ZWB7 27HE Combi
ZWB7 27HE Combi
GREENSTAR HE combi
Wall mounted condensing boiler for central heating and mains
fed domestic hot water
Contents
1.4 Accessories
• Standard horizontal flue kit at 100 mm outside
diameter for flues upto 4 m in length.
• Flue duct kits for horizontal (125 mm outside
diameter) for flue lengths upto 13 m and vertical flue
systems for flue lengths uto 15 m. Fitting instructions
are sent with these kits.
• Heating programmer
• Timer
• Security kit.
min. min.
Z
5 5
Y X
120
906
850
861
101
13
103 200
30
35 360
440
395 250
Fig. 1
13 Manifold assembly
101 Outer case
103 Facia cover
X Standard Concentric Horizontal Flue System: min. 310 mm
Alternative Concentric Flue System: min. 250 mm
Y Standard Concentric Horizontal Flue System: 158 mm
Alternative Concentric Flue System: 121 mm
Z Standard Concentric Horizontal Flue System: 105 mm
Alternative Concentric Flue System: 130 mm
120
221.1
221.2 349
234.1
234
27
226
20 102
32.1
29
36
271 6
415
43
9
63
416
358
18
64
423
7 18.1
355
418
6.1 15
8.1
88
295 98
417 4
Fig. 2
4 Heatronic control 102 Inspection window
6 Heat exchanger safety temperature limiter 120 Fixing points
6.1 Hot water NTC sensor 221.1 Flue duct
7 Testing point for gas supply pressure 221.2 Combustion air intake
8.1 Pressure gauge 226 Fan assembly
9 Flue gas temperature limiter 295 Appliance type sticker
15 Relief valve 234 Testing point for combustion products
18 Pump 234.1 Testing point for combustion air
18.1 Pump speed selector switch 271 Flue duct
20 Expansion vessel 349 Cover plate for twin flue duct connection
27 Automatic air vent 355 Plate-type domestic hot water heat exchanger
29 Air gas Mixer unit 358 Condensate trap
32.1 Electrode assembly 415 Cover plate for cleaning access
36 Temperature sensor in CH flow 416 Condensate collector
43 CH flow 417 Clip for fixing outer case
63 Adjustable gas flow restrictor 418 Data plate
64 Adjusting screw for min. gas flow volume 423 Siphon
88 3-way valve (combi)
98 DHW flow switch (combi)
1.7 Function
Fig. 3
4 Bosch Heatronic control 63 Adjustable gas flow restrictor
6 Temperature limiter, heat exchanger 64 Adjusting screw for min. gas inlet flow volume
6.1 Hot water NTC sensor 69 Control valve
7 Testing point for gas supply pressure 84 Motor
8.1 Pressure gauge 88 3-way valve
9 Flue gas temperature limiter 90 Venturi
13 Manifold 91 Pressure relief valve
15 Safety valve 93 Water flow regulator
18 Central heating pump 94 Diaphragm
20 Expansion vessel 95 Pushrod with switch cam
26 Charging valve 96 Microswitch
27 Automatic vent 97 Valve for hot water flow volume
29 Mixer unit 98 Water valve
29.1 Bi-metallic thermostat for combustion air compensation 221 Flue duct
30 Burner 226 Fan
32 Flame sensing electrode 229 Inner casing
33 Igniter electrode 234 Testing point for flue gas
35 Heat exchanger with cooled combustion chamber 234.1 Testing point for combustion air
36 Temperature sensor in CH flow 317 Display
43 CH flow 355 Plate-type heat exchanger
44 Hot water flow 358 Condensate trap
45 Gas inlet 423 Siphon
46 Cold water inlet 443 Diaphragm
47 CH return
52 Solenoid valve 1
52.1 Solenoid valve 2
55 Filter
56 Gas valve CE 427
57 Main valve disc
61 Reset button
33
364 365 61 317 366 367 363
ECO
4.1
25 V
230 V
153 136 310
135
230V/AC
312 318
315
313 124 789
328 151 84
p
302
L N Ns Ls LR
300 314
p
p M
161
96
328.1
g
9 6 g
M M o
r
r o
mains supply 18 226
52 52.1
56
o o
bl
36 6.1
bl
bl
bl bl
32
Fig. 4
4.1 Ignition transformer 161 Link
6 Temperature limiter, heat exchanger 226 Fan
6.1 Hot water NTC sensor 300 Code plug
9 Flue gas temperature limiter 302 Earth connection
18 Pump 310 Temperature control for hot water
32 Flame sensing electrode 312 Fuse, slow T 1,6 A
33 Ignition electrode 313 Fuse, slow T 0,5 A
36 Temperature sensor in CH flow 314 Connector for programmer
52 Solenoid valve 1 315 Terminal block for programmer
52.1 Solenoid valve 2 317 Digital display
56 Gas valve CE 427 318 Connector for timer
61 Reset button 328 Terminal block for AC 230 V Mains supply
84 Motor, 3-way valve 328.1 Link
96 Microswitch, hydraulic switch 363 Indicator lamp for burner
135 Master switch 364 Indicator lamp for power supply
136 Temperature control for CH flow 365 “Chimney sweep” button
151 Fuse, slow 2.5 A, AC 230 V 366 Service button
153 Transformer 367 ECO button
APPLIANCE
Refer to Fig.1
Appliance
water flow
diagram A drain cock should be fitted at
the lowest point of the heating
circuit and the appliance
WRC approved
filling loop Lockshield
valve
Domestic
hot water Central heating flow
Radiator
valve
BS stop valve.
