . . . . . . . . . . . . . . 7-31
7-4 Arc-restr aining Metal Barriers
Subdividing Long Arcs Into Several 7-20 Generati ng Station With Unit-
Serially Related Short Arcs ....... 7-4 connecte d Generato r ........ .... 7-31
7-5 Magnetic Blowout. ........ ...... 7-4 7-21 Nuclear Generati ng Station, Unit-
connecte d With 'I\.vo Station
7-6 Typical Molded-Case Air-Magnetic Service 'Transfor mers ........ .... 7-32
Circuit Breaker . . . . . . . . . . . . . . . . . 7-5
7-22 Nuclear Generati ng Station With
7-7 Arc Bubble in a Plain Oil Circuit Generato r Circuit Breaker ........ 7-33
Breaker ........ ........ ....... 7-6
7-23 Fossil Fuel Generati ng Station With
7-8 Plain Explosion Pot From Which Generato r Circuit Breaker ........ 7-34
Arc-enclosing Devices Evolved .... 7-7
7-24 Bus Types ........ ........ ..... 7-35
7-9 Ruptor Interrupt ing Device With
Serpentin e Throat, a Later Version 7-25 Isolated- Phase Bus Enclosur e
of the Explosion Pot ........ ..... 7-7 Designs ........ ........ ....... 7-36
13196308
13196308
TABLES
TABLE PAGE
13196308
13196308
EXECUTIVE SUMMARY
Objecti ve
This volume aims to develop guidelines for the de-
sign, procurem ent, installation, testing, and main-
tenance of the station service auxiliary power
supply equipme nt. It also means to identify mod-
ern practices and requirem ents for medium-
voltage switchgear, secondar y unit substations,
motor control equipme nt, and generato r circuit
breakers .
Approa ch
Pertinent information was accumulated from a na-
tional survey of utility requirem ents. A search of
literature about station service auxiliary equip-
ment was performe d to identify specific informa-
tion on power plant applications. Additionally, the
EPRI Review Coipmittee, with members from 11
utilities in various areas of the United States, and
other industry experts reviewed the material for
technica l adequacy and completeness. This infor-
mation provided the basis for this volume of the
Power Plant Electrical Reference Series.
13196308
13196308
ACRONYMS
&
ABBREVIATIONS
Contactor A device for repeatedly establishing and Unit transformer A power system supply trans-
interrupting an electric power circuit. former (generator step-up) that transforms all or a por-
Disconnecting or isolating switch A mechanical tion of the unit power from the unit (generator) to the
switching device used for changing the connections in power system voltage.
a circuit or for isolating a circuit or equipment from
the source of power. It is required to carry normal load
current continuously and abnormal or short-circuit cur-
rents for short intervals as specified. It is also required 7.3 CIRCUIT BREAKERS-THE ORY OF
to open or close circuits either when negligible current ARC INTERRUPTION
is broken or made or when no significant change occurs
in the voltage across the terminals of each of the switch Although very different in appearance and inter-
poles. rupting medium (air, oil, vacuum, sulfur hexa-
load-interrupter switch An interrupter switch de- fluoride [SF6 ]), all circuit breakers depend on the
signed to interrupt currents not in excess of the zero pause and deionization of the current path
continuous-current rating of the switch. It may be to effect current interruption.
designed to close and carry abnormal or short-circuit
currents as specified.
ELECTRIC ARC CHARACTERISTICS-THE ZERO
Motor control center An assembly of motor con- PAUSE
trollers, having modular design to permit rearrange-
ment, interchange, and easy replacement of modular When the circuit breaker opens, the contacts sep-
parts. arate and an electric arc flows between the sepa-
Motor controller A device or group of devices that rated contacts. A useful characteristic of an
serves to govern, in some predetermined manner, the electric arc is that it requires a minimum burn-
electric power delivered to the motor or group of motors ing voltage to be sustained. When the driving volt-
to which it is connected. age goes below the minimum arc voltage, current
Panel board A single panel or a group of panel units flow substantially decreases; and the hot, ionized
designed for assembly in the form of a single panel, gases begin deionizing and dissipating. During the
including buses, with or without switches and/or auto- next fraction of a second, the dielectric strength
matic overcurrent protective devices for the control of of the gap between the separating contacts in-
light, heat, or power circuits. A panel board is designed creases and, if the dielectric strength increases
to be placed in a cabinet or cutout box. It may be placed
faster than the circuit recovery voltage, the cir-
in a control board lineup, open or accessible from the
rear.
cuit has been interrupted. In an ac circuit the
current goes through zero twice each cycle, a
Secondary-unit substation A unit substation in
phenomenon called the current zero pause. The
which the low-voltage section is rated 1000 V and below.
example in Figure 7-1 has an extremely long zero
Station service (startup) transformer The trans- pause. The dotted line portions of current (J) in
former, connected to high-voltage transmission lines,
the zero pause zone represent the normal current
used to feed station auxiliary loads during the station
startup sequence.
Switchgear A general term covering switching and (J)
iliary loads.
(V) = Arc voltage
(Vi! 1 = Reignition voltage
Unit substation A substation consisting primarily of (V8 1 = Burning voltage
one or more transformers that are mechanically and <Vr l = Extinguishing voltage
electrically connected to, and coordinated in design
13196308
with, one or more switchgear or motor control assem- Figure 7-1 AC Arc Current and Voltage Across Arc Plotted
blies or combinations thereof. Versus Time
AUXILIARY ELECTRICAL EQUIPMEN T 7-3
waveshape. Figure 7-2 illustrates two examples of shown in Figure 7-3. Plate 1 is made either
reignition voltage versus time. Variations in con- of a heat-shock -resistant material, such as
tact material and size, radiation losses, and other ceramic, or an organic material, such as
phenomen a account for the difference between fiber. The arc is initiated at the lower end of
two interruptin g devices. All circuit interrupte rs the slot and rises or is pushed to the upper
depend on the zero pause for circuit interruptio n slot portion. As the arc rises in the slot, the
whether the medium is air, oil, SF6 , or vacuum. shape of the slot squeezes or pinches the
The method is always the same, although the arc, converting it into a long, thin, low-
medium and details vary: current arc that is readily extinguish ed dur-
ing the zero pause.
■ Separate contacts, creating an arc
■ Deionized space in the gap during the zero ■ Arc-restraining Metal Barriers If an arc is
pause to restore high dielectric strength transferre d to a series of metal plates
(Figure 7-4), the resultant series of arcs will
require a higher driving voltage to sustain
800 ~ - - - ~ - - - - ~ - - - - - , them. In addition, arc elongation in the in-
::,..
dividual arcs and the cooling effect of the
., 600 metal plates combine to effect arc extinction
2
C7>
at a current zero. This principle alone is
0
>
sufficient at relatively low voltages and
C
400 currents.
0 /
:;:; /,.....
·c
■ Magnetic Blowout Magnetic blowout is any
.,
-~
200
a:: means for magnetica lly elongating and dis-
placing an arc when the contacts separate
(Figure 7-5). Magnetic blowout may be used
100 200 .300 to create high-speed turbulent motion, caus-
Time (µsl ing mixing of the hot arc gases with the sur-
rounding cool air and transferrin g the arc
Figure 7-2 Reignition Voltage for Various Deionizing Times into arc chutes or metal barriers.
AIR-MAGNETIC CIRCUIT BREAKERS All air-magne tic circuit breakers utilize one or
more of these principles. 1ypical air-magnet ic cir-
Air-magnetic circuit breakers all depend on one cuit breakers are shown in Figure 7-6.
or more of the following principles for operation:
Hydrogen 70%
Acetylene 20%
1a, 1b = Main contacts Methane, carbon dioxide, oxygen,
2a, 2b = Horn-shaped arcing contacts
nitrogen 10%
3 = Arc
4o-4d = Arc-restraining metal barrier
The most significant component in the inter-
Figure 7-4 Arc-restraining Metal Barriers Subdividing Long rupting process is hydrogen, which is an excellent
Arcs Into Several Serially Related Short Arcs interrupting medium because it has the property
of deionizing arcs at a rapid rate. When the zero
OIL CIRCUIT BREAKERS pause occurs, the arc energy within the bubble
Developed 90 years ago, the oil circuit breaker is drops to zero. The bubble wall continues to boil
the oldest type of power circuit breaker still in use releasing more saturated vapor and particles of
today. Oil circuit breakers are used only for out- oil into the residue of the arc. This results in a
door applications, having been supplanted by air- rapid increase of the reignition voltage of the arc
magnetic (and other) circuit breakers for indoor path. Thus, at an early current zero, the arc is ex-
applications around 1940. Although not readily tinguished (Figure 7-7a).
available in today's domestic market, oil circuit
breakers are still in service. An understanding of 011 Displacement In an oil circuit breaker, when
their operating principles is useful. the contacts separate and generate the gas bub-
Before discussing breaker structures, the ble, the gas energetically displaces oil, causing the
properties of insulating oil as an interrupting body of oil above the bubble to rise (similar to the
4 4
1= Arc
2 = Magnetic field of ore current
3a, 3b = Poles of electromagnet
4 = Magnetic blowout field
5 = Barriers
5o = Inverted V-shoped slots
reaction from the charge of steam or combustion 'typical Oil Circuit Breakers There are two
in an engine). For this reason, the term oil piston types of oil circuit breakers.
has been used with reference to the displacement
of oil within a breaker tank. The oil-piston effect ■ Plain Break-7ype Breaker The plain break-type
results in circuit breaker reactions: a downward circuit breaker is the earliest design. It is
thrust when the oil piston is accelerated and an characterize d by limited interrupting capabil-
upward thrust when it hits the dome of the tank. ity, high rate of oil carbonizatio n, and high
Circuit breaker reactions may be several times the circuit breaker reaction in larger interrupt-
weight of the breaker and must be accommodated ing ratings.
in the foundation or mounting of an oil circuit
breaker (Figure 7-7b). ■ Arc-enclosing-1ype Circuit Breakers Later de-
signs used arc-enclosing devices to contain
the gas bubble, to increase gas pressure, and
to introduce more turbulence in the gas
bubble. The results were lower arc energy,
less carbonizatio n, faster interruption, and
lower circuit breaker reaction, all of which
permitted greatly increased interrupting
ratings. Low-arc-energy arc-enclosin g circuit
breakers are referred to by their mode of
operation or by trade designations indicating
their manufacture rs, or both. Such terms
are, for instance, Explosion Pot, Deionization
Grid, or Ruptor.
Arc core
Arc envelope
NOTE:
Bubble .>•::
formations
vary according
-r:.-i::;_
to different
i--i-:=-
breaker . /.~)
structures.
./I:/· Zone of superheated
L-- /._:: ;-..·,:·· '
vapor
;./!> ~
Boiling bubble
surface and zone
of saturated vapor
very small spots that move about rapidly, repel- breaker types may range from 4 to 20 A. Switching
ling each other. These small spots have a very high the same unloaded transformers produced over-
current density and emit streams of electrons voltages exceeding 7 per unit. We may conclude that
without liberating much metal vapor. The inter- current chopping in vacuum contactors and circuit
rupter then behaves as a vacuum diode; as cur- breakers is not a serious problem when they con-
rent decreases, the electron flow falls to zero, and tain modern suitable contact materials. There are,
electrons cease to cross the gap. The inverse volt- however, some application areas that require atten-
age strength rapidly increases to a high value as tion when using vacuum equipment (1 ).
the cool anode is not able to emit electrons, and
the circuit is interrupted. Vlrtual Current Chopping A reignition in one
phase of a three-phase system may induce a high-
Arc lnstablllty An interesting problem with frequency transient in the other two phases, which
vacuum interrupters results from arc instability. may cause the total current in the two phases to pass
The diffuse arc is unstable because each spot through zero. It is possible that the current in all
requires a minimum intensity to emit electrons; three phases will interrupt simultaneously.
below this value it abruptly ceases to operate. This
explains the well-known propensity of vacuum Reignition After current interruption, if the
equipment to produce overvoltages by current transient recovery voltage rises faster than the
chopping. The problem can be eased principally vacuum interrupter dielectric strength, multiple
by the manufacturer's selection of contact mate- ignition will occur. All vacuum interrupters are
rial. Tost results have shown current chopping in susceptible to multiple reignition irrespective of
vacuum contactors to range from 0.5 to 5 A and the chopping current level. The following condi-
vacuum circuit breakers from 2 to 10 A, depend- tions are vulnerable to multiple reignition:
ing on contact material. Switching unloaded trans-
formers with vacuum circuit breakers produced ■ A motor with locked-rotor current of 500 A
overvoltages 13196308
at 2 to 3.1 per unit. Chopping cur- or less switched off during locked-rotor con-
rent for minimum oil, SF6, and air-blast circuit ditions. Motor starting current (locked-rotor
AUXILIARY ELECTRICAL EQUIPMENT 7-7
rated speed.
