Nader NDB5 Products Specification
Nader NDB5 Products Specification
Models: NDB5
Date: 20181030
Edition 4 version
Product
Circuit breaker for equipment
Name Implementatio
n date
20181030
1 Application
NDB5 series circuit breaker for equipment (hydraulic-magnetic circuit breaker) is applied
in electrical system, of which the rated current is from 0.5A to 63A and the rated voltage is
AC230/400V, AC250V, AC480/277V (50/60Hz) or up to DC125V, to protect the circuit against the
overload current and short-circuit current. It is also can be used to make and break the circuit
infrequently. The product is widely used in computer and its peripheral equipment, industrial
2 Product Photos
https://www.quisure.com
Implementation
File number NDT500473 Edition 4 version 20181030
date
Note:
(1) The maximum rated current for 1-pole is 63A.
(2) 1P + N, 3P and 3P+N breakers are only available for AC type breaker.
(3) Parallel connected products only available for DC breakers. Furthermore, 2 pole parallel is
minimum for 20A, the maximum for 100A; 3 pole parallel is minimum for 105A, and
maximum for 150A
(4) NDB5 series HMCB can attach with auxiliary and alarm contact;
Implementation
File number NDT500473 Edition 4 version 20181030
date
There are two types of accessories available, auxiliary alarm contact and single auxiliary
contact.
1:Auxiliary alarm contact is consisted by a set of auxiliary contact(1NO+1NC) and a set
of alarm contact(1NO+1NC).
2:Single auxiliary contact is consisted by a set of auxiliary contact(1NO+1NC) ;
Accessary is assembled on the right pole of circuit breaker
Auxiliary contact is used to indicate the breaking-closing status of circuit breaker;
Alarm contact indicates circuit breaker`s fault tripping status;
Auxiliary and alarm contact should be bought with circuit breaker.
NDB5 series circuit breaker for equipment with accessories products comply with CCC
certification requirements.
(5) Above table lists are common types. The tripping curve, rated current, etc. can be made
according to the client's requirements. Special type will be made for those products which are
made according to client's requirement and won't be listed in the above table.
4 Main Specifications
Number
1P 1N 2P 3P 3N 2PU 3PU
of Poles
AC230/ AC230/
Rated DC80/12 AC400/415V DC80/ AC400/415V
240/250 240/250 DC80V
Voltage 5V AC480/277V 125V AC480/277V
V V
20,3
0.5,0.6,0.7,0.8,0.9,1, 105,
0,40,
1.5,2,2.5,3,3.5,4,4.5, 110,
Rated 0.5, 0.6, 0.7, 0.8, 0.9, 1, 1.5,2, 2.5,3,3.5, 4, 4.5, 5, 50,6
5,5.5,6,6.5,7,7.5,8,8. 120,
Current 5.5, 6,6.5, 7 ,7.5,8,8.5, 9, 9.5, 10, 12, 15, 16, 20, 0,63,
5,9,9.5,10,12,15,16, 125,
(A) 24, 25, 30, 32, 35, 40, 45, 50 70,8
20,24,25,30,32,35,4 135,
0,90,
0, 45,50,55,60,63 150
100
Installatio
35mm DIN Rail & Miniature Rail
n
Tripping J2,J4,J
Z2,Z4,Z6 J2,J4,J6 J2,J4,J6 Z2,Z4,Z6 J2,J4,J6 Z2,Z4,Z6
Curve 6
➢ Comply with standards: IEC/EN 60934, IEC/EN 60947-2, GB/T 17701, GB/T 14048.2, UL1077,
UL489A
➢ Rated working voltage: DC80V, DC125V,AC230/240/250V, AC400/415V,AC480/277V
➢ Frequency: 50/60Hz
➢ Mechanical endurance: 10000 times (including electrical endurance: 6000 times)
➢ Auxiliary/alarm contact technical parameters:
Auxiliary contact: DC125V 0.5A, AC 250V 6A;Alarm contact:DC250V 0.25A, AC250V 5A;
Mechanical & electrical life:15000 times(electrical life 10000 times);
Working frequency withstand voltage:1500V;
➢ Certificates: CCC, UL1077, UL489A, TUV, CE
➢ Cable Capacity:0.5~25mm², up to 35 mm²(2P in parallel:), up to 70 mm²(3P in parallel)
Implementation
File number NDT500473 Edition 4 version 20181030
date
LINE
LOAD
2)Configuration & Installation Dimension of the product with 57mm operation face
LINE
LOAD
Implementation
File number NDT500473 Edition 4 version 20181030
date
b:
Switch on direction
DIN Rail Installation. The breaker should be mounted within 5°of the mounting plane in
case the characters of the product are affected.
Operation method :The product handle can stay in three position, which will indicate
three working status of the product accordingly. When the handle stay in free trip position,
the product handle should be turned off to the end of the switch off direction and kept at the
position for at least one second firstly so that the machanism can be relatched. Then the
product can be switched on to fulfill the function of loading and protecting. When the handle
is at the switch off postion, the product can be switched on by turning the handle to fulfill the
function of loading and protecting. When the handle is at the switch on positon, the product
can be switched off either by turning the handle to cut off the load or automatical tripping to
Implementation
File number NDT500473 Edition 4 version 20181030
date
free trip position in specific time when the loading increase to conventional tripping current.
9、The wiring diagram of accessary
1) The wiring diagram of auxiliary contact
Auxiliary
11 Handle
CB status contact
position
status
12
OFF
14 12 11
OFF
14
ON
Load
ON
14 12 11
Electrical
TRIP
tripping
14 12 11
Line
The status diagram for handle`s position
91 Alarm
Handle
CB status contact
position
status
92
OFF
94 94 92 91
OFF
Load ON
ON
94 92 91
Electrical
TRIP
tripping
94 92 91
Implementation
File number NDT500473 Edition 4 version 20181030
date
ON
OFF
2.7
10.2 NDB5 series HMCB can attach only one pair of auxiliary signal function, which
terminal is pluggable connection strap.
Please refer below picture for auxiliary contact,“11,12,14” are auxiliary contact terminal
number.
ON
OFF
2.7
should be stored in the warehouse where there are ventilation. The relative humidity there
should not exceed 90%(20±5℃), and the ambient temperature there is between -40℃ to
+85℃. In addition, there should not be acidic, alkaline and corrosive gas in the air. The
products should not be deposited more than 3 years in the above mentioned conditions
since the producing date.
12 Safety notice
1) Do not disassemble the product with permission.
2) Attention to live part when the breaker is energized and avoid touching them.
3) Please make sure reliable connection to avoid fault tripping or terminal damager caused
by exceptional heas resulting from unsuitable connection. During installation,the fasten
torque of the body screw should be 2N.m, it should be 3.5 N.m fasten torque for the
busbar screw of the two pole parallel product and 10 N.m for the three pole parallel
product.
4) Please maitain the distance of 30mm from the arc jet slot of the product during
installation to avoid short current.