REF542plus Om 755869 ENg
REF542plus Om 755869 ENg
Operator's manual
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Issued: 01.11.2002 Operator's manual
Version: G/15.02.2010
Contents
Copyrights ................................................................................. 7
1. Introduction..............................................................9
1.1. This manual.............................................................. 9
1.2. Use of symbols ......................................................... 9
1.3. Intended audience ..................................................... 9
1.4. Product documentation ............................................. 10
1.5. Document revisions.................................................. 10
2. Safety information................................................... 11
3. HMI features ........................................................... 13
3.1. Control area............................................................ 13
3.2. Info and Menu area.................................................. 15
3.3. REF 542plus status information area .......................... 17
4. Behavior at power up .............................................. 19
5. Changing the language displayed ............................ 21
6. Control modes........................................................ 25
6.1. Available control modes ............................................ 25
6.2. Changing the control modes ...................................... 25
7. Operating the primary objects.................................. 27
8. Viewing and resetting alarms ................................... 29
8.1. Viewing alarms........................................................ 29
8.2. Resetting alarms...................................................... 29
9. Viewing measurements ........................................... 31
10. Viewing events ....................................................... 33
11. Viewing and changing the protection settings ........... 35
11.1. Viewing the protection settings................................... 35
11.2. Changing the protection settings ................................ 35
11.2.1. Changing the protection key mode.................. 35
11.2.2. Changing the protection parameters................ 36
11.2.3. Changing the active parameter set ................. 38
11.2.4. Viewing and changing control parameters ........ 39
12. Setting the time and date......................................... 41
13. Command page ...................................................... 43
14. REF 542plus commissioning mode........................... 45
14.1. Binary input commissioning page ............................... 46
14.2. Binary output commissioning page ............................. 47
14.3. Analog input commissioning page .............................. 48
14.4. Analog output 4- 20 mA commissioning page ............... 50
3
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
4
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
5
6
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Copyrights
The information in this document is subject to change without notice and should not
be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for
any errors that may appear in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third
party nor used for any unauthorized purpose.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
7
8
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
1. Introduction
1.1. This manual
Before attempting any operation with REF 542plus, read this manual carefully first.
This manual describes how to use the interface of REF 542plus (LD HMI, Local
Detached Human Machine Interface). Note that HMI views and pictures are to be
considered exemplary.
Do not make any changes to the REF 542plus configuration unless you
are authorized to do it and familiar with REF 542plus and its Operating
Tool. This might result in malfunction and loss of warranty.
This publication includes the following icons that point out safety-related conditions
or other important information:
The warning icon indicates the presence of a hazard which could result
in personal injury.
The information icon alerts the reader to relevant facts and conditions.
9
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
* layout
Applicability
This manual is applicable to REF 542plus Release 3.0, software version V4F08x.
10
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
2. Safety information
11
12
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
3. HMI features
The REF 542plus is shown in Fig. 3.-1. This HMI features a back-illuminated LCD,
8 push buttons, several LEDs and an electronic key sensor. This new international
HMI is a part of the product release of REF 542plus, starting from release 2.5.
The resolution of the display is 320x240 (QVGA) and the display supports full
Unicode character set. Consequently, all languages, for example Chinese, can be
displayed clearly. With this HMI two different languages can be handled
simultaneously. The local language can be defined as the first language with the
related operating tool. Then, the second language becomes automatically English.
The language on the HMI can be changed from one to the other very easily.
A051327
The LCD in the SLD view provides a graphical representation of the primary
objects controlled or monitored by REF 542plus in the switchgear. The right half of
the LCD is for plain text visualization such as measurements and protection events.
The contrast level is automatically controlled for an optimum reading, it can also be
adjusted as wanted.
The left side of the HMI panel is for primary objects control. The command buttons
and the information related to the switchgear control are placed on this area
13
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051328
This section of the display shows the Single Line Diagram (SLD) of the controlled
panel and the measurement bars. Text can be added in this section to improve the
understanding of SLD.
* Command buttons
The Primary Object Control can be performed with the following push buttons to
allow operating the primary objects if configured as “selectable”. The command
push buttons for local operation of the switching devices are:
14
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
provided. The Super User key is also needed to access the commissioning test
mode. The password codes stored in the key can be customized in each
REF 542plus for access restriction purposes.
* SLD view: this is the graphical part of the LCD. This part shows the single line
diagram of the switchgear. The status of the primary objects is dynamically
updated after every operation. If for example the circuit breaker has been opened,
its representation will reflect it.
The right side of the HMI LCD is for information and menu browsing. The buttons
to navigate through the menus and to change items are placed on this area.
A051333
Pressing this button, the unit goes back to the former menu.
The enter push button to enter into the selected menu or to select the
highlighted submenu.
15
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
* LED bars: The three LED bars are available to show the most relevant
measurements acquired by REF 542plus for a quick inspection of the switchgear
load situation. The three bars are marked M1, M2, and M3. Each bar is
composed of twelve LEDs, ten green and two red ones. The ten green LEDs are
normally dedicated to display between 0% and 100% of the nominal value of the
configured measurement. Each LED corresponding then to 10% of the nominal
value. The two red LEDs indicate an overload condition of 20%. The
measurements displayed by the bars are set with the Operating Tool.
* Indication LEDs: 8 freely programmable, three-color LEDs are available for
indications. There are 4 pages of these LEDs. As a result, a total of 32 indication
options can be programmed for events and status regarding protection, control,
monitoring, binary inputs and so on. The assignment of the LED to a specific
condition is done with the Operating Tool.
* Infrared (IrDa) interface: This is the IrDa serial interface port to connect
REF 542plus to a personal computer. By using the appropriate cable and the
Operating Tool, the following actions are possible:
* Download a configuration into the unit.
* Upload the current configuration from the unit.
