Sierra Leaone - Project - VC0-Report
Sierra Leaone - Project - VC0-Report
Auteur
Project: Sierra Leaone
Variant: Nouvelle variante de simulation
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
Project summary
Geographical Site Situation Project settings
Kagbeli Latitude 8.57 °N Albedo 0.20
Sierra Leone Longitude -13.19 °W
Altitude 11 m
Time zone UTC
Meteo data
Kagbeli
Meteonorm 8.1 (2010-2021), Sat=100 % - Synthétique
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 106556 units Nb. of units 24 units
Pnom total 65.00 MWp Pnom total 52.80 MWac
Pnom ratio 1.231
Results summary
Produced Energy 101799899 kWh/year Specific production 1566 kWh/kWp/year Perf. Ratio PR 84.43 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Predef. graphs 7
Single-line diagram 9
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 10 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Jinkosolar Manufacturer SMA
Model JKM-610N-78HL4-BDV Model Sunny Central 2200
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 610 Wp Unit Nom. Power 2200 kWac
Number of PV modules 106556 units Number of inverters 24 units
Nominal (STC) 65.00 MWp Total power 52800 kWac
Modules 6268 Strings x 17 In series Operating voltage 570-950 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.23
Pmpp 60.15 MWp
U mpp 718 V
I mpp 83751 A
Array losses
Thermal Loss factor DC wiring losses LID - Light Induced Degradation
Module temperature according to irradiance Global array res. 0.094 mΩ Loss Fraction 1.5 %
Uc (const) 37.3 W/m²K Loss Fraction 1.0 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
AC wiring losses
Inv. output line up to injection point
Inverter voltage 385 Vac tri
Loss Fraction 1.13 % at STC
Inverter: Sunny Central 2200
Wire section (24 Inv.) Copper 24 x 3 x 2500 mm²
Average wires length 84 m
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
Main results
System Production
Produced Energy 101799899 kWh/year Specific production 1566 kWh/kWp/year
Performance Ratio PR 84.43 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
Loss diagram
1837 kWh/m² Global horizontal irradiation
+1.0% Global incident in coll. plane
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
Predef. graphs
Diagramme d'entrée/sortie journalier
PVsyst V7.3.1
VC0, Simulation date:
08/04/24 16:20
with v7.3.1
Predef. graphs
Distribution de la puissance de sortie système