Fire Detection System Manual
Fire Detection System Manual
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07, Autronica Fire and Security
Table of Contents
1. Introduction ..................................................................... 7
1.1 About the Handbook .......................................................................... 7
1.2 The Reader ........................................................................................ 7
1.3 Reference Documentation ................................................................. 7
1.4 Components ...................................................................................... 8
9. Supervisory ..................................................................... 40
9.1 Indications during Supervisory ........................................................... 40
9.2 Actions to be Taken during Supervisory ............................................ 40
12. Disabling.......................................................................... 46
12.1 Introduction ........................................................................................ 46
12.2 Disable Menu ..................................................................................... 46
12.3 Disabling Activated / Deactivated Components ................................. 47
12.4 Disabling Detection Zones ................................................................. 47
12.5 Disabling Alarm Zones....................................................................... 47
12.6 Disabling Points ................................................................................. 47
12.7 Disabling Fire Alarm Devices............................................................. 48
12.8 Disabling Outputs (Loop Outputs/Local Outputs) .............................. 48
12.9 Disabling Inputs (Loop Inputs/Local Inputs)....................................... 48
12.10 Disabling Routing Equipment ............................................................ 48
12.11 Disabling Loop IO Carriers ................................................................ 49
12.12 Example – How to Disable a Detection Zone .................................... 49
13. Enabling........................................................................... 51
13.1 Introducion ......................................................................................... 51
13.2 Enable Menu ...................................................................................... 51
13.3 Enabling Deactivated Components ................................................... 52
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 4
Introduction
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 5
Introduction
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 6
Introduction
1. Introduction
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 7
Introduction
1.4 Components
The Autroprime Interactive Fire Alarm System comprises the following components
(EN-54) :
B C
Fire Alarm
C Device
A Control
and
Fire indicating E F
A
detectors equipment
Fire Alarm Fire Receiving
D Points Routing Eq. Station
D
Manual J K
call-points
Fault Warning
Fault Warning
Receiving
Routing Eq.
Station
G H
Control for
Automatic Automatic Fire
Fire Protection Eq. Protection Eq.
L
Power
Supply
Note:
The lines linking the various components on the illustration indicate information flows,
and not physical interconnections.
Item G and H and some other items may need to be provided with a seperate power supply.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 8
The Operator Panel
2.1 Introduction
The Operator Panel BS-210, including an upper and a lower section, is an
integrated part of the Fire Alarm Control Panel BS-200, BS-200L and BS-200M.
The Repeater Panel BS-211 is identical with the Operator Panel, with the exception
of the alphanumeric keypad at the lower section.
The other Autroprime panels; the Information Panel BV-210 (no operating buttons
available) and the Fire Brigade Panel BU-210 consist only of the upper section of
the panel.
During normal operation, the backlight in the panel display is ON. No operating
buttons and indicators are visible, except for the Power indicator that always
displays a steady green light when the power is ON and the
Apart from this, only indicators relevant to the actual condition are visible. For
example, if a fault is present the fault indicator will have a yellow light. A backlight
will appear only on buttons that are currently available (relevant to the actual
condition).
The illustration below shows the Operator Panel with its panel display, operating
buttons and indicators.
Indicators
Panel display
Upper
section
Lower
section
Alphanumeric keypad /
Operating Buttons
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 9
The Operator Panel
2.2 Indicators
Pre Alarm One or more detection zones are in the pre-alarm state.
Remote Call Steady red light when the message is sent to a remote device, for example, the
Fire Brigade.
Remote Call Response Steady yellow light when an acknowledge message is received from the remote
device, for example, the Fire Brigade.
Fault The presence of a fault.
• Pulsing light
Unacknowledged fault warnings exist
• Steady light
All fault warnings have been acknowledged
Disabled Function Steady yellow light when one or more of the following components are in the
disabled state:
• detection zones and alarm zones
• individual points
• outputs and inputs
• Fire Alarm Devices, Fire Alarm Routing Equipment, Fire Protection
Equipment and Fault Warning Routing Equipment.
Test Condition Steady yellow light when one or more of the following components have been
manually set to the test condition:
• detection zones and alarm zones
• fire alarm devices
• outputs
Supervisory Condition The presence of an input device (for example, door control units, monitor and
control units) that is in the supervisory state.
