Electrical Engineers Interactive Society
Electrical Engineers Interactive Society
8. CASE STUDIES
3 ф supply to LT side, HT side shorted. Note : - L.T side (132KV) current could not be
measured, because of the use of “ER” relay in the
Primary Currents. circuit.
3. REF relay
0 mA
8.1.4 Analysis Of Preliminary Check Up (2) E/F Æ 19 mAÆ? (Doubt)
(3) REF Æ 2.5 mA
Secondary current on E/F of 220 KV side relay = 18 mA. (4) Differential relay
So, Primary current on neutral path of 220 kv side = H.T. L.T. Op. Coil
(18mA x 300) = 5.4 Amp 0.22 A 0.25 A 0.4 mA
Now corresponding primary current on neutral path of 0.23 A 0.23 A 0.2 mA
132 kv side =5.4 x 220/132 = 9 Amp. 0.25 A 0.23 A 0.3 mA
Net current on neutral path = (9~5.4) Amp = 3.6 Amp
Secondary 132 LV side current = 9/600 = 15 mA 8.2.3 PLAN : - The circuit was planned to be
Secondary NCT current = 12mA (measured connected as described fig. No.
approximately)
Net REF current = Residual current of (220 kv ~ 132 kv) REF CIRCUIT FOR AUTO-TFR
+ Secondary NCT current = (18 – 15) + 12 mA Note: 220 KV side line CTR = NCT = 300 / 1
If (additive) = 15 mA * 220 Kv side line CTR = 300/1
If (Subtractive) = 6 mA ** 132 KV side line CTR = 300/1
As REF was measured with current of 21 mA. So doubt
was on the C.T connection polarity. 8.2.3 Current Calculation.
Suppose “y” Amp is the residual current on 220
8.1.5 Accordingly NCT terminals were reversed KV CT secondary. Then corresponding primary current
= 300 x Amp. This current will pass through neutral i.e.
1) The current measured by instruments are not neutral primary current = 300y Amp. As VA i.e. rating if
accurate and dependent on the accuracy factor of transformer on primary and secondary side being same.
measuring instruments and equipment like C.T, A.C.T i.e. VI = constant.
etc in the circuit. Iα (1/V) for transformer
2) The circuit is assumed being in the connection Neutral primary current for 132 KV side
as fig. No. = 300y (200/132) = 500y Amp
(Without physical check up of the secondary circuit). Residual secondary current = 500y/300
= 1.66666y = (5/3)y
8.1.6 Proceedings After Reversal Of NCT Terminals Net NCT secondary current = Net NCT primary current /
300 = (500y-300y)/300= (2/3)y
(A) The transformer was idle charged and current were Net residual current through REF
measured. = (Net residual 132 KV side current – Net residual 220
IDEL CHARGE KV side current) = {(5/3)y-y}=(2/3)y
REF Æ Nil (1.2 mA), E/F Æ 3.8 mA, R Æ 4.2 mA, [For direction of current flow, refer fig ]
Y Æ 2.8 mA, B Æ 5.5 mA Hence for any kind external fault due to which
the residual current only will be increased, but not the
(B) The transformer was loaded and currents were REF relay. But for internal fault, the REF will actuate.
measured * Separate core should be selected for REF only
LOADING CONDITION on 220 KV side if available, or else otherwise the back
REF Æ Nil (1.2 mA), E/F Æ 18 mA Æ? (Doubt), up core can be chosen for this practice in this case.
Over R Æ 0.45 A, Y Æ 0.45 A, B Æ 0.45 A ** Separate core, particularly (300/1) ration
must have to used on 132 KV side. This core no way
(C) Current were measured after 30 mnts of loading. should be mixed with back up or any other protection.
REF Æ 0.5 mA (10 mA range), Then shut down was taken and physically
E/FÆ 19 mA (100 mA) Æ? (Doubt) circuit was checked on the 220 KV C/R panel
RÆ 0.46 A (1 Amp range), Y Æ 0.47 A (1 Amp
range) B Æ 0.48 A (1 Amp range) 8.3 Findings On The Circuit
i)The circuit connection was like fig. No
8.2 PROBLEM
Again the same problem repeated as mentioned 8.4 Modification Of The Circuit
in the data above i.e. tripping of transformer on REF i. The differential core was separated and used
with tripping of External feeder sometimes only REF only for differential circuit only.
relay. ii. Separate core from 132 KV line CT was
changed from (600/1) to (300/1) ratio and used
8.2.1 Detail Study for REF circuit.
iii. Circuit was used as per the standard Auto
8.2.2 Preliminary check up (with load) Transformer circuit.
H.T side (220 KV) 8.4.1 Final Conclusion
Current on ammeter: 78 Amp After modification of the circuit, the transformer was
C.T.R: 300/1 charged and stood O.K. The problems as described
(1) B/U secondary current: above were solved and the transformer did not trip
R Æ0.24, YÆ 0.24 A, BÆ 0.24 A further for the external fault on any feeder.