Fixed spindle type
Water
6 720 610 576 -09.2O
main
Hose Hose
union union
Test
cock
Test
Temporary hose
cock
3.5 Wall mounting frame assembly B Screw the pre-plumbing manifold with two screws to
the wall mounting frame.
B Take the wall mounting frame out of the package and
screw together with 6 screws as shown in fig. 7. Use
the inner lugs on the top and bottom horizontal
sections for the appliances that are 440 mm wide.
Fig. 9
50 35
120-130
260
6 720 610 576-06.1O
Fig. 10 Manifold
43 CH flow
47 CH return
112 Gas cock
171 Domestic hot water
172 Cold water relief
2.
1.
6 720 610 602 - 03.1O
Fig. 12
Fig. 14
Minimum dimensions of flue terminal positions (all types) (see fig. 14)
Dimension Terminal Position (kW input expressed in net) Balanced flues room sealed: Fanned draught
A1) Directly below an opening, air brick, opening windows, etc. 300 mm
Table 9
1) In addition, the terminal should not be nearer than 150 mm (fanned draught) to an opening in the building fabric formed for the pur-
pose of accommodating a built-in element such as a window frame.
H 3%
120
Centre (30 mm/meter)
line of
flue Top of the
opening wall
and mounting
appliance frame
Appliance
H
Standard Horizontal Flue 158 mm
6 720 610 602 - 07.1O
Optional Horizontal Flue 121 mm
Terminal
Assembly
Flue
Turret Maximum 1600mm
Outer
Wall
No Clamp
Clamp Extension
Duct
Terminal
Assembly
Flue
Turret
Outer
Clamp Wall
Clamp
No
Clamp Extension Extension
Duct Duct
6 720 610 602 - 10.1O
Duct Clamp
Flue Extension Air Duct
Turret
Raised Ring
locating the
terminal relative
120 to the outside
wall face
4 Electrical connections
B Always disconnect the power supply to
4.1 Connecting the appliance
the appliance at the mains before carry- To gain access to the mains connection remove the
ing out any work on the electrical sys- drop down facia cover. The drop down cover is
tems and components. removed by lowering it to the horizontal position and
pushing firmly upwards at the rear of the supports to
All control and safety systems are built into the appli- release the cover. Lift cover from the appliance.
ance. After installation (or in the event of an electrical fault) the
B Allow mains cable to protrude at least 50 cm from electrical system shall be checked for short circuits,
wall. fuse failure, incorrect polarity of connections, earth con-
B To make splash-water proof (IP): cut the cable grom- tinuity and resistance to earth.
met hole size to match diameter of cable, see fig. 26. B Pull out cover panel at the bottom and remove. Refer
to fig. 24.
It must be possible to isolate the appliance. The appli-
ance must be earthed.
