Technical Department

Technical Offer For Cables Generally to IEC 60502-1

Annealed Stranded Plain Copper Conductors, Insulated with XLPE Compound Suitable For Operating
Temperature 90°C And Sheathed By PVC Compound
General Information:

- Short Description: Cu/XLPE/PVC


- Voltage: 0.6 / 1 (1.2) kV
Stranded Plain Copper Conductor Circular Uncompacted for size < 10 mm2, Circular
- Conductor: Compacted for size >= 10 mm2 and Sector shape for size >= 50 mm2 according to IEC
60228 Class 2
- Insulation / Temperature: Cross Linked Polyethylene according to IEC 60502-1 / 90°C
- Sheathing Material / Color: PVC / Black

Cable Marking: ENERGYA POWER CABLES-ELSEWEDY HELAL No. of cores x size 0.6/1 kV Cu/XLPE/PVC Manufacturing Year

Printing Type: Ink Jet Or Embossed

Core Identification:
-2 Cores: Red, Black
Drawing Description
1- Copper Conductors
- Binder tapes and fillers may be used when necessary 2- XLPE Insulation
3- P.P Filler (optional)
Packing: 4- Binder Tape
-Cable shall be supplied in lengths as indicated in technical schedule on wooden reels . 5- PVC Sheathing
-Both ends of the cable shall be sealed to prevent the ingress of moisture during transportation and storage.
-Each reel shall be marked with type, size and length of Cable, and weight.
-This information shall be written on metallic tag nailed properly to the flange.

Tests:
-Routine tests generally to IEC 60502-1 are performed on the cables and test certificate will be supplied on request.
-Electrical Resistance of the conductors shall be tested on IEC 60228.
-Voltage Test: No breakdown of The insulation shall occur, The applied Voltage and duration will be as per IEC 60502-1.
-Hot Set Test for XLPE insulation according to IEC 60502-1

Electrical Data:
Maximum conductor operating temperature: 90 °C
Maximum conductor temperature during S.C: 250 °C
Laying conditions at trefoil formation are as below:
-Soil thermal resistivity 120 ˚C.Cm/Watt
-Burial depth 0.5 m
-Ground temperature 25 °C
-Air temperature 30 °C
-Frequency 50 Hz

Specifications:
Cutting Conductor AC Min Average
Approximate Approximate Minimum Maximum Conductor S.C.C
No. of Size Length Resistance at Thickness of Current Carrying Capacity
Outer Cable Weight Bending Conductor DC for
(MT) Flange/Outer Max. Oversheathing
width
Operating
Diameter (mm)± Resistance at Liad in
Cores (mm2) (Kg/Km)± 5 % Radius (mm) ± 10 % Temp. and 1 sec (KA) mm In duct Free Air
2.5 (mm) 20 °C (Ω/Km) Ground
50Hz (Ω/Km)
2X10 13.7 325 210 5000 1600 / 1088 1.83 2.333 1.43 1.24 89 75 87
-The above data is approximate and subjected to manufacturing tolerance.

Prepared By Approved By
Heba Mohamed Mahmoud Hamdeen
Technical Design Engineer Technical Section Head

10/29/2024 CR #