QUESTIONS FOR DISCUSSION FOR
THE NEXT INTERACTION
( IN THE MONTH MAY-2007)
Q1. What is the fundamental difference between E/F and
REF Relay
Q2. Why REF protection is not considered as 100%
protection to the equipment winding?
Q3 Should the concept of using REF protection to the
Transformer winding and Generator winding be same. If
not explain?
Q4. Which protection is better, either REF protection or
Differential protection for Transformer.
Q5. Should REF protection be effective for transformer
with impedance grounding?
Q6. Can REF protection be provided for the transformer
with delta winding?
Q7. Can performance of REF relay be reduced if its
residual current circuit is obtained in series with E/F
relay in the scheme
Q8. What is the usual standard and rating of electrical
equipment above which REF relay must be provided as
one of the protection scheme?
Q9. Why REF relay is grouped under high impedance
Relay.?
ANSWER TO THE QUESTIONNAIRES RELATED For the case of unloaded Tertiary winding, the
TO THE PROCEEDING two open delta terminals are taken out in the form of two
“STUDY ON TERTIARY WINDING IN POWER bushings. For protection of these windings these two
TRANSFORMER WITH CASE STUDY ON THE windings are shorted and directly connected to the solid
FAULT DUE TO THIS WINDING.” earth. But for some cases with unloaded Tertiary
(From Previous Issue) winding, three terminals are internally shorted and
earthed to the body of transformer
Q1). Why the name of this winding has been kept as Q4.)How the differential protection is provided by the
Tertiary Winding? consideration with other regular windings in the
Ans. In usual practice every transformer is terminated as system?
2 sides with nomenclature of Input Supply as primary Ans. For the consideration of tertiary winding to the
side and output supply as secondary side. The windings Differential circuit, the current contribution to the
are accordingly called Primary Winding and secondary secondary circuit from the CTs used in the system to be
winding also. But excluding to these windings the extra taken into account. Here the Differential relays should
third winding is also provided in the transformer. have the facility to accommodate currents from Primary,
Because first two windings are terminated primary and Secondary and Tertiary windings. Under healthy
secondary so this extra winding is called Tertiary condition the current through the operating coils should
winding be zero but for the case of fault on any one of the
winding the unbalance value of current should be able to
Q2). Why the rating of this winding (MVA) is lass than actuate the relay to issue the trip signal for the
that of the regular (HT, LT) winding? transformer.
Ans. Rating of the winding in transformer depends upon
the voltage rating of the winding and current capacity of Example-
the winding under loading condition. The primary and 500kV / 138kV / 13.45kV, 120MVA / 90MVA /
secondary windings are considered as the main windings 30MVA star/star/delta transformer.
of the transformer. So the current rating of these
windings is accordingly designed to cater maximum CT ratio: 200/5; 500/5; 400/5 on primary, secondary and
rating of the transformer. But the tertiary winding is the tertiary respectively
auxiliary winding distinctly separated from both the Load current on 500kV side = 138.6A
primary and secondary windings, used mainly either for Load current on 138kV side = 376.5A
protection purpose or for auxiliary loading to the system. Load current on 13.45kV side = 1288A
Main purpose of this winding is not to cater the actual Current at 138kV corresponding to 120MVA is 502A
load to the system. Because of these specific reasons, the Current at 13.45kV corresponding to 120MVA is 1551A
rating of this winding is designed with less MVA as Secondary current from 500kV line side corresponding
compared to the regular windings. Moreover higher to 120MVA is 3.46A
current rating windings need extra insulation, cooling Therefore ratio star/delta interposing CT for the primary
system and also costly in comparison to the present trend side is 3.46/5/√3 = 3.46/2.89A
on Delta winding. So considering the above factors the Similarly the ratio of star/delta interposing CT on
rating is chosen less in comparison to the regular secondary side is 6.28/5/√3 = 6.28/2.89A
windings. . Ratio of star/star interposing CT on the tertiary side is
17.17/5A.
