Yuasa Technical Data Sheet

Yuasa NP7-12 Industrial VRLA Battery

Specifications
Nominal voltage (V) 12
10-hr rate Capacity to 1.8V/Cell at 20°C (Ah) 6.4
20-hr rate Capacity to 1.75V/Cell at 20°C (Ah) 7
Dimensions
Length (mm) 151 (±1)
Width (mm) 65 (±1)
Height over terminals (mm) 97.5 (±2)
Mass (kg) 2.2
Terminal Type
FASTON - Quickfit / release (JST where stated) 4.75
Operating Temperature Range
Storage (in fully charged condition) -20°C to +60°C
Charge -15°C to +50°C
Discharge -20°C to +60°C
Storage
Capacity loss per month at 20°C (% approx.) 3
Case Material
Layout
Standard ABS (UL94:HB)
FR version available UL94:V0
Charge Voltage
Float charge voltage at 20°C (V)/Block 13.65 (±1%)
Float charge voltage at 20°C (V)/Cell 2.275 (±1%)
Float Chg voltage tmp correction factor from std -3
20°C (mV)
Cyclic (or Boost) charge Voltage at 20°C (V)/Block 14.5 (±3%)
Cyclic (or Boost) charge Voltage at 20°C (V)/Cell 2.42 (±3%)
Cyclic Chg voltage tmp correction factor from std -4
20°C (mV