* After a fault, upload the fault recorder data. This is possible only if the fault
recorder has been previously enabled with the Operating Tool.
Upload other information (measurements, binary inputs status, binary output status).
Do not make any changes to the REF 542plus configuration unless you
are familiar with REF 542plus and the Operating Tool. This might
result in malfunction and loss of warranty.
16
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051338
17
18
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
4. Behavior at power up
At power up, the HMI unit shows on the LCD for a few seconds the following:
A051339
After that, the LCD left part shows the switchgear single diagram while the right
part shows the default menu. When the initialization is completed and the unit is
operational, the ready LED is on.
19
20
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A060408
The following Fig. 5.-2 shows how to change the active language on the HMI. The
prerequisite is that there is a local language defined. Do as follows:
* Go to the main menu by pressing MENU .
* Press UP and DOWN simultaneously to get to the Language page.
* Press ENTER to execute the language change.
21
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A060409
The former HMI of the REF 542plus (HMI Version V4) can still be
applied together with the base unit having the new firmware of release
2.5. provided the firmware of the HMI is upgraded accordingly. After
upgrading the firmware the HMI V4 behaves almost the same as the
new international HMI V5. Due to the low resolution of the LCD on
the former HMI, the displaying certain languages, such as Chinese, is
not possible. Other languages, such as Russian with cyrillic characters,
can be used as the first language.
Starting from release 2.5 SP1, an optional Ethernet module for the
IEC 61850 communication protocol can be applied. Therefore, new
menu items appear on the HMI display. Because of the limitation of the
existing memory, the use of the HMI version V4 is not reasonable and
it is not recommended anymore.
22
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
23
24
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
6. Control modes
6.1. Available control modes
Local Control
It is possible to control the circuit breaker and other primary objects from the HMI
using the object control buttons. Open and close operations are possible only if the
interlocking logic programmed into the unit allow them. Remote control from the
SCADA is inhibited. Uploading and downloading the configuration via the optical
interface is possible.
Remote Control
The control of the circuit breaker and other primary objects from the HMI is
inhibited. The control is possible only remotely. Uploading and downloading the
configuration via the optical interface is possible.
No Control
It is not possible to control the circuit breaker and other primary objects both from
the HMI and remotely. Any kind of operation apart from the protection trip is
inhibited. Uploading and downloading the configuration via the optical interface is
possible.
Both the local control and remote control from HMI are possible. Uploading and
downloading the configuration via the optical interface is possible.
The next figure shows how to change the control mode. At first the menu E-Key
must be selected. Then the control key must be placed in the electronic key sensor.
Select then the desired control mode by using UP and DOWN until it is
highlighted. Confirm the selection by pressing ENTER . After pressing ENTER
, the E-key status menu will appear again. Verify that the required control mode
has been properly set in the unit looking in the lower left corner of the HMI. A text
string there indicates the currently selected control and protection mode.
25
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051340
Fig. 6.2.-1 Changing the control mode by using the control key
26
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Press to step through the available objects until the desired object is selected (it
will appear highlighted in the SLD). The object remains highlighted until the open
or close push button is pressed or the time-out has elapsed.
27
28
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
The presence of an alarm, when latched, is indicated by the alarm LED turned on or
by one of the 8 x 4 pages user programmable LED’s turned on to red. The
conditions or the events that generate an alarm are defined and programmed with the
Operating Tool.
When an alarm is active, the corresponding LED is turned on to red. Select the
alarm menu with the navigation buttons. Then, this menu displays the text
associated to the alarm condition. The displayed text is defined with the Operating
Tool.
There are four pages of alarms and each page reports eight alarms at most. Use the
navigation button to browse through the pages.
A051341
At first, the reset menu must be selected. Select the reset menu with the navigation
buttons. Highlight the reset alarm line in the menu and then press ENTER .
29
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Some alarms might not be reset before the cause that generated it has been removed.
For example, an alarm due to an error in the tripping circuit (coil supervision)
cannot be reset before the tripping coil is replaced. Whereas an alarm generated by a
trip of a protection function is normally reset with this procedure.
A051342
30
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
9. Viewing measurements
REF 542plus offers complete measurements set to the user. To view the
measurements, select the measurement menu with the navigation button. Use the UP
and DOWN buttons to browse the measurement pages.
The available measurements depend upon the unit configuration. In the maximum
configuration, the following measurements are displayed:
* IL1, IL2, IL3, in A; line currents, measured values
* U1E, U2E, U3E, in kV; phase to earth voltages, measured values
* UL12, UL23, UL31, in kV; phase-to-phase voltages, computed values.1)
* IL1 mean, IL2 mean, IL3 mean, in A; mean currents in the observation period,
computed values
* IL1 max, IL2 max, IL3 max, in A; maximum peak currents in the observation
period, computed values
* Frequency, in Hz; measured values
* Active power, in kW; reactive power in kVAr, apparent power in kVA, computed
values
* Power factor, computed value
* Active energy in MWh, reactive energy in Mvarh; computed values
* Operating hours, in hours. This is the total working hours of the unit
* Switch cycle, number the circuit breaker close-open cycles
* Added switched current, in kA; sum of the interrupted currents by the circuit
breaker
* THD (total harmonic distortion)
The observation period is set with the Operating Tool. It can be from 0
minutes up to 30 minutes. If the observation period is set to 0, the
corresponding measurements are disabled.
The refresh time for the displayed measurements is about half second.
1)
REF 542plus can also use phase-to-phase voltage transformers. When used,
phase-to-phase voltages are measured and phase to earth voltages are computed.
31
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051343
32
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
For each event, the following information is recorded: involved protection function,
event type, relevant measurement (current, voltage, frequency), date and time (up to
milliseconds). Events are displayed using the full screen; the single line diagram is
thus not visible.
A051344
To display the protection events, select the Start/Trip menu with the navigation
buttons. Use UP and DOWN to browse through the events.