Q3) Suggest the methods of protections to be provided
for Tertiary winding? Q5) Why Tertiary winding is kept near to the core of
Ans. From the loading consideration, the Tertiary the transformer?
winding is categorized as 1.Loading Tertiary Winding Ans . The objective of using the tertiary winding in
2.Unload Tertiary Winding. transformer have already been discussed in detail ( Feb-
Loading Tertiary Winding provides external terminals in 07 Issue).The purpose of using the same near to the core
the form of three terminal bushings for availing the loads has the following advantages
to the auxiliary transformers/ station transformers. These .1.Tertiary winding is either of medium or low rated
bushings when loaded to the external circuit need to be voltage winding in the transformer. Now the insulation
protected from external faults. So the normal O/C,E/F required for this winding in comparison to the main
relays along with differential protection is to be provided winding is less. So more space is not demanded for the
in the system. But when this type of Loading Tertiary is accommodation of this insulation in the transformer. To
not loaded then it is called Floating Tertiary winding. If economize the design of transformer, the Tertiary
this Tertiary winding is planned to be kept in floating winding is kept near to the core.
condition, then it should be connected with LA of rating 2. During working condition, according to t5he type of
(Phase Voltage Of winding x √2 x 0.9 /√3) as the core used in the transformer, the excitation current is
protection to the electro static effect on the tertiary developed. The magnitude of this excitation current,
winding. Sometimes instead of using LA in the system particularly the effect of third harmonic excitation
any one of the external terminal can be connected current causes voltage unbalance, heating effect etc on
directly to the solid earth. the external load circuit.
But due to use of tertiary winding near the core,
the short circuit third harmonic current or exciting third meet the objectives of the tertiary windings as discussed
harmonic current doesn’t affect to the external load earlier.
circuit or even to the transformer. The closed path Basically the broken Delta points are taken out
circulation is resulted on the closed Delta tertiary in the form of 2 bushings and made available on the top
winding. of the transformer.
These terminals are being connected together, solidly
Q6 ) Why Tertiary winding is Delta connected? earthed to avoid the problems due to electro static
Ans. The objective of using the tertiary winding in effects. Sometimes these terminals are kept inside the
transformer has already been discussed in detail (Feb-07 transformer and directly connected to the body.
Issue). From the objectives it is seen that for transformer
different currents like Third Harmonic Short Circuit Q10) What is the type of tertiary winding physically
Current, Exciting Current, Unbalance Current etc are used for the power Transformers?
developed in the transformer. These currents operate to Ans. As already discussed that tertiary windings are of
increase the stress on the transformer insulation. But two types [loading and unloaded tertiary]. On technical
because of Delta connected Tertiary winding, the effects ground it is advisable the followings regarding the use of
of the above currents substantially get eliminated due to tertiary windings.
circulation of the same internally. 1.Note: - Central Board of Irrigation and Power (CBIP)
and Standardization and Optimization Sub-Committee
Q7) Can REF Protection be provided for this winding? (SOSC) under Development Council for Heavy
Ans. For REF protection it is needed to bring the Electrical Industry constituted by Government of India
currents from line CTS and Neutral CT. The residual have recommended that the delta connected stabilized
current is brought from the vector sum of current from windings should be eliminated up to transformer of
line CTS and neutral current is brought from NCT.But rating 50MVA.
for delta connected Tertiary winding the neutral terminal 2.For the power transformer of rating above 50 MVA,
in not made available in practice. So REF protection is the tertiary winding should be used. If possible the
usually not provided for tertiary windings. loading tertiary windings should be provided to avoid
the unbalance current, third harmonic effects in the
Q8) Why this winding is also called stabilized winding? load.
Ans. The salient features for the use of Tertiary winding
in the Power Transformers have already been discussed
in the Feb-07 issue. The following concepts have been
DIFFERENT QUESTIONS ASKED BY THE
explained also for declaring this winding as stabilized MEMBERS OF THE SOCIETY
winding.
