Dedicated

C&I / Utility ESS

Self-Consumption Demand Charge Micro-grid EV charge Station Frequency Integration

Off Grid V2G Back Up Peak Shifting Renewable Regulation

Battery
storage systems have been proven to be“extremely lucrative”
for commercial and industrial (C&I) field.
MAXIMUM SAFETY
FOR YOUR ENERGY
Providing a continuous and reliable supply of power from a flexible mix of conventional and renewable sources
is the goal of power generation in the energy evolution.

C&I/Utility ESS
Key Features

Vertical industry Three-levels monitoring Optimal Electricity Rack mounted or container


Integration Chain and management mechanism Long cycle life and superior based system configuration
design performance

UL9540A Test Summary


 Target BESS temparature less than gas vent tenperature
 Temparature increase of target walls less than 97 °C175 °F)
 The flame indicator shall not propagate flames beyond the width of initiating BESS
 No flaming outside the test room

Certification

UL1973 IEC62619 UL9540A IEC63056 VDE

01
Power
Distribution

02
Power Distribution
Back Up
Battery energy storage system (BESS) serves as ideal back-up for instant power supply, Seamless Switch to off grid mode in the very short time
and realize the Uninterruptible power supply.
How it benefit?
Avoid devices stop working and reduce economic losses once outage or disconnection from the grid.

EMS

Solar
② ②

① When solar is sufficient, solar charge the battery and power battery.
② When the solar is weak, Battery power the load.

Charge
Battery
Grid Discharge

ATS
When grid fails or claudy day, battery power the load.

Combiner DG
PV Panel DG

When battery in low mode, DG start to power the load.

Communication cable Load


Power Cable
Load

BESS Continuous Power to the load

EV Charge Station/V2G
Uncontrolled charging demand in an electric vehicle charging station (EVCS) can potentially result in the overloading of the grid coupling
transformer and affect the transformer’s lifetime. BESS in PV integrated EV charging station for reducing transformer overloading and provid-
ing battery-to-grid service

How it benefit?
Delay the investment of grid structure.
Reduce transformer overloading and PV smoothing within battery SOC constraints.

03
Power Distribution
Micro-grid
A microgrid is a self-sufficient energy system that serves a discrete geographic footprint, such as a college campus, hospital complex,
business center, rural areas, shop or island use.
How it benefit?
Operate independently
Avoid high cost to expand a grid connection
Save electric bill
EMS ①
Solar
② ②

① When solar is sufficient, solar charge the battery and power the load.
② When the solar is weak, solar and battery power the load.
PCS

Charge
Battery
Discharge

When at night or claudy day, battery power the load.


Combiner
PV Panel DG

DG

Communication cable
When battery in low mode, DG start to power the load.
Power Cable Load
BESS

Load

Continuous Power to the load

Large-Scale Off grid


Solar plus storage system will be the main power source to produce and store energy for rural and remote off-grid area. DG as backup to
support daily comsuption.

How it benefit?
Safe, low-maintenance power supply
Reduce fuel cost and air pollution
Reliable supply without a grid connection

EMS


Solar
② ②

PCS ① When solar is sufficient, solar charge the battery and power load.
② When the solar is weak, solar adn battery power the load.
Combiner
PV Panel

Charge
DG Battery
Discharge

Combiner When at night or claudy day, battery power the load.


PV Panel

DG
PCS

Combiner
PV Panel Load

Load
Communication cable
PV Panel Combiner Power Cable

Continuous Power to the load

04
Power Distribution
Peak Shifting
With purpose of reducing peak demand and economy of operation, compensate local transformer limit.

How it benefit?
Save on their electricity bills by reducing peak demand ( Commercial and industrial customers)
Reduce the operational cost of generating power during peak periods (Utilities )
Investment in infrastructure is delayed due to the flatter loads with smaller peaks ( Owner)

EMS

High

PCS

Low

Electric cost
Combiner Grid
PV Panel

Charge
Battery
Communication cable
Power Cable
Discharge
Load

BESS

Frequency regulation
BESS will be imperative to ensure that frequency regulating services can be provided when required and meet the charge/discharge
requirements imposed on assets providing enhanced frequency response.

How it benefit?

Reduce the investment of power generation,save cost


Constant balancing act to manage system frequency stability.

EMS

Communication cable
Power Cable

Load

Grid F [Hz]
50.1
50

49.9
Step- Up Step- Up Step- Up
transformer transformer transformer

Charge the battery quickly from grid when the


PCS PCS PCS energy is abundant, Discharge when the energy
is less available, keep regular frequency.

Charge
Battery
Discharge

BESS BESS BESS

05
Power
Generator

06
Power Generator
Grid Service
BESS will be imperative to ensure that frequency regulating services can be provided when required and meet the charge/discharge
requirements imposed on assets providing enhanced frequency response.
How it benefit?
Reduce the investment of power generation,save cost
Constant balancing act to manage system frequency stability.