Where:
■ Vacuum interrupter contacts separate at a
time less than 0.5 ms from natural sinusoidal
current zero. This condition may occur 18%
L = ungrounded motor inductance at locked-rotor
condition
of the time on a three-phase system.
f = supply frequency
■ The natural frequency of the transient
recovery voltage on the load side of the in- I locked-rotor current
terrupter is between 0.5 and 5.0 kHz. C capacitance of cable
£ cable length
Cv capacitance per unit length of cable
fn natural frequency of the load
Insulating
shell
Throat
1000
900
500 800
700
-+-Ha
-◊-#6
400 -■-#4
.., ..,
:!:: :!:: 600 -c- #2
..,
~ :5en -•- #1
en C -A- 1/Q
C 300 500
..!? ..!?
Q)
-x- 2/0
Q)
:0 :0 -o- 3/0
0 0
0 0 400 --- 4/0
200 E
E
:, :,
Coble
E E size
·x ·x0 300
0 0
::::E
100 • ::::E
200
~1/
100 '-=-_....__... ..__ _.___ __.__ ___.~___.
o~-~ -~---400
-~-~
500 600 50 100 150 200 250 300 350
100 200 300
Motor horsepower Motor horsepower
o. Maximum length of shielded coble, 4160 V b. Maximum length of shielded coble, 2300 V
2500
; 2000
I
:5en
C
..!?
.,
1500 , I -+-2300 V
V
:0
0 / .-,,,,-· -◊-4160
0 1000
.,
◊.,,. Nonshielded
E
:,
E
·x 500
.J
I
► ' .,,.- -· .,,.~
coble
' ◊/
0
::::E
0
0 100 200 300 400 500 600
Motor horsepower
c. Maximum length of nonshielded coble, 2300 end 4160 V, ell coble sizes
extinction properties of the gas. Studies show that gage gas pressure. With special attention given to
transient voltage levels due to current chopping are the types of interrupte r envelopes and seals, some
lower in magnitude than other modern interrupting SF6 interrupte rs are sealed for life and require little
mediums. Multiple reignitions, with resulting tran- or no maintenan ce throughou t their service life.
sient overvoltages, are nonexisten t with medium- When an SF6 circuit breaker is operated and the
voltage SF6 interrupte rs. The pressure of the gas contacts part, the usual arc is produced. Thermal
may be continuou sly monitored, and the breaker conductivi ty of SF 6 is very high, even at elevated
may be controlled as a function of the condition of temperatu res. Thus, when the current is decreas-
the interrupte r. Some SF 6 interrupte rs can provide
13196308 ing, the arc temperatu re drops quickly. Below about
significant interruptio n performan ce even at zero- 2100°K, the SF 6 molecules recombine , and
AUXILIARY ELECTRICAL EQUIPMENT 7-9
AVAILABLE EQUIPME NT
a. SF 6 puffer-typ e pole unit
(cutaway view) Medium-voltage switchgear, nominally rated be-
tween 2.5 and 38 kV, is currently available using
vacuum, air-magnetic, and SF6 circuit breakers.
The majority of power plant application s are at
4.16, 7.2, or 13.8 kV, using vacuum or air-magnetic
circuit breakers.
Switchgear is constructe d in conforman ce with
American National Standards Institute (ANSI) Stan-
dard C37.20-1969/IEEE Standard 27-1974 (2) .
Medium-voltage switchgear, built as metal-clad,
has the following attributes:
■ Instruments, meters, relays, secondary con- especially those with instantaneous contact ele-
trol devices, and their wiring are isolated by ments and some solid-state relays with elec-
grounded metal barriers from all primary tromechanical components, are susceptible to
circuit elements with the exception of short varying degrees.
lengths of wire as at instrument transformer
terminals.
MEDIUM-VOLTAGE SWITCHGEAR
■ The door through which the circuit inter- COMPONENTS
rupting device is inserted into the housing
Major parts of medium-voltage switchgear are:
may serve as an instrument or relay panel
and may also provide access to a secondary
■ Secondary Enclosure Located at the front of
or control compartment within the housing.
the unit, this component has a hinged panel
with necessary instruments control and pro-
Removable circuit breaker elements are either
tective devices mounted on it. Terminal
horiwntal draw-out or vertical-lift design. Both are
blocks and some protective devices are
self-aligning and self-coupling. The vertical-lift de-
mounted within the compartment.
sign is older and was originally designed to directly
replace vertical-lift indoor oil circuit breakers. ■ Primary Enclosure The primary enclosure
The principal advantage of vertical-lift equip- contains high-voltage equipment. It consists
ment is that primary contact separation is clearly of the circuit breaker compartment, bus
visible in the test and disconnected positions. compartment, cable termination compart-
Horizontal draw-out equipment may be easily in- ment, and auxiliary compartments for volt-
stalled manually as the heavy circuit breaker need age (and control power) transformers. Each
not be lifted. Both designs are considered equally compartment is separated from the others
acceptable. by metal barriers.
A common problem is susceptibility of relays to Interference interlocks are mounted in the
mechanical shock when mounted on compartment circuit breaker compartment to permit only
doors. Opening and closing the door may produce insertion of a circuit breaker with the correct
sufficient mechanical shock to cause spurious voltage, current, and interrupting ratings.
operation of relays. All electromechanical relays,
Figure 7-13
13196308 Example of Air-Blast Circuit Breaker psolating section open)
7-12 POWER PLANT ELECTRICAL REFERENCE SERIES
■ Circuit Breaker Removable Element This ■ Voltage (PotentiaV 'Iransformers Voltage trans-
removable circuit breaker, air-magnetic or formers are used to permit reasonable insu-
vacuum type, has a stored energy spring lation levels in instrument circuits. They are
operating mechanism, interlocks, primary used for wattmeters and voltmeters and for
and secondary (most vendors) disconnecting ground fault detection.
devices, antipump relays, and a limited num-
■ Primary Bus Conductors The devices connect
ber of auxiliary switches (see Volume 10 for
all units in the switchgear lineup. Primary
details). The assembly is equipped with
bus conductors and connections are covered
wheels for easy movement along the floor.
with insulating material throughout.
■ Aul(iliary Switches Optional circuit breaker
■ Automatic Shutters Automatic shutters cover
and stationary auxiliary switches are avail-
primary circuit connections when the circuit
able for interlocking and control purposes.
breaker removable element is in the discon-
Auxiliary switches are 'fypes a and b (see
nected, test, and removed positions.
Volume 10 for details): 'fype a open when the
circuit breaker is open, and 'fype b closed ■ Ground and 'Jest Device This device is an op-
when the circuit breaker is open. tional draw-out element that may be inserted
into a metal-clad switchgear housing in place
MechanlsnH>perated Control (MOq Auxlllary of a circuit breaker. It provides access to the
Switches MOC switches are operated directly primary circuits to permit temporary connec-
from the breaker mechanism and are available in tions of grounds or testing equipment to the
the following types: HV circuits. It may be manual, with six bush-
ings for connection to primary circuits, or
■ Operate with the circuit breaker in both may include a three-pole, two-position selector
connected and test positions switch and stored-energy grounding switch.
■ Operate with the circuit breaker in the con-
nected position only SWITCHGEAR RATINGS
■ Operate with the circuit breaker in the con-
Medium-voltage switchgear is rated in selected
nected position, but operate with the circuit
continuous current steps from 1200 through
breaker in the test position if manually
3000 A, with short-circuit current ratings from 12
selected
to 48 kA, as shown in ANSI Standard C37.06-1979
(3). Note that manufacturers do not necessarily
A limited number of auxiliary switches are
offer all ratings listed in the ANSI standard, and
mounted on the circuit breaker removable ele-
most manufacturers also have nonstandard circuit
ment, and a larger number (as required) are
breaker ratings, usually with higher close-and-
mounted in the secondary enclosure and linked
latch capability in selected ratings. Tobie 2 of ANSI
mechanically to the circuit breaker. Auxiliary
Standard C37.06-1979 lists standard indoor oilless
switches mounted either on the circuit breaker
circuit breaker ratings for switchgear.
removable element or in the secondary enclosure
Salient parts of switchgear circuit breaker
may be any of the above types, arranged by either
ratings are (4):
the mechanical linkage or sliding contacts on the
secondary coupling.
■ Rated Ma1~imum Voltage The rated maximum
voltage of a circuit breaker is the highest
Truck-operated Contact (TOCJ Auxlllary
root-mean-square (rms) voltage, above nomi-
Switches roe auxiliary switches are mounted
nal system voltage, for which the circuit
in the circuit breaker compartment and operate
breaker is designed and is the upper limit
when the circuit breaker is moved to the operat-
for operation.
ing position. roe switches may be used for inter-
locking and remote positi'll indication. ■ Rated Voltage Range Factor, K The rated volt-
age range factor K is the ratio of rated maxi-
■ Current 1hmsformers Current transformers mum voltage to the lower limit of the range
are used to protect personnel and secondary of operating voltage in which the required
devices from high voltage and to reflect pri- symmetrical and asymmetrical interrupting
mary current flow in relays, instruments,
13196308
capabilities vary in inverse proportion to
and meters (see Volume 8). operating voltage.
AUXILIARY ELECTRICAL EQUIPMEN T 7-13
■ Rated Frequency The rated frequency of a maximum crest, does not exceed 1.6 K times rated
circuit breaker is the frequency at which it short-circu it current; the maximum crest value of
is designed to operate. Other frequencie s which does not exceed 2. 7 times rated short-circu it
usually require special considerat ion. current; and therms value mof which over the 3-s
■ Rated Continuous Current The rated continuous period does not exceed K times short-circuit current.
current of a circuit breaker is the designated
limit of current in rms amperes at rated fre- Symmetri cal Versus Total Current Basis of Rat-
quency that it will carry continuou sly without ings of Circuit Breakers The original unified
exceeding designated temperatu re limitations. series of standards for circuit breakers based on
■ Rated Standard Operating Duty (standard those of American Institute of Electrical Engineers
duty cycle) The standard operating duty of a (AIEE) and National Electrical Manufactu rers
circuit breaker is two-unit close-open (CO) Association (NEMA) and data from the Association
operations with a 15-s interval between of Edison Illuminating Companies and NEMA were
·operation s (CO-15s-CO). developed from 1941 through 1953 and pub-
lished in the following documents : ANSI Standard
■ Rated Interrupting Time The rated interrupt- C37.4-1953 (5), ANSI Standard C37.5-1953 (6), ANSI
ing time of a circuit breaker is the maximum Standard C37.6-195 3 (7), ANSI Standard
permissibl e interval between energizing the C37.7-1952 (8), ANSI Stanpard C37.8-1952 (9), ANSI
trip circuit at rated control voltage and in- Standard C37.9-1953 (10), and ANSI Standard
terrupting the main circuit on all poles C37.12-1981 (11).
when interruptin g a current equal to 25% In these original standards the basis of the in-
or more of the required asymmetri cal inter- terrupting rating was established as the highest
rupting capability at rated maximum voltage. current to be interrupte d at the specific operat-
■ Rated Permissible Tripping Delay, Y The rated ing voltage. It was the rms value, including the de
permissibl e tripping delay of a circuit componen t at the instant of contact separation ,
breaker is Y and is the maximum time that as determine d from the envelope of the current
the circuit breaker is required to carry K wave. Since this method of rating was based on
times rated short-circu it current after closing total current, including the de componen t, it be-
on this current and before interruptin g. came known as the total current basis of rating.
Commencing in 1951, the AIEE Switchgear Com-
■ Permissible Tripping Delay, T Tripping the cir- mittee began developing a method of rating based
cuit breaker may be delayed. The rated per- on symmetric al interruptin g current. The goals
missible tripping delay Y at lower values of were to simplify application that used high-speed
current is in accordanc e with the following relaying and fast-clearing circuit breakers and to
formula: bring American standards into closer agreemen t
with accepted internation al standards.