Concepts on Q1. Why Loads are not connected during Boost Charge
1. Reduction in Third Harmonic Contents of the output Condition of a battery Charger?
voltage Q2.Why Tap Cell is connected in Boost Charge Mode
2. Reduction in zero Sequence phase impendence of the but not in Float Charge mode?
transformer. Q3.Why Wave Trap is connected in Rph and Bph but
3. Permits to cause internal circulation of third harmonic not in Yph
exciting current. Q4.Why CTS are connected between Bus Coupler
4. Restricts the transformer of unbalance three phase breaker and Transfer Bus Isolator?
loads Q5.We know that Voltage is directly proportional to
All the above concepts are related to develop a smooth frequency, but sometimes voltage decreases but not the
and balanced loading pattern to the transform. as tertiary frequencies why?
winding helps to stabilize the above effect ,so it is also
called “STABILISED WINDING” Er.P.K.Panigrahi [132/33 KV Salipur Grid S/S
MobNo-9853351091]
Q9) What is the difference between Loading Tertiary Answer to Q1: - During the Boost charge condition “
and Unloaded Tertiary? Non-connection of the load “ to the battery system is a
Ans. Loading Tertiary is designed properly with the mis-concept. Actually during Boost Charge condition,
declaration of its rated voltage, rated F.L. Current and the blocking Diode and necessary DC Contactor being in
rated MVA to the system. This type of tertiary winding action, supplies the battery voltage to the load terminals
contains three external terminals for loading of the from the Tap Cell Connection. [For other details refer
auxiliary systems like station auxiliaries, other small Jan-07 issue for Boost Charge mode explanation].
loads etc.
Practically in the form of three distinct Answer to Q2 Refer Jan-07 issue for Boost Charge
bushings, terminals are taken out for loading of the Mode explanation
windings. The necessary protection are also provided to
this type of winding [as already discussed in Qno.3] Answer to Q3 .Two types of line couplings are generally
The unloaded tertiary winding is not required to used for carrier communication purposes.
be designed strongly on the consideration of MVA rating 1.Line to Ground Coupling
or loading pattern of the system. This winding is kept to 2.Line-to-Line Coupling
For Line to Ground Coupling, any one of the phase to this protection system
conductors can be used with wave trap and coupling Note:- General practice the voltage range is 110V/√3 as
capacitor on it. Preferably either Rph or Bph line the standard .Availability of 110V is the special case as
conductor is used for this purpose. described above .
When the transmission line is long, Line-to-
Line Coupling is used so as to reduce the carrier energy Answer to Q7:- The Power Factor term is completely
loss .for this case breakage of any line conductor will not associated with the kind of load to the network.
affect the communication or relaying channel where as in According to the types of loads [resistive, inductive,
the case of Line to Ground Coupling it is affected. For capacitive etc] the current from the system voltage
this practice as on standard preference extreme phase varies, either becomes in phase, lagging or leading to the
conductors are chosen for the coupling units. There is no supply voltage .So the question asked leads to some
any specific reason for using the wave traps in Rph and misconceptions regarding the supply source. Voltage that
Bph but for convenience and to avoid communication supplied is usually taken as the reference and current
interference external phases are taken into practice. changes its direction according to the type of load.
Answer to Q4 ;- .The involvement of Bus Coupler Q8.How ‘WTI’ indicates the temperature and what is
breaker comes into circuit for the case of coupling the its principle?
two buses in the network. These two buses in the Q9.What is the working principle of Induction
network may be main bus and transfer bus or Bus-1 and Furnace?
Bus-2.When it is established for the case of main bus and Q10.What are the classes of CTs and how they are
transfer bus the following explanation holds good. classified?
The Bus Coupler breaker comes into action Q11.what is relay coordination and why it is required?
either to provide parallel path to the system or separate
individual path to maintain the faulty breaker in the Er.Ambuj kant & Er. Sunil S.Mathew [ Bhusan Steels
network. During the current flow through the Bus And Power Ltd, Jharsuguda] Mobile No-94375 58955
Coupler breaker circuit, the positioning of the CTs
should be available towards the load side, due to the Answer to Q8:- WTI stands for Winding Temperature
energisation of CTS at the near end of load. So the CTs Indicator and generally used in electrical device to
are connected between Bus coupler Breaker and Transfer measure the temperature of the winding .The principal
Bus Isolator. But it may be noted here that the placement element of WTI contains 1.A Heater Coil 2.measuring
of CTs can be done also in between Bus Coupler breaker Bellow and 3. Adjustable shunt resistor.