EMS
Communication cable
Upper System Power Cable

Sequence diagram

F[Hz]
Main transformer 50.1
Grid
50
49.9

Step-Up Step-Up Step-Up


transformer transformer transformer
Charge battery from grid when the power is
abundant, Discharge battery to compensate
PCS PCS PCS power of grid and keep regular frequency.

Charge
Battery
Discharge

BESS BESS BESS

Renewable Integration
Storage helps smooth the power supply, enabling electricity to flow even when the sun isn’t shining or the wind isn’t blowing. It brings more
reliability, more resiliency, and many of these systems can be used for voltage correction, and frequency response in the grid.

How it benefit?
Adding storage to distributed fixed-orientation PV is assumed to increase the capacity credit
Reduce grid investment for renewable energy connection
Reduce grid stress from renewable inrush

EMS Communication cable


Power Cable
Solar

Charge battery from grid when the power is


abundant, Discharge battery to compensate
PCS PCS PCS power of grid and keep regular frequency.

Charge
Battery
Discharge

07
SPECIFICATION

Battery Module Basic Parameters H48050 H48074 H32148-C

Energy (kWh) 2.4 3.55 4.74

Nominal Voltage(V) 48 48 32

Battery Capacity(Ah) 50 74 148

Voltage Range(V) 43.5~54 43.5~54 30~36

Dimension (W*D*H mm) 442*390*100 442*390*132 330*628*150.5

Weight(kg) 24 32 48

Powercube X1 Powercube X2
Basic Parameters
(50Ah) (74Ah)

Powercube X series Battery Module H48050 H48074

Battery System Capacity(kWh) 24 35.5

Battery System Voltage(V) 864 864

Battery System Voltage Range (V) 783~972 783~972

Efficiency(@0.5C-rate) 96% 96%

Depth of Discharge 95% 95%

Cycle Life >8000, @25 >8000, @25

Design Life 15+Years 15+Years

Operation Temperature () 0~50 0~50

Humidity 5%~95% 5%~95%

Altitude(m) 2000 2000

Battery Module Qty.(Optional) 2~18 2~18

Certification IEC62619/VDE2510-50/UL1973/CE/CEC

Rack Dimension (W*D*H mm) 600*505*2130 600*505*2130

Weight(kg) 317 397

08
SPECIFICATION
Powercube-H1
Basic Parameters
(50Ah)

Powercube H series Battery Module H48050


200~1000V
Battery System Capacity(kWh) 36

Battery System Voltage(V) 864

Battery System Voltage Range (V) 783~972

Efficiency(@0.5C-rate) 96%

Depth of Discharge 95%

Cycle Life >8000, @25

Design Life 15+Years

Operation Temperature () 0~50

Humidity 5%~95%

Altitude(m) 2000

Battery Module Qty.(Optional) 5~18

IEC62619/VDE2510-50/
Certification
UL1973/CE/CEC

Rack Dimension (W*D*H mm) 600*505*2130

Weight(kg) 437

Powercube-H2
Basic Parameters
(74Ah)

