Sintesog–gg
panels,gnetwork,gg
andgaccessoriesg
Planning Tool
Answersgforginfrastructure.
Yourgsystemgforgfiregdetection,gg
alarming,gandgcontrol:gSinteso
Danger
management
Remote access system from
with SintesoView Customer network Ethernet Siemens
Security module
(firewall)
FN2009-A1
Security module
(firewall)
FN2009-A1
Ethernet switch
FN2008-A1 Backbone (FCnet/LAN)
Ethernet switch Ethernet switch Ethernet switch
FN2008-A1 FN2008-A1 FN2008-A1
Manual call
point
FDM223
Alarm
sounder FDnet
FDS221 Fire control panel Fire control panel Fire terminal
FC2020 FC2020 FT2040
Fire control panel
Sounder base Floor repeater FC2060
FDSB291 terminal FT2010
Cluster
(FCnet/SAFEDLINK)
ASA neural
Fault transmission
fire detector
FDOOTC241
Alarm transmission Input module
FDCI222
Floor repeater
display FT2011
ASA wide-spectrum
smoke detector Fire control panel ASA heat detector
FDO241 FDnet ASA neural
fire detector
FC2040 FDT241
Collective FDOOT241-9
detector LaserFOCUS
Alarm VLF-500
sounder beacon Input/output module Radio
FDS229-R FDCIO222 smoke detector
DOW1171 FDnet Stub line
Radio gateway
Video Fire FDCW221 Smoke detector
DO1101A-Ex ASA flame
Controller
Extinguishing detector
FDV241 CCTV camera
control unit XC1001-A Safety barrier FDF241-9
DA wide-spectrum
smoke detector SB3
FDO221
ASA neural Sinorix Manual call Input/output ASA linear Mimic
fire detector extinguishing point module “transponder” smoke detector display driver
Manual release FDOOT241-9 solution FDM223 FDCIO223 FDL241-9 FT2001-A1
Ethernet
Backbone (FCnet/LAN)
Cluster (FCnet/SAFEDLINK)
FDnet
Application:gcomplexgbuildingg
Network in a complex building, for example a hospital.
Description Benefits
In complex buildings, the fire safety system can – Only one remote transmission to fire brigade – Timely hand-over thanks to parallel commis-
be adapted to local circumstances. The control necessary for entire system sioning of individual panels or clusters
panels as well as fire terminals are networked – One interface to common pager system – Distributed intelligence: complete control in
together via clusters (FCnet/SAFEDLINK). These – Overview of entire system from any configured the event of a fire is mapped in a cluster; this
clusters are interconnected via industrial LAN terminal enables ideal adaptation to structural as well as
technology per backbone (FCnet/LAN) to create – Fiber-optic backbone with high immunity to process requirements
an EN 54-compliant overall system. electromagnetic disturbance
– System-wide EN 54-compliant operation
Backbone (FCnet/LAN)
Cluster (FCnet/SAFEDLINK)
Application:glargegcampus
Extensive network spanning large distances, for example a production plant in the
pharmaceutical industry.
Description Benefits
A campus comprises numerous, independent – Intelligently arranged network structure with – Distributed intelligence: complete control
buildings. These have their own organization clearly defined clusters in the event of a fire is mapped in a cluster;
and structure that can be mapped ideally with – Only one control panel necessary to access this enables ideal adaptation to structural
a cluster of up to 16 panels. The backbone entire system with all subnetworks and process conditions
connects these clusters to an EN 54-compliant – Backbone is EMC protected and EN 54-compliant – Security personnel has entire campus in view
network. – Commissioning is possible at several locations – The right information at the right place:
simultaneously (gain in time) pre-defined views can be displayed according
– Only one central connection to pager system to customer requirements over the entire
for entire system system; all controls can be configured to
fulfill site-specific requirements
Backbone (FCnet/LAN)
Cluster (FCnet/SAFEDLINK)
Topologyg1g
Up to 16 panels can be networked in a cluster (FCnet/SAFEDLINK) – if connected
to a danger management system. Without a danger management system, even up to
32 panels can be networked.
Danger
management
system from
Siemens
Ethernet
Without connection to
a danger management
system: up to 32 panels
can be networked in a
cluster.
