CP40
CP40
PSS 21H-1B3 B3
Product Specifications
PSS 21H-1B3 B3
Page 2
• Twinaxial (Dual-Conductor Coaxial) Fieldbus • Fiber Optic Fieldbus Extension (Figure 3) - The
Extension (Figure 2) - Using twinaxial cable, the fiber optic Fieldbus can optionally extend the
Fieldbus can optionally extend outside of the distance as well as add application versatility and
enclosure and can be up to 1800 m (6000 ft) in security. Overall Fieldbus length can be up to
length. Up to 64 Fieldbus Modules (excluding 20 km (12.4 mi). Like the twinaxial Fieldbus
expansion modules) attach to the extended bus configuration, the fiber optic Fieldbus
through Fieldbus isolators. (Up to 24 Fieldbus configuration supports up to 64 Fieldbus Modules
Modules, excluding expansion modules, can (excluding expansion modules), up to 24
connect to each isolator.) The twinaxial Fieldbus Modules per isolator.
extension may be redundant.
2. CONNECTION OF THE FIBER ISOLATORS TO THE FIELDBUS MODULES (FBMs) IS SIMILAR TO THAT SHOWN IN FIGURE 2.
3. ANY TWINAXIAL FIELDBUS SEGMENT CAN BE EXTENDED TO SERVICE FBMs IN ANOTHER ENCLOSURE. (TWINAXIAL
CABLING BETWEEN ENCLOSURES IS SHOWN IN FIGURE 2.)
All three Fieldbus configurations use serial data The Control Processor 40 connects to the Panel
communication complying with Electronic Industrial Display Stations and Fieldbus Modules via either of
Association (EIA) Standard RS-485. The data two types of Fieldbus communications media:
transmission rate is 268.75 Kbps. twinaxial cable or fiber optic cable. Figure 4 shows a
typical twinaxial Fieldbus configuration, and Figure 5
Panel Display Station Interfacing shows a typical fiber optic Fieldbus configuration.
The Control Processor 40 achieves the capability to (Refer to Fiber Optic Fieldbus Product Specification
interface Panel Display Stations when the DSI (Panel Sheet PSS 21H-7P1 B3 for additional fiber optic
Display Station Interface) block is selected via the Fieldbus application information.)
configurator. In this capacity, the Control
Processor 40 can interface up to 24 Panel Display Cluster I/O Subsystem Interfacing
Stations, or a combination of Fieldbus modules The Control Processor 40 interfaces with the Fieldbus
(which may include associated Auto/Manual Stations) Cluster Input/Output Subsystem that consists of the
and Panel Display Stations mixed on the same Fieldbus, a multi-slot chassis configuration of a
Fieldbus. (Note, however, that per configuration rules, Fieldbus Processor (FBP10), analog/digital Fieldbus
one Panel Display Station counts as two Fieldbus Cards (FBCs), and power supply and power monitor
Modules.) card. These Cluster I/O subsystems meet the needs
Control strategies should be planned such that all of applications where a high number of channels per
blocks involved with the Panel Display Station, card are required. Figure 6 shows a typical twinaxial
Auto/Manual Station, and the control loops being Fieldbus configuration. (Refer to the Fieldbus Cluster
monitored or controlled are in the same Control I/O Subsystem PSS 21H-2T1 B3 for additional
Processor 40, and ideally in the same compound. information.)
FIELDBUS*
TCA TCA TCA
TERMINATING TERMINATING
RESISTOR FIELDBUS RESISTOR
CONTROL FIELDBUS
PROCESSOR ISOLATOR TERMINATING ISOLATOR
40** RESISTOR
CB
DW OR A/M DW OR DW OR
PLUG PLUG PLUG
PLUG STATION PLUG PLUG
Figure 4. Panel Display Station Interface Configuration using Twinaxial Fieldbus (Typical Configuration)
PSS 21H-1B3 B3
Page 5
TCA TCA
END BUS MID BUS END BUS
MODEM* MODEM* MODEM*
TERMINATING TERMINATING
RESISTOR RESISTOR
TERMINATING
RESISTOR TCA TERMINATING
RESISTOR
CONTROL
FIELDBUS FIELDBUS
PROCESSOR TERMINATING
ISOLATOR ISOLATOR
40** RESISTOR
* OPTIONALLY FAULT-
CB
TOLERANT
FBMXX FBM22 PANEL PANEL FBM22 FBM22
** OPTIONALLY (1) (N) DISPLAY DISPLAY (1) (24)
REDUNDANT STATION STATION
(N + 1) (24)
ABBREVATIONS:
TCA = Termination Cable DW OR
Assembly PLUG A/M DW OR DW OR
PLUG PLUG PLUG
A/M = Auto/Manual STATION PLUG PLUG
DW = Discrete - Wire
Connector A/M A/M
CB = Coupling Block STATION STATION
Figure 5. Panel Display Station Interface Configuration using Fiber Optic Fieldbus (Typical Configuration)
FIELDBUS*
TCA TCA TCA
TERMINATING
RESISTOR
TERMINATING CLUSTER I/O SUBSYSTEM CLUSTER I/O SUBSYSTEM
RESISTOR
CONTROL FBP10 FBP10
PROCESSOR
40**
ICH12 CHASSIS ICH19 CHASSIS
N = UP TO 12 CARDS N = UP TO 19 CARDS
* OPTIONALLY REDUNDANT
** OPTIONALLY FAULT-TOLERANT TO/FROM TO/FROM
ABBREVATIONS: PROCESS DEVICES PROCESS DEVICES
TCA = Termination Cable Assembly
FBP = Fieldbus Processor NOTE: FBP INTEGRATORS HAVE BUILT-IN FIELDBUS ISOLATORS.