T = y K (rated short-circuit current) 12 (Eq. 7 .4 ) The principal change from the total current
short-circuit current standard was the basis of rating. The rated short-
through circuit breaker
circuit current was established as "the highest
■ Rated Short-Circuit Current The rated short- value of the symmetric al componen t of the short-
circuit current of a circuit breaker is the circuit current in rms amperes;' measured from
highest value of the symmetric al componen t of the envelope of the current wave at contact sepa-
the polyphase or phase-to-p hase short-circu it ration, which the circuit breaker is required to in-
current in rms amperes. It is measured from terrupt at rated maximum voltage. This rating
the envelope of the current wave at the instant structure became known as the symmetric al cur-
of primary arcing contact separation , which rent basis of rating.
the circuit breaker is required to interrupt at The symmetric al current basis of rating group
rated maximum voltage. of standards was published in 1964 and consoli-
dated with intervenin g supplemen tary standards
■ Rated Short-time Current-carrying Capabil- in 1979 in the following documents : ANSI/Institute
ity The circuit breaker is capable of carrying, of Electrical and Electronics Engineers (IEEE) Stan-
for 'Th = 3 s, any short-circu it current the dard C37.04-1979 (4), ANSI Standard C37.06-1979
rms value of which, determine d from the
13196308 (3), ANSI/IEEE Standard C37.09-1979 (12), ANSI/
envelope of the current wave at the time of IEEE Standard C37.010-1979/IEEE Standard
7-14 POWER PLANT ELECTRICAL REFERENCE SERIES
APPLICATIONS AND RELATED REQUIREMENTS Equipment may be selected based on load re-
quirements and available short-circuit currents.
Medium-voltage switchgear is used to feed loads Circuit breakers may be used for motor starting,
throughout the plant, usually secondary unit sub- applied on motors with full-load current up to the
stations and large motors that are not cycled fre- circuit breaker continuous current rating. Because
quently. Medium-voltage switchgear is available, power systems continue to grow, even after the
as applicable, from 2.4 through 38 kV. Historically, equipment is purchased and installed, it is advis-
the trend has been to use higher-voltage systems. able to be on the conservative side in ampacity and
Currently power plant electrical systems use 4.16-, short-circuit ratings. Methods of calculating short
7.2-, and 13.8-kV class medium-voltage switchgear.
13196308 circuits and applying circuit breakers are delineated
(See Volume 3, System Planning.) in ANSI Standard C37.010-1979/IEEE Standard
AUXILIARY ELECTRICAL EQUIPMENT 7-15
320-1979. Volume 3 also discusses sizing medium- inductance and capacitance. ANSI/IEEE Standard
voltage circuit breakers. C37.011-1979 (14) presents more discussion and
Most electrical equipment, such as motors, calculation procedures.
buses, and transformers, may be temporarily over-
loaded, and there may be some resultant accept- Capacitive Current Switching Breakers used
able reduction in useful life. Circuit-breaker for capacitive current switching require careful
continuous-load current may be increased based consideration. For single-shunt bank or back-to-
on low ambient temperature or increased from back switching, it will usually be conservative to
a low-current load for an allowable time based on use 1.25 times the nominal capacitor current at
maintaining the same hot-spot temperature, which rated capacitor voltage for ungrounded neutral
does not constitute an overload condition. operation, or i.35 times the nominal current for
Circuit breakers may also carry load currents grounded neutral operation, for calculating re-
higher than permitted by ambient compensation quired breaker ampacity. Note that not all circuit
for emergency load periods, which may cause a breakers have back-to-back switching capability.
reduction in operating life of the equipment. ANSI Only circuit breakers specifically manufactured
Standard C37.010-1979/IEEE Standard 320-1979 for back-to-back switching are so rated (3).
(13) and Supplement b (16) give overload and Complex capacitor switching requires fur-
emergency-load-carr ying capability. ther analysis. Refer to ANSI/IEEE Standard
Exceeding interrupting ratings and related capa- C37.012-1979 (15) and the vendor for calculation
bilities (without the manufacturer's consent) may methods and recommendations.
result in circuit breaker failure to interrupt, prob-
ably catastrophically. Repetitive Duty Circuit breakers should not be
If the interrupting ratings and related capabili- used for repetitive duty, such as motor starting.
ties of a circuit breaker are exceeded, for exam- If the circuit breaker is cycled more than once a
ple, because of substitution of a lower impedance day, it may be worn out or will require major
transformer or changes in the system, the follow- maintenance every two or three years. Circuit
ing changes must be made to correct the situation: breakers are usually not designed for highly
repetitive duty. Repetitive duty such as motor
■ Change the system to reduce available short- starting is better served by using medium-voltage
circuit current; divide the system into motor starters.
smaller units (see Volume 3).
■ Add lumped impedance (reactors) to reduce
short-circuit current.
■ Replace circuit breaker(s) with higher inter- 7.5 SECONDARY UNIT SUBSTATIONS
rupting rated circuit breakers.
Secondary unit substations have a medium-voltage
Transient Recovery Voltage 1ransient recovery to low-voltage transformer, and a lineup of low-
voltage is the voltage that initially appears across voltage switchgear mechanically and electrically
the open poles of a circuit breaker immediately coupled. A double-ended substation has two unit
after the arc is extinguished. Following current substations with a tie circuit breaker between the
zero, the voltages on both sides of the circuit two low-voltage switchgear sections. Secondary
breaker recover to their driving source voltages. unit substations are fed from medium-voltage
The circuit breaker is stressed by the voltage switchgear at 2.4 to 13.8 kV. When two unit sub-
cfrfference between both voltages. For successful stations are fed from the same circuit breaker, a
interruption, the breakdown voltage of the circuit load break switch is frequently used as an isolat-
breaker must always exceed the recovery voltage. ing means. The transformer is usually a three-
1ransient recovery voltage requirements for phase unit, transforming the 5- to 15-kV primary
medium-voltage switchgear are not currently (1985) voltage to distribution voltage levels, which may
defined in the standards, but the IEEE Switchgear be 120 through 600 V. The most commonly used
Committee will incorporate them in the near fu- distribution voltage is 480 V. The low-voltage
ture. There have been suspected cases of transient switchgear section feeds motor control centers
recovery voltage failures of 15-kV class switchgear and other large unit loads and motors of perhaps
(17); however, transient recovery voltage problems 100 to 200 hp, which are not frequently cycled.
are usually associated with transmission line
13196308 Low-voltage switchgear used today is invariably
switching-systems with considerable distributed comprised of air-magnetic circuit breakers.
7-16 POWER PLANT ELECTRICAL REFERENCE SERIES
INCOMING LINE SECTION transformers are restricted due to fire code re-
quirements. Indoor application requires installa-
When one secondary unit substation is fed from tion in a vault, an expensive and inconvenient
a medium-voltage circuit breaker, the incoming structure.
line is usually connected directly to the medium-
voltage to low-voltage transformer. When two or ■ Less-Flammable Liquid Transformers Until
three secondary unit substations are fed from one recently, this category of transformer was
medium-voltage circuit breaker, the incoming line filled with askarels, synthetic halogenated
is usually connected to an unfused air load- hydrocarbons containing polychlorinated
interrupter switch. The air-interrupter switch pro- biphenyls (PCBs) as coolants. PCBs are no
vides an isolating means so that one secondary longer acceptable because they are not 100%
unit substation may be deenergized without biodegradable. Currently, less-flammable
deenergizing others connected in parallel. liquid transformers are filled with polydi-
The load-interrupter switch has a quick-make, methylsiloxane (also called dimethyl silicone
quick-break spring operating mechanism and or silicone fluid) or processed hydrocarbons.
switch element capable of making and latching Less-flammable liquids are defined as
fault current and breaking full-load current. Load- having a fire point not less than 300°C. In-
interrupter switches are available in ratings of 600 stallation requires liquid containment in a
and 1200 A, 2.4 through 38 kV, with momentary noncombustible building, liquid containment
ratings up to 80 kA, and fault closing ratings up and an automatic fire extinguishing system,
to 61 kA. or a vault in a combustible building. Insur-
Disconnecting switches will also be found with- ance companies may require additional pro-
out arc-interrupting devices, capable of inter- tection in a combustible building.
rupting only negligible current. They must be
interlocked with the main circuit breaker in the ■ Nonflammable Liquid 'Iransformers A non-
low-voltage switchgear section of the secondary flammable transformer is defined as having
unit substation, so that the disconnect switch will no flash point, no fire point, and being non-
be required only to interrupt magnetizing current flammable in air. When rated 35 kV and
to the secondary unit substation transformer. lower, such transformers may be installed in-
When purchasing new equipment, a user should doors without restrictions.
give preference to a load interrupter switch rather 1\vo fluids are currently in use in the non-
than a disconnect (magnetizing current) switch to flammable category:
eliminate interlocking requirements. Indeed, the □ Perchloroethylene (Cl2 :CCl2 ), also known as
cost of interlocks will probably exceed any savings ethylene tetrachloride, tetrachloroethylene,
that result from omission of arc interrupting Perclene, Perk, and Wecosol. Perchloroethy-
devices. lene is a colorless liquid with an etherlike
odor. It is an excellent solvent and is widely
TRANSFORMERS used in the dry-cleaning and metal-
degreasing businesses. It is a relatively safe
A secondary unit substation transformer is typi- fluid to use and has a long history of safe
cally rated between 225 and 3000 kVA, three- use in the dry-cleaning and chemical in-
phase, 2.4 to 13.8 kV primary to 208 to 600 V dustries. It is, however, moderately toxic
secondary. Volumes 2 and 3 discuss transformers and requires proper handling for complete
in more detail. There are seven kinds of transform- safety.
ers in three categories in use, although some are Perchloroethylene is moderately toxic by
used infrequently: ingestion, with a probable lethal dose be-
tween 1 oz and 1 pt for a 150-lb man
■ Oil-immersed 'Iransformers The oldest and (500 mg/kg body weight).
least expensive design transformers use Overexposure to perchloroethylene vapors
mineral oil and paper insulation in a sealed will result in headaches, confusion, nausea,
tank. They are entirely satisfactory for out- and lack of coordination. Extreme over-
door installations and chemically active en- exposure could result in severe personal
vironments. Indoor applications of oil-filled injury or death. Adequate ventilation must
13196308
AUXILIARY ELECTRICAL EQUIPMENT 7-17
■ Sealed Dry-Type 'Iransformers This type of Table 7.1 Comparative Cost of Transformers
transformer has a dry-type core and coil as-
Transformer Type Percent
sembly in a sealed tank, filled with a non-
flammable gas. The gas is commonly Oil-filled 100
hexafluoroethane (F 3 CCF3 , also called Freon Silicone-liquid-filled 130
116, perfluoroethane, and carbon hexafluo- Nonflammable liquid-filled 140
ride) or nitrogen (N 2 ). These gases are be- Ventilated dry-type
nign compared with most chemicals, but 150oC 60-kV BIL 125
15QOC 95-kV BIL 140
precautions should be taken in event of a aooc 60-kV BIL 135
large gas spill. Hexafluoroethane has the aooc 95-kV BIL 150
same characteristics as other fluorocarbons Totally enclosed nonventilated dry-type 160
as noted under trichlorotrifluoroethane, and Cast-coil dry-type 190
nitrogen is, of course, a simple asphyxiant.
Sealed dry-type 250
Because the transformer assembly is iso-
lated from the external environment, sealed
dry-type transformers may be applied in all
environments. Because the gas meets the Selecting the lowest cost transformer option in-
definitions of a nonflammable fluid, trans- volves three categories:
formers can be applied without restrictions.
Sealed dry-type transformers may be used ■ Acquisition cost
advantageously in areas that require explo- ■ Installation cost
sion-proof equipment. ■ Present value of annual costs
■ Cast-Coil and Encapsulated-Coil Transformers Selecting the lowest-cost transformer can be done
Cast-coil and encapsulated dry-type trans- by calculating installation cost plus present value
formers have their coils cast or encapsulated of the annual cost:
in epoxy or polyester resins. They are imper-
vious to moisture and most chemical environ-
1. Calculate total losses at the expected load
ments. Cast-coil and encapsulated-coil trans-
(LEL).
formers are considered nonflammable and
are recommended for indoor and outdoor
(Eq. 7-6)
installations for all but extreme environ-
ments. Extreme environments would be ex-
Where:
cessive dust or dirt that could clog cooling
ducts, corrosive contaminants that could at-
LEL total transformer losses at the expected
tack exposed conductors, and conducting load
contaminants that could promote tracking
failures. Le core losses, vendor data, remains con-
stant at all loads (no load loss)
Transformers 501 kVA and larger may be fur- L-r total winding losses at full load, vendor
nished with forced-cooling fans, giving additional data
forced-cooled capacity of 15 or 25% for oil-filled F fraction of 100% load expected on the
and silicone-liquid-filled units, 33% for ventilated transformer
dry types, and 50% for cast-coil and trichlorotri-
fluoroethane-filled vapor-cooled units. 2. Calculate annual operating cost (C0 ).