Cluster Fault transmission
(FCnet/SAFEDLINK)
Alarm transmission
Characteristics of topology example Key data
– Easy networking of panels – Max. number of networkable panels: 32
– Operation of panels as stand-alone solution or – Max. number of networkable panels if
networked with a total length of up to 460 km connected to a danger management
– Data rate can be adapted to line quality system: 16
– Max. distance between panels with
copper cable:
• without repeater: 1,000 m
• with repeater: 2,000 m
– Max. distance between panels with
fiber-optic cable:
• multi mode: 2,500 m
• single mode: 15,000 m
– Max. number of panels with
system-wide view: 5
Topologyg2
Up to 64 panels in one EN 54-compliant system with widely varying combinations
of clusters and backbone – and with connection to a danger management system
via a customer network.
Danger
management
Remote access system from
with SintesoView Customer Network Ethernet Siemens
Backbone (FCnet/LAN)
Cluster Cluster
(FCnet/SAFEDLINK) (FCnet/SAFEDLINK)
Fault transmission
Alarm transmission
Characteristics of topology example Key data
– EN 54-compliant networking of up to 64 panels – Max. number of networkable panels
via backbone incl. clusters (EN 54-compliant): 64
– Extensive networks spanning long distances – Max. number of clusters: 14
– Highest system availability thanks to system- – Max. number of networkable panels
wide redundancy per cluster: 16
– Panels in different clusters can communicate – Number of panels with system-wide view: 5*
with each other
– Only one remote transmission to fire brigade * more with appropriate system topology
necessary for entire system
– Distributed building complexes can be
ideally protected
– Backbone realized with fiber-optic cable
Topologyg3
Use of a customer network to transmit relevant information from several locations
to a central danger management station.
Danger
management
system from
Siemens
Locality 1 Locality 2
Ethernet Ethernet
Customer Network
Cluster Cluster
(FCnet/SAFEDLINK) (FCnet/SAFEDLINK)
Fault transmission Fault transmission
Alarm transmission Alarm transmission
Characteristics of topology example Key data
– Connection of independent location with a – Max. number of networkable panels
danger management station via IT network per cluster: 16
provided by the customer
– Reduced installation or maintenance costs The maximum number of clusters, panels or data
thanks to usage of customer networks points is dependent on the management station.
– Autonomous clusters with their own remote
transmission to fire brigade (to fulfill EN 54
regulations)
SintesogPlanninggToolg–gpanels,gnetwork,gandgaccessories
Answersgforginfrastructure.
Danger management system Network components Expansion and networking options
The danger management system from Siemens is connected via Ethernet. Security module (firewall) FN2009-A1 The security module can be easily Loop extension (FDnet) RS232 module (isolated) FCA2001-A1 Sounder module FCA2005-A1
To enable remote operation with SintesoView, a Customer network Ethernet It is either directly connected to the backbone (via Ethernet switch) or via Protects devices and networks in auto- integrated into a panel with: FCI2003-A1 This module is needed, for example, for The sounder module has connections
PC can be connected to an Ethernet switch along the customer network by using adequate safety measures (e.g. safety mod- mation and industrial communication – FHA2029-A1 for housing (Comfort) The loop extension makes it operating an event printer. It is plugged for 4 conventional sounder lines (primary
the backbone. Access to a certain panel in a cluster Security ule or PC software). Each station addressed by the danger management with a combination of different security Art. no.: S54400-B79-A1 possible to double the number into the PMI mainboard. The RS232 lines; 4x up to 1 A, max. 2 A total). The
will be granted by installing an L1 license key into module system must be enabled by means of the license key (L2). measures such as firewall and VPN of loops (e.g. from 2 loops to 4 module is not contained in the set for sounder module is screwed to the assem-
this panel. (firewall) – FHA2030-A1 for housing (Large
(Virtual Private Network) via IPsec tunnel: loops or from 4 loops to 8 loops) the event printer. bly plate FHA2007-A1.
FN2009-A1 Extension)
– data espionage while retaining a constant total Art. no.: A5Q00005327 Art. no.: A5Q00014866
Remote access – data manipulation Art. no.: S54400-B81-A1 number of addresses on the
with SintesoView – unauthorized access FDnet line card (e.g. 2 loops
Security RS485 module (isolated) FCA2002-A1 License key L1 FCA2012-A1
module Art. no.: S54400-F95-A1 with 126 addresses each or 4 This is needed, for example, for operat- Activates the SintesoView function. For
Ethernet switch FN2008-A1
(firewall) loops with 63 addresses each). ing the following modules: operating SintesoView, an L1 has to be
The Ethernet switch connects clusters
FN2009-A1 with the backbone: Art. no.: A5Q00010136 – Fire brigade display panel installed in only one station.
