Numerical

Motor Protection
Adding to the PROCOM range of modular relays, the
NPM800 relays protect high power MV and LV motors.

As well as the usual functions of


protection, NP800 relays provide
monitoring, measurement and
recording of the electrical quantities
of the network.
The relays can be set locally, using
either the keypad or the RS232 port,
or remotely using the RS485 port.
The calculation of electrical values is
achieved by Fast Fourier
Transforms.
The settings, readings, measurements
and recordings are all available
locally or remotely.

Functions

• Thermal overload [49] • Locked rotor [51LR]


• Short-circuit between phases [50] • Start authorisation by number of starts
• Earth fault [51N] [66]
INDUSTRIELLE DE CONTRÔLE • Pump un-priming [37I] • Start inhibition by temperature [5]
ET D’EQUIPEMENT • Unbalance, loss of load or phase • Measurement of starting current and time
11, rue Marcel Sembat reversal [46] • Circuit breaker failure protection [50BF]
94146 ALFORTVILLE Cedex • Too long starting [48] • Latching output contacts [86]
Tél : +33 1 41 79 76 00
Fax : +33 1 41 79 76 01
Site : www.icelec.com
E-mail : [email protected]
CHARACTERISTICS
Auxiliary Supply
• Auxiliary supply ranges 19 to 70 – 85 to 255 / DC or AC 50 or 60 Hz
• Typical burden 6W (DC), 6 VA (AC)
• Power off withstand 20 ms
• Memory backup 72 hours
Analogue Inputs
• Phase current inputs In 1 or 5A measurement from 0.3 to 24 In – burden at In < 0.2 VA
continuous rating 3 In, short duration withstand 100 In/1s
display of primary currents from 0 to 64 kA
• Earth current input In0 1 or 5A measurement from 0.03 to 2.4 In0 – burden at In0 < 0.5 VA
continuous rating 2 In0, short duration withstand 40 In0 / 1s
display of primary current from 0 to 6.4 kA
Earth current input from Ring CT 100/1 adjustment from 0.6 to 48 A primary
• Display accuracy phases current: 2% from 0.6 In to 1.4 In, 5% under and over
Zero sequence current : 2% from 0.06 In to 0.14 In, 5% under and over
• Recommended CTs 5VA 5P15
Logical Inputs (4, 8 with option)
• Level 0 < 10V range 19 to 70 Vdc / Vac – < 33V range 85 to 255 Vdc / Vac
• Level 1 > 20V range 19 to 70 Vdc / Vac – > 37V range 85 to 255 Vdc / Vac
• Burden < 15 mA
Relays Outputs (4, 8 with option)
• Relay A, B option E, F double contact NO, permanent current 8A
closing capacity 10 A/4 s
short circuit current withstand 100A/30ms
breaking capacity DC with L/R = 40 ms: 50W
breaking capacity AC with cos ϕ = 0. 4:1250 VA
• Relay C, watchdog, option D, G changeover contact, permanent current 16 A
closing capacity 25 A/4 s
short circuit current withstand 250 A/30 ms
breaking capacity DC with L/R = 40 ms: 50W
breaking capacity AC with cos ϕ = 0.4: 1250 VA
Locked Rotor and Start Authorisation/Inhibition [5] [51LR] [66]
• Too long starting current threshold 1 to 10 Iref
• Start time 2 to 200 s
• Locked rotor threshold 1 to 10 Iref
• Locked rotor time delay 0.2 to 10.0 s
• Number of authorised starts (N) from 1 to 4
• Time during which N starts are authorised 15 to 60 min
• Time during which new start is inhibited 15 to 60 min
• Hot starting control 40 to 100% ΘIref
Thermal Overload [49]
• Timing curves according to IEC 255-8
• Heating time constant CTE 4 to 180 min, class 5
• Cooling time constant 1 to 6.0 CTE, in step of 0.1
• Negative sequence factor 0 to 9
• Starting factor 50 to 100%
• Thermal reference current Iref. 40 to 130% In, class 5
• Thermal alarm threshold 80 to 100% Θ Iref, class 5
• Restarting inhibit thermal threshold 40 to 100% Iref, class 5
Phase/Earth Fault Overcurrent and Too Long Start [50] [51N] [48]
• Phase fault thresholds 0.3 to 24 In
• Earth fault thresholds 0.03 to 2.4 In
• Independent operating time [50] 40, 50 or 60 ms including trip relay for I ≥ 2 Is, to 3 s
Adjustable up to 3 s
• Independent time delays from 40 ms to 300 s
• Accuracy of independent times ± 2% or 20 ms
• Timing curves [51N] and [48] according to IEC 255-4, ANSI IEEE and configurable (factory set, consult us)
• Dependent time delays class 5
Pump Unpriming [37I]
• Current threshold 0.2 to 1.4 In
• Release time 0.06 to 120 s
• Resetting percentage 105 to 107%
NPM800
Unbalance, Loss of Load or Phase Reversal [46]
• Ineg threshold 20 to 80% In
• Operating time 1 to 10 s
• Resetting percentage 93 to 95%
Motor Starting Function
• Coefficient 50 to 200%
• Starting duration 40 ms to 300 s
Load Shedding option
• Operating time 60 ms to 120 s
