Tutorial - Frequency Control in Power Systems
Tutorial - Frequency Control in Power Systems
Example 1 [P. Kundur, “Power System Stability and Control”, Mc-Graw Hill Inc]
A small power system consists of 4 identical 500 MVA generating units feeding a total load of 1020 MW.
The inertia constant of each unit is 5.0 on 500 MVA base. The load varies by 1.5% for a 1% change in
frequency. The load drops by 20 MW suddenly.
(a) Determine the inertia constant and the load damping constant expressed on 2000 MVA base.
(b) Calculate the frequency deviation assuming that there is no speed governing system.
Answer
( )
-
( ) + ( )
-
( ) ( )
( ) ( )
( )
( )
The load reduces by 20 MW.
⁄
( )
( ) ( )
(a) ( )
-
( ) - ( )
+ +
-
⁄
( ⁄ )
⁄
For stability;
( ) ( )( )
( ) ( )( )( )
( )( )
( ) ( )
( )( )( )
Load change
( )
Dr. W. D. Prasad, Department of Electrical Engineering, University of Moratuwa Page 3
Steady-state frequency deviation
( )
A single area consists of two generating units with the following characteristics.
The units are operating in parallel, sharing 900 MW at the nominal frequency. Unit 1 supplies 500 MW
and unit 2 supplies 400 MW at 60 Hz. The load is increased by 90 MW.
(a) Assume there is no frequency-dependent load. Find the steady-state frequency deviation and the
new generation on each unit.
(b) The load varies 1.5% for every 1% change in frequency. Find the steady-state frequency deviation
and the new generation on each unit.
Answer
The given speed regulation values are with respect to the individual device bases. Therefore, the data need
to be expressed with respect to a common base. Select a common base of 1000 MVA.
⁄ ⁄
( )
New load of each Unit 1 and Unit 2:
(b)
( )
⁄ ⁄
Frequency deviation ( )
New frequency
Change in generation of Unit 1 and Unit 2:
( )
( )
New load of each Unit 1 and Unit 2:
Note:
In the second scenario, the total generation change is 84.375 MW. However, the change in load is
90 MW. Therefore, there is a difference of 5.625 MW. This is due to the change in load due to
frequency drop.