• A pulsing light
Unacknowledged points in Supervisory state exist
• Steady light
All points in Supervisory state have been acknowledged
System Fault Steady yellow light when a system fault is present.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 10
The Operator Panel
Delayed Activation Steady yellow light indicates that Immediate Output Actioning
has been changed to delayed output actioning (manually or
automatically by using the Day/Night function), meaning that
a delay period is active for Fire Alarm Devices (FAD), Fire
Alarm Routing Equipment (FARE) and all other outputs that
are connected to the detection zone of this type.
Annunciator Fault Pulsing yellow light when a fault is detected (and not
accepted) on one or more Fire Alarm Devices (FAD). Steady
yellow light when accepted.
The yellow Fault indicator will have the identical behaviour.
Remote Call Fault Pulsing yellow light when a fault is detected (and not
accepted) on Fire Alarm Routing Equipment (FARE). Steady
yellow light when accepted.
The yellow Fault indicator will have the identical behaviour.
Annunciator Disabled Steady yellow light when one or more Fire Alarm Devices are
disabled.
The Disabled Function indicator will also have a steady yellow
light when one or more FADs are disabled.
Disabling an alarm zone will also disable the FADs in this
zone.
Remote Call Disabled Steady yellow light when the signal to Fire Alarm Routing
Equipment (FARE) has been disabled.
The Disabled Function indicator will also have a steady yellow
light when FARE is disabled.
Reduced Detection Steady yellow light when a MultiSensor is switched into
Operation Class “Heat Only”.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 11
The Operator Panel
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 12
The Operator Panel
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 13
The Operator Panel
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 14
The Operator Panel
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 15
The Operator Panel
The internal buzzer can be silenced by pressing the Mute Panel button.
If the cause for making the buzzer signal sound is still present, the buzzer will
resound after a predefined time.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 16
Operation Mode
3. Operation Mode
3.3 Conditions
In Operation Mode, the system can be in quiescent condition (lowest priority), or in
one or any combination of the following conditions:
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 17
Operation Mode
Whenever a detector detects a transition from one alarm level to another (from
lower level to the highest level), this event is reported to the system as a Pre Alarm
or Fire Alarm signal, which in turn will initiate the appropriate actions.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 18
Operation Mode
The example below shows a situation where 2 detection zones are in alarm state.
The first and the last detection zone are shown in the display, including information
on the name of detectors and locations. The total number of zones is shown in the
upper right corner of the display.
Total number of
detection zones
in alarm state
• Scroll (up and down) with the arrow buttons to find and select the
wanted point.
A black mark on the vertical scroolbar on the right side of the display indicates that
you can scroll downwards (or upwards) to reveal more information. Note that this is
not indicated on the illustration.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 19
Operation Mode
At this stage, the resound timer will start (if it has been configured). The resound
timer will restart on each operation of the Silence button.
Holding the Silence button down for more than 5 seconds will activate the Resound
function.
The alarm zones are automatically resounded to their alarm states on timeout
(configurable) of the Silence resound timer.
3.10.1 Overview
Autroprime supports the following disablement sources:
• Individual
A unit is disabled by an individual command issued to the specified unit.
Applicable to all units with disabling capabilities.
• Loop
A unit is disabled by its corresponding loop being disabled. Applicable to points,
FADs, FPEs and panels connected to loops (DID).
• Detection Zone
A point is disabled by a command to its corresponding detection zone, affecting
all points in the detection zone, including any manual call points. Applicable to
points only.
• Alarm Zone
FADs in an alarm zone will be disabled.
• Disable Input Unit
A detection zone is disabled by a command from a Disable Input Unit. Applicable
to detection zones only.
• Modbus
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 20
Operation Mode
Example:
A Point is disabled from a Zone (Detection Zone disable command issued from the
Fire Alarm Control Panel) and from a Disable Input Unit. For the Point to become
enabled, a DZ enable command must be issued from the Operator Panel and the
Restore button on the Disable Input Unit must be pressed.
The system provides the following types of detection zones with different properties:
• Immediate Action detection zone
• Dependency Action detection zone
• Delayed Action detection zone
• Delayed Dependency detection zone
• SOLAS (Safety of Life at Sea) detection zone
The property of a detection zone as well as the type of point (detector or manual
call point) will determine how the system responds to the signal - with respect to
action.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 21
Operation Mode
For example, a detection zone in alarm can activate a number of alarm zones. The
delay period before activation can be defined according to the property of the
chosen detection zone type.
An alarm zone can give both an alarm signal (EVACUATE) and a neighbouring
alarm zone signal (ALERT) with a different pattern.