ICH = Industrial Chassis
Figure 6. Twinaxial Fieldbus Cluster I/O Subsystem Interface Configuration (Typical Configuration)
PSS 21H-1B3 B3
Page 6
FIELDBUS*
TCA TCA TCA TCA TCA
TERMINATING
RESISTOR TERMINATING
RESISTOR
CONTROL
PROCESSOR
40**
UCM RACK FIO RACK UFM RACK UIO RACK
Figure 7. Twinaxial Fieldbus SPECTRUM Migration Subsystem Interface Configuration (Typical Configuration)
PSS 21H-1B3 B3
Page 7
SPEC 200 Control Interfacing Control is via the software resident in the Control
For migration of SPEC 200 control to I/A Series Integrator and in the SPEC 200 I/O Equipment
Systems, the Control Processor 40 interfaces via a Control Blocks (ECBs) operating at the CP level.
single or redundant I/A Series Fieldbus with the Figure 8 illustrates a typical configuration with
SPEC 200 Control Integrator subsystem. This multiple Control Integrators in the SPEC 200
subsystem consists of individual Control Integrators, subsystem. (Refer to PSS 21H-7R1 B3 SPEC 200
and Fieldbus Isolators attached within the SPEC 200 Control Integrators for additional information.)
rack.
FIELDBUS*
TCA
N = UP TO 24 CARDS N = UP TO 24 CARDS
TO/FROM TO/FROM
PROCESS DEVICE(S) PROCESS DEVICE(S)
ABBREVATIONS:
* OPTIONALLY REDUNDANT TCA = Termination Cable Assembly
** OPTIONALLY FAULT-TOLERANT SSFBI = SPEC 200 Single Fieldbus Isolator
Figure 8. Twinaxial Fieldbus SPEC 200 Control Subsystem Interface Configuration (Typical Configuration)
PSS 21H-1B3 B3
Page 8
FIELDBUS*
TCA
SPEC 200 MICRO NCM RACK 1 SPEC 200 MICRO NCM RACK 2
TERMINATING
RESISTOR
MSFBI* MSFBI*
CONTROL TERMINATING
PROCESSOR RESISTOR
40**
N = UP TO 24 CARDS N = UP TO 24 CARDS
TO/FROM TO/FROM
PROCESS DEVICE(S) PROCESS DEVICE(S)
ABBREVATIONS:
* OPTIONALLY REDUNDANT TCA = Termination Cable Assembly
** OPTIONALLY FAULT-TOLERANT MSFBI = SPEC 200 MICRO Single Fieldbus Isolator
Figure 9.
Twinaxial Fieldbus SPEC 200 MICRO Control Subsystem Interface Configuration (Typical Configuration)
PSS 21H-1B3 B3
Page 9
PSS 21H-1B3 B3
Page 10
FUNCTIONAL SPECIFICATIONS
Processor Type Process I/O Capacity
CONTROL PROCESSOR LOCAL
Microprocessor-based Intel 486DX4 (running at 24 Fieldbus Modules(D), maximum
100 MHz) with stored programs, using high-speed EXTENDED
communication capability. 64 Fieldbus Modules(D), maximum (24 maximum on
NODEBUS PROCESSOR any one Fieldbus isolator)
82596CA LAN CoProcessor PANEL DISPLAY STATION INTERFACING
FIELDBUS PROCESSOR Up to 64 FBMs(D) or FBM equivalents (24 maximum
8344AH MicroController with serial port on any one Fieldbus isolator). One Panel Display
Station counts as two FBMs. For example, if 24
Memory FBMs are used, only 20 Panel Display Stations may
SIZE be used.
4 MB storage
ERROR DETECTION Power Requirements
Parity provides single-bit error detection for each INPUT VOLTAGE (REDUNDANT VOLTAGE)
byte. 39 V dc typical
CONSUMPTION (PER NON-FAULT-TOLERANT
Process I/O Communications MODULE)
LOCAL TWINAXIAL(A) FIELDBUS 15 W, maximum
Type
EIA RS-485 Indicators
Distance Red and green light-emitting diodes (LEDs) indicate
10 m (30 ft) operational status.
ENVIRONMENTAL SPECIFICATIONS(A)
Operating Storage
TEMPERATURE TEMPERATURE
0 to 60°C (32 to 140°F) -40 to +70°C (-40 to +158°F)
RELATIVE HUMIDITY RELATIVE HUMIDITY
5 to 95% (Noncondensing) 5 to 95% (Noncondensing)
ALTITUDE ALTITUDE
-300 to +3,000 m (-1,000 to +10,000 ft) -300 to +12,000 m (-1,000 to +40,000 ft)
(A)
The environmental ranges can be extended by the type of enclosure containing the module. {Refer to the applicable Product
Specification Sheet (PSS) which describes the specific enclosure that is to be used.}
PHYSICAL SPECIFICATIONS
Configuration Mounting
Single-width processor module. The fault- tolerant May be placed in any of the following mounting
version consists of two single-width processor structure slots:
modules with two interconnecting buses (X-bus and – 1 X 8 Mounting Structure
Z-bus). – Industrial Enclosures (IE16 and IE32),
Structural Foam or Metal
Mass (Maximum) – Field Enclosure 8, Structural Foam or Metal
1.7 kg (3.75 lb) for a single, non-fault-tolerant module.
In the fault-tolerant version, the two modules must be
mounted in adjacent mounting structure slots with the
two interconnecting buses.
PSS 21H-1B3 B3
Page 12
Foxboro, I/A Series, SPEC 200, SPEC 200 MICRO, and SPECTRUM are trademarks of The Foxboro Company.
Siebe is a registered trademark of Siebe, plc.
Intel is a trademark of Intel Corporation.