POLYCAB THREE CORE MV AS/NZS 1429.1 12.7/22 (24) KV POLYCAB THREE CORE MV AS/NZS 1429.1 12.

7/22 (24) KV
MV Cable with Copper Conductor, XLPE Insulation, Copper Screen and Unarmoured MV Cable with Copper Conductor, XLPE Insulation, Copper Screen and Unarmoured

ELECTRICAL CHARACTERISTICS:
No. Core Max. DC Max. AC Approx. Approx. Approx. Continuous Current Rating No. of Core Cross Max. Charging Zero Electric Short circuit
of Cross Resistance Resistance Capacitance Inductance Reactance Buried direct In a In Air Cores sectional Area pulling tension Current sequence Stress at rating of
Cores sectional at 20˚C at 90˚C in ground buried duct on conductor per phase impedance Conductor Screen Phase conductor
Area
No. mm2 kN Amps/Km Ohms/Km kV/mm kA, 1 sec
3 35 2.45 0.64 1.83 3.7 5.0
No. mm2 Ω/km Ω/km µF/km mH/km Ω/km Amps
3 50 3.5 0.68 1.66 3.5 7.2
3 35 0.524 0.668 0.16 0.625 0.196 153 133 170
3 70 4.9 0.8 1.50 3.4 10.0
3 50 0.387 0.494 0.17 0.604 0.190 181 158 204
3 95 6.65 0.88 1.41 3.2 13.6
3 70 0.268 0.342 0.2 0.569 0.179 221 193 253
3 120 8.4 0.96 1.36 3.1 17.1
3 95 0.193 0.246 0.22 0.551 0.173 262 231 304
3 150 10.5 1.04 1.32 3.1 21.4
3 120 0.153 0.196 0.24 0.533 0.167 298 264 351
3 185 12.95 1.12 1.29 3.0 26.4
3 150 0.124 0.159 0.26 0.521 0.164 334 297 398
3 240 16.8 1.24 1.26 2.9 34.3
3 185 0.0991 0.127 0.28 0.509 0.160 377 336 455
3 300 21 1.32 1.24 2.9 42.8
3 240 0.0754 0.097 0.31 0.496 0.156 434 390 531
3 400 28 1.48 1.22 2.8 56.9
3 300 0.0601 0.078 0.33 0.484 0.152 489 441 606
3 500 35 1.64 1.21 2.7 71.5
3 400 0.047 0.062 0.37 0.473 0.149 553 501 696
3 500 0.0366 0.049 0.41 0.462 0.145 632 574 800

*: Current Ratings are based on IEC 60502-2 & IEC 60287, Max. Conductor Temperature at 90®C, Ambient
temperature at 30®C in Air / at 20®C in Ground, Thermal resistivity of Soil 1.5 k.m/W & for earthenware ducts
1.2k.m/W and Depth of Laying 0.8m.

Current rating de-rating factors for other than 30®C ambient air temperature.

20 25 35 40 45 50 55 60
1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

Current rating de-rating factors for other than 20®C ground temperature.

10 15 25 30 35 40 45 50
1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76

OUR CERTIFICATION
ABS OUR CERTIFICATION
ABS
ISO ISO ISO ISO ISO ISO
9001 14001 45001 9001 14001 45001
106 107