Tobie 7-1 presents the approximate cost of trans-
formers relative to the lowest-cost oil-filled unit. C0 = LEL x H x D x CE + annual insurance
Choosing the optimum transformer type is not
+ maintenance (Eq. 7-7)
a simple problem. The installed cost of the lowest•
cost oil-filled unit can easily exceed more expensive
types when vaults, fire protection, and liquid- Where:
containment costs are added. Environmental con-
C0 total annual operating cost
straints, such as a corrosive atmosphere or high
humidity, may 13196308
rule out ventilated dry types and LEL total transformer losses at expected
perhaps even cast-coil transformers. load
AUXILIARY ELECTRICAL EQUIPMENT 7-19
■ Shunt Trip A shunt trip provides for remote Low-voltage circuit breakers may be furnished
electrical tripping of a circuit breaker. It with series-current limiting fuses to extend short-
may be controlled by a switch, push button, circuit interrupting ratings to 200,000 A
or protective relays. symmetrical.
Representative examples of low-voltage switch-
■ Undervoltage Trip Optional undervoltage trip gear are shown in Figure 7-14.
protects against severe undervoltage by auto-
matically tripping the circuit breaker. An
undervoltage trip device picks up at approxi- LOW-VOLTAGE SWITCHGEAR RATINGS
mately 85% of bus voltage and trips the cir-
cuit breaker between 30 and 60% of bus Low-voltage s~itchgear is rated from 225 through
voltage. An optional time delay to trip is 4000 A, 14,000 through 200,000 rms symmetrical
available to eliminate nuisance tripping dur- ampere interrupting rating in conformance with
ing transients. ANSI Standard C37.16-1980 (22). The 200-kA ratings
are attainable only with current-limiting fuses.
• Key Interlocks Circuit breakers have a provi- Note that manufacturers do not necessarily offer
sion for a key interlock that may be required all ratings listed in the ANSI standards, and some
to ensure correct sequence of operations.
manufacturers have some nonstandard circuit
■ Auxiliary Switches Optional circuit breaker breaker ratings, usually with higher ampacity and
auxiliary switches are available for interlock- interrupting ratings. However, the 225-A frame
ing and control purposes. Auxiliary switches size is not currently in production, and the 600-A
are 'Types a and b: open when the breaker is frame size is becoming obsolete. ANSI Standard
open, and closed when the breaker is open, C37.16-1980 lists low-voltage switchgear ratings.
respectively. Salient parts of the switchgear ratings (23) are:
■ Voltage Transformers Voltage transformers are ■ Rated Maximum Voltage The rated maximum
used to permit reasonable insulation levels in voltage of a circuit breaker is the highest
instrument circuits. They are used for watt- rms voltage, three phase or single phase, at
meters, voltmeters, and ground fault detection. which it is designed to perform. Rated maxi-
■ Operations Counter An operations counter is mum voltages are 635, 508, and 254 V. For
optional on low-voltage breakers. fused circuit breakers, the 635-V rating be-
comes 600 V to match the fuse rating.
■ Bell Alarm With Lockout An optional bell
■ Rated Frequency Rated frequency is the fre-
alarm switch operates a and b contacts. It
operates when the circuit breaker is tripped quency at which the circuit breaker is de-
automatically (any means other than manual signed to operate. Rated frequency is 60 Hz.
trip button or shunt trip). The contacts may ■ Rated Continuous Current The rated continu-
be used for remote alarm of an automatic ous current of a circuit breaker is the rms
trip. The lockout feature mechanically locks current at rated frequency that it will carry
the circuit breaker open upon automatic without exceeding designated temperature
tripping and must be manually reset. limitations. The rated continuous current of
a circuit breaker equipped with direct-acting
■ Electric Lockout An optional electric lockout
trip devices or fuses with a rating lower
device electrically interlocks breakers so that
than the frame size is limited to the rating
two cannot be closed at the same time.
of those devices.
■ Remote Close Solenoid for Manually Operated
■ Rated Short-Time Current For an unfused cir-
Breaker This option provides a means to
cuit breaker, the rated short-time current is
electrically close a manual circuit breaker
the current at which it is required to per-
from a remote location. The circuit breaker
form its short-time current duty cycle (two
must be charged manually.
periods of ½-s current flow, separated by a
■ Solid-State Trip Device Thst Set A portable in- 15-s interval of zero current) at rated maxi-
strument for field-checking all solid-state trip mum voltage under prescribed test condi-
device functions and calibration. tions. This current is the rms symmetrical
13196308
AUXILIARY ELECTRICAL EQUIPMENT 7-21
□.
-0 -
~ ~
-
_,
/
/
I".
--,V
b . L o w-vo ltage ci rcu it breaker (rear vi ew )
13196308
7-22 POWER PLANT ELECTRICAL REFERENCE SERIES
value measured at one-half cycle after short- IEEE Standard 141-1976 (24), IEEE Standard
circuit initiation. Fused circuit breakers do 241-1983 (25), IEEE Standard 242-1975 (26), and
not have a rated short-time current because Volume 3.
the fuses will blow. Only the circuit breaker Note that all circuit breakers, whether used as
element of a fused circuit breaker assembly main, feeder, or tie circuit breakers, must meet
has a rating as described above. the same short-circuit current requirements. Ap-
■ Rated Short-Circuit Current The rated short- plication of switchgear circuit breakers above their
circuit current uses either unfused circuit short-circuit current ratings in cascade is not
breakers or fused circuit breakers. recommended.
□ Unfused Circuit Breakers The rated short-
circuit current of an unfused circuit
APPLICATIONS AND RELATED REQUIREMENTS
breaker is the current at which it performs
its short-circuit current duty cycle at rated Low-voltage switchgear is used to feed loads
maximum voltage under prescribed test grouped near the secondary unit substation. The
conditions. This current is the rms symmet- loads are low-voltage motor control centers (per-
rical value measured one-half cycle after haps two per feeder circuit breaker), and low-
short-circuit initiation. voltage motors rated perhaps 100 hp or larger. Cir-
□ Fused Circuit Breakers The rated short- cuit breakers may be selected based on full-load
circuit current of a fused circuit breaker is ampacity of the connected loads. Motor starting
the current at which it performs its short- current may be disregarded as the rating structure
circuit current duty cycle under recognizes this use, and the circuit breakers will
prescribed test conditions. The short- withstand motor starting current without harm.
circuit duty cycle consists of an O (open) As indicated earlier, circuit breakers should not
followed by a CO (close-open) operation. be used for repetitive duty (for example, motor
The time between O and CO operations is starting), because they may wear out or require
that time necessary to replace fuses and excessive maintenance in two or three years. Motor
reset the open-fuse trip device. This cur- starters and contactors are more suitable for
rent is the rms symmetrical value meas- repetitive operations.
ured one-half cycle after short-circuit ANSI/IEEE Standard C37.16-1980 (22) gives circuit
initiation. breaker ratings in horsepower for motor starting.
■ Rated Control Voltage The rated control volt-
age is the voltage at which the mechanism
of the circuit breaker is designed to operate
when measured at the power terminals of Example 2 How to Select Circuit Breakers
the operating mechanism with highest cur-
rent flowing. Rated control voltages and volt- A secondary unit substation with a 1000-kVA, 13.8-
age ranges are listed in ANSI Standard to 480-V transformer provides a short-circuit cur-
C37.16-1980 (21). rent capability of 25,000 A, including motor con-
tributions at the switchgear low-voltage bus. How
Circuit breakers are selected to have interrupting do we select circuit breakers?
ratings greater than the short-circuit current avail-
able at the switchgear bus. In determining suit- ■ Main Circuit Breaker Full-load current is
ability for system conditions, consideration should 1203-A self-cooled or 1603-A fan-cooled. A
be given to: 2000-A circuit breaker with interrupting
rating above 25 kA will be acceptable.
■ Source contribution
■ Circuit Breaker Size Required to Control a
■ Motor contribution
■ System power factor 200-hp Induction Motor The motor full-load
■ 'fype of operating mechanism current is 240 A. Any breaker with full-load
■ Duty cycle ratings equal to or greater than 240 A and
■ 'fype of trip devices 25,000 A short-circuit current is acceptable.
The lowest available current rating is 800 A,
Guidance in calculating providing a generous margin.
13196308 short-circuit currents is
given in ANSI/IEEE Standard C37.16-1980 (22),
AUXILIARY ELECTRICAL EQUIPMENT 7-23
■ Class I, Type A
7.6 MOTOR CONTROL c No terminal boards for load or control
connections.
LOW-VOLTAGE MOTOR CONTROL □ Connection diagrams only for each combi-
nation controller or control assembly.
Low-voltage motor control equipment in generating
::i Sketches of the overall dimensions of the
station auxiliary systems is usually a motor control
center wherein motor starters are combined in control centers.
plug-in units in vertical assemblies. Standard sizes ■ Class I, Type B
and types are defined in NEMA Industrial Controls u Unit control terminal boards are provided.
and Systems series standards: NEMA Standard ICS Load terminal boards are provided for
1-1983 (27), NEMA Standard ICS 2-1983 (28), NEMA combination starters size 3 or smaller. Ter-
Standard ICS 4-1983 (29), and NEMA Standard
minal boards are mounted on or adjacent
ICS 6-1983 (30). to each unit. No load terminal boards are
A combination motor controller unit includes an provided for feeder trip units.
externally operable circuit disconnecting means,
c Connection diagrams only for each combi-
circuit overcurrent protection, and a magnetic mo-
nation controller or control assembly.
tor controller with associated auxiliary devices
::i Sketches of the overall dimensions of the
when required (NEMA Standard ICS 2-1983,
Sect. 322.02 (28)). control centers. ·
A control power transformer may be furnished ■ Class I, Type C
to operate at 120 V for control circuits, rather than
□ Master section terminal boards, including
the supply voltage that may be 480 or 600 V. This
load terminals for combination controllers
practice eliminates the safety hazard of having
size 3 or smaller, and all control terminals
high voltages, perhaps 480 or 600 V, in control cir-
for all combination controllers or control
cuits of control boards.
assemblies in each vertical section are
Feeder tap units include an externally operable
mounted on the stationary structure. Also,
means for circuit disconnection and branch-circuit
complete wiring is provided between com-
overcurrent protection, principally used for non-
bination controllers or control assemblies
motor loads.
and their master terminal boards. No load
Motor control centers are defined in terms of
terminal boards are provided for feeder
class and type in NEMA Standard ICS 2-1983,
tap units.
Sect. 322 as follows:
□ No wiring between sections or between
■ Class I Class I motor control centers consist any master terminals.
of a mechanical grouping of combination o No interconnecting between any combina-
motor control, feeder tap assemblies, and tion controllers or control assemblies. All
other units arranged in a convenient assem- outgoing wires from any unit will be car-
bly. They include connections from the com- ried to the master terminal board, except
mon horizontal power bus. They do not wiring for combination controllers size 4
include interwiring or interlocking between or larger.
units or to remote devices and do not include CJ Connection diagram for each combination
system engineering. controller or control assembly.
■ Class II Class II motor control centers consist c Sketch of main terminal boards showing
of a grouping of combination motor control, general location of terminals.
feeder tap assemblies, and other units D Sketches of the overall dimensions of the
designed to form a complete control system. control centers.
They include electrical interlocking and inter-
wiring between units and to remote devices, ■ Class II, Type B
including connection to the common power o Unit control board provided. Unit load ter-
bus. minal blocks provided for combination con-
trollers size 3 or smaller. Terminal boards
Class and 1ype of Motor Control Center Motor are mounted on or adjacent to each unit.
control centers are manufactured to the following No load terminal boards are provided for
classes and types13196308
with the following features: feeder tap units.
7-24 POWER PLANT ELECTRICAL REFERENCE SERIES
13196308
7-26 POWER PLANT ELECTRICAL REFERENCE SERIES
600
unsolved and causes unnecessary motor
deterioration. Another danger is the possi-
-.,...
C
500
\
bility of an overload relay being set to auto-
matically reset itself on a two-wire control
...
::,
0
400
\ scheme where personnel injury could result
"O
0 '\ Motor heating curve from a motor suddenly starting without
~ warning. The automatic reset feature does
--
::, 300
\
" ""' "-
-..... r-- .___
have its place, however, protecting a motor
that is isolated, such as in an oil field
-.,
0
C
200
r--..
