PAC-SF46EPA Databook
PAC-SF46EPA Databook
Table 3-14-1 The equivalent power consumption by Indoor units, LOSSNAY, OA processing units, controllers
Indoor, OA unit Indoor unit BC controller MA RC. LOSSNAY ME Remote Contr. Timers, System Contr. ON/OFF Contr.
Sized P20-P140 Sized P200,P250 CMB-P-V PAR-21MAA PAR-F27MEA PAC-SC30GRA GB-50A PAC-YT40ANRA
GUF-50,100 PAC-YT51CRB PAC-SE51CRA PAC-SF44SRA
PAR-FA32MA PZ-52SF PAC-YT34STA
LGH-RX-E G-50A
1 7 2 0 1/4 1/2 3 1
*RC : Remote Controller
Table 3-14-2 The equivalent power supply of Trans. Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster Power supply unit Outdoor unit Outdoor unit
PAC-SF46EPA PAC-SC50KUA Connector TB3 and TB7 total * Connector TB7 only
25 6 32 6
*If PAC-SC50KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.
With the equivalent power consumption values in Table 3-14-1 and Table 3-14-2, PAC-SF46EPA can be designed into the air-
conditioner system to ensure proper system communication according to 3-14-1-A, B, C.
3-14-1-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, OA process units and ME remote controller,
Timers and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor
unit sized P200, 250 is counted as 2 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.
3-14-1-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consump-
tion reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC50KUA is used to supply power at TB7 side, count
from TB3 side only.
3-14-1-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption
reaches 6, a PAC-SF46EPA should be set.