The appliance must be connected to the mains through 0 3 4
2
a 6 A double pole isolator with a contact separation 5
1
3 mm in all poles and supplying the appliance and con- E
0 3 4
2
5
1
E
Fig. 25
B Cut cable grommet to diameter of cable. 4.2 Mains Voltage external controls
connections
0 3 4
2 NOTE: Only double insulated controls not requiring an earth can be used
5
1 Ns Ls LR Ns Ls LR
E ST8
ST8
Switched Live
Switched Live
Remove Link
Neutral
Neutral
Live
Live
Motor
230 V Room Thermostat Connections
230 V Programmer Connections
8-9
230 V room thermostat and Ns Ls LR
5-7 Programmer Connections ST8
Series
connection
Live
to be made
Sw
10-12 13-14
ed
itc
Neutral
safe
it ch
he
Ne
6 720 610 332-12.1R
Live
d
ut
Live
Sw
ra
Li
l
ve
Fig. 26
B Feed cable through cable grommet and connect the Motor
mains supply cable, see fig. 27. 6 720 610 576 - 22.1O
L N NS L S L R
4130-14.1R
Fig. 27
5 Commissioning
27
ECO
364
363 8.1
135 E
310
295 15
170
Fig. 29
8.1 Pressure gauge 5.1 Commissioning
15 Safety valve
27 Automatic vent
61 Reset button Never run the appliance when empty or
135 Master switch unpressurised.
136 Temperature control for central heating
170 Service cocks on CH flow and return
171 Hot water Benchmark Water Treatment: For optimum perform-
172 Gas cock (shown in on position) ance after installation, this boiler and its associated cen-
173 Cold water service cock tral heating system should be flushed in accordance
295 Appliance type sticker
310 Temperature control for hot water
with the guidelines given in BS7593:1992 - Treatment
317 Multifunction display of water in domestic hot water systems. Full instructions
358 Condensate trap are supplied with proprietary cleansers sold for this pur-
363 Indicator lamp for burner pose. If an inhibitor is to be used after flushing, it should
364 Indicator lamp for power supply be used in accordance with the inhibitor manufacturers
365 “Chimney sweep” button
366 Service button
instructions.
367 ECO button To drain the appliance shut the system valves and open
the pressure relief valve.
Suitable flushing agents and inhibitors are available
from Betz/Dearborn Tel.: 0151 4209563 and Fernox
Tel.: 01799 550811. Instructions for use are supplied
with the these products.
B Before commissioning, the gas supply pressure must
be tested (see page 29).
B Unscrew the condensation trap (358) and pull out, fill 5.3 Switching on the central heating
with approx. 1/4 l of water and refit. Refer to fig. 29.
The central heating flow temperature is adjustable
B Adjust charge pressure of expansion vessel to static between 35°C and 88°C. Refer to table 12, page 26.
head of the central heating system (see page 26).
B Open all system radiator valves. B Turn the temperature control to set the flow tem-
perature to a level appropriate to the type of central
B Turn on service valves (170), fill central heating sys- heating system:
tem to pressure of 1 - 2 bar through the WRc
approved filling loop. Refer to fig. 29. – Underfloor heating: e.g. setting “3”
(approx. 50°C)
B Vent radiators.
– Low-temperature heating: setting “E”
B Refill heating system and set the pressure to 1 bar. (approx. 75°C)
B Turn on cold water service cock (173). Refer to – Central heating systems for flow temperatures up
fig. 29. to 88 °C: limited “max” setting for low-temperature
B Check that the gas type specified on the identifica- operation (see page 26).
tion plate matches that of the gas supply. When the burner is alight, the red indicator lamp
B Turn on gas cock (172). Refer to fig. 29. lights up.
Fig. 31
If the display alternates between -II- and 5.5 Setting the domestic hot water
i the central heating flow temperature, the
trap filling programme is active.
temperature and flow rate
5.5.1 Domestic hot water temperature
The trap filling programme ensures that the condensa- The hot water temperature can be set to between
tion trap is filled after the appliance has been installed approx. 40 °C and 60 °C.
or after the appliance has been out of use for a long This temperature is not shown on the display.
period or the mains supply has been interrupted. For
that reason, the appliance remains at minimum heating
output for 15 minutes.
Comfort mode: button is not lit (factory setting) If the appliance is to be left for long periods switch the
central heating off:
The appliance is held constantly at the set temperature.
This means that hot water is available almost instanta- B Add a suitable anti-freeze fluid to the water in the
neously at the tap. Consequently the appliance will central heating system.
switch on at intervals, even if no hot water is being Suitable products are available from Betz-Dearborn
drawn. Tel.: 0151 4209563 and Fernox Tel.: 01799
550811.
ECO mode with demand detection, button is lit
The demand detection function enables maximum gas
5.8 Pump anti-seize function
and water economy.
Briefly turning a hot water tap on and then off again sig-
This function prevents the central heating
nals demand to the appliance which then heats up the
water to the set temperature. i pump seizing after long periods of inactiv-
ity.
Hot water is thus available in about 1 minute.
ECO mode, button is lit Every time the pump is switched off, a timer is started.