... , - where personnel would be required to
travel a considerable distance to reset the
.,...
0
b. Tripped position
unit
Figure 7-18 Bimetallic Overload Relay
c:=:::=J:F~¼~n-'~-;:r:::=::::::=J-
motor A second advantage of most bimetallic
overload relays is the incorporated adjust-
ment. This allows the trip point to be set
from approximately 85 to 115% of the
rated ultimate trip current.
~5"==-
To magnet
Most bimetallic overload relays also have
coil removable interchangeable heater elements,
13196308
permitting easy changes of current rating
Figure 7-17 Melting-Alloy Overload Relay without removing the entire thermal relay.
AUXILIARY ELECTRICAL EQUIPMENT 7-27
large control power transformer can fur- They are mounted in a readily accessible
nish control power to a lineup of starters. area for easy replacement. An available op-
Both schemes are satisfactory, but indi- tion is an anti-single-phasing trip bar. The bar
vidual control power transformers provide is activated by a blown fuse on any phase
greater system reliability. If a single large and immediately trips the contactor to shut
control power transformer fails or a protec- down the motor.
tive fuse blows, the entire motor control
■ Contactor The contactor may be air magnetic
center is out of service. Conversely, with in-
or vacuum interrupting. Both are acceptable.
dividual control power transformers, only
The air-magnetic contactor is easier to
one starter is out of service.
inspect and evaluate, but the vacuum-
□ Motor Control Center Application For typical interrupting contactor will require less main-
wiring diagrams and control schemes, see tenance. Note that there is no need for con-
Volume 10. For overload relay applications cern about current chopping with vacuum
and circuit coordination, see Volume 8. contactors. The propensity to current-chop
depends on vacuum contact or contact mate-
MEDIUM-VOLTAGE MOTOR CONTROL rial. Material that vaporizes easily under
arcing reduces the propensity to current-chop
Medium-voltage motor controllers comprise dis-
and is used in vacuum contactors.
connecting means, current limiting fuses, contac-
tor, current transformers, and protective relays. ■ Contactor Operating Mechanism Contactor
A control power transformer is also usually operating mechanisms are of two types: elec-
provided. Controllers are made to meet two classes trically held and mechanically latched. The
of performance (NEMA Standard ICS 2-1983, electrically held mechanism that drops out
Sect. 324 (28]). (opens the contactor) in event of loss of volt-
age or severe undervoltage, is appropriate for
■ Class El controllers employ their contactors most applications. Mechanically latched
for both starting and stopping the motor mechanisms are for use when the contactor
and for interrupting· short-circuit currents or must stay closed during severe undervoltage
fault currents exceeding operating overloads. or loss-of-voltage conditions. Examples would
be fire pumps, transformer feeders, capacitor
■ Class E2 controllers employ their contactors
for starting and stopping the motor and em- bank switching, and loads where the motor
is more expendable than the function of
ploy fuses for interrupting short-circuit cur-
equipment being served.
rents or fault currents exceeding operating
overloads. ■ Current 'Iransformers These are used to iso-
late the protective relays from high voltages
Ratings Medium-voltage motor controllers are and high currents.
available in various motor ratings up to 8000 hp
■ Protective Relays Optional protective relays
and 7200 V. Standard ampacity ratings are 180 A
applicable to medium-voltage motor con-
and 360 A, and nonstandard ratings are available
trollers are:
up to 800 A.
□ Thermal eutectic and bimetallic thermal
Volume 8 discusses protective relays and When performance is unsatisfactory or contact re-
their applications. sistance is too high, they should be discarded and
replaced. Molded-case circuit breakers should be
■ Control Power 1ransformer A fused control
mechanically operated periodically to prevent sei-
power transformer is furnished to provide
zure of parts. Additionally, some have a test button
power to the contactor and ancillary devices.
to exercise the trip unit, which should be benefi-
Medium-voltage controllers are built into struc- cially exercised at the same time.
tures nominally 90 in. high and may be bused to-
gether in lineups and with other equipment.
7.8 DC EQUIPMENT
Transmission system
transformer
Generator bus
T,
Generators
Station
service bus
directly to the main transformer, and a high-voltage found application principally in nuclear power sta-
circuit breaker is used for synchronizing and tions. Nuclear power stations are required to have
switching operations (Figure 7-20). Off-site power two independent off-site power sources to ensure
is brought in through a station service (startup) capability for safe shutdown and public safety.
transformer for startup and is transferred to the Without a generator circuit breaker, this require-
station auxiliary transformer when the generator ment is met by using two station service trans-
has been synchronized and connected to the formers fed by two independent power lines
system. (Figure 7-21).
However, generator circuit breakers are available Using a generator circuit breaker permits back-
today that will match the capabilities of the largest feeding through the main transformer with the
available generators. They are costly and have generator circuit breaker open; thus, the main
Transmission system
High-voltage
circuit breaker
Unit transformer
Station service
(startup)
transformer
Unit auxiliary
transformer
Generator
T,
1 Station service bus
13196308
Figure 7-20 Generating Station With Unit-connected Generator
7-32 POWER PLANT ELECTRICAL REFERENCE SERIES
♦
Optional - - - - - :
I
I
I
----1
,--- ---- ---7
~Swit ch yard
I
I
I
I I
I L ____ _ I_ _ _ _ _ _J
L ____ _ _j
Unit
transform er
Generato r
Transformers
Figure 7-21 Nuclear Generating Station. Unit-connected With Two Station SeNice
step-up transfor mer circuit. Note that this provides transfor mer or bus fault but will not interrup t the
no protecti on from generat or short-cir cuit current system short-cir cuit current in event of a generato r
contribu tions to faults in the step-up and station fault.
service transfor mers. The generat or short-ci rcuit
current contribu tion has a long time constan t and High-Fa ult Interru pting Capabl llty This ar-
contribu tes signific antly to the damage in event rangem ent imposes no limits to the short-ci rcuit
of an internal transfo rmer failure. protecti on system, permitti ng simplici ty and flex-
ibility in the protecti on system.
Medium -Fault Interru pting Capabi lity Med- Operati on of generat or circuit breaker s is differ-
ium-fau lt interrup ting capabili ty permits isolation ent from most circuit breaker applications. In con-
13196308
of the generat or from a step-up or station service trast to circuit breaker s on air-insu lated overhea d
AUXILIARY ELECTRICAL EQUIPMENT 7-33
I
I
----1
r----------7
~ Switchyard
I
I
Unit IL __________ _JI
transformer
Generator
circuit Unit auxiliary Station service
breaker transformer (startup)
7,
transformer
Generator
1l Station service
I)
l
I)
l -i
Station service
bus A bus B
lines, where fault current paths can usually be or aluminum. They may be bare or insulated
considered self-breaking, generator breakers are throughout. Bus conductors are usually plated at
tripped open in case of faults and are not reclosed bolted conducting joints.
until the cause of the fault is determined and Bus enclosures may be fabricated from aluminum
repaired or isolated. or steel. Aluminum enclosures must be used above
2000-A bus ratings to avoid hysteresis losses pres-
ent in steel. Enclosures may be ventilated or non-
7.10 BUS ventilated, indoor or outdoor, and may be rated
"proof' or "tight" against rain or dust and other con-
There are three types of bus in use: taminants. Wind loading and ice loading may be re-
quired. Service conditions will dictate which type
■ Nonsegregated-Phase Bus A nonsegregated- of bus structure is required.
phase bus is one in which all phase conduc-
tors are in a common metal enclosure with-
out barriers between phases (Figure 7-24a). BUS RATINGS
■ Segregated-Phase Bus A segregated-phase bus Electrical bus is rated similarly to its connected
is one in which all phase conductors are in equipment, including the following items:
a common metal enclosure but are segre-
gated by metal barriers between phases
■ Rated Voltage The rated voltage of a bus
(Figure 7-24b).
structure is the highest nominal system volt-
■ Isolated-Phase Bus An isolated-phase bus is age at which it is designed to operate.
one in which each phase conductor is en-
closed by an individual metal housing and ■ Rated Frequency The rated frequency of a
separated from adjacent conductor housings bus structure is the frequency at which it is
by an air space (Figure 7-24c). designed to operate.
L-------------------:
Transmission system
Unit transformer I
I
I
~ Optional station
service transformer
rvyv"
Generator
circuit I
breaker I
Unit auxiliary I
transformer I
Generator
T, I
I
')
I
l Station service bus
~
Figure 7-23 Fossil Fuel Generating Station With Generator Circuit Breaker
■ Rated Momentary Current The rated momen- Nonsegregated- phase bus may have heaters to
tary current of a bus structure is the rms to- prevent condensation and wall brackets and vapor
tal current that the bus structure will be barriers where the bus passes through external
required to withstand. building walls.
■ Withstand Tost Voltage A withstand test volt-
age is a voltage that a bus structure must SEGREGATED-PHASE BUS
withstand without flashover or other electrical
failure when the voltage is applied under Segregated-phase bus may be used where space limi-
specified conditions. Low-frequency voltages tations prevent use of isolated-phase bus. It has sub-
are expressed as volts rms for a specific time, stantially the same flux-neutralizing characteristics
and impulse voltages are expressed in crest as isolated-phase bus but higher losses because of
voltage of a specific wave. unfavorable geometry. It gives much greater protec-
tion from phase-to-phase faults than nonsegregated-
Consideration of the solar radiation effect on out- phase bus and is useful when high momentary cur-
door sections is recommended. Note that solar radi- rents and impulse voltages may be found.
ation may typically add 15°C rise to outdoor
sections (34). A sunscreen may be added to elimi-
ISOLATED-PHASE BUS
nate solar heating effects when they are excessive.
Stray-Flux Problem Isolated-phase bus has
NONSEGREGATED-PHASE BUS evolved over the last 50 years in response to the
stray-flux problem. As generator size increased,
Nonsegregated- phase bus is available with ratings generator lead current increased. At 8000 A and
up to 10,000 A, 5- through 34.5-kV, 80-kA short- above, stray flux can result in heating of steel
circuit current. This bus enclosure, both ventilated members in proximity to the bus, such as build-
or nonventilated, is available for indoor and out- ing steel, reinforcing bars in concrete, pipe
door applications. Nonsegregated-phase bus is used hangers, gas and water pipes, cable trays, ladders,
to connect the station service transformer and railings, platforms, and other components. Tom-
startup transformer to medium-voltage switchgear. peratures achieved due to stray flux will not be
It also may be used as the generator leads from high enough to affect structural strength or com-
small power plants. bustibility but are a serious safety problem. The
13196308
AUXILIARY ELECTRICAL EQUIPMENT 7-35
a. Nonsegregated-phase bus
b. Segregated-phase bus
c. Isolated-phase bus
Table 7.2 Electromagnetic Forces and Stray-Flux Heating From Isolated-Phase Bus
For example, a self-cooled 25,000-A bus would When the generator is hydrogen cooled,
probably not be economical unless very short. there is danger of hydrogen leakage from
Conversely, a force-cooled 12,000-A bus would the bushings into the bus cooling system;
P,robably not be economical unless exceedingly however, seal-off bushing may be provided at
long, due to the incremental cost of the cooling the generator terminals. The generator bush-
unit. Below 14,000 A, the bus savings for forced ings and terminals must still be cooled, so
cooling are minimal and easily eclipsed by the cost air from the supply duct is introduced into
of the cooling unit. the generator termin~tion compartment
In event of loss of cooling air, bus conductor and through dampers and discharged to the at-
enclosure temperature will sharply rise well above mosphere. Hydrogen detectors may be
allowable temperatures. To prevent this, load cur- placed near the bushings to give an alarm in
rent must be reduced to the self-cooled rating. the event of hydrogen leakage. An alterna-
How much time is available for orderly load reduc- tive is placing hydrogen detectors near the
tion depends on the self-cooled rating and the in- generator bushings (with no seal-off bush-
itial temperature of the bus. If the time interval ings) and changing the cooling system to
is insufficient, a lower self-cooled rating is appli- once-through operation upon a hydrogen
cable. To eliminate this problem, redundancy may leak alarm to prevent hydrogen buildup in
be built into the cooling package. At the least, a tp.e cooling system.
spare mounted motor may be provided. Many
modern power plants provide 100% redundant The basic cooling system consists of a single fan
cooling packages. with drive, water, air-to-water heat exchanger, and
makeup filter. An additional damper and air duct
Three General Arrangements of Forced- to the atmosphere may be added for once-through
Coollng Systems operation in the event of loss of cooling water or
hydrogen alarm (Figure 7-27).
