LKSM-VFD

1.8/3 kV
1.8/3 kV CABLES

Armoured power and control cable


with improved EMC-screening

• Flame-retardant • Halogen-free • Low smoke emission • Oil resistant (SHF2 only)

CONDUCTOR Stranded copper conductor 16–300 mm2, IEC 60228 Class 5


INSULATION XLPE
CABLING/BEDDING Cabling, cores twisted together, with optional fillers or dummy cores for
symmetrical and round construction. Bedding, lapped tape.
SCREEN Copper tape, coverage 100%
ARMOUR Copper wire braid, coverage > 90%, IEC 60092-350
RIP CORD For conductors ≥ 16 mm2
SHEATH Polyolefine SHF1, IEC 60092-360
Thermosetting polyolefine SHF2 on request
Standard colour black, other colours on request
REFERENCE STANDARD IEC 60092-353

APPLICATION
Armoured power and control cable. For fixed installation in most areas, and on open deck in ships and offshore units.
Specially designed cables to meet requirements for Variable Frequency Drivers (VFD). Suitable for voltage peaks up
to 3 kV.

PHYSICAL PROPERTIES: MAIN CHARACTERISTICS:


CORE IDENTIFICATION Colour code for 1…4 RATED VOLTAGE 1.8/3 kV (3.6 kV)
core cables, number code FIRE PERFORMANCE IEC 60332-1-2
for 5...37 core cables IEC 60332-3-22
MARINE TYPE ABS, BV, CCS, CRS, DNV, HALOGEN-FREE IEC 60754 series
APPROVALS KR, LR, RINA
SMOKE EMISSION IEC 61034 series
OIL RESISTANCE IEC 60811-404 conditions
(SHF2 only) according to 60092-360/SHF2
TRANSFER IMPEDANCE IEC 61196-1 (typical value
26 dB over 1 mΩ/m at 100 MHz
[20 mΩ/m])
MIN. INSTALLATION
TEMPERATURE -15 °C
OPERATING TEMPERATURE -40 – 80 °C fixed installation
MAXIMUM CONDUCTOR
TEMPERATURE 90 °C

Subject to change without prior notice. See latest update on our webpage. © 2022 Helkama Bica Oy. All rights reserved.
46

helkamabica.com
[email protected]
Tel: +1 (954) +358 2 410
603-8813 8700+1 (954) 633-7868
| Fax: | www.go2cee.com
LKSM-VFD 0.6/1 kV
No. of conductors x Cross-section Nominal outer Weight Min. bending

1.8/3 kV CABLES
Part number Current rating A Note
Conductor area (mm2) of armour mm2 Ø (mm) kg/km radius mm (fixed)
26918 1 x 10 4.7 12.5 280 71 75 x
26920 1 x 16 5.6 14.5 355 94 85 x
26922 1 x 25 8.5 16.0 495 123 95 x
26924 1 x 35 9.4 17.0 620 153 100 x
26926 1 x 50 10.4 18.5 780 196 110 x
26928 1 x 70 11.4 20.5 985 240 120 x
26930 1 x 95 12.6 22.5 1245 284 135 x
26932 1 x 120 13.7 24.0 1505 331 145 x
26934 1 x 150 14.8 26.0 1790 381 155 x
26936 1 x 185 15.8 27.5 2110 429 165 x
26938 1 x 240 17.7 31.0 2730 507 185 x
26940 1 x 300 19.0 33.5 3310 582 200 x
26892 3 x 10 13.2 23.5 1030 50 140 1)
26871 3 x 16 16.6 27.0 1325 66 160 1)
26873 3 x 25 17.0 30.0 1735 86 180 1)
26875 3 x 35 18.8 32.0 2155 107 190 1)
26877 3 x 50 29.1 36.5 2880 137 220 1)
26879 3 x 70 35.3 40.0 3760 168 240 1)
26881 3 x 95 35.7 44.0 4630 199 265 x
26883 3 x 120 38.8 48.0 5615 232 285 x
26885 3 x 150 42.2 53.0 6920 267 315 x
26887 3 x 185 45.7 56.0 8110 300 335 x
26889 3 x 240 50.5 62.0 10425 355 375 x
26893 3 x 95 + 3 x 16 35.7 44.0 4495 199 265 2)
26895 3 x 120 + 3 x 25 38.8 48.0 5580 232 285 2)
26897 3 x 150+ 3 x 25 42.2 53.0 6635 267 315 2)
NOTE!
PE-rules PE rules, for cables > 16 mm² the PE-conductor must be half of main conductor and min. 16 mm².
PE rule according to IEC 60092-352, Electrical installations in ships (Choice and installation of electrical cables)
x = Protective earth (PE) rules are NOT fulfilled.
1) = Single Armour can be used as Protective Earth. PE-rules are fulfilled.
2) = Three additional protective earth (PE) conductors. PE-rules are fulfilled.
3) = Double Armour can be used as Protective Earth. PE-rules are fulfilled.
Information given is indicative and doesn’t involve any warranty on results.
We reserve the right to change this datasheet.

Other sizes on request.