33
34
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
The protection functions currently installed in the unit can be seen in the menu
protection functions. Select the menu protection functions with the navigation push
buttons.
A051345
Use UP and DOWN to highlight the desired protection function and press
ENTER . Then, the protection parameters will be displayed in one or more
pages.
35
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
The procedure to change the protection mode is identical to changing the control
mode. At first, the menu E-Key must be selected. Then the protection key must be
placed in the electronic key sensor. Select then the required protection mode by
using UP and DOWN until it is highlighted. Confirm the selection by
pressing ENTER . After having pressed ENTER push button, the E-key
status menu will appear again. Verify that the required protection mode has been
properly set in the unit, looking in the HMI lower left corner.
A051346
Fig. 11.2.1.-1 Changing the protection mode by using the protection key
Select the menu protection functions with the navigation push buttons and highlight
the desired protection function. Press ENTER to select it. Press ENTER
again and the cursor will automatically go to the first parameter. Use Up or
Down buttons to modify the parameter as wished. After completed, press
ENTER and use Up and Down button to select the next parameter to
change.
Repeat the procedure for all the parameters that need to be modified. Then press
to go back to the list of currently installed protection functions. Repeat the
procedure for every protection function that needs to have the setting modified.
36
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051347
Press again to leave the protection functions menu. The unit will then ask what
to do with the changes:
A051348
37
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Select the desired choice with Up or Down and then press ENTER to
confirm it. The meaning of the choices is as follows:
Store permanently: The new parameters are stored in the unit internal memory. They
will be used immediately and for all the next starts.
Save temporarily: The new parameters are used immediately but are not saved in the
unit internal memory. Next starts will use the old parameters.
Discard changes: The new parameters are discarded. There are no effects.
Do not switch off the Base Unit power supply during parameter
storing. The whole unit configuration might be corrupted and a new
configuration download might be necessary.
Most of the protection functions have two different parameter sets to cope with
different plant situations. This menu allows seeing and changing the active
parameter set.
Changing the active parameter set is possible only with the protection in the set
mode.
Select the active set page menu and press ENTER to make the change.
A051349
38
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Select the Control menu with the navigation push buttons and highlight the desired
control function. Press ENTER to select it. Press again and the cursor will
automatically go to the first control parameter. Use the Up or Down button
to modify the parameter as wished. After the modification, press and use Up
Down to select the next parameter to change.
Repeat the procedure for all the parameters that need to be modified. Then press
to go back to the list of currently installed protection functions. Repeat the
procedure for every control function that needs to have the setting modified.
A051350
39
40
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Standalone unit: The internal time of the unit has to be set to the current value. To do
it, select the service menu and then the MC time submenu with the navigation
buttons.
A051351
41
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Usually, the SCADA transmits to the unit the time and date according to the used
protocol services. There are some differences depending on the used protocol.
* IEC 60870–5–103 protocol: The IEC 60870–5–103 module is the time master.
Setting the time and date from the HMI is inhibited.
* LON LAG 1.4 protocol: The LON module is the time master. Setting the time
and date from the HMI is inhibited.
* SPA bus and MODBUS protocol: usually, the SCADA sets the time and date,
and setting the time and date from the HMI is inhibited.
42
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051352
43
44
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Entering this mode STOPS the execution of the protection and control
functions. The application software is not running. However, it is not
deleted from the permanent memory of the unit. The commissioning
test mode should be entered when the switchgear is de-energized and
in a safe state.
When the Base Unit starts the e-key is detected. The commissioning mode is
entered. Verify this reading on the start-up status line “COMMISSIONING
MODE”. When this text is visible, the e-key can be unplugged from the e-key
sensor.
This mode allows driving directly the binary outputs of the Base Unit.
If they are connected to primary objects, operations are thus possible.
The interlocking functions are disabled. Before accessing this mode,
put the switchgear in safe conditions.
45
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051353
This page displays the current status of the binary input channels on the binary IO
modules. There are 14 binary inputs per module available. For the binary inputs
numbering see Section 19.2. Binary inputs and outputs.
46
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051354
On this page, it is possible to force the status of the binary outputs. All the outputs
can be driven with the exception of the watchdog.
47
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051355
This page shows the analog measurements acquired by the analog input module.
The shown values are independent on the rated primary current or voltage of the
primary sensors. The measurements are reported in absolute values taking into
consideration as nominal values of the secondary windings 1 Amp and 100 V. If the
5 Amp current inputs are connected applying the nominal rated current, it will be
shown 1 A.
48
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051356
Fig. 14.3.-1 Analog inputs commissioning page for the 3CT, 3VT, 1VT, 1CT module
With sensor inputs, the displayed values are the voltages read by the analog
channels. For example, by using the voltage divider 10.000/1 applying 20 kV on the
sensor, the measurement will show 2 Volt. For the current sensor 80 A/150 mV,
applying 80 Amp on the sensor the measure will be 0.150 Volt.
49
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051357
Fig. 14.3.-2 Analog inputs commissioning page for the 6 sensor module connected to 3
voltage divider and 3 Rogowski coils
This page allows setting the value of the analog channels in the 4-20 mA module.
50
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051358
From this page, it is possible to read the analog measurements of the Analog Input
4-20 mA module. The shown measurements will be depending on the connected
sensor type. In case of a general 4-20 mA sensor, the value of the applied current to
the channel is displayed. In case of a SF6 Trafag sensor, the density and the
temperature are displayed.
51
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051359
This page displays the status of the optical inputs on the main module. This mode is
available only with main modules equipped with the optical inputs
(1VCF751021R0803, X74 only and 1VCF751021R0801 for all).
52
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051360
This page allows driving the optical output on the main module (only type
1VCF751021R801).