If after 24 hours the pump has not run again, it is
Water is not heated up until hot water is drawn. This
switched on for a period of 5 minutes.
means that there is a longer waiting period before hot
water is available.
5.9 Fault Condition
5.5.2 Hot water flow rate
The flow rate is factory set to 8 l/min. A list of faults that may occur is given on
Under standard conditions (2 bar) supply pressure, one
full turn is equivalent to approximately 2 l/min.
i page 43.
B To increase the flow rate (max. 14 l/min): In the unlikely event of a fault occuring while the appli-
turn screw on flow switch anti-clockwise (+). ance is in operation:
The outlet temperature will decrease relative to the The display then shows a fault code and the button -
increase in the flow rate. may also flash.
B To reduce the flow rate (min. 8 l/min): If the button flashes:
turn screw on flow switch clockwise (–).
B Press and hold the button until the display shows
The outlet temperature will increase relative to the
“– –”.
decrease in the flow rate.
The appliance will then start up again and the display
will show the central heating flow temperature.
If the button does not flash:
B Switch the appliance off and then on again at the
master switch.
The appliance will start up again and the central heat-
ing flow temperature will be displayed.
Fig. 33
6 Individual settings
6.1 Mechanical settings B Rotate yellow button through 180° and replace (dot
facing inwards).
6.1.1 Checking the size of the expansion vessel The CH flow temperature is no longer limited.
Maximum pressure at maximum CH flow temperature is
2.5 bar. If the pressure is greater than this then fit an Control setting CH flow temperature
extra expansion vessel. Refer to table 11. 1 approx. 35°C
System Capacity – BS7074:1 2 approx. 43°C
3 approx. 51°C
Expansion Vessel Pressure and System Capacity 4 approx. 59°C
5 approx. 67°C
Expansion Vessel litres 10
E approx. 75°C
Expansion Vessel bar 0.75 max approx. 88°C
Charge Pressure
Table 12
System 1 bar litres 82
6.1.3 Changing the heating pump characteristic
pressure
and 1.5 bar litres 46 The speed of the central heating pump can be altered
capacity on the pump terminal box.
0,5
3
Limited maximum setting for low-temperature
operation 0,4
Fig. 34
6.2.4 Setting the maxim CH flow temperature B Refer to the settings tables for heating and cylinder
(Service Function 2.5) charging output to obtain the relevant code for the
The maximum CH flow temperature can be set to desired heating output in kW (see page 45).
between 35°C and 88°C (factory setting). B Turn the temperature control until the display
shows the desired code number.
6.2.5 Setting the switching difference The display and the and buttons will flash.
(Service Function 2.6)
B Measure the gas flow rate and compare with the fig-
If the appliance is connected to an out- ures specified for the code number displayed. If fig-
i side-temperature controlled programmer,
the programmer sets the switching differ-
ures do not match, adjust the code number!
B Press and hold the and buttons simultane-
ence. ously until the display shows [ ].
It does not need to be set on the appli- The heating output is now stored.
ance.
Fig. 38
Natural gas
234
• Appliances for natural gas type G20 are factory set
to Wobbe-Index 15 kWh/m3 and 20 mbar supply
pressure and sealed.
Conversion kits
6 720 610 332-57.1R
Fig. 41
B Turn the temperature control until the display
shows 2.0 .
After a short delay, the current operating mode set-
ting will be displayed (0. = Normal mode).
Fig. 42
B Turn the temperature control until the display B Turn the temperature control anti-clockwise until
shows 2. the display shows 1. (= min. rated heat output).
(= max. rated heat output). The display and the button will flash.
The display and the button will flash.
63
Fig. 44 Fig. 46
B Measure the CO level.
CO2 reading If the CO level is over 300 ppm, the gas volumetric
at max. CO2 reading flow rate is too high. Reduce the gas flow rate on the
rated heat at min. rated adjustable gas flow restrictor (63) until the CO level
Gas Type output heat output is below 100 ppm.
Natural gas type 9.5 % 9.2 % B Re-adjust the CO2 level if necessary.
H (23) B Recheck the levels at min. and max. rated heat output
LPG 11.3 % 11.0 % and re-adjust if necessary.
(propane) B Turn the temperature control anti-clockwise as
Table 15 far as the stop so that the display shows 0.
B Measure the CO level. (= Normal operating mode).