The top-level alarm zone (default) is called the Parent Alarm Zone. A system
consists of a Parent Alarm Zone, usually with several “sub-level” alarm zones in an
hierarchy. Each “sub level”-alarm zone is related to a specific area of, for example,
a building. If an alarm occurs in a Parent Alarm Zone, all Fire Alarm Devices
(FADs) within this zone, plus all FADs belonging to all “sub-level”-alarm zones will
be activated.
Immediate Action applies to all units that can be activated by a Immediate Action
Detection Zone.
At least two detectors in the same detection zone must be in alarm state before
actions are initiated.
It is also possible to configure the system in such a way that a Large Alarm will be
initiated if at least two detectors in the entire system are in alarm state, regardless
of which detection zone each detector belongs to.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 22
Operation Mode
When the operator panel receives a fire alarm signal from a point in a Delayed
Action detection zone (configurable), the actioning of outputs to Fire Alarm Devices
(FAD) and/or Fire Alarm Routing Equipment (FARE) can be delayed.
The purpose of this type of alarm organization is to give an immediate warning, but
to delay the activation of outputs. In this way the cause of the alarm can be
investigated before the system automatically initiates the evacuation of the
protected premises and signals the local fire brigade.
Delayed Action is based on the first point reporting the fire. A second point in alarm
in the same detection zone will not affect the delay of the connected outputs.
In an alarm situation, the actioning of outputs will be delayed when the detection
zone has been defined as a Delayed Action detection zone (configurable) and the
point(s) in this Delayed Action detection zone has been set to Override Delay and
Dependency, NO.
The operation of delays to outputs for Fire Alarm Devices (FAD) apply to:
• detectors and/or
• manual call points and/or
• signals from specific zones
The operation of delays to outputs for Fire Alarm Routing Equipment (FARE) apply
to:
• detectors and/or
• signals from specific zones
The delay is divided into two delay periods, Initial delay, T1 (configurable) and
Prolonged Delay, T2 (configurable). The default value for T1 is 1 minute and 2
minutes for T2.
The T1 delay period is started when a Fire Alarm signal from a point is received.
Actions will be initiated after the T1 delay period has expired. Pressing PROLONG
DELAY, will terminate T1 and the delay period T2 will start.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 23
Operation Mode
T1 for different detection zones may start at different times, however, when Prolong
Delay has been pressed, T2 for all detection zones will start at the same time.
If one or more Delayed Action detection zones have entered the Fire Alarm state
and are in their T1 or T2 periods, the delayed actions can be immediately initiated
by pressing the Activate Outputs button. Activation of a manual call point will also
give immediate action (provided that the point has been set to Override Delay and
Dependency, YES).
In Day Mode, outputs that are configured to be activated by these detection zones
will operate according to their actual configuration, i.e. Silent Alarm, Small Alarm or
Large Alarm as follows:
• When a fire alarm signal from the first detector in alarm is received, the following
will occur:
o The detection zone will enter the Silent Alarm state, and all FPE outputs
configured to be activated on Silent Alarm will be activated. The T1 delay
period will start.
o When the T1 delay period expires, the detection zone will enter the Small
Alarm state. All FPE outputs configured to be activated on Small Alarm will be
activated. The T2 delay period will start.
o When the T2 delay period expires, the detection zone will enter the Large
Alarm state. All FPE outputs configured to be activated on Large Alarm will
operate.
• Note that, at any time, if an alarm from a second detector within the same
detection zone is received, the detection zone will always enter the Large Alarm
State. This means that all (not yet activated) FPEs configured to be activated on
Silent, Small and Large Alarm will be activated.
In Night Mode, outputs are always activated on the first detector in alarm and the
system will always enter the Large Alarm state. As with Day Mode this means that
all (not yet activated) FPEs configured to be activated on Silent, Small and Large
Alarm will operate.
Note that when a point sends an alarm signal, and this point has
been set to Override Delay and Dependency, YES, the Delayed
Dependency detection zone will enter the Large Alarm state
directly, regardless of Day or Night Mode.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 24
Operation Mode
A detection zone configured as SOLAS Detection Zone (Safety of Life at Sea), has
a two-minute delay from when a Point enters an alarm condition until the
associated Detection Zone initiates the activation of the configured Fire Alarm
Devices (FADs) and outputs.
During this period a countdown timer is shown in the panel display and the user has
the ability to block the activation of FADs and/or outputs during the two minute
period.