53
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051361
54
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
15. Connection to PC
15.1. Infrared (IrDa) to RS232 converter cable
Fig. 15.1.-1 REF 542plus serial cable with optical infrared (IrDa) interface
A060412
Fig. 15.1.-2 Interface on the HMI for the serial cable with optical infrared (IrDa)
55
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A standard Ethernet cable can be used to connect the base unit via the TCP/IP port
interface to the PC.
When the connection is set up with the appropriate cable, it is possible to download
the configuration into REF 542plus with the Operating Tool. Connect the infrared
(IrDa) converter to the foreseen connector on the HMI and the D-sub connector to
the PC or connect the base unit to the TCP/IP port of the PC with an Ethernet cable.
Start Operating Tool on the PC and configure the serial port or the TCP/IP port to be
used inside the program.
A100790
REF 542plus Configuration Tool is able to configure the REF 542plus device
connected via a serial port RS232 or an Ethernet TCP/IP port. To configure the
communication port (serial RS232 or TCP/IP) of the computer to be used to transmit
the configuration for the application, the corresponding applicable dialog must be
edited. After starting the Configuration Tool software, open Main menu > Connect
> Port configuration. The opening dialog window has three tabs.
56
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A100570
On the first tab it is possible to select the communication port. The other two tabs
are for configuring the serial port and TCP/IP settings.
General tab
The first tab is used to select the type of connection of REF 542plus to the PC. The
connection can be Serial or TCP/IP. The type of communication must be selected
before configuring it in the other tabs of the window. A section with a description of
all the current settings regarding both serial port and the TCP/IP port is also
provided.
57
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A100572
To configure the serial port (RS232) of the computer, the applicable Serial tab must
be activated.
58
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A100574
The tab has five option fields where the settings for the computer serial port can be
made.
Select the COM port where the RS232/Infrared (IrDa) cable or RS232 null-modem
cable is plugged in.
59
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
After the download of the configuration file by using the service or the
debug port, press ENTER to end the download process.
Base Unit slave address: This number can be from 1 to 254. When several Base
Units are connected to the same HMI, this number uniquely identifies the Base Unit.
The default address is 99. To configure or change the Base Unit slave address, there
are two methods:
* Open the application file with the Operating Tool and change it in the hardware
settings.
A051365
* Via the HMI menu > Service page > Communication > HMI PORT
60
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051366
Fig. 15.5.1.-3 Changing the Base Unit address from the HMI
Please note:
The configuration download starts as soon as the relevant push button on the
Operating Tool is clicked.
The previous configuration inside REF 542plus is destroyed and overwritten by the
new one.
REF 542plus is fully operational during the download. After the download,
REF 542plus starts to write the new configuration in the non-volatile with a low
priority task in background. This task might take several seconds.
Do not switch off Base Unit power supply during the storing. The
whole unit configuration might be corrupted and a new configuration
download might be necessary.
The download is possible in all control modes, provided the status of the protection
is switched by the corresponding electronic key in operational mode.
After the download, REF 542plus automatically starts with the new configuration.
61
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
When the download is completed, the unit may change the operational
status of the output relays due to the new logic configured in the
application file. It is strongly recommended to put the switchgear in
safe conditions before performing the download.
A100576
The "Remote device" section allows setting the IP address of the REF 542plus unit
involved in a direct communication with Configuration Tool.
The "Local Network Properties" section shows a list of the Ethernet adapters
currently installed in the PC. Once an Ethernet adapter is selected, the related TCP/
IP parameters are shown as read-only:
62
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
* Mac address
* Type of connection (static or DHCP)
* IP address
* Subnet mask
* Default gateway
Both the REF 542plus unit and the PC must be connected to the same
network.
A100578
63
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
* Click Change Settings to open the TCP/IP dialog window to enter the new
settings.
A100580
If the new parameters are correct, the Save Settings button becomes available.
* Click Save Settings to start the renewing of the PC Ethernet card.
64
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A100582
Fig. 15.5.2.-4 Changing the PC TCP/IP settings and properties from Control Panel
* Click Internet Protocol to open a dialog window that allows making changes to
the TCP/IP parameters.
65
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A100584
With the Operating Tool, it is possible to upload the current configuration inside
REF 542plus. Set the Operating Tool and the PC as for the download and click the
menu Transfer/load from REF 542plus.
Please note:
The uploaded configuration overwrites the current one inside the Operating Tool.
The upload is possible in all control modes and does not affect the functioning of the
unit.
66
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
With the Operating Tool, other information can be uploaded from REF 542plus.
Different data can be uploaded:
* The fault recorder file
* The binary input status
* The binary output status
* The measurements
* The software version
All this data is accessible with the Operating Tool from the transfer menu. Refer to
the Operating Tool manual for more details.
67
68
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
16. Troubleshooting
16.1. Error messages
When the HMI is not able to communicate with the Base Unit, the following
information appears on the LCD:
A051367 2
Fig. 16.1.-1 HMI is not able to communicate with the Base Unit
Solution:
Check that the Base Unit is powered and regularly working. Look at the status LED
on the connector panel (Slot X7).
The LED close to the analog inputs is related to the watchdog. When the Base Units
is working this LED is on with a weak light.
The other LED is related to the communication with the HMI. When the
communication is properly working, this LED is blinking. When the communication
is not working, the LED can be either ON or OFF. It depends on when the
communication is interrupted.
Check that the connection cable between the HMI and the Base Unit is inserted both
in the HMI and in the Base Unit (Base Unit connector X73 and HMI connector
X20) and properly tighten.
Check the slave address of the connected Base Unit to be polled. The address is
configured in the application file. If you do not know you can enter the following
page by pressing ENTER.
69
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Power Up Operations
After pressing the key the Power Up Operation menu is shown as in the
following Fig. 16.1.-2.
A051437 2
If the older version of the HMI V4 is used, the menu of the Power Up
Operations is slightly different in accordance to the menu in the former
release 2.0. The menu is as shown in the following Fig. 16.1.-3.