If the CO level is over 300 ppm, the gas volumetric The display and the button will flash.
flow rate is too high. Reduce the gas flow rate on the B Press and hold the button until the display
adjustable gas flow restrictor (63) until the CO level shows [ ].
is below 100 ppm. B Reset the temperature controls and to their
B Re-adjust the CO2 level if necessary. original positions.
The display will revert to the CH flow temperature.
B Remove testing probe from the flue gas testing point
(234) and refit sealing plug.
B Re-seal gas valve adjusting screw and gas flow
restrictor.
B Replace outer case and secure.
utes in which to measure the levels. After B CO- and CO2 levels.
that, the appliance switches back from B Refit sealing plug.
“chimney sweep” mode to normal mode. B Press and hold button until the display shows – –.
The button will stop flashing and the display
B Remove sealing plug from combustion air testing shows the CH flow temperature.
point (234.1, fig. 47).
B Insert testing probe about 80 mm into the testing
point and seal testing point.
234
234.1
Fig. 47
B Measure O2 and CO2 levels.
B Refit sealing plug.
B Press and hold button until the display shows – –.
The button will stop flashing and the display
shows the CH flow temperature.
8 Maintenance
B Always disconnect the appliance from
the electrical power supply (fuse, circuit
breaker) before carrying out any work on
the electrical systems or components.
Date
If the display shows 2 or 3, the ionisation current is OK. The heat exchanger should only be
If the display shows 0 or 1, the electrode assembly
(32.1, page 6) must be cleaned or replaced.
i cleaned if the control pressure is
2.2 mbar (depression) or less.
Domestic hot water B Remove cleaning access cover (415, page 6) and
If the flow rate is too slow: the metal plate below it, if present. Refer to fig. 2.
B remove the domestic hot water heat exchanger and B Unscrew condensation trap and place suitable con-
replace, tainer underneath. Refer to fig. 50.
-or- B Remove the fan and the burner as described in the
B descale with a descaling agent approved for use on text headed “Burner” (see page 35).
stainless steel.
B Before removing the heat exchanger shut the inlet
valve and drain the hot water circuit.
B Use new seals when replacing the heat exchanger.
Fig. 50
Fig. 48
4.
6 720 610 332-73.1R
Fig. 51 2.
B Clean the heat exchanger from top to bottom using 3.
the brush. Refer to fig. 52. 1.
Fig. 54
B Remove burner and clean components. Do not use a
wire brush. Refer to fig. 55.
Fig. 52
B Remove the fan and the burner (see section headed
“Burner”) and flush the heat exchanger from the top.
B Clean out the condensate collector and trap connec-
tion (with other end of brush).
1.
H 2O
2.
Fig. 55
Fig. 53
B Refit the clean-out cover using a new seal and B Re-assemble burner in reverse order using a new
tighten screws to torque of approx. 5 Nm. seal.
B Adjust gas/air ratio. Refer to section 7.2.
Diaphragm in mixer unit B Replace and re-connect the assembly taking care not
to mislay the inspection window.
B Take care not to damage diaphragm
(443) when removing and refitting it. Siphon
B Unscrew the clip and disconnect the pipe to the
B Open mixer unit (29). siphon.
B Carefully withdraw diaphragm (443) from fan intake B Remove the yellow plug to drain the siphon.
tube and check for soiling and splits. B Unscrew the securing nut from beneath the side
facia and remove the siphon. Refer to figure below.
B Refit and prime the siphon.
3.
443 Condensate
Drain
Siphon
1.
29
2.
6 720 610 790 - 07.1O
Fig. 56 Fig. 57
B Carefully refit diaphragm (443) the correct way round
into the fan intake tube.
Condensation trap
In order to prevent spillage of condensate, the conden-
sation trap should be completely removed, (see
page 34, fig. 50).
B Unscrew condensation trap and check connection to
heat exchanger is clear.
B Remove condensation trap cover and clean.
B Fill condensation trap with approx. 1/4 l of water and
refit.
Electrode assembly
B Switch off the master switch.
B Pull off the leads from the electrodes. Refer to fig. 2.
B Unscrew the two fixing screws and carefully remove
the electrode assembly. Refer to fig. 49.
B Clean the electrodes with a non-metallic brush. (The
spark gap should be 4,5 mm ± 0,5 mm.)
Expansion vessel
The expansion vessel should be checked once a year.
B Depressurise appliance.
B If necessary, adjust expansion vessel charge pres-
sure to static head of the heating system.
Electrical wiring
B Check the electrical wiring for physical damage and
replace any damaged wires.