The Activate Outputs button can be used to activate the FADs and outputs that are
in this two minute transition period or that have previously been blocked.
The Silence button can be used to control the FADs independently of the Block
operation. The Silence function will affect all FADs that have been activated.
Autroprime also has a Resound function that will reverse the effect of Silence.
Three “levels” have been defined regarding the progress of a fire alarm situation
that can be utilized to activate outputs. If delays are activated, the normal situation
will be that all activations will take place at the ‘Large Alarm’ level, both signalling
the fire brigade (FARE), sounders (FADs) and any other delayed output (FPE).
Activating outputs (FPE) at other levels may be obtained selecting these levels
through configuration.
The table on the next page indicates which levels are available for different types of
detection zones.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 25
Operation Mode
Silent Alarm
Any fire alarm signal will be indicated at the panel without any delay, and this is the
Silent Alarm level. An output may be configured to be activated at this level, as an
example to trigger a coded message through a voice alarm system or an output to
make on site technical personnel aware of the situation.
The delay timer T1 will be started and a countdown timer will be shown in the
display. For a Delayed detection zone the operator may now initiate a prolonged T2
period.
Small Alarm
In the case of a Delayed Dependency detection zone there is an automatic transfer
from the initial T1 delay period to the prolonged T2 delay period. When this transfer
occurs the level will be increased to Small Alarm. Looking at a shopping centre this
level may be used for another voice alarm message making the employees start
the preparations for an evacuation. The display will show the T2 countdown.
(Small alarm level is also shown for Delayed and Dependency zones, but should
not be used as an activation criteria for outputs.)
Large Alarm
The table below shows that this level is the last one (or only) for all types of
detection zones. There are different ways of getting to this level, either elapsed
timers (T1 and/or T2), a second alarm signal or a panel operation. If not configured
otherwise, all outputs will be activated at this level, fire brigade (FARE), sounders
(FAD) and any other outputs (FPE).
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 26
About «In the Event of….»
The list above covers the most common events. In addition to these, a great
number of combinations of events may, of course, occur.
For each event there is an overview of all indications on the panel, plus the
necessary actions to take. All alarm handling and display pictures shown in the
subsequent chapters are based on the following:
• To operate the panel, Access Level 2 is required. This means that the person
operating the panel, must use a key before the panel can be operated. This is
indicated with a key.
• As you proceed through the steps in the different events, the comments field will,
when necessary, provide additional information and show the different options
you have.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 27
In the Event of a Fire Alarm
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 28
In the Event of a Fire Alarm
Comments: In this example, a total of 2 detection zones are in alarm state. If you want to
view detailed zonal/point information for each zone before investigating the
scene(s), go to step 5. If not, investigate the scene(s), then go directly to
step 7.
move back using the Cancel button , then select another point in
step 5 and repeat step 6. If not, go directly to step 7.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 29
In the Event of a Fire Alarm
If no points are signalling an alarm, the system is reset and the display will return to its idle state.
If there are points still signalling an alarm when the system has been reset, go to step 9.
10 Scroll downwards
11 Scroll downwards
12 To select a specific
point, scroll with the
arrow up/down buttons
to highlight this point.
To multiselect several
consecutive points in
the list that are to be
disabled, press and
hold down the Select
button
and at the same time
scroll with the arrow up
or down button (a mark
will appear to the left of
each the selected
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 30
In the Event of a Fire Alarm
To multiselect points
one-by-one, press the
Select button to mark a
point, then scroll to
another point in the list
and press the Select
button once more to
mark the next one.
twice.
To reactivate the point(s), you have to enable the points that have been disabled.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 31
In the Event of a Pre Alarm
Comments: The detection zone(s) and point(s) in pre alarm state are highlighted in the
display.
The red Pre Alarm indicator is pulsing.
When several zones are in pre-alarm state, the More Events indicator is
pulsing.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 32
In the Event of a Pre Alarm
Comments: In this example, a total of 3 points are in Pre Alarm state. If you want to view
detailed point information before investigating the scene(s), go to step 5. If
not, investigate the scene(s), then go directly to step 7.
move back using the Cancel button , then select another point in
step 5 and repeat step 6. If not, go directly to step 7.
7 To acknowledge a Pre
Alarm, press the red
Silence button.
Comments: When the situation is under control (smoke is exhausted, new glass replaced
in the manual call points, etc.), the system should be returned to normal
operating mode (step 8).