A060410
Select HMI <-> Base Unit address scanning menu item and press ENTER.
The HMI will start polling all the addresses to find the connected Base Units. When
a unit is found, its address and the feeder name are reported.
70
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051438 2
Select the HMI <-> Base Unit address to change the address to be polled.
A051439 2
Only with the older version of the HMI V4, the HMI can be tested
without connection to the base unit. The test must be done by using the
foreseen menu item on the Power Up Operations. The HMI V5 must
only be tested in connection to the base unit and by using the related
test menu after reaching the ready status.
71
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051440 2
A051441 2
Solution:
Download the configuration into the unit by using the serial cable and the Operating
Tool.
The following message appears when the downloaded configuration has not been
saved inside the unit due to an internal error.
72
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051442 2
Fig. 16.1.-8 REF 542plus configuration is not stored in the unit internal memory
Solution:
Try to download the configuration again. If after two or three attempts the error
remains, contact ABB.
Wrong configuration
The following message appears when a not correct configuration has been
downloaded in the Base Unit. This message can also appear when the configuration
contains protection functions that exceed the unit functionality level.
A051443 2
The WRONG CONFIGURATION can also be caused by other reasons. The error
handling will be described in Appendix D, where the Self Supervision is explained.
73
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
In some cases, there might be the need to delete the configuration stored inside the
REF 542plus. For example, when the RED alarm is on, it is not possible to
download a new configuration inside REF 542plus. The following procedure deletes
the configuration inside REF 542plus:
* Switch off the Base Unit power supply (disconnect the X10 connector from the
Base Unit).
* Press simultaneously the UP and DOWN buttons on the HMI and keep
them pressed.
* Switch on the Base Unit again.
74
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
The primary object status is usually acquired by REF 542plus with two distinct
contacts: one that is closed when the object is closed and another that is opened.
When the object is opened, the same two contacts with two different positions are
needed.
The primary object is visualized in open position with a dotted line when both
contacts are opened (REF 542plus has no voltage at both contact inputs).
A051444
Fig. 16.3.-1 REF 542plus has no voltage at both inputs indicating the primary object
position
The primary object is visualized both in open and closed positions when both
contacts are closed (REF 542plus has voltage at both its contact inputs).
A051445
Fig. 16.3.-2 REF 542plus has voltage at both inputs indicating the primary object
position
Solution:
Check the wiring of the primary object. Verify that REF 542plus connectors are
properly inserted and tightened.
75
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Note: When the primary object in such an undefined positions, issuing an open
command will activate the open coil on the circuit breaker. The open operation is
never blocked. The close operation with the object in the undefined position is
blocked. A close command will be discarded and will turn the interlocking error
LED on.
76
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
17. Terminology
Term Description
Ethernet Physical communication network to transfer Internet data of
the REF 542plus to the PC and back.
Modbus By extension, communication board implementing the
Modbus protocol for REF 542plus.
77
78
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
18. Abbreviations
Abbreviation Description
BIO Binary input and output board
CAN Controller area network
CB Circuit-breaker
CT Current transformer
EEPROM Electrically Erasable Programmable Read-Only Memory
FUPLA Function block programming language; Functional pro-
gramming language; Function plan; Function chart
GPS Global positioning system
HMI Human-machine interface
HW Hardware
IBB Interbaybus
ID Identifier; identification
IEC International Electrotechnical Commission
IP Internet protocol
LCD Liquid crystal display
LD Logical device
LED Light-emitting diode
LON Local operating network
MC Micro controller
PC Personal computer
RAM Random access memory
SCADA Supervision, control and data acquisition
SLD Single-line diagram
SNTP Simple Network Time Protocol
SPA Data communication protocol developed by ABB
TCP Transmission Control Protocol
VT Voltage transformer
79
80
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051446
Fig. 19.-1 REF 542plus wide housing connections plate with mixed analog input
connector
81
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051447
Fig. 19.-2 REF 542plus standard housing connections plate with mixed analog input
connector
82
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Connector Meaning
X72 Mainmodule RS232 service or debug interface
X73 HMI connection
X74 Time synch input
X75 HSTS Input
X76 HSTS Input
X77 HSTS Output
X80 Analog inputs
X81 Sensor 1
X82 Sensor 2
X83 Sensor 3
X84 Sensor 4
X85 Sensor 5
X86 Sensor 6
X87 Sensor 7
X88 Sensor 8
REF 542plus can have a maximum of 8 analog input channels. These inputs are
divided into three measurement groups:
* Measurement Group 1: channel 1, channel 2, channel 3
* Measurement Group 2: channel 4, channel 5, channel 6
* Measurement Group 3: channel 7, channel 8
Group 1 and group 2 have to be homogeneous, which means they can measure 3
currents or 3 voltages. For example, measurements of 1 current and 2 voltages are
not allowed.
Group 3 can get any type of signals: 2 currents, 2 voltages, 1 current and 1 voltage
and so on. Group 1 and group 2 can be used for homogeneous current or voltage
measurements both from instrument transformers and non-conventional sensors.
Group 3 can be used in a heterogeneous way.
Channel 7 and 8 in group 3 can be used for earth-fault current with CT type input;
residual voltage, or for the synchrocheck function with VT or sensor type input.
The input CT 0.2A is commonly used with a toroidal transformer for sensitive earth-
fault current measurement.
83
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
The Rogowsky coil can be used for current sensing. The correct ratio of the
Rogowsky coil is selected with the Operating Tool. The resistive divider can be used
for voltage sensing. The ratio is selected with the Operating Tool. The physical input
on the unit is the same both for voltage and current sensing, the selection is done via
the Operating Tool. Therefore, it is possible for example to use 6 Rogowsky coils, 6
voltage dividers, or 3 Rogowsky coils and 3 voltage dividers.