Battery Module H48074


Powercube H series
200~1000V Battery System Capacity(kWh) 42.62

Battery System Voltage(V) 864

Battery System Voltage Range (V) 783~972

Efficiency(@0.5C-rate) 96%

Depth of Discharge 95%

Cycle Life >8000, @25

Design Life 15+Years

Operation Temperature () 0~50

Humidity 5%~95%

Altitude(m) 2000

Battery Module Qty.(Optional) 5~18

Certification IEC62619/UL1973/CE

Rack Dimension (W*D*H mm) 600*505*2130

Weight(kg) 461

09
SPECIFICATION

Battery Module
Basic Parameters HM2A180

Energy (kWh) 5.68

Norminal Voltage(V) 38.4

Battery Capacity(Ah) 148

Dimension (W*D*H mm) 315*820*171.5

Weight(kg) 55

BMS
Basic Parameters S1000M2A180 S1000M2A180J

AC Supply for BMS 100-290Vac/50Hz/1.3A NA

System Operation Voltage (Vdc) 0~1000 0~1000

Dimension (W*D*H mm) 315*710*171.5

Weight(kg) 19

Powercube-M2A-180
Basic Parameters
(148Ah)
Powercube M2
Battery Module HM2A180

Battery System Capacity(kWh) 107.98

Battery System Voltage(V) 883.2

Battery System Voltage Range (V) 800.4~993.6

Efficiency(@0.5C-rate) 96%

Depth of Discharge 90%

Cycle Life >7000, @25

Design Life 15+Years

Operation Temperature () 10~40

Humidity 5%~95%

Altitude(m) <2000

Battery Module Qty.(Optional) 1~23

Certification IEC626 19/CE/UN38.3

Rack Dimension (W*D*H mm) 803*845*2130

Weight(kg) 1228

10
SPECIFICATION

Battery Module
Basic Parameters HM3A180

Energy (kWh) 5.68

Norminal Voltage(V) 38.4

Battery Capacity(Ah) 148

Dimension (W*D*H mm) 375*820*171.5

Weight(kg) 61

BMS
Basic Parameters S1000M3A180L S1500M3A180L S1000M3A180J

AC Supply for BMS 100~230Vac/50Hz 100~230Vac/50Hz NA

System Operation Voltage (Vdc) 0~1000 0~1500 400~1000

Dimension (W*D*H mm) 375*710*171.5

Weight(kg) 13

Powercube-M3A-180
Basic Parameters
(148Ah)
Powercube-M3
Battery Module HM3A180

Battery System Capacity(kWh) 164.81

Battery System Voltage(V) 1305.6

Battery System Voltage Range (V) 1101.6~1468.8

Efficiency(@0.5C-rate) 96%

Depth of Discharge 90%

Cycle Life >7000, @25

Design Life 15+Years

Operation Temperature () 10~40

Humidity 5%~95%

Altitude(m) <2000

Battery Module Qty.(Optional) 1~34


UL1973, UL9540A, IEC62477-1, IEC62619, UKCA,
Certification CE LVD, CE EMC, UN38.3, VDE-AR-E 2510-50

Rack Dimension (W*D*H mm) 1365*845*2130

Weight(kg) 1798

11
SPECIFICATION

Battery Module
Basic Parameters HM5A180F

Energy (kWh) 15.36kWh

Norminal Voltage(V) 64

Battery Capacity(Ah) 240

Dimension (W*D*H mm) 460*900*160.5

Weight(kg) 110

Basic Parameters S1000M5A180J S1500M5A180E S1500M5A180J


BMS
AC Supply for BMS 230Vac/50Hz 230Vac/50Hz N/A

System Operation Voltage (Vdc) 0~1500 0~1500 450~1500

Dimension (W*D*H mm) 460*858*160

Weight(kg) 30

Powercube-M5A-64
Battery System
(240Ah)

Battery Module HM5A180F

Battery System Capacity(kWh) 322.56

Battery System Voltage(V) 1344


Powercube-M5A-64
Battery System Voltage Range (V) 1131~1491

Efficiency(@0.5C-rate) 96%

Max.Continuous Current(Ah) 180

Peak Current(Amps) 210A@5min/320A@30sec

Over Current/Duration (Amps/ms) 10000A/2ms

Depth of Discharge 95%

Cycle Life >7000, @25

Design Life 15+Years

Operation Temperature () 10~40

Humidity 5%~95%

Altitude(m) <4000

Battery Module Qty.(Optional) 1-21

Certification UL1973, UL9540A, IEC62477-1, IEC62040-1, IEC62619,UKCA, CE LVD,


CE EMC, UN38.3, VDE_x0002_AR-E 2510-50 GB36276 GB34131

Rack Dimension (W*D*H mm) 1050*925*2215

Weight(kg) 2520

12
SPECIFICATION

Mechanical Characteristics POWERCUBE20HM1 POWERCUBE40HM1

Battery System Powercube M1C Powercube M1C

System Voltage Range(Vdc ) 736(690~828) 736(690~828)

Charging/Discharging Rate 0.5C 0.5C

Battery String Amount 12 24

System Capacity (MWh) 1.421 2.841

Mechanical Characteristics POWERCUBE20HM2 POWERCUBE40HM2

Battery System Powercube M2 Powercube M2

System Voltage Range(Vdc ) 806(680~907) 806(680~907)

Charging/Discharging Rate 0.5C 0.5C

Battery String Amount 12 25

System Capacity (MWh) 1.432 2.983

Mechanical Characteristics POWERCUBE20HM3 POWERCUBE40HM3

Battery System Powercube M3 Powercube M3

System Voltage Range(Vdc ) <1000 <1500 <1000 <1500

Charging/Discharging Rate 0.5~1C 0.5~1C

Battery String Amount 10 6 22 16

System Capacity (MWh) 1.194 1.091 2.625 2.546

Dimension(L*W*H,M) 6.096*2.438*2.896 12.192*2.438*2.896

Temperature -20~60

Communication port CANBUS/Modbus TCP/IP

13
SPECIFICATION

Mechanical Characteristics POWERCUBE20HM5 POWERCUBE40HM5

Battery System Powercube M5 Powercube M5

System Voltage Range(Vdc ) <1000 <1500 <1000 <1500

System Capacity (MWh) 2.509 2.634 5.108 5.268

Battery String Amount 16 8 32 16

Dimension(L*W*H,M) 6.096*2.438*2.896 12.192*2.438*2.896

Weight (Ton) 28 27 58 56

Temperature -20~60

Communication port RS485/CAN/Ethernet

14
www.pylontech.com
[email protected]

Cube the Force

Pylontech datesheet-PY23PCI0526

Pylon Technologies Co., Ltd


No. 71-72, Lane 887, Zu Chongzhi Road,
Zhangjiang Hi-Tech Park Pudong,
Shanghai 201203, China