Comments: The red Pre Alarm indicator goes off, and the panel enters its idle state.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 33
In the Event of a Fire Alarm -
with Alarm Delay
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 34
In the Event of a Fire Alarm -
with Alarm Delay
Comments: In this example, 1 point is in alarm state. If you want to view detailed point
information before investigating the scene, continue with the next step. If not,
investigate the scene, then go directly to step 7.
Comments: If you want to view detailed information for another point (if any);
move back using the Cancel button , then select another point in
step 3, repeat step 4.
Comments: The delay is divided into two delay periods, Initial Delay, T1 (configurable)
and Prolonged Delay, T2 (configurable).
The T1 delay period is started when a Fire Alarm signal from a point is
received. Actions will be initiated after the T1 delay period has expired.
Pressing Prolong Delay will terminate T1 and the delay period T2 will start.
T1 for different detection zones may start at different times, however, when
Prolong Delay has been pressed, T2 for all detection zones will start at the
same time.
6 Investigate the
scene(s), and carry out
the necessary actions.
Comments: The next action depends on whether or not there really is a fire.
If there is not a fire, go to step 10 (press the green Reset button).
If there really is a fire, continue with the next step.
If no points are signalling an alarm, the system is reset and the display will return to its idle state.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 36
In the Event of Faults
- System Fault
- Annunciator Fault
- Remote Call Fault
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 37
In the Event of Faults
Comments: In this example, a total of 2 points are in Fault state. If you want to view
detailed information for each point in Fault state before investigating the
scene(s), continue with the next step. If not, go directly to step 6.
4 To select a point,
scroll with the arrow
up/down buttons.
5 To view detailed
information for a
selected point, press
then scroll
downwards
move back using the Cancel button , then select another point in step
4, repeat step 5. If not, go directly to the next step.
Fault messages provide the following information:
1. A description of the fault.
2. A suggestion on how to solve the problem.
3. The time of event.
6 Investigate the
scene(s) and carry
out the necessary
actions.
Comments: Now you may acknowledge either each fault one by one (Acknowledge), or
you can acknowledge all faults (Acknowledge All).
7 To acknowledge the
fault(s), move back
one level using the
Cancel button
Comments: Faults can be acknowledged from the detailed information window as well.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 38
In the Event of Faults
Press
Comments: When a fault is acknowledged, an asterisk (*) appears to the left of the
acknowledged point.
When all faults have been acknowledged, the yellow Fault indicator and all
other fault indicators will go steady.
When all faults have been repaired, the system can be reset.
Comments: The yellow Fault indicator and all other fault indicators go off, and the panel
enters its idle state (if faults have been repaired).
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 39
Supervisory
9. Supervisory
4 To view detailed
information for the
selected point, press
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 40
Supervisory
then scroll
downwards
5 Investigate the
scene(s) and carry
out the necessary
actions.
Comments: Now you may acknowledge the point in Supervisory state (Acknowledge).
6 To acknowledge the
point in Supervisory
state, move back one
level using the Cancel
button
Comments: The point in Supervisory state can be acknowledged from the detailed
information window as well.
Press
Comments: When the point is acknowledged, an asterisk appears to the left of the point.
The yellow Supervisory indicator will go steady.
The system can now be reset.
Comments: The yellow Supervisory indicator goes off, and the panel enters its idle state.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 41
Menu Mode
and hold down the Enter button for a few seconds.
The number and type of menu selections that appear in the display in Menu Mode
depends on the current access level (1, 2 or 3).
NOTE: If the panel is set to access level 1 (no key or password), the following is shown in
The Silence the display:
button and the
Reset button can
be operated both
in Menu Mode
and in Operation
Mode.
If the panel is set to access level 2 (the key is turned clock-wise), six different menu
selections are shown in the display, including System Status, Disable, Enable,
Show Unit Properties, Report and Enter Service Mode. If the panel is set to access
level 3 (Service Mode is entered using a password), the seventh menu selection
Exit Service Mode is shown in the display.
• To manually re-enter operation mode, press and hold down the Enter button
for a few seconds.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 42
Menu Mode
• Press Enter twice, then use the alphanumeric keypad and type the password
that has been selected during commissioning (4 characters).
The menu selections Service and Exit Service Mode now appear in the display.