– Managed Ethernet switch (FAT) [DE] Art. no.: A5Q00018856
– 4x10/100 Mbit/s RJ45 connections Network module (SAFEDLINK) – Fire brigade display panel with inte-
– 2x100 Mbits/s multi mode BFOC FN2001-A1 grated fire brigade operating panel
Backbone Fire control panel Fire control panel Fire control panel
– LED diagnosis With this module, the station can (FAT and FBF) [DE & CZ]
License key L2 FCA2013-A1
Activates the SintesoView function and
Fire control panel be networked via the cluster. – EVAC module [NL] the connection to the danger manage-
(FCnet/LAN) Ethernet switch
FN2008-A1
FC2040-AA FC2040-AE FC2040-AG FC2040-BB
To fulfill special requirements regarding
redundancy, a cluster with a second panel
For this purpose it is necessary
to install a network module. In
– UGA 20 [FR]
The RS485 module (isolated) is plugged
ment system. Every station that needs
consisting of: consisting of: consisting of: consisting of: and a second switch to the backbone can to be accessed by a management system
Clusters can be networked via an Ethernet back- case of additional requirements into the PMI mainboard. must have L2 installed.
Control unit Control unit Control unit Control unit be added. For example for:
bone, using industrial LAN technology. Siemens is in terms of the degrade mode Art. no.: A5Q00009923
– Optional: event printer FTO2001 – Optional: event printer FTO2001 – Optional: event printer FTO2001 – Including Nordic key switch for – Cluster with more than 512 detectors/ Art. no.: A5Q00018857
the first manufacturer who offers this as EN 54- function, 2 network modules can
– Optional: key switch KABA FTO2005 – Optional: key switch KABA FTO2005 – Optional: key switch KABA FTO2005 operation access manual call points
approved solution. With standard IT architecture, be installed.
Operating add-on Operating add-on Operating add-on – Optional: event printer FTO2001 – Cluster with remote transmission in
building structures and organizational processes For example for:
– Optional: 48 or 96 display groups – 48 display groups each with one – 96 display groups each with one Housing systems with more than 512 detectors
can be ideally represented. – Networked panels with more
each with one red and one yellow red and one yellow LED (overall) red and one yellow LED – Large: 430x796x260 mm (WxHxD) Art. no.: S54400-F94-A1 than 512 FDnet devices
Characteristics of networking via backbone
– Ethernet switch to connect a cluster (FCnet/
LED (overall) – Optional: 96 display groups each
with one red and one yellow LED
Housing – With A3 plan compartment
– 150 W power supply
The Ethernet switch can be easily inte- – Networked panel with connec- Housings
Housing – Comfort: 430x796x160 mm (WxHxD) grated into panels or additional housings tion to remote transmission
SAFEDLINK) to the backbone (FCnet/LAN) – Optional: up to two 150 W addi-
– Comfort: 430x796x160 mm (WxHxD) Housing – 150 W power supply using the corresponding mounting kits: and with more than 512 FDnet
– Redundant transmission thanks to circular wiring System-wide view – Comfort: 430x796x160 mm (WxHxD) – Max. battery capacity: 2x26 Ah tional power supply (FP2005-A1) Housing (Eco) FH2001-A1 Housing (Large) FH2005-A1
– 150 W power supply – FHA2029-A1 for housing (Comfort) devices
– Redundant connection possible due to two with the fire terminal – 150 W power supply – Max. battery capacity: 2x45 Ah – Max. battery capacity: 2x7 Ah Housing for larger batteries
– Max. battery capacity: 2x26 Ah Art. no.: A5Q00016854
Ethernet switches FT2040-EZ – Max. battery capacity: 2x26 Ah
Art. no.: S54400-B79-A1 Art. no.: A5Q00012851 – 430x398x80 mm (WxHxD) – Max. battery capacity: 2x65 Ah
Art. no.: A5Q00016100 Art. no.: A5Q00025413
– Increased EMC protection thanks to fiber-optic – FHA2030-A1 for housing (Large – Optional: power supply kit (70 W) – 430x796x260 mm (WxHxD)