1
3
2 4
3 4 1
7 181 465 330-10.1R
3
2
2 4
1
E
Fig. 59
1
Fuses
3
2 4
Alternatively
B After removing the siphon release the four Allen
screws and remove and replace the pump head.
3.
Fig. 60
B Switch off the appliance.
B Disconnect the appliance from the power supply.
B Undo lower pipe union on gas pipe (1.). Refer to
fig. 60. 1.
B Remove fan lead and earth connector (2.). The earth 1.
connector has a positive clip fixing.
B Remove fixing screws attaching fan to the burner
cover (3.).
B Remove fan together with gas pipe and mixer unit.
B Separate the fan from the pipe and mixer unit by 2.
twisting the mixer unit to release it (4.). Fig. 61
Fig. 62
After refitting:
B Fill system, bleed and re-pressurise
(see Installation Instructions).
8.3.13 Burner
B Refer to section 8.2.
Fig. 63
8.3.14 Flow switch B Pull forward from the top and lift the heat exchanger
from the casing.
B Shut the mains water inlet valve and drain the domes-
tic hot water circuit. B Transfer components, as necessary, to the new heat
exchanger.
B Pull-off the connectors from the micro-switch.
B Ensure that all the seals are in place and all of the
B Unscrew the inlet and union connection and remove
connections are tight before re-commissioning the
the assembly.
appliance.
B Reset the domestic hot water flow rate on the new
assembly.
OUTLET
INLET
Fig. 64
9 Appendix
Display
code Description Remedy
A7 Hot water NTC sensor defective. Check hot water NTC sensor and connecting lead for
circuit breaks/short circuits.
A8 Break in communication Check connecting lead to programmer
AC Module not detected. Check connecting lead between TA211E/TR212E
and Heatronic
b1 Keyed plug not detected. Insert keyed plug correctly, test and replace if neces-
sary.
C1 Fan speed too low. Check fan lead and connector, and fan; replace as
necessary.
d3 Jumper 8-9 not detected. Connector not connected, link missing, underfloor
heating limiter tripped.
E2 CH flow NTC sensor defective Check CH flow NTC sensor and connecting lead.
E9 Safety temp. limiter in CH flow has tripped. Check system pressure, check safety temp. limiters,
check pump operation, check fuse on pcb, bleed
appliance.
EA Flame not detected. Is gas cock turned on? Check gas supply pressure,
power supply, igniter electrode and lead, ionisation
sensing electrode and lead, flue duct and CO2 level.
F0 Internal error. Check electrical connector contacts, programmer
interface module ignition leads are not loose; replace
pcb if necessary.
F7 Flame detected even though appliance switched off. Check electrode assembly, dry pcb. Flue clear?
FA Flame detected after gas shut off. Check gas valve and wiring to gas valve. Clean con-
densation trap and check electrode assembly. Flue
clear?
Fd Reset button pressed by mistake. Press reset button again
P1, P2, P3, Please wait, initialisation in progress. 24 V fuse blown. Replace fuse.
P1...
Table 17
Fig. 66
9.5.1
9.5
Appendix
** NOTE:
The appliance controls can be set to one of
.
Heat input
Gas valve Fan runs for
Mains Green Hot Pump ON Fan to modulates to
Pre-heat Demand closes. upto 3 mins. Pre-heat
switch light water Diverter valve start speed. maintain the
mode.** ends. Red light Pump runs mode.**
ON. ON. demand. operates. Gas valve opens. delivery
OFF. for 30secs.
temperature.
Ignition sequence
No
Fig. 67
9.5.2
Over temperature
Burner remains OFF
Gas valve shuts. shut-down if water
Room thermostat
and/or mains
programmer or Boiler
link ON operates to
Mains Green AND CH
Pump ON
Fan to
Burner
stabilises at
Fan speed
reduces
Fan min.
Boiler
unused for
Yes *
Minimum
match
switch light Electronic facia speed for system load
demand. start speed. start speed over 15 long heat input
ON. ON. programmer 90 secs. and CH
Gas valve opens. for 5-10 secs secs. period.* for 15min.
(if fitted) ON control
AND setting.
CH control knob
No
ON. ce
Ignition sequence
Gas valve
Pump and Fan
Ignition spark for Burner lights. Yes CH demand closes.
run for upto
5 seconds. Red light ON. satisfied. Red light
3 mins.
OFF.
No
Repeats 5 times Fan runs to purge * NOTE: The sequence ensures that the condensate siphon is not empty
before lock-out. gas from burner. after long OFF periods. (More than 24 hours without a demand).
Appendix
47
Appendix