To enter the Service menu, use the arrow down button to scroll down and select
Service, then press the Enter button
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 43
System Status
11.1 Introduction
NOTE: The System Status menu is accessed from the main menu in Menu Mode. The
System Status Menu is accessed with access level 1 (no key or password
Access Level 1
(no key or
required).
password
required). The menu gives the current status of the following conditions:
• Alarms
• Pre Alarms
• Faults
• Disablements
• Tests
• Supervisory
• Activated Outputs/Inputs
• To enter the Menu Mode from operation mode or the panel’s idle state, press
and hold down the Enter button for a few seconds.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 44
System Status
The total number of detection zones (in this example, 2) in alarm state is shown in
the upper right corner of the display.
• Use the arrow down button to scroll down and select a detection zone.
• To view detailed information for a point, press
• Use the arrow down button to scroll down and view all information.
• To return to Operation Mode, press and hold down the Enter button for a
few seconds.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 45
Disabling
12. Disabling
12.1 Introduction
From the Disable menu you can disable the following:
NOTE:
• Detection Zone
Access Level 2
• Alarm Zone
(access by key).
• Point (detectors, manual call points)
• Fire Alarm Device (FAD)
• Loop Outputs
• Local Outputs
• Loop Inputs
• Local Inputs
• Routing Equipment (FARE/FWRE)
• Loop IO Carriers
When disabling components, a disable time span is given. The disable time span
can be changed for already disabled components by entering the disable menu.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 46
Disabling
Both activated and deactivated disabled components will remain switched off until
enabled.
A disable time span can be set. When the disable time span expires, the detection
zone will automatically be enabled. The detection zone can also be enabled
manually from the Enable Menu.
A disable time span can be set. When the disable time span expires, the alarm
zone will automatically be enabled. The alarm zone can also be enabled manually
from the Enable Menu (or disablement window).
A disable time span can be set. When the disable time span expires, the point(s)
will automatically be enabled. The point(s) can also be enabled manually from the
Enable Menu (or disablement window).
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 47
Disabling
You can disable a single unit (FAD)/alarm circuit, or all units (FADs) in a selected
Alarm Zone.
A disable time span can be set. When the disable time span expires, the FAD(s)
will automatically be enabled. The single FAD or all FADs in a selected Alarm Zone
can also be enabled manually from the Enable Menu.
A disable time span can be set. When the disable time span expires, the outputs
which control Fire Protection Equipment will automatically be enabled. The outputs
can also be enabled manually from the Enable Menu.
A disable time span can be set. When the disable time span expires, the signals
from external equipment to the inputs will automatically be enabled, i.e. received by
the panel/system.
Fire Alarm Routing Equipment (FARE): In the event of an alarm, no fire alarm
signals/fault signals will be sent to the fire brigade.
Fault Warning Routing Equipment (FWRE): In the event of a fault, no fault warning
signals will be sent to, for example, the security firm.
A disable time span can be set. When the disable time span expires, the Routing
Equipment which is disabled will automatically be enabled. The equipment can also
be enabled manually from the Enable Menu.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 48
Disabling
• To enter the Menu Mode from operation mode or the panel’s idle state, press
and hold down the Enter button for a few seconds.
• Use the arrow down button to scroll down and select Disable.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 49
Disabling
• Use the arrow button to scroll down and select, for example, “Detection Zone1”.
• Use the alphanumeric display to enter the disable time span (hours:minutes).
Note that the yellow Disabled Function indicator is lit (steady yellow light).
The detection zone and all points within this detection zone are disabled.
After a period of time, the display will enter operation mode. The disabled detection
zones are shown in the display.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 50
Enabling
13. Enabling
13.1 Introducion
From the Enable menu you can enable the following components :
• Detection Zone
• Alarm Zone
• Point (detectors, manual call points)
• Fire Alarm Device (FAD)
• Loop Outputs
• Local Outputs
• Loop Inputs
• Local Inputs
• Routing Equipment (FARE/FWRE)
• Loop IO Carriers
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 51
Enabling
You can enable a single unit (FAD)/alarm circuit, or all units (FADs) in a selected
Alarm Zone.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 52
Enabling
Fire Alarm Routing Equipment (FARE): In the event of an alarm, fire alarm signals
may be sent to the fire brigade (configurable).
Fault Warning Routing Equipment (FWRE): In the event of a fault, fault warning
signals will be sent to, for example, the security firm.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 53
Enabling
• To enter the Menu Mode from operation mode or the panel’s idle state, press
and hold down the Enter button for a few seconds.
• Use the arrow down button to scroll down and select Enable.