■ Endfed Air is admitted to the center-phase It is recommended that the forced-cooling system
enclosure at the generator and flows to the on isolated-phase bus be run even when the bus
transformer termination, where it divides is not in use, in order to preclude condensation
and returns to the cooler through the two in the bus.
outer-phase enclosures (Figure 7-26a).
■ Centerfed When air velocity for proper cool-
ing becomes too high (over 40 mph), air is ISOLATED-PHASE BUS ACCESSORIES
admitted halfway between the generator and
The following accessories are commonly furnished
transformer (Figure 7-26b). The quantity of
with an isolated-phase bus:
air required is the same, but velocity is cut
in half. Pressure drop is reduced, and less
■ Voltage 'Iransformers and Surge Protection
horsepower is required for the fan.
Integrity of the isolated-phase construction
■ One-Way If the above systems are insufficient, continues into surge protection and voltage
then air flows one way. Air is admitted to transformer cubicles. Each surge protector
each phase at the generator and returned and voltage transformer is mounted in an
to the cooler from the transformer end individual-phase compartment and is con-
(Figure 7-26c). 13196308 nected to the main bus by isolated-phase bus.
7-38 POWER PLANT ELECTRICAL REFERENCE SERIES
Air
Damper from bus Air
(normal to bus
Makeup
air filter Arrows show
direction of
position) t
air flow
Air duct to t t
at mos p_he_rre_;:c=::,;...-r---r---==~
b. Center-fed
Full-size Plenum C/C Fan
makeup
air filter
Generator Transformer
terminals terminals a. Normal operation - air recirculated
Deionizer
.... .. grid
and
damper
....
.... Air
from bus A'ir
to bus
Dam er
_...,_~,L.;.,J,.•- Makeup
air filter
.,_
Plenum Arrows show Air duct to
direction of at m osph_e_rre-"'=CL..-r---r--~_..;,;.._,
cir flow Full-size
Fon
makeup Plenum C/C Fan
air filter
c. One-way
testing. The open gap with links removed process is imperfect or the plating is scratched,
shall be large enough to provide safe isola- galvanic action between the aluminum and silver
tion from energized sections. will result in blistering and failure of the plating.
■ 1elescoping Disconnecting Switches Used in
Silver plating on aluminum should be kept covered
with inert grease to eliminate this problem.
lieu of disconnecting links. At high ampaci-
.Tin plating on aluminum has been used success-
ties, removing disconnecting links may take
an unreasonable time. fully for 20 years and is recommended. Joint resis-
tance will be slightly higher than with silver
■ 1ransformer Adapter Hoods A set of three plating but is easily accommodated in the design.
hoods to seal off the bus when the trans-
former is out of service.
■ Bushing Enclosures For generator and trans- 7.11 ENVIRONMENTAL
former, including flexible boots. CONSIDERATIONS
• Cooling Package Consists of a fan belt driven
by a motor, a heat exchanger with cooling Usual service conditions are defined as:
coils, return air plenum, fresh-air filters,
dampers, return air duct, vibration boots, ■ Where the ambient temperature is not above
and all associated equipment. 40°C or below - 30°C
■ Where the altitude is not above 3300 ft
■ Crossover Ducts and Dampers At the genera- (1000 m)
tor and transformer as needed, including air
ducts, air control baffles, deionizing baffles, Any conditions outside the "usual" service con-
and thermostat on the bus enclosures as ditions are considered special and will require
required. attention.
■ Filtered Drains At the low point in verti-
cal sections to prevent accumulation of ABNORMAL TEMPERATURES
condensation.
Abnormally low temperatures may result in circuit
breaker malfunction due to congealed lubricants
BUS MAINTENANCE
or increased friction due to parts shrinkage. Ab-
At periodic intervals buses should be inspected normally high temperatures may result in failure
and maintained. to interrupt rated short-circuit currents. In either
case, the manufacturer should be consulted. Low
■ Examine bolted bus joints for signs of heat- temperatures may be remedied by special lubri-
ing or looseness. Check bolts for tightness cants and parts selection. High temperatures may
per the vendor's recommendations. also require special lubricants and probably
■ Examine bus insulators and insulation. Insu- derating.
lators and insulation should be cleaned. Do
not use chemical solvents on insulation, HIGH ALTITUDE
because they may chemically react with the
insulation. For applications at altitudes higher than 3300 ft
(1000 m), the basic impulse level and rated maxi-
■ Bus coolers will require routine maintenance mum voltage must be reduced due to lower dielec-
on moving parts: tric strength of the air. Also, the rated continuous
□ Maintain motor (Volume 6) current must be reduced due to lower convection
□ Clean or replace air filters loss through the afr. Refer to ANSI/IEEE Standard
o Replace fan belts C37.04-1979 (4) and ANSI Standard C37.010-1979/
IEEE Standard 320-1979 (13) for guidance.
Bus conductors will be copper or aluminum and
plated with silver or tin at bolted joints. Note that
HOSTILE ENVIRONMENT
silver is never plated directly onto aluminum be-
cause of galvanic problems. The plating procedure In general, there are no remedies for exposure to
on aluminum has several intervening steps ending abrasive dust, explosive dust or gas, steam, salt
13196308
with copper, upon which the silver is plated. If the spray, excessive moisture, flooding, dripping, coal
7-40 POWER PLANT ELECTRICAL REFERENCE SERIES
Minimum insulation resistance values specified by environmental conditions dictate the frequency of
the manufacturer should be met before energizing. maintenance required; however, at the minimum,
If the manufacturer's recommended values are not an 18-month maintenance is recommended. For
available, the values in Tobie 7-3 (36) may be used. specific information on maintenance of devices such
Normally, dry transformers will have readings 5 as circuit breakers, relays, and other equipment, sep-
to 10 times the above minimums. arate instruction books for each device are generally
'Iransformers may be dried before installation or available. Under normal conditions, protective re-
after an extended shutdown by the following lays are not generally called on to function; thus,
methods: it is imperative to check functional operation of
these devices regularly.
■ Internal heat
■ External heat
■ External and internal heat RECOMMENDED SCHEDULED MAINTENANCE
Switchgear should be given the following main-
Refer to the vendor or ANSI/IEEE C57.94-1982
(36) for detailed drying recommendations. tenance at regular intervals.
Table 7.4 Equipment High-Potential Test Voltages 7. If equipped with heaters, verify that all heaters
are energized and operating.
Nominal Voltage Factory Test Field Test Field DC Test
Class Voltage Voltage Voltage 8. Inspect and maintain air filters.
(kV) (kV) (kV) (kV)
0.6 2.2 1.65 2.3 9. Inspect bolted electric bus joints for signs of
overheating-discoloration and oxidation-
4.16 19.0 14.25 20.25
and test for bolt tightness.
7.2 26.0 19.5 27.5
13.8 36.0 27.0 37.5 ■ Bolts With Belleville Spring Washers There
14.4 50.0 37.5 52.5 are two schools of thought, and both
23.0 60.0 45.0 are acceptable.
34.5 80.0 60.0 □ Tighten until the Belleville washer is
flat. If the bolt is stretched beyond its
elastic limit, the Belleville washer will
3. Clean and lubricate the racking mechanism. take up the slack.
□ Tighten until the Belleville washer is
4. Check primary disconnect device contacts for
flat and back off a vendor-specified
abnormal wear or overheating. Discoloration
amount. The Belleville washer will
of silvered surfaces is not harmful unless a
accommodate thermal expansion and
chemically active atmosphere has generated
contraction.
sulfides on the surface.
Sandpaper, steel wool, or other abrasive ■ Bolts With Lockwashers (not lubricated)
cleaners should never be used on silver-plated Tighten to the manufacturer's specified
parts. If necessary, silver polish may be used. torque, or the following (37), if none are
Before replacing the breaker, apply a thin given.
coat of contact lubricant to primary discon-
nect contacts/studs. Bolt Diameter Torque
5. Measure resistance of the circuit breaker con- (silicon-bronze or steeV (ft•lb)
tacts by making millivolt-drop tests or using ¾ 20
a microohmmeter. Millivolt-drop tests are ½ 40
made by passing a substantial current (100 A ¾ 55
is suggested) and measuring millivolt drop by
placing voltmeter probes on the studs or con-
ductors. Contact resistance may be calculated MAINTENANCE PROBLEMS UNIQUE TO
by using Ohm's law: EACH TYPE OF CIRCUIT BREAKER
■ Circuit breaker will not Auxiliary switch b stage ■ High resistance through Clean, adjust, replace
close (solenoid operated) maladjusted contacts contacts; adjust
Blown fuse in closing contact pressure
circuit
■ Slow circuit breaker Interference in moving
Bad contacts in
operation, erratic parts
contactor
operation
Low voltage
(spring operated) Spring-release coil is
damaged 011 Circuit Breakers Oil circuit breakers may re-
Spring-release armature quire maintenance in three areas: main and arcing
maladjusted contacts, interrµpting devices, and condition of the
oil.
■ Circuit breaker is Latch bite too small
unstable, trips Latch worn
■ Examine contacts for excessive erosion and
spontaneously
wear. Arc tracks and small pits on the arcing
■ Mechanism will not contacts are acceptable. Contacts with heavy
charge (motor-spring erosion or cracks should be replaced.
operated)
Current-carrying contacts excessively scored
□ Spring charging Defective motor or worn should be replaced. Contact pressure
motor will not run Worn brushes springs may anneal, causing inadequate pres-
Blown fuse sure and resulting in contact overheating
Motor disconnect and burning.
switch not reset
(if furnished) ■ Interrupting devices are commonly made
with fiber or plastic components. These
□ Spring charging Sheared key on cam
components erode during interruption and
motor runs, will not Spring-release latch not
charge closing spring holding-no roll
should be replaced when erosion is notice-
clearance, latch not able. Excessive contact erosion may be
resetting, latch worn caused by severely eroded interrupting
devices.
■ Circuit breaker will not Blown fuse in trip
trip circuit ■ Oil is carbonized during operation of the cir-
'!rip coil damaged cuit breaker. Large particles will settle to the
'Irip armature bottom of the tank, and small particles will
maladjusted remain in suspension. There are many tests
Auxiliary switch a stage used to evaluate the quality of insulating oil
maladjusted (38), but the best criterion of oil quality for
Low voltage
circuit breaker applications is dielectric
strength. Oil should be drawn from the bot-
Air-Magnetic Circuit Breakers The major com- tom of the tank, after running off oil con-
ponents of air-magnetic circuit breakers that re- taining any sediment or free water that may
quire the most maintenance include the arcing be present. The oil test cup has disk elec-
contacts, which are considered expendable com- trodes 1.0 in. (25 mm) in diameter with
ponents, the main current-carrying contacts, and square corners, spaced 0.100 in. (2.54 mm). It
the arc chutes. Care should be exercised when is filled with oil to a depth of at least 0.80 in.
maintaining the arc chutes in older equipment that (20 mm) above the disks. Voltage is applied
may contain asbestos. Loose asbestos, which may (60 cycle), increasing at a rate of 3 kV ± 20%
be inhaled, is a serious health hazard. When work- (rms) per second until continuous break-
ing with loose asbestos particles, vacuum to re- down is achieved. Occasional momentary dis-
move loose particles, maintain adequate charges that do not result in a permanent
ventilation, and use approved breathing appara- arc may occur and should be disregarded
tus. Material with embedded asbestos is not con- (39). A minimum breakdown voltage of 25-kV
sidered a health hazard unless it is abraded or rms is acceptable for oil circuit breakers.
machined, releasing loose asbestos. Note that it is essential that good hygienic
Air-magnetic circuit breaker problems and ap- practice be followed by those working with
13196308
proaches to solutions follow: insulating oil. Liquid contact is irritating to
7-44 POWER PLANT ELECTRICAL REFERENCE SERIES
the eyes and, when repeated or prolonged, ■ Control valves may fail to operate properly
to the skin. Wash exposed skin areas with due to worn seals. A preventive maintenance/
soap and water several times during the replacement schedule is recommended to
working day. Oil-soaked clothing should not preclude failure.
be worn. Work clothes should be laundered
at least once a week. ■ Arc chutes will show erosion and should be
replaced when it becomes significant. Exces-
■ No continuity Broken lift rod, check shock sive contact erosion may be caused by se-
through absorber verely eroded arc chutes.