cabling Art. no.: A5Q00016852 FP2003-A1 – Optional: power supply kit (70 W)
Extension)
– Easily programmable, EN 54-compliant system- – Optional: event printer FTO2001-A1 FP2003-A1 or
Art. no.: S54400-B81-A1
wide control – Optional: 48 or 96 display groups – Optional: power supply kit (150 W)
Ethernet switch
– Configurable view of each panel Backbone (FCnet/LAN) FN2008-A1 each with one red and one yellow LED FP2004-A1 and additional power
– Each panel can be used as a router panel (please (overall) supply (150 W) FP2005-A1
read separate documentation). Art. no.: A5Q00016865 – Optional: event printer FTO2001-A1
Key data – Optional: 48 or 96 display groups
In the basic version each
– Max. number of panels in EN 54 system: 64 FC2040 control panel
Repeater (SAFEDLINK) FN2002-A1 Housing (Standard) FH2002-A1 each with one red and one yellow LED
– Max. number of panels in a cluster: 16 contains: The repeater doubles the range between – Max. battery capacity: 2x12 Ah (overall)
– Max. number of networkable clusters: 14 Alarm transmission 2 FCnet stations (from 1,000 m to 2,000 m). – 430x398x160 mm (WxHxD) Art. no.: A5Q00019543
Fault transmission
– Number of panels placed directly on backbone: 4* A separate power supply is needed. – Optional: power supply kit (70 W)
Fire controls
– Number of panels with system-wide view:
– Max. distance between clusters
5*
Cluster (FCnet/SAFEDLINK) Monitoring of 2 conven-
tional sounder lines
Art. no.: S24236-B2502-A1 FP2003-A1 or
– Optional: power supply kit (150 W)
Flush mounting bezel one HU
FHA2017-A1
(fiber optic: multi mode): 3,000 m FP2004-A1 and additional power Optional bezel for flush mounting
* more with appropriate system topology supply (150 W) FP2005-A1 installation for all fire control panels
– Optional: event printer FTO2001-A1 and FT20 operator terminals;
The following guidelines must be considered
– Optional: 48 or 96 display groups 530x500 mm (WxH)
– To fulfill the EN 54 norm, only 1 Ethernet switch
each with one red and one yellow LED Art. no.: A5Q00024719
is required to connect control panels with less
(overall)
than 512 fire detectors to the backbone.
Art. no.: A5Q00018931 Flush mounting bezel two HU
Fire control panel Fire control panel FHA2015-A1
Housing (Comfort) FH2003-A1 Optional bezel for flush mounting
FC2020 (2-loop) Fire control panel FC2040 (4-loop) FC2060 (modular) – Max. battery capacity: 2x26 Ah installation for all fire control panels
– 430x796x160 mm (WxHxD) and FT20 operator terminals;
– Optional: power supply kit (70 W) 530x886 mm (WxH)
Fire control panel FC2020-AZ Description Description Technical data Description FP2003-A1 or Art. no.: A5Q00024621
consisting of: The FC2020 is a compact 2-loop fire control panel. The FC2040 is a compact 4-loop fire control panel. FDnet detector lines The FC2060 is a modular fire control panel. – Optional: power supply kit (150 W)
Cluster Control unit
– Optional: event printer FTO2001
It has the following features:
– 2 FDnet loops
It has the following features:
– 4 FDnet loops
– Number of addresses: max. 504
– Number of loops/stubs: 4/8
It has the following features:
– 4 FDnet loops
FP2004-A1 and additional power
supply (150 W) FP2005-A1
(FCnet/SAFEDLINK) – Optional: key switch KABA FTO2005
Housing
– Integrated inputs/outputs for peripherals
– Integrated control unit
– Integrated inputs/outputs for peripherals
– Integrated control unit
– Optional with loop extension:
8 loops/16 stubs
– 5 slots for additional module bus cards
– Integrated inputs/outputs for peripherals
– Optional: event printer FTO2001-A1
– Optional: 48 or 96 display groups
– Integrated power supply – Integrated power supply Inputs and outputs – Integrated control unit each with one red and one yellow LED Housing (Eco + plan compartment)
– Standard: 430x398x160 mm (WxHxD)