and main isolator if it is found convenient in the network. The heater coil is fitted around the measuring
bellow and supplied from the winding CT secondary
Answer to Q5: . The voltage as asked might be the circuit these coil simulates Hot Spot Temperature of the
terminal voltage which changes due to different reasons winding over the top Oil temperature due to current from
like variation of load current, Electrical actions like cross the winding CT. The measuring bellow reacts to the
and demagnetization effect etc. But the actual EMF simulated temperature and top oil temperature measured
[Electro Magnetic Force] that generated by the by the probe connected to thermal pocket. So the
generator/alternator depends upon the frequency. The combined temperature becomes indicative by the
change of EMF is directly proportional to the frequency indicator
not the Terminal Voltage available at the load ends. During the normal condition if the transformer
is not energized to the supply system then the reading of
Q6.Why PT of different rating is used WTI and OTI becomes same .So it is understood that the
[110V /√3 and 110V] principle of thermal indicator are same, but for WTI case
Q7.If the Power Factor is leading then what will winding CT plays the role for rise of temperature above
happen i.e. what is its effect on the load (if Unity then oil temperature
what is its effect) .
Answer to Q9:- The answer is maximum related to
Er.R.P.Sahoo [220/132/33 KV Grid S/S mechanical section than the Electrical section .kindly
Katapali,OPTCL,] Mobile No-98612 50298 cooperate and bear with us for no answering this
question.
Answer to Q6; -. The rating of the PT on secondary side
depends upon the connection practice of the same on Answer to Q10:- .CTs are classified in different
primary side. Usually Primary side is connected between categories but for electrical circuit purpose CT can be
line conductor and earth terminal .So the primary side of classified of the following three types.
such PT is declared as the magnitude of [Line 1. Metering class 2. Protection class 3. Special purpose
Voltage/√3]. Now the secondary voltage is accordingly protection class
considered for the standard practice of 110V /√3.But for
some special purpose like the sensitive Ground Fault 1.Metering class- Metering core accuracy class is
Protection [Directional], the broken delta secondary usually mentioned as [0.1,0.2,0.5,1,3,5,0.2s, 0.5s]
voltage is required to be availed from the PT Lower the limit of error causes more accuracy and vice-
secondaries. Sometimes it is needed to avail 110V supply versa.
2.Protection Class- Protection Class of accuracy is with direction, because of phase angle difference among
generally expressed as [5P, 10P, 15P etc]. The them. So these meters provide either direction of display
expression is always followed by ALF (Accuracy Limit reading.
Factor) and expressed as 5P10, 10P20 etc But for ammeter and voltmeter, only the single
5P10: - Stands for the accuracy class with 5% composite parameter either voltage element or current element is
Error for 10 times Primary current in CT. used to measure the reading of the instruments. So the
3. Special purpose protection class:- Such type of CT direction factor does not come into picture and display
core is best suitable for the relaying circuit to the balance becomes unidirectional.
protection schemes like differential circuit, distance
relays etc.. The Knee Point Voltage( Kn) excitation Answer to Q15:- For a particular reference between
current and secondary resistance play the important role pneumatic and spring, it can not be judged regarding the
to decide the performance of the CT performance of the breaker mechanism. Pneumatic
Answer to Q11:- The gradation of the Relays in the system has its own advantages like simplicity in
network and settings of the Relays according to the Short operation and less mechanical stiffness of the operating
Circuit fault MVA on the system is called Relay Co- system. But the major disadvantages are its leakage in
Ordination the system and maintenance to avoid corrosion to the
The purpose of the relay Co-Ordination is to develop operating system.
a systematic tripping action of the necessary and Spring mechanism is gaining popularity now-a-days,
associated relays on the network during the time of fault. due to its performance activities towards operation of
If the relays are properly co-coordinated the faulty breaker mechanism. More over the leakage and corrosion
lines/equipments get isolated due to in time operation due to air contamination to the operating mechanism is
active relays. completely absent. So the breaker with spring
mechanism is better in comparison to the pneumatic
Q12. What is the necessity of VAR in the electrical mechanism.
system, mainly in transmission system?
Q13.What is the measuring accuracy class ( Cl 0.2,0.5 Q. 16: In which frequency we should stop for recording
etc..) for the measuring devices? the power consumption in energy meters
Q14. Why “MW Meter” shows both +ve and –Ve Q17.In case of 3ph, 4wire system, and the neutral is
reading ( i.e. Export and Import) while current disconnected. Why the meter showing the value above
(Ammeter) only shows one side reading? 350volts in 2 phases?
Q15 Which type of Breaker mechanism is better Q18.What is the behaviour of CT and PT if core is
“Pneumatic’, “Spring” or Both and Why? saturated and in which condition saturation will occur?
Q19.In, which condition the phase angle, changes from
Er. NirbiShankar Sahoo [220/132/33 KV Grid S/S its normal value of supply voltage?