contacts Deteriorated contacts
SF6 Circuit Breaken The amount of mainte-
■ Excessive oil Low opening velocity nance required for SF6 circuit breakers is a func-
throw upon Circuit breaker may be over- tion of the circuit breaker size and design. SFs
operation loaded equipment rated for 72 kV and above has become
Interrupting devices badly well known. At these levels, it is not unusual to
eroded be concerned about large volumes of gas, leaks,
gas contamination, and complex apparatus. At
Vacuum Circuit Breaken Vacuum circuit break-
medium-voltage levels, design and materials have
ers require significantly less maintenance than air-
overcome almost all maintenance requirements as-
magnetic or oil circuit breakers. The vacuum in-
sociated with high-voltage designs. Continuous cast
terrupter is a sealed unit, and obviously no work
epoxy envelopes and special liquid gas seals have
can be done on the contact structure.
created permanently sealed interrupters that are
Indeed, in most cases it cannot even be seen.
precharged at the factory. The gas need not be
Contact erosion may be measured by mechanical
checked unless the operational policy dictates.
adjustment, and a high-potential (hi-pot) test is
Serviceability can be checked by observation of
recommended to verify vacuum integrity. Contact
contact wear by external means. Contact wear and
resistance may be measured by a millivolt-drop
mechanism lubrication might be considered every
test or with a microohmmeter and should be with-
two or three years depending upon the number
in the manufacturer's acceptable range.
of operations. 'fypical load-break operations range
When applying abnormally high voltage across
from 5000 to 10,000 uses without service, depend-
a pair of contacts in a vacuum, X rays may be
ing upon break type.
generated. Radiation may increase with an in-
SF6 is an excellent interrupting and insulating
crease in voltage, and/or decrease in contact spac-
medium. There are, however, some precautions
ing. X radiation produced during hi-pot testing at
in the use of the SF6 gas. In the medium-voltage
recommended voltages and contact spacing is ex-
levels, the volume of gas per interrupter is very
tremely low and well below the maximum permit-
small. The volume of gas of a 38-kV, 32-kA inter-
ted by standards. However, as a precautionary
rupter would expand to 0.5 ft 3 at atmospheric
measure, it is recommended that personnel stay
pressures. Considering the density is five times
at least 1 m away from and in front of the circuit
that of air, it would be extremely difficult to ob-
breaker during high-pot testing.
tain concentrations of gas sufficiently high under
normal conditions to cause any concern.
Air-Blast Circuit Breaken Air-blast circuit
Although SF 6 is highly stable, high-temperature
breakers will principally require maintenance in
decomposition and recombination lead to formation
the contacts, compressor-air control valves, and
of lower fluorides of sulfur, metal sulfurs, and
arc chutes.
metal fluorides, most of which are toxic.
■ Contacts are treated in the same way as are
oil circuit breakers. SFs electric arc, etc. SFs + SF4 + SFz + SzFz
HzO
SF4 - SOF2 + ZHF (Eq. 7•12) For further discussion, refer to EPRI EL-1646,
Study of Arc By-Products in Gas-insulated Equip-
HzO ment (40).
SOF2 - SO 2 + ZHF (Eq. 7·13)
1. S. F. Farag and R. G. Bartheld. "Guidelines for the American National Standards Institute, 1979. ANSI
Application of Vacuum Contactors:• In IEEE 'Irans- Std. C37.010-1979/IEEE Std. 320-1979.
actions on Industry Applications, vol. IA-22, no. 1. 14. Application Guide for 'Iransient Recovery Voltages
New York: Institute of Electrical and Electronics for AC High-Voltage Circuit Breakers Rated on a
Engineers, January/February 1986, pp. 102-8. Symmetrical Current Basis. New York: American
2. Switchgear Assemblies Including Metal-enclosed Bus. National Standards Institute, 1979. ANSI/IEEE Std.
New York: American National Standards Institute, C37.011-1979.
1974. ANSI Std. C37.20-1969/IEEE Std. 27-1974. 15. Application Guide for Capacitance Current Switching
3. Preferred Ratings and Related Required Capabilities of AC High-Voltage Circuit Breakers Rated on a
for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. New York: American
Symmetrical-Current Basis. New York: American National Standards Institute, 1979. ANSI/IEEE Std.
National Standards Institute, 1979. ANSI Std. C37.012-1979.
C37.06-1979. 16. IEEE Standard for Emergency Load Current-carrying
4. Rating Structure for AC High-Voltage Circuit Break- Capability. New York: American National Standards
ers Rated on a Symmetrical Current Basis. New York: Institute, 1985. ANSI/IEEE Std. C37.010b-1985 (sup-
American National Standards Institute, 1979. plement to ANSI/IEEE C37.010-1979).
ANSI/IEEE Std. C37.04-1979. 17. W. G. Reinmiller, R. W. Katterhenry, and S. R. Lam-
5. Definitions and Rating Structure for AC High-Voltage bert. "'Iransient Recovery Voltage Failures of 'Iwo
Circuit Breakers Rated on a Total Current Basis. New 15-kV Indoor Oilless Circuit Breakers:· In IEEE 'Jrans-
York: American National Standards Institute, 1953. actions on Power Apparatus and Systems, vol.
ANSI Std. C37.4-1953. PAS-102, no. 8. New York: Institute of Electrical and
Electronics Engineers, August 1983, pp. 2578-84.
6. Methods for Determining the RMS Value of a Sinu-
18. N. Irving Sax. Dangerous Properties of Industrial
soidal Current Wave and Normal Frequency Recov-
Materials. New York: Van Nostrand Reinhold Co.,
ery Voltage, and for Simplified Calculations of Fault
1984.
Currents. New York: American National Standards
Institute, 1953. ANSI Std. C37.5-1953. 19. Maintenance and Handling of Perchloroethylene-filled
Electrical Equipment. Palo Alto, Calif.: Electric Power
7. Schedules of Preferred Ratings for Power Circuit
Research Institute, January 1986. EL-4407.
Breakers. New York: American National Standards
Institute, 1953. ANSI Std. C37.6-1953. 20. "Freon 113 Material Safety Data Sheet:' Wilming-
ton, Del.: E. I. du Pont de Nemours & Co., October
8. Interrupting Rating Factors for Reclosing Services.
1985. E-77815-1, rev. 10/85.
New York: American National Standards Institute,
21. "Freon Fluorocarbons: Properties and Applications:•
1952. ANSI Std. C37.7-1952.
Wilmington, Del.: E. I. du Pont de Nemours & Co.
9. Rated Control Voltages and Their Ranges. New York: G-1, E-03528-1, rev. 3/85.
American National Standards Institute, 1952. ANSI
22. Preferred Ratings, Related Requirements, and Appli-
Std. C37.8-1952.
cation Recommendations for Low-Voltage Power Cir-
10. Test Code for Power Circuit Breakers. New York: cuit Protectors. New York: American National
American National Standards Institute, 1953. ANSI Standards Institute, 1980. ANSI Std. C37.16-1980.
Std. C37.9-1953.
23. Low-Voltage AC Power Circuit Breakers Used in En-
11. Guide to Specifications for Alternating Current Power closures. New York: American National Standards
Circuit Breakers. New York: American National Stan- Institute, 1981. ANSI Std. C37.13-1981.
dards Institute, 1981. ANSI Std. C37.12-1981. 24. Recommended Practice for Electric Power Distribu-
12. Test Procedures for AC High-Voltage Circuit Breakers tion Plants. New York: Institute of Electrical and Elec-
Rated on a Symmetrical Current Basis. New York: tronics Engineers, 1976. IEEE Std. 141-1976.
American National Standards Institute, 1979. 25. Recommended Practice for Electric Power Systems in
ANSI/IEEE Std. C37.09-1979. Commercial Buildings. New York: Institute of Elec-
13. Application Guide for AC High-Voltage Circuit Break- trical and Electronics Engineers. ANSI/IEEE Std.
ers Rated on a Symmetrical Current Basis. New York: 241-1983.
13196308
7-48 REFERENCES
13196308
BIBLIOGRAPHY
"Bibliography of Switchgear Literature:' In IEEE 1ransa.c- 1ransactions on Power Apparatus and Systems, vol.
tions on Power Apparatus and Systems, vol. PAS-104, PAS-87. New York: American Institute of Electrical
no. 12. New York: Institute of Electrical and Electron- Engineers (now Institute of Electrical and Electron-
ics Engineers, December 1985, pp. 3643-56. ics Engineers), August 1968, pp. 1724-30.
Burkhardt, P., E. Vadasgi, and M. Seidel. "DC Generator Engmann, G. R., and A. D. McCown. "Expected Switch-
Breakers for Extremely High Service and Short-Circuit ing Life for Safety-related Metal Clad Switchgear Ap-
Currents:' Brown-Boveri Review, vol. 64, no. 4, April 4, plied in a Boiling Water Reactor Generating Unit:' In
1975, pp. 131-38. IEEE 1ransactions on Power Apparatus and Systems,
Coriangla, Amado, and Harris F. White. "Isolated-Phase vol. PAS-100, no. 5. New York: Institute of Electrical
Bus Enclosure Loss Factors:' In IEEE Iransactions on and Electronics Engineers, May 1981, pp. 2459-63.
Power Apparatus and Systems, vol. PAS-87, no. 7. New Fault Analysis in Gas-insulated F,quipment. Palo Alto, Calif.:
York: Institute of Electrical and Electronics Engineers, Electric Power Research Institute, February 1980.
July 1968, pp. 1622-28. EL-2248.
Controlled Impedance Short-Circuit Limiter. Palo Alto,
Fault Detection Sensors for Gas-insulated F,quipment. Palo
Calif.: Electric Power Research Institute, September
Alto, Calif.: Electric Power Research Institute, Febru-
1977. EL-537.
ary 1982. EL-2249.
Controlled Impedance Short-Circuit Limiter. Palo Alto,
Calif.: Electric Power Research Institute, August 1978.
Fundamental Investigation of Arc Interruption in Gas
Flows. Palo Alto, Calif.: Electric Power Research Insti-
EL-857.
tute, January 1977. EL-284.
Criteria for Class 1E Power Systems for Nuclear Power
Generating Stations. New York: Institute of Electrical Guide for Calculating Losses in Isolated-Phase Bus.
and Electronics Engineers, 1980. IEEE Std. 308-1980. New York: American National Standards Institute,
1969. ANSI/IEEE Std. 37.23-1969.
Development of a Circuit Breaker for Large Generators.
Palo Alto, Calif.: Electric Power Research Institute, "High-Voltage Circuit Breaker Standards in the U.S.A.-
January 1982. EL-2195. Past, Present, and Future:· In IEEE 1ransactions on
Power Apparatus and Systems, vol. PAS-98. New York:
Development of a Current Limiter Using Vc!cuum Arc Com-
Institute of Electrical and Electronics Engineers,
mutation, Phase 1: A Feasibility Study for Using Arc In-
January-June 1974, pp. 590-600.
stability in Vacuum for Current Limitation. Palo Alto,
Calif.: Electric Power Research Institute, March 1977. IEEE Guide for 1emperature Correlation in the Connec-
EL-393. tion of Insulated Wire and Cables to Electronic F,quip-
Development of Current-limiting Conductor. Palo Alto, ment. New York: Institute of Electrical and Electron-
Calif.: Electric Power Research Institute, February ics Engineers, 1955. IEEE Std. 55-1593.
1977. EL-286. Investigation of Feasibility of Vacuum Arc Fault-Current
Development of Distribution and Subtransmission SF6 Limiting Device. Palo Alto, Calif.: Electric Power Re-
Circuit Breaker and Hybrid 1J-ansmission Interruptor. search Institute, December 1977. EL-538.
Palo Alto, Calif.: Electric Power Research Institute, Janssen, F. J. G. Measurements at the Sub-ppm Level of
June 1978. EL-810. Sulfur-Fluoride Compounds Resulting From the De-
Durso, R. G. "Restoring Flood-damaged Electrical Equip- composition of SF6 by Arc Discharge. KEMA Scientific
ment:' Plant Engineering, vol. 34, no. 13, June 26, 1980, and Tochnical Report, vol. 2, no. 2. Arnhem, The
pp. 87-90. Netherlands: N. V. KEMA, 1984, pp. 9-18.
Dwight, H.B. "Some Proximity Effect Formulas for Bus Kennedy, G. P. "Application of Motor Control Centers
Enclosures:' In IEEE 7J-ansactions on Power Apparatus to Systems Having High Available Fault Currents:' In
and Systems, vol. PAS-83. New York: American Insti- IEEE Iransactions on Industry Applications, vol. lA-9,
tute of Electrical and Electronics Engineers, Decem- no. 6. New York: Institute of Electrical and Electron-
ber 1964, pp. 1167-72. ics Engineers, November/December 1973, pp. 666-71.