• Tripping time 100 to 500 ms
• Level 1 to 6
Reload option
• Operating time 1 to 120 s
• Reclosing time 100 to 500 ms
Counters
• Break current A2 per phase I1 or I3 maximum 64 106 kA2
• Number of operations 0 to 10,000
User Programmable Functions [input – output]
• Time delay of the user programmable inputs
• Status in or out of service
• Operating and release time delays 40ms to 300 s
• Assignment of name (maximum 14 characters)
• Assignment of one or more output relays (alarm or trip)
Programming
• Display French, English
• Configuration software under Windows® 95, 98, NT, 2000, XP
French, English, Spanish, Italian
MODBUS® Communication (option)
• Transmission asynchronous series, 2 wires
• Interface RS 485
• Transmission speed 300 to 115 000 bauds
IEC 60870 – 5 – 103 Communication (option)
Consult us
Disturbance Recording
• Number of recordings 4
• Total duration 52 periods per recording
• Pre fault time adjustable from 0 to 52 periods
Environment
• Transient impulses 5 ns IEC 801.4 class 4 (equivalent IEC 255-22-4 class 4)
• Shock IEC 255-4 class 3 (5 kV – 1,2/50µs)
• Dielectric withstand IEC 255-5 class 3 (2 kVrms – 1 min)
• Insulation resistance > 1 000 MΩ according to IEC 255-5
• EMC emissivity EN 55011 class A – EN50081-2 group 1
• EMC susceptibility IEC 255-22 (1/2/3/4)
• Operating temperature -10 to + 55°C – IEC 68-2-1/2
• Vibrations IEC 255.21.1 class 1
• Mechanical shocks IEC 255.21.2 class 1
• E.U. low voltage directive 89/336/CEE dated 03.05.1989
• Water and dust protection IP51 – IEC 529 (front face)
Presentation
• Height 4U
1
• Width 4/ 19"
• Brackets 19" rack mounting option
• Display 2 lines of 16 characters
• Output relays 3 or 7, user programmable
• Logical inputs 4 or 8, user programmable
• LED indication 1 for Watchdog, and 4 user programmable
Dimensions
• Height, Width, Depth 173 x 106.3 x 250 mm
• Weight 4 kg
Characteristics • Remote reading of disturbance recording and event log
• Self-diagnosis: RAM, ROM, EEPROM, output relays, A/D converters, auxiliary
• 2 ranges of auxiliary supply voltages covering any supply, cycles of execution of the software, hardware anomaly
DC or AC voltage • Test of wiring, phase rotation and direction of current
• Configuration and parameter setting by local HMI or • LED "Starting authorised (or inhibited)" with settable function
off-line or on-line PC
• Reading and saving relay configuration using PC Options
• Measurement of electrical quantities: Average,
instantaneous and maximum values of I1, I3 and Io • Communication by Modbus® or IEC 60870-5-103 protocol
currents • Remote control: trip or reclosing, load-shedding with level of priority, and
Display expressed in primary current (I1 and I3 from reconnection control
0 to 10 kA, I0 from 0 to 1,0 kA) • 4 user programmable output relays and 4 user programmable logical inputs
• Measurement of the starting current • 2 dependent time, configurable and downloadable curves
• Measurement of the starting time (factory set, consult us)
• Measurement of the negative sequence current • Trip circuit supervision (a group of 4 inputs is required)
• Measurement of the thermal state
• Indication of the number of authorised starts
• 2 setting groups, locally or remotely selectable
Functional diagram
• Breaker failure monitoring: discrepancy of interlocks,
local or remote control of reclosing / tripping
• Assistance with circuit breaker maintenance: number
of operations and break current I2 per phase
counters, alarms
• Breaker failure monitoring by checking disappearance
of the currents when opening the circuit breaker
• Configuration and operation software compatible with
Windows® 95, 98, NT, 2000, XP
• User interface with access to all functions
• Time stamping of internal events with 1 ms resolution
• Event recording: 250 locally recorded events,
200 retained in the event of loss of auxiliary supply
• Storing of measurements and active settings group
• Local/remote acknowledgement of events
• Disturbance recording according to Comtrade format:
storage of four 52 periods recordings
• Disturbance recording initiated by binary input, setting
software or communication network
• Recording of current and duration of the last start
• Motor starting function: shift of phase, zero sequence
and inverse current thresholds from external input
• Remote setting, remote reading of measurements,
counters, alarms, and parameter settings