To detect which analog input module is present inside the unit, look in the
identification label stick on the unit itself, or on the HMI service page under the HW
identification submenu.
A051450
The analog input for sensor is the same both for voltage and current sensing. To find
out whether an input is for current or for voltage, the Operating Tool is needed. X81
corresponds to analog input 1 (sensor 1 in the Operating Tool), X82 to analog input
2 (sensor 2 in the Operating Tool) and so forth.
A051451
The connector for conventional instrument transformer has twenty-four pins. The
following Table 19.1.-1 defines which input is connected to what:
84
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
12 T8/1
13 T4/3
14 T2/B T2/2
15 T6/3
16 T7/B T7/2 T7/A
17 T4/B T4/2
18 T2/3
19 T6/B T6/2
20 T7/R T7/3 T7/B
21 T4/R T4/1
22 T2/R T2/1
23 T6/R T6/1
24 T7/1
Example:
To determine the pins for the analog input module 1VCF750170R0817: 3CTs,
3VTs, 1CTs; used with transformers with 1 A on the secondary windings.
Analog input 1; the current transformer for phase 1 must be connected on pins 11
and 3 (common).
Analog input 2; the current transformer for phase 2 must be connected on pins 22
and 14 (common).
Analog input 3; the current transformer for phase 3 must be connected on pins 10
and 2 (common).
Analog input 4; the voltage transformer for phase 1 to earth must be connected on
pins 21 and 17.
Analog input 5; the voltage transformer for phase 2 to earth must be connected on
pins 5 and 1.
Analog input 6; the voltage transformer for phase 3 to earth must be connected on
pins 23 and 19.
Analog input 7, for the toroidal transformer for the residual current must be
connected on pins 24 and 16 (common).
85
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051453
The picture above shows the connector for the mixed analog input module when
both sensors and conventional instrument transformers are used. To find out which
connector is used for what, identify the module code from the identification label
stick on the unit and see Table 19.1.-1.
X40 (inputs), X41 (outputs) for the third module, available with the wide housing
only.
REF 542plus can be equipped with two different types of binary inputs and outputs
modules: static or with electromechanical relays.
19.2.1. Static
In the static module, digital inputs are implemented with optocouplers and digital
outputs are implemented with power transistors. Two different module types are
available, with control coil continuity and without.
Each module features: 14 digital inputs, 3 power outputs, 4 normal outputs, 2 signal
outputs, 1 watchdog output and optionally 2 coil supervision circuits. For more
information, refer to the REF 542plus Technical Reference Manual.
86
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051454 2
Fig. 19.2.1.-1 Two static binary input and output modules with and without coil
continuity check
19.2.2. Electromechanical
19.2.2.1. BIO3
Twelve different types of BIO3 are available depending upon the supply voltage and
other features.
87
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051455
Fig. 19.2.2.1.-1 2 BIO3 modules with interconnected inputs and the static output
The 4 analog outputs, when present, are available at connector X50 accordingly to
the following diagram (see Fig. 19.3.1.-1). The not used pins, including the
shielding of the cable are connected to ground.
88
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051457
When present, the 4-20 mA analog input module uses connector X50. Sensor’s
connections are shown in Fig. 19.3.2.-1 X51 and X52 are service interfaces of no
use for the user. The output contact BO1 is for the future use.
89
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051458
Only passive sensors, for example those that are powered from the loop
can be connected to the 4…20 mA analog input module.
The communication module uses connectors from X60, X61, X62, X63, X64 and
X65 depending on the physical media type (RS 845, glass or plastic fiber).
90
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
19.3.6. HMI
A051459
Fig. 19.3.6.-1 shows the back side of the HMI. The connector for the HMI power
supply is X10, which is located on the right-hand side of the Fig. 19.3.6.-1. The
serial cable for the connection to the base unit is to place on the other connector X20
on the left-hand side.
Respect the right polarity on the HMI power supply to avoid damages
to the unit.
91
92
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051460
20.1. Commands
The command in this submenu can be activated if the active mode is Local or Local
& Remote. In other modes the activation will be denied.
From this page, it is possible to reset alarms and other quantities. Some reset actions
are possible only if REF 542plus is in the proper mode. The possibility of reset in
the different submenus is described in the following:
93
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Reset alarm: the LED's alarm indication can be reset in this submenu, independent
of the active mode
A051461
Fig. 20.2.-1 Attempt to resetting the fault recorder in the wrong mode
Select the quantity to reset with UP and DOWN and press ENTER to
execute.
A051462
94
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Reset alarm: can only be reset, if there is no active alarm present anymore. An
attempt to reset an alarm caused for example by an interrupted open coil is
impossible as long as the coil is not replaced.
Reset max. values: this sub menu resets the maximum and mean current values in
the observation period. Also the sum of switched off current is reset from here.
Reset is only possible in Local or Local & Remote modes.
Reset energy values: all the energy values (active, reactive, apparent) are reset from
here. Reset is only possible in Local or Local & Remote modes.
Reset CB cycles: a circuit breaker cycle is a close operation and the subsequent open
operation. The unit sums the cycles. This cycle number is reset from here. Reset is
only possible in Local or Local & Remote modes.
Reset fault recorder: the fault recorder data is cleared from here. Reset is only
possible in Local or Set Local modes.
Reset events: the events are cleared from here, if the mode is in Set Local.
Reset counters: the unit working hours are reset from here. Reset is only possible in
Local or Local & Remote modes.
20.3. Protection
The parameter of the Protection submenus, Active set page and Protection, can only
be changed in mode Set Local by applying the protection electronic key.
20.4. Control
The parameter of the Control submenus can only be changed in mode Set Local by
applying the protection electronic key.
20.5. Test
The test of the primary object can only be performed in local mode.
The service page menu is composed of several submenus. Browse through the
submenus with UP and DOWN buttons. Press ENTER to enter the
selected submenu.