• Use the arrow button to scroll down and select, for example, “Detection Zone1”.
• To mark the selected detection zone, press the Select button
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 54
Enabling
• If Enable Delayed Activation is set to NO, all delays will be disabled (i.e.
immediate actioning).
• If Enable Delayed Activation is set to YES, the system will delay the activation of
outputs from points (set to “Override Delay and Dependency NO”) in detection
zones configured as Delayed Action Detection Zones or Delayed Dependency
Detection Zones.
• If Day Mode Operation Times are configured or the property for an onboard input
is set to Day/Night Mode, the system will automatically change the default value
NO to YES when the new configuration is saved and the system is restarted, i.e.
all delays will be automatically enabled.
o If Enable Delayed Activation is set to NO, all delays will be disabled (i.e.
immediate actioning).
o If Enable Delayed Activation is set to YES all delays are again enabled and
controlled by Day Mode Operation Times or Day/Night inputs.
• Use the arrow down button to scroll down and select Enable.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 55
Show Unit Properties
14.1 Introduction
From the Show Unit Properties menu you can view properties for the following
NOTE:
units:
Access Level 2 • Detection Zones
(access by key).
• Alarm Zones
• Points (fire detectors, manual call points)
• Fire Alarm Devices (FAD)
• Loop Outputs
• Local Outputs
• Loop Inputs
• Local Inputs
• Loop IO Carriers
• Mimic Panels
• Activation Groups
• External Interfaces
• Detection Loops
• Operator Panels
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 56
Show Unit Properties
Using the Function button after selecting a detection zone gives the following
menu selections:
• Show Member Points
• Show Connected Units
Using the Enter button after selecting an alarm zone reveals the following
properties:
• name of the Alarm Zone
Using the Function button after selecting an alarm zone gives the following
menu selections:
• Show Member Fire Alarm Devices
• Show Neighbour Alarm Zones
• Show Activating Detection Zones
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 57
Show Unit Properties
14.5 Points
Using the Enter button after selecting a point reveals the following properties:
• name of the point
• override Delay and Dependency (YES or NO)
In an alarm situation, the actioning of outputs will be delayed when; the detection
zone has been defined as a Delayed Action detection zone (configurable) and
the point(s) in this Delayed Action detection zone has not been set to Override
Delay and Dependency, i.e. set to No.
• performance class day setting (Normal 1, Normal 2; Industrial; depending on the
type of detector)
• operation class day setting (MultiSensor with heat, MultiSensor only, Heat only)
• performance class night setting (Normal 1, Normal 2; Industrial)
• operation class night setting (MultiSensor with heat, MultiSensor only, Heat only)
Using the Function button after selecting a point gives the following menu
selections:
• Show Connected Units
Using the Function button after selecting a fire alarm device gives the following
menu selections:
• Show Connected Units
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 58
Show Unit Properties
Using the Function button after selecting a loop output gives the following
menu selections::
Not applicable to Fire Alarm Devices, Fire Alarm Routing Equipment and Fault
Warning Routing Equipment:
• Show Activating Detection Zones
• Show Activating Points
• Show Activating Inputs
• Show (activating) Activation Groups
• Show Activaing Outputs
Not applicable to Fire Alarm Routing Equipment and Fault Warning Routing
Equipment:
• Show Connected Units
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 59
Show Unit Properties
Using the Function button after selecting a local output gives the following
menu selections (note that the menu selections are not applicable to all outputs):
Not applicable to Fire Alarm Devices, Fire Alarm Routing Equipment and Fault
Warning Routing Equipment:
• Show Activating Detection Zones
• Show Activating Points
• Show Activating Inputs
• Show (activating) Activation Groups
• Show Activating Outputs
Not applicable to Fire Alarm Routing Equipment and Fault Warning Routing
Equipment:
• Show Connected Units
Using the Function button after selecting a loop input gives the following menu
selections:
• Show Connected Units
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 60
Show Unit Properties
Using the Function button after selecting a local input gives the following menu
selections:
• Show Connected Units
Using the Function button after selecting a local input gives the following menu
selections:
• Show All Carrier Units
• Show Carrier Points
• Show Carrier Inputs
• Show Carrier Outputs
Using the Function button after selecting a unit gives the following menu
selections:
• Show Mimic Boards
• Show Mimic Inputs
• Show Mimic Outputs
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 61
Show Unit Properties
Using the Enter button after selecting an activation group reveals the following
properties:
• The name of the local output
• Activate group on Unit State:
meaning which alarm level the points within this activation group will react to
(pre-alarm or alarm).