Via the powerful FCnet/SAFEDLINK, up to 32 panels – Automatic configuration – Automatic configuration – Integrated power supply (overall) FH2006-A1
– 70 W power supply – 1 relay output for RT alarm
can be networked (fire control panels and fire – Networkability via FCnet/SAFEDLINK – Networkability via FCnet/SAFEDLINK – Automatic configuration Art. no.: A5Q00009906 Eco housing with A4 plan compartment;
– Max. battery capacity: 2x12 Ah – 1 relay output for RT fault
terminals). or Ethernet or Ethernet – Networkability via FCnet/SAFEDLINK 430x398x80 mm (WxHxD)
– 1 monitored alarm output
Art. no.: A5Q00015550 or Ethernet
Characteristics of networking via the system bus – 1 monitored fault output Housing (Large extension) Art. no.: A5Q00022364
– Wiring with two-wire lines Technical data – 2 monitored sounder outputs (1 A each) FH2004-A1
– Redundant transmission thanks to circular wiring – 12 configurable inputs/outputs 24 V Technical data Housing for larger batteries
– Increased safety due to degrade mode using a FDnet detector lines – Max. battery capacity: 2x65 Ah
– 1 Ethernet connection (RJ45) Housing (Standard + plan
second network module – Number of addresses: max. 252 FDnet detector lines – 430x398x260 mm (WxHxD)
– Optional: sounder module for splitting the compartment) FH2007-A1
– No additional cabling necessary for degrade Fire control panel FC2020-EZ – Number of loops/stubs: 2/4 – Number of addresses: max. 1,512 – Optional: power supply kit (70 W)
sounder line output into 4 monitored outputs (2 A) Standard housing with A4 plan
mode; even for systems with more than 512 fire – Optional with loop extension: – Number of integrated loops/stubs: 4/8 FP2003-A1 or
consisting of: compartment;
detectors 4 loops/8 stubs – Optional: expandable up to 28/56 loops/stubs – Optional: power supply kit (150 W)
Control unit 430x398x160 mm (WxHxD)
– Configurable view of individual panels Inputs and outputs Inputs and outputs FP2004-A1 and additional power
– 24 display groups each with one red Art. no.: A5Q00022369
Key data – 1 relay output for RT alarm – 1 relay output for RT alarm supply (150 W) FP2005-A1
and one yellow LED
– Max. number of panels in a cluster:
– Max. number of panels in a cluster
32 – Optional: key switch KABA FTO2005
– 1 relay output for RT fault
– 1 monitored alarm output
Fire terminal FT2040 – 1 relay output for RT fault
– 1 monitored alarm output
– Optional: event printer FTO2001-A1
– Optional: 48 or 96 display groups 19“ mounting kit FHA2016-A1
Housing – 1 monitored fault output – 1 monitored fault output each with one red and one yellow LED Enables all fire control panels and
if connected to a danger management
system: 16
– Standard: 430x398x160 mm (WxHxD) – 1 monitored sounder output (1 A) Description Technical data – 2 monitored sounder outputs (1 A each) (overall) operator terminals to be mounted in a
– 70 W power supply – 8 configurable inputs/outputs 24 V – 12 configurable inputs/outputs 24 V 19‘‘ frame; 430x100x324 mm (WxHxD)
– Max. distance between panels with The FT2040 has the following features: – DC 24 V system power supply Art. no.: A5Q00018778
– Max. battery capacity: 2x12 Ah – 1 Ethernet connection (RJ45) – 1 Ethernet connection (RJ45)
copper cable – Integrated control unit – Alarm current: 130 mA Art. no.: A5Q00020179
• without repeater: 1,000 m Art. no.: A5Q00016827 – Optional: sounder module for splitting the – Separate DC 24 V supply input possible – Optional: sounder module for splitting the
• with repeater: 2,000 m sounder line output into 4 monitored outputs (2 A) – Redundant DC 24 V supply input sounder line output into 4 monitored outputs
– Max. distance between panels with
fiber-optic cable
– Networkability via FCnet/SAFEDLINK
or Ethernet
Module bus cards for FC2060 Operating add-ons
• multi mode: 2,500 m
Line card (FDnet) FCL2001-A1 Operating add-on (2xLED incl.)