Elgar, Everett C., Robert H. Rehder, and Nathan Kubica, P., and D. J. Love. "Generator Breaker Provides
Swerdlow. "Measured Losses in Isolated-Phase Bus and Advantages Over Unit Connection:' Power Engineering,
Comparison With Calculated Values:• In AIEE vol. 86, no. 5, May 1982, pp. 54-57.
13196308
7-50 BIBLIOGRAPHY
13196308
INDEX
Accessibility, 7-41 Capacitive current switching, 7-15 Dry-type transformers, 7-17, 7-18,
Accessories, 7-2, 7-37 Cast-coil, 7-18 7-40
Aging, 7-1 Circuit breaker, 7-1, 7-2, 7-3, 7-5, Duty cycle, 7-13, 7-20, 7-22
Air-blast circuit breakers, 7-6, 7-9, 7-6, 7-7, 7-8, 7-9, 7-10, 7-11,
7-10, 7-11, 7-44 Electric arc, 7-2, 7-17
7-12, 7-13, 7-14, 7-15, 7-16,
Air load-interrupter switch, 7-16 7-19, 7-20, 7-27, 7-28, 7-29, Electric lockout, 7-20, 7-30
Air-magnetic circuit breakers, 7-3, Electromagnetic forces, 7-36
7-30, 7-31, 7-32, 7-39, 7-41,
7-4, 7-5, 7-9, 7-10, 7-15, 7-19, Emergency load periods, 7-15
7-42, 7-43, 7-44, 7-45
7-43, 7-44 Encapsulated-coil transformers,
Circuit breaker enclosures, 7-19
Altitudes, 7-39 7-18
Circuit breaker removable
Ambient temperature, 7-15, 7-27, Eutectic, 7-24, 7-28
element, 7-12, 7-19
7-39, 7-40 Eutectic alloy, 7-24
Class and type of MCC, 7-23
Ambient temperature sensitivity, Clearances, 7-36, 7-41, 7-42 Fault-interrupting, 7-1, 7-32
7-27 Close-and-latch, 7-12 Field discharge resistors, 7-30
Antipump relays, 7-12 Combination motor controller, Field rheostat, 7-30
Arc chutes, 7-3, 7-43, 7-44 7-23, 7-24 Flammable liquids, 7-16
Arc constriction, 7-3 Condensation, 7-34, 7-38, 7-39, Forced-cooled, 7-36, 7-37
Arc elongation, 7-3 7-40 Forced-cooled capacity, 7-18
Arc-enclosing, 7-5, 7-7 Contactors, 7-1, 7-2, 7-27, 7-28, Full-voltage starting, 7-29, 7-30
Arc instability, 7-6 7-29, 7-30, 7-43 Fused circuit breaker, 7-20, 7-22
Arc-restraining metal barriers, 7-3 Contact pressure, 7-42, 7-43 Fuses, 7-20, 7-22, 7-24, 7-27, 7-28,
Arc voltage, 7-2 Continuous current, 7-2, 7-9, 7-12, 7-30, 7-43
Askarels, 7-16 7-13, 7-14, 7-20, 7-24, 7-33,
Asymmetrical, 7-11, 7-12, 7-13, Galvanic problems, 7-39
7-39
7-14 Generator circuit breakers, 7-1,
Control circuits, 7-23, 7-24
Atmospheric corrosion, 7-40 7-10, 7-30, 7-31, 7-32
Control compartment, 7-11
Automatic shutters, 7-10, 7-12 Ground and test device, 7-12
Control power transformer (CPTh),
Auxiliary service system, 7-1, 7-29 Grounded neutral operation, 7-15
7-11, 7-23, 7-27, 7-28, 7-29,
Auxiliary switches, 7-12, 7-20, 7-41 Heaters, 7-24, 7-26, 7-34, 7-42, 7-45
7-30, 7-43 Control voltage, 7-13, 7-22, 7-27 High-potential tests, 7-41, 7-44
Available short-circuit current, Corrosion of copper or silver, 7-40 Horizontal draw-out, 7-11, 7-19
7-14, 7-15 Cracking, 7-4 Horsepower ratings, 7-22, 7-24
Crossover ducts and dampers, Hydrogen alarm, 7-37
Basic impulse insulation level, 7-17
7-39 Hydrogen leakage, 7-37
Bell alarm, 7-20, 7-30
Current chopping, 7-6, 7-8, 7-9, Hygroscopic, 7-17
Belleville Springs Washers, 7-42
7-28 Hygroscopic salts, 7-40
Bimetallic, 7-24, 7-26, 7-28, 7-30
Current limiting fuses, 7-19, 7-20,
Bimetallic overload relays, 7-24, Installation requirements, 7-40
7-27, 7-28
7-26 Insulating oil, 7-4, 7-43
Current transformers, 7-12, 7-28,
Bolted conducting joints, 7-33 Insulation resistance, 7-40, 7-41
7-29
Bus, 7-1, 7-2, 7-12, 7-15, 7-19, 7-20, Interference interlocks, 7-11
Current zero pause, 7-2
7-23, 7-28, 7-29, 7-32, 7-33, Interrupting medium, 7-2, 7-4, 7-8,
7-34, 7-36, 7-37, 7-38, 7-39, De switchgear, 7-30 7-44
7-41 Deionization, 7-2, 7-3, 7-5, 7-9, Interrupting time, 7-13, 7-14, 7-30
Bus ampacity, 7-36 7-10 Ionized gases, 7-2
Bus compartment, 7-11, 7-19 Dielectric strength, 7-2, 7-3, 7-5, Isolated-phase bus, 7-1, 7-33, 7-34,
Bus conductors, 7-10, 7-12, 7-33, 7-6, 7-7, 7-9, 7-39, 7-43 7-36, 7-37, 7-38
7-37, 7-38, 7-39 Disconnecting switches, 7-2, 7-16, Isolating means, 7-15, 7-16
Bus enclosures, 7-33, 7-34, 7-36, 7-28, 7-39
Key interlocks, 7-20, 7-29
7-38, 7-39 Distribution voltage, 7-15
Bushing enclosures, 7-39 Double-ended substation, 7-15 Less-flammable liquid, 7-16
Bus joints, 7-39, 7-42 13196308 Driving voltage, 7-2, 7-3 Load break switch, 7-15, 7-32
7-52 INDEX
Load-interrupter switch, 7-2, 7-16 Primary enclosure, 7-11 Symmetrical component, 7-13
Load-interrupting, 7-1 Protective relays, 7-20, 7-28, 7-29, Symmetrical current basis, 7-13,
Load-switching, 7-1 7-41 7-14
Lockwashers, 7-42 Puffer design, 7-9 Symmetrical interrupting current,
Lower impedance transformer, 7-13, 7-14, 7-32
7-15
Rated maximum voltage, 7-12,
Symmetrical interrupting rating,
Lubricants, 7-39, 7-42 7-13, 7-14, 'i;'-20, 7-22, 7-39
7-14
Rated momentary current, 7-34
Magnetic blowout, 7-3, 7-4 Rated voltage range factor, 7-12 Thermal conductivity, 7-8
Magnetic motor controller, 7-23 Ratings in cascade, 7-22 Thermal overload relay, 7-27, 7-28,
Maintenance, 7-1, 7-8, 7-15, 7-17, Reactors, 7-38 7-30
7-18, 7-22, 7-26, 7-28, 7-39, Recovery voltage, 7-2, 7-3, 7'.7, Thermal relays, 7-24, 7-26, 7-27
7-40, 7-41, 7-42, 7-43, 7-44, 7-10, 7-15 Tie circuit breaker, 7-15, 7-22
7-45 Reignition, 7-3, 7-4, 7-6, 7-7, 7-9 Tin plating, 7-39
Maximum crest, 7-13 Relative humidity, 7-40 Torque, 7-42
Mechanical interlocks, 7-10 Reliability, 7-1, 7-27, 7-32, 7-41 Total current basis, 7-13, 7-14
Mechanical shock, 7-11 Removable element, 7-10, 7-11, Toxicity, 7-17, 7-45
Mechanism-operated control 7-12 'Iransient recovery voltage, 7-6,
(MOC), 7-12 Repetitive duty, 7-1, 7-15, 7-22 7-7, 7-15
Melting alloy, 7-24, 7-26, 7-30 Running protection, 7-24 'Irichlorotrifluoroetha ne (C 2 Cl 3 F3 ),
Metal barriers, 7-3, 7-4, 7-10, 7-11, 7-17, 7-18
7-19, 7-33 Sealing bushings, 7-38
'!rip-free operation, 7-42
Metal-clad, 7-10, 7-12, 7-19 Secondary enclosure, 7-11, 7-12
'!ruck-operated contact (IDC), 7-12
Metal-enclosed, 7-19 Secondary-unit substations, 7-1,
Metallic vapor arc, 7-5 7-2, 7-14, 7-15, 7-16, 7-22 Undervoltage trip, 7-20, 7-29
Molded-case circuit breakers, 7-29, Segregated-phase, 7-33, 7-34 Unfused circuit breaker, 7-20, 7-22
7-30 Self-cooled, 7-36, 7-37 Unit auxiliary transformer, 7-1,
Motor circuit protector, 7-27, 7-30 Self-extinguishing design, 7-9 7-2, 7-32
Motor control centers, 7-1, 7-2, Serpentine passage, 7-5 Unit substation, 7-1, 7-2, 7-15
7-15, 7-23, 7-24, 7-28, 7-29, Service-limit, 7-24 Unit transformer, 7-1, 7-2, 7-32
7-30, 7-41 Short-circuit current, 7-2, 7-13,
Vacuum circuit breaker, 7-5, 7-6,
Motor control equipment, 7-23, 7-14, 7-15, 7-22, 7-24, 7-27,
7-10, 7-44
7-29, 7-30 7-28, 7-29, 7-30, 7-32, 7-34,
Vacuum interrupter, 7-5, 7-6, 7-7,
Multiple reignition, 7-6, 7-7, 7-8 7-39
7-9, 7-44
Short-circuit current ratings, 7-12,
Natural frequency, 7-7 Vault, 7-16, 7-18
7-19
Neutral grounding equipment, Vertical-lift, 7-11
Short-time current, 7-13, 7-20
7-38
Vertical section, 7-23, 7-39
Shunt trip, 7-19, 7-20, 7-29
Nonflammable liquids, 7-16 Vibration isolation, 7-40
Silver plating, 7-39
Nonsegregated-phase bus, 7-33, Virtual current chopping, 7-6, 7-7
Solar radiation, 7-34
7-34
Voltage (potential) transformers,
Speed control, 7-30
7-12
Oil circuit breaker, 7-4, 7-5, 7-6, Standard operating duty, 7-13
Starters, 7-1, 7-23, 7-24, 7-27, 7-28, "Whiskers;' 7-40
7-11, 7-14, 7-43, 7-44
Oil displacement, 7-4 7-30 Withstand test voltage, 7-34
Oil-immersed transformers, 7-16 Stationary auxiliary switches, 7-12 Working space, 7-41
Station service (startup)
Oil piston, 7-5
transformer, 7-1 . 7-2, 7-31,
Oil-piston effect, 7-5
7-32, 7-34
Operations counter, 7-20
Overload condition, 7-15 Stored energy spring operating
Overload relay, 7-24, 7-26, 7-27, mechanism, 7-12, 7-19
Stray-flux problem, 7-34
7-28
Sulfates, 7-45
Panel boards, 7-1, 7-2, 7-29, 7-30 Sulfur hexafluoride (SF 6), 7-2, 7-3,
Perchloroethylene (Cl2 :CC12 ), 7-16, 7-6, 7-7, 7-8, 7-9, 7-10, 7-44,
7-17 7-45
Permissible tripping delay, 7-13 Switchgear assembly, 7-2
Plating, 7-39, 7-40 Switchgears, 7-1, 7-2, 7-7, 7-9,
Polychlorinated biphenyls (PCBs), 7-10, 7-11, 7-12, 7-13, 7-14,
7-16 7-15, 7-16, 7-19, 7-20, 7-22,
Power circuit 13196308
breaker, 7-4, 7-19 7-29, 7-30, 7-34, 7-40, 7-41
13196308
POWER PLANT ELECTRICAL REFERENCE SERIES 7
>
C
--
><
r-
>
::a
-<
rn
r-
rn
n
EPRI -I
::a
Electric Powor
Research Institute
-~
r-
rn
0
.-,.
C
3:
rn
z-I