• Activation Group Dependency:
meaning how many points within this activation group that must be in alarm state
before actions are initiated (1-5 and All).
Using the Function button after selecting an activation group gives the following
menu selections:
• Show Member Points
• Show Connected Units
Using the Enter button after selecting serial port settings reveals the following
properties:
• bits per second
• word length
• parity
• stop bits
• hardware interface (RS-232, etc.)
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 62
Show Unit Properties
Using the Enter button after selecting IP Address Settings reveals the following
properties:
• own IP address
• gateway IP address
• subnet mask
Using the Enter button after selecting ESPA interface settings reveals the
following properties:
Show Settings
• name
• port (not in use, serial or TCP/IP)
• port number
• restore factory settings or not (No/Yes)
• display size (default 128), then
press Enter.
• line length (default 12)
• alphabet type (7 bits, 8 bits, or GSM)
• fault detail (Yes/No)
• startup message
Show Events
• alarm
• pre-alarm
• fault
• supervisory
• startup
• test
Show Receivers
• user name
• receiver number
• show (events)
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 63
Show Unit Properties
Using the Enter button after selecting MODBUS interface settings reveals the
following properties:
Show Settings
• name
• port (not in use, serial or TCP/IP)
• TCP/IP address
• port number
• mode (slave or master)
• restore factory settings or not (Yes/No)
• slave address (default 128)
• slave ID (default 12)
• Handshake (Yes/No)
• Report Fault (Yes/No)
• Fault Timer (default 10 seconds)
Using the Enter button after selecting Voyage Data Recorder settings reveals
the following properties:
• name
• port (not in use, serial or TCP/IP)
• port number (default 0)
• restore factory settings or not (Yes/No)
• log volume mini (Yes/No)
• active time (default 4 minutes),
determines how often a message is sent to the VDR to ensure that there is a
proper communication between the system and the VDR.
• update time (default 120 minutes),
determines how often the VDR receives a full update of all fires and fault
statuses.
Using the Enter button after selecting Show Remote Access gives the following
alternatives:
• Show Server and Web Access
• Show User Management
• Show Clients
• Show Client Proxy Server
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 64
Show Unit Properties
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 65
Report
15. Report
15.1 Introduction
The Report menu provides the following submenus:
NOTE:
• Read Log
Access Level 2
• Show Topology
(access by key).
• Show Date and Time
• Software Version Information
• Configuration Version Information
Most of the events are self-explanatory, except for Metrics which is described in the
example in the next chapter 15.3.1.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 66
Report
15.3.1 Metrics
The Metrics log contains the following metrics:
1 Each time the system starts, a «metrics» log entry is created per loop providing the
number of loops of different types, for example:
<Class = Metrics: Reason = Loop Units: Info = Loop_1: Phys = 127, Cpu = 0, Csu = 0, Psv = 59,
Pnosv = 48, Inp = 6, Out = 6, Fad = 8>
2 Each time a Self Verify is carried out (10 min after startup, + daily at 10 am)
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 67
Report
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 68
Service Commands
16.1 Introduction
From the operator panel you can perform service commands. To use the Service
Commands, access level 3 is required.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 69
Service Commands
• To stop the test, use the arrow button to select Stop Test, then press Enter
twice.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 70
Service Commands
The duration of the signal and the interval between each signal are configurable
(normally 1 second ON and 30 seconds OFF). The test signal is given the lowest
priority. In the event of an alarm, the alarm signal will thus override the test signal.
• To stop the test, use the arrow button to select Stop Test, then press Enter
twice.
The duration of the signal and the interval between each signal are configurable
(normally 1 s econd ON and 30 seconds OFF). The test signal is given the lowest
priority. In the event of an alarm, the alarm signal will thus override the test signal.
• To stop the test, use the arrow button to select Stop Test, then press Enter
twice.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 71
Service Commands
NOTE:
Before this test is performed, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is to
be tested.
• To stop the test, use the arrow button to select Stop Test, then press Enter
twice.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 72
Service Commands
NOTE:
Before this test is performed, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is to
be tested.
• To stop the test, use the arrow button to select Stop Test, then press Enter
twice.
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 73
Appendix
17. Appendix
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 74
Appendix
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 75
Appendix
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-OPERAT/FGB, Rev. A. 2018-03-07,
Autronica Fire and Security AS
Page 76
Appendix