95
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051463
20.6.1. Statistics
This submenu shows the FUPLA cycle time and other information related to the
current configuration in the unit.
A051464
20.6.2. Versions
This submenu displays information on the firmware versions loaded inside the unit.
96
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051465
This submenu shows the reference information of the hardware modules installed
into REF 542plus.
A051466
To display the information select the row and press ENTER . When the
information is available in the selected module, the following page will be displayed
(this information is stored in a dedicated EEPROM on the module itself).
97
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051467
When the information from the module is not available the following page is
displayed.
A051468
When the information stored on the module is corrupted, the following page is
displayed.
98
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051469
When the module is not present or the module is not able to publish the HW
identification data, the following page is displayed.
A051470
20.6.4. Communication
This subpage displays the information related to the communication ports available
and configured in REF 542plus.
99
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080290
When the port is not installed or configured, the following page will be displayed.
A051642
When the IEC 60870-5-103 communication module is installed the following page
is displayed.
100
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051645
In this subpage, it is possible to block the monitoring direction of the module. For
more information, refer to the Communication Module User Manual.
A051646
The IEC Test mode menu allows setting and resetting the test mode of the IEC
module. For more information, refer to the Communication Module User Manual.
101
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051647
When the COM-L module for LON communication is installed and active, the
following page displays the configured Node ID.
A051643
102
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
When the SPA bus communication module is installed, the following page is
displayed.
A051648
It is not possible to modify the SPA bus slave address of the unit on this page.
When the Modbus module is installed and properly working, the following page is
displayed.
A051644
103
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
When the CAN port has been enabled the following pages display the CAN
communication settings.
A051649
Only channel 1 is currently available. To enter the next subpage, select Channel 1
and press ENTER . The following page is displayed.
104
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051650
A051651
From this page, it is possible to issue direct operation to the CAN communication
subsystem. For more information, refer to the CAN Communication User Manual.
105
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051652
In this page, it is possible to change the node address of the CAN communication.
This setting is allowed only when the REF 542plus node is in the Pre-Operational
status.
106
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051653
In this page, it is possible to change the Base Unit slave address used to
communicate with the HMI.
When the Base Unit address is changed, the communication with the
HMI is lost. To restore it, the Base Unit address must be inserted in the
HMI as well. Select the menu item Base Unit Slave Address and insert
the same address of the Base Unit.
107
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051654
This page shows the current settings of the Ethernet communication subsystem.
Here, it is possible to visualize the IP and MAC address. The IP and MAC addresses
cannot be changed from this page.
A051655
108
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
When the Ethernet module is applied, the following subpages appear after you select
the corresponding Ethernet communication submenu, depending on the actual
condition. The following Fig. 20.6.4.8.-1 shows a case where the Ethernet board is
not supported:
A070398
The next Fig. 20.6.4.8.-2 shows a case where there is no Ethernet module present.
109
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070399
In normal situation where the Ethernet module is installed, the following subpage
appears when you select another submenu, as shown in Fig. 20.6.4.8.-3:
A080292
110
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
To select the desired subpage, click the UP and DOWN buttons. The
subpages are divided into two categories for value settings and info.
The General Settings subpage displays the configuration parameters coming from
the REF 542plus main module, whereas the General Info subpage displays the status
values and configurations coming from the Ethernet communication module. The
following two figures, Fig. 20.6.4.8.-4 and Fig. 20.6.4.8.-5, show the related
subpages.
A080294
111
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080296
To move from one subpage to another click the UP , and DOWN buttons.
You can go back to the FB COM Ethernet page from each subpage by clicking the
MENU button.
TCP/IP subpage
The TCP/IP subpage consists of two pages for each configured communication port,
port1 or port2. The following two figures Fig. 20.6.4.8.-6 and Fig. 20.6.4.8.-7 show
the TCP/IP Settings subpage and the TCP/IP INFO subpage.
112
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080298
A080300
At the moment, you can either use port 1 or port 2. If you apply port 2 , the subpages
shown in the following two figures are displayed.
113
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080302
A080304
SNTP subpage
114
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080306
If SNTP is enabled, the related subpage consists of two different subpages, as shown
in the following two figures Fig. 20.6.4.8.-11 and Fig. 20.6.4.8.-12.
A080308
115
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080310
You can move from one subpage to another by clicking the UP , and DOWN
buttons. You can go back to the FB COM Ethernet subpage by clicking the MENU
button.
Protocols subpage
The Protocols subpage consists of a page for each configured protocol on Ethernet
board, IEC61850 or MODBUS TCP.
The following figure 20.6.4.8.-13 shows the Protocols subpage for the IEC61850
protocol.
116
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080312
The following figure 20.6.4.8.-14shows the Protocols subpage for MODBUS TCP
protocol.
A080314
The pages shown when the protocol is currently disabled are presented in 20.6.4.8.-
15(IEC61850) and 20.6.4.8.-16(MODBUS TCP).
117
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A080316
A080318
This page shows the active char map used by the HMI. Refer to the Operating Tool
User Manual on how to change it.
118
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051656
The LCD screen contrast can be adapted to different light condition from this
submenu.
A051657
The load flow direction determines how REF 542plus computes energy and power.
It is set with the Operating Tool and it is also dependent upon the current and
voltage transformers (or sensors) connections in the primary parts.
* FORWARD: the power is flowing from the switchgear to the load (outgoing
feeder).
* BACKWARD: the power is flowing into the switchgear (incoming feeder).
119
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051658
This submenu allows testing the HMI and the primary part of the switchgear.
When the test HMI is selected, all its features will be tested by switching them on
and off.
HMI buttons are not available during the test. The displayed
information on the HMI does not reflect the switchgear’s actual status.
REF 542plus is protecting the switchgear during the HMI test. The
HMI test takes a few seconds.