• single mode: 15,000 m
For 252 FDnet devices on max. 4 loops FCM2006-A1
– Max. number of panels with
or 8 stubs. This contains 48 display groups each
system-wide view: 5
Art. no.: A5Q00009875 with one red and one yellow LED. Any
events can be allocated to the LEDs;
Line card (collective) 427x200x25 mm (WxHxD)
FCL2002-A1 Optional: Event printer FTO2001-A1
To connect collective Siemens standard Art. no.: A5Q00021771
detectors on 8 stubs (MS7/9, MS24,
FDnet In the basic version
each FC2020 control
Fire terminal FT2040-AZ Fire terminal FT2040-EZ
In the basic version
each FC2060 control DS11/Sigmacon/SymoLINE600, and
FDOOT241-9).
Operating add-on (4xLED incl.)
panel contains: panel contains: FCM2007-A1
The FDnet (Field Device network) is a modern, Alarm transmission consisting of: consisting of: Alarm transmission
Art. no.: A5Q00010502 This contains 96 display groups each
Fault transmission Fault transmission
multipurpose bus system. It allows rapid, fail-safe Fire controls Control unit Control unit Fire controls
with one red and one yellow LED. Any
communication between the Sinteso™ bus elements Monitoring of 1 con- – Optional: event printer FTO2001 – 24 display groups each with one red Monitoring of 2 con- I/O card (programmable) events can be allocated to the LEDs;
ventional sounder line ventional sounder lines 427x200x25 mm (WxHxD)
and the fire control panel. – Optional: key switch KABA FTO2005 and one yellow LED FCI2008-A1
Characteristics of networking via the detector Housing – Optional: key switch KABA FTO2005 12 programmable inputs/outputs with Art. no.: A5Q00021772
bus
Fire control panel FC2020-AA Fire control panel FC2020-AE Fire control panel FC2020-BB Housing selectable behavior in degrade mode.
– Eco: 430x398x80 mm (WxHxD) Floor repeater display FT2011 Floor repeater terminal FT2010-A1 Fire control panel FC2060-BB Fire control panel FC2060-AA
– Use of all cable types (shielded or unshielded) consisting of: consisting of: consisting of: – Optional: 70 W power supply – Eco: 430x398x80 mm (WxHxD) Art. no.: S54400-A6-A1 Key switch Kaba FTO2005-C1
Used for the display of messages from Used for the display and control of consisting of: consisting of:
– Integration of star-shaped cable networks without Control unit Control unit Control unit – Max. battery capacity: 2x7 Ah – Optional: 70 W power supply Kaba lock cylinder with installation
the monitored area messages from the monitored area Control unit Control unit accessories and keys Kaba 8 #100.
modifications to cable network – Optional: event printer FTO2001 – Optional: event printer FTO2001 – Including Nordic key switch for – Optional: 48 or 96 display groups each – Max. battery capacity: 2x7 Ah
– Shielding not necessary with one red and one yellow LED in – Optional: 48 or 96 display groups each Art. no.: A5Q00017706 Art. no.: A5Q00014104 – Including Nordic key switch for – Optional: event printer FTO2001 Usable optionally for enabling operation.
– Optional: key switch KABA FTO2005 – Optional: key switch KABA FTO2005 operation access
operation access – Optional: key switch set KABA 2005
– 2-wire loop
– Power supply to all bus elements via the FDnet
Operating add-on Operating add-on – Optional: event printer FTO2001 Eco housing with 48 display groups
(FH2001-E1) or with 96 display groups
with one red and one yellow LED in
Eco housing with 48 display groups – Optional: event printer FTO2001 Operating add-on
Power supply Art. no.: A5Q00010113
– Optional: 48 or 96 display groups – 48 display groups each with one red Housing Shared properties
(except “transponder” FDCIO223, LaserFOCUS, (FH2001-G1) (FH2001-E1) or with 96 display groups Housing – Optional: 48 or 96 display groups, Key switch Nordic FTO2006-B1
each with one red and one yellow LED and one yellow LED – Comfort: 430x796x160 mm (WxHxD) – Backlit display with plain text display (6 lines of 40 characters each) Power supply kit (70 W)
extinguishing control unit XC10, video fire Art. no.: A5Q00016702 (FH2001-G1) – Large: 430x796x260 mm (WxHxD) each with one red and one yellow LED Key set with mounting accessories. Opti-
(overall) – Optional: 96 display groups each with – With A3 plan compartment – Power supply and communication (individually addressed) via FDnet, FP2003-A1
controller FDV241) Art. no.: A5Q00016720 – With A3 plan compartment (overall) mally applicable for operation clearance.