B.Padar,OPTCL,] Mobile No-98612 70781
Er.Tapan samant & Pradip Ku
Answer to Q12:- .VAR in system plays the role for Samal[MRT,Wesco,Burla] Mobile No-9938560206
control of voltage levels. Particularly in transmission line
the VAR generated or absorbed in the system adjusts the Answer to Q16:- .There is no any particular standard for
voltage level. the energy meter beyond which we should stop recording
If there is a deficiency of reactive power voltage the power consumption the meter. However fundamental
levels will fall. Conversely if there is an excess of frequency of 50HZ is taken as the standard for energy
reactive power voltage levels will rise. Therefore the measurement.
voltage level in a power system is carried out by Sometimes due to the presence of harmonics the
controlling the generation, the absorption, and the flow frequency of the system becomes other than the normal
of reactive Volt Ampere (VARs) in the system. value. For detail IS 14697:1999 and IS 13779:1993 may
be referred as the standard.
Answer to Q13:- Every measuring device in electrical
system if connected in the secondary side of the Answer to Q17:- .For 3ph,4wire system neutral is
instrument transformers then the accuracy of these considered as the reference terminal and voltages are
devices depends upon the sensitivity of the instruments. accordingly displaced with each other by the balance
Every device is declared with its accuracy class (0.2,0.5 magnitude of phase displacement 1200.The voltages in
etc). The accuracy class gives an idea regarding the limit the meter taking the neutral point as the reference
of error of the instrument. The lower the accuracy class accordingly are displayed. Now for the disconnection of
the limit of error is less and accuracy is more. The neutral point to the system, the reference point is
following table is provided for reference. different. But for particular case of reverse connection of
any one of the voltage coil internally will result the
Answer to Q1 4:- “.MW Meter”, MVAR Meter, Energy voltage of magnitude √3 times as that of reference, as
meters etc work on the principle of directional relay. like asked in the question.
These instruments need current coils and voltage coils in
action to cause the power reading in display.
Involvement of current and voltage coils are associated
Explanation:- for some time (without any load). If the reverse reactive
Vector diagram with neutral in connection to the system power detection relay is not in the system, what should
and earthed causes the voltage in regular sequence. be the effect on the alternator during the above
Though ‘YPH’ coil is reversly connected still due to mentioned condition?
earth reference the open end potential becomes in regular
sequence. Er.Santanu Dash. OCL, RAJGANGPUR
VR=V ang 00 , Vy=V ang -120, VB=V ang 1200 , 9437226095(Mobile)
Answer to Q20:- For HT cable termination work
B
ang 1200
Now VN=VR+ Vy+ VB = V ang 00 + Vang 600+ V ang joints spark ,then oxygen /atmospheric contamination to
it enhances this sparking. Moreover air pocket /void etc
B
120 0= 2V ang 60
VRN = VR - VN = V ang 00 - 2V ang 60 =√3V ang -90 also becomes responsible for rupture of the cable. Plain
VYN = Vy - VN = V ang 60 - 2V ang 60 = -V ang 600 = V brass cable glands cannot provide proper tightness
ang -120 0 among the strands of the cable conductor so end points
VBN = VB - VN = V ang 120 0 - 2Vang 600 = V(-1.5 – need to be moulded by jointing kit with proper skirts
j0.866) = -√3V ang 300 = √3V ang -1500 over it.
So when any one phase reverses and neutral is Earthing of the shield for HT cable at both end
disconnected then any two of the phases will show points are always advisable if the earth terminals are
proper and reduced with least resistance as possible. But
voltage of magnitude √3V = 350 to 400volt as explained
the case of abnormality in earth resistance or earthing
in detail vector diagram.
points, due to electrostatic potential difference, certain
leakage current starts to flow through the sheath and
causes burning of the shielding material.
So for such condition it is advisable to earth at one
terminal of earth proper resistance for single earth
terminal the circulation current does not occur.
5. Email Address: -
6. Technical Profile ##
$$ $$
7. Mode of Payment Rs 200 /- 1 Year Subscription ,Rs 350 /- for 2 Years subscription
Signature
## ( Your experiences in Technical field, Technical Topics of interest for Technical Interaction for Every month’s
Question Answer Session
(Example:- Protection & Control of Electrical equipments, Operation & Maintenance of Electrical equipments,
Installation practices of the Equipments etc…)
Sl No of the member
Receipt No
Remarks