120
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051659
The circuit breaker and other switching devices can be tested from this submenu.
The object control buttons are used to perform the desired tests. A warning message
is displayed before leaving the test primary object mode.
Verify the primary object’s correct position before leaving the test
mode and before energizing the switchgear. Make sure all the primary
objects are back in the correct positions.
121
122
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051660
The trip by the above-mentioned protection function is released at the absolute time
25/05/2006, 07:45:15.862, which is indicated by arrow 3, see Fig. 21.-1.
As long as the current is not interrupted, the start signal remains active. Arrow 2
indicates that the current is flowing for a time duration of 73 ms.
123
124
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Software supervision
Software faults require different kinds of handling and these can be modelled by
defining a level that identifies the fault’s critical nature:
* Level 1
Level 1 faults are irrecoverable fatal errors. After fault detection, the system is
not able to guarantee safe execution of the protection and control functions. The
irrecoverable fault forces REF 542plus to stop any activities and it can only be
restarted after a power-switch cycle (power off/on) or after a configuration
download (if possible).
* Level 2
Level 2 faults are recoverable fatal errors. They are similar to level 1 faults
except that REF 542plus, instead of stopping any activities, resets and therefore
automatically restarts and signals the reset cause.
* Level 3
Level 3 faults are errors that do not affect safe execution of the protection and
control functions. In general, they are handled by signalling the fault via an HMI
error message and a SPA event.
125
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Supervision by bootloader
REF 542plus has an on-chip bootloader that handles the software upgrade and the
entering into Factory test mode. The bootloader supervises RAM (Random Access
Memory) and FLASH (MC non-volatile memory) application program correctness.
At normal start-up, it performs a simple RAM test that verifies the presence of the
RAM chip and its memory size. The exhaustive RAM test has to be performed if the
Factory test mode is activated.
If the RAM test is passed, the bootloader verifies the presence and the correctness of
the application program which is stored in FLASH. The presence is verified through
a pre-defined pattern check in a fixed FLASH location and the correctness is
verified through application program checksum calculation.
126
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Reset
REF 542plus performs a complete and deep analysis of the last reset cause. The
reset can be the result of a normal situation or a HW/SW fault detection. A normal
situation can be either of the following two:
* Power-switch cycle
REF 542plus power is switched OFF and than ON.
* Commissioning test end
REF 542plus is in commissioning test mode and the user exits from the
commissioning test HMI menu.
127
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
Moreover, the exception stack frame data, which includes very important
information needed when analysing the real root cause of the SW exception, is
available on the DEBUG port.
Configuration
128
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Note that all version checks are performed by REF542CONF before configuration
download. Therefore, the fault can occur only after a REF 542plus firmware
upgrade/downgrade or after FLASH configuration data corruption.
The DSP supervision verifies correct DSP start-up and correct DSP working status
during normal operation.
129
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
The COM module is an optional module that can be installed in the REF 542plus
housing. Its supervision is done only if the COM module is detected at start-up or
configured by REF542CONF. The supervision verifies correct COM module
configuration start-up and correct COM working status during normal operation.
130
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
The AI20mA (20 mA analogue input module) is an optional module that can be
installed in the REF 542plus housing. Its supervision is done only if the AI20mA
module is detected at start-up or configured by REF542CONF. The supervision
verifies correct AI20mA start-up and correct AI20mA working status during normal
operation.
131
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
The AI20mA configuration is built by the MC from the AI20mA sensors and
Warnings configuration. It is sent to the AI20mA that performs a consistency
check on it.
* AI20mA-MC configuration
The MC does not start normal operation if the AI20mA is configured but not
detected at start-up.
FLASH data
132
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
133
134
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
To connect a Telnet client to the Ethernet module as the Telnet server, few
operations are necessary. How to connect a common PC is shown below. Both the
Ethernet module and PC must be connected to the same network. Adjust the IP
parameters of the PC Ethernet port so that it is in the same subnet:
A070410
In the above figure, the PC Ethernet port is configured to communicate with the
address 192.168.2.203 and with subnet 255.255.255.0. The subnet value must
match the subnet value set in the Ethernet module, while only the first three digits of
the IP address must match with the ones of the Ethernet module, the fourth digit
must be different. After that it is possible to verify a remote connection with a ping
command.
To perform the ping command, select Run in the PC Start menu. Then type the ping
command by specifying the Ethernet board IP address, as illustrated in the following
Fig. 23.-2:
135
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070411
In the example above, the PC sends a ping command to an Ethernet board connected
to the net with the address 192.168.2.106. If the connection is correct, the following
window appears after the execution of the ping command:
A070412
Now, it is possible to establish a connection with the Telnet server of the Ethernet
module. As before, use the Run command in the PC Start menu. After that, type the
telnet command specifying the Ethernet board IP address as displayed in the
following figure:
A070413
136
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070414
A connection with the Ethernet board Telnet server is now established. The Ethernet
module Telnet server allows different logging levels to enable different functions
and commands. You can access Telnet without any log in operation by simply
pressing the Enter key twice. Note that the Telnet connection is automatically closed
if it stays inactive for more than two minutes.
Access to Telnet as a basic user allows functions to monitor the Ethernet board
status and general information.
Specific commands
137
REF 542plus 1MRS755869
Multifunction Protection and Switchgear Control Unit
Operator's manual
The disks’ contents display the contents of the Flash disk (C:) and Ram disk (D:).
Three commands are available:
You can check the SNTP module state by using the following five commands:
You can check the internal interface state with the command:
You can also view the factory test result file with the command:
The following set of commands can be used to check the state of the Dual Channel
operation modality:
138
1MRS755869 REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Finally, the section Time configuration and state collects following commands:
139
1MRS755869 EN 2/2010
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa
FINLAND
+358 10 22 11
+358 10 22 224 1094
http://www.abb.com/substationautomation