Housing one red and one yellow LED (overall) – 70 W power supply additional 24-V supply possible For the independent power supply of
Key data – 150 W power supply Housing
– Comfort: 430x796x160 mm (WxHxD) Housing – Max. battery capacity: 2x17 Ah – 282x207x79 mm (WxHxD) fire terminals such as FT724-ZZ Art. no.: A5Q00010129
– Up to 40 T-taps – Optional: up to two 150 W addi- – Large: 430x796x260 mm (WxHxD)
– 150 W power supply – Comfort: 430x796x160 mm (WxHxD) Art. no.: A5Q00025412 – Max. 8 FT2010/FT2011 per FC2020
– Up to 126 bus elements on one loop tional power supply (FP2005-A1) – 150 W power supply Art. no.: A5Q00016005
– Max. battery capacity: 2x26 Ah – 150 W power supply ASA neural – Max. 16 FT2010/FT2011 per FC2040 Event printer FTO2001-A1
– Cable lengths up to 3.3 km with up to 126 bus – Max. battery capacity: 2x45 Ah – Optional: up to two 150 W additional
– Max. battery capacity: 2x26 Ah fire detector – Max. 50 FT2010/FT2011 per FC2060 The event printer FTO2001-A1 is installed
elements Art. no.: A5Q00016829 Art. no.: S54400-C4-A2 power supply (FP2005-A1) Power supply kit (150 W)
FDOOT241-9 directly in the control panel or in the ter-
Art. no.: A5Q00016851 – Max. battery capacity: 2x45 Ah FP2004-A1 minal. It is a thermal printer which logs
Power supply for installation in empty all events. An RS232 module (isolated)
Art. no.: A5Q00023048
housings. Optional: Additional power FCA2001-A1 is required for operating
supply with FP2005-A1 is possible. the event printer. This is not contained
Alarm sounder Art. no.: A5Q00020825 in the printer set and must be ordered
FDS221-R separately.
Additional power supply (150 W) Art. no.: A5Q00010126
FDnet FP2005-A1
Additional power supply can be Event printer DL3750+
connected in the housing directly
Legend for the interfaces: (For further details see also the Sinteso after FP2004-A1.
Monitored external event printer for serial
connection or via Ethernet. Optional:
Planning Tool – FDnet devices)
Backbone (FCnet/LAN) Network to connect clusters Art. no.: A5Q00018779 RS232 module (isolated) FCA2001-A1
Manual call point, red
Cluster (FCnet/SAFEDLINK) Network to connect panels
FDM223 Art. no.: A5Q00023962
FDnet Network to connect Sinteso devices
© Siemens 2010
Answers for infrastructure.
■ Megatrends driving the future ■ Increase productivity and efficiency
The megatrends – demographic change, through complete building life cycle
urbanization, climate change, and glo- management
balization – are shaping the world today. Building Technologies offers intelligent
These have an unprecedented impact integrated solutions for industry, com-
on our lives and on vital sectors of our mercial and residential buildings, and
economy. public infrastructure. Over the entire
facility’s life cycle, our comprehensive
■ Innovative technologies to answer and environmentally conscious port-
the associated toughest questions folio of products, systems, solutions,
Throughout a 160-year history of pro- and services for low-voltage power
ven research and engineering talent, distribution and electrical installation
with more than 50,000 active patents, technology, building automation,
Siemens has continuously provided its fire safety and security ensures the:
customers with innovations in the areas – optimum comfort and highest energy
of healthcare, energy, industry, and efficiency in buildings,
infrastructure – globally and locally. – safety and security for people,
processes, and assets,
– increased business productivity.
Siemens Switzerland Ltd
Industry Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel +41 41 724 24 24
The information in this document contains general descriptions of technical options available,
which do not always have to be present in individual cases. The required features should therefore
be specified in each individual case at the time of closing the contract.
© Siemens Switzerland Ltd, 2010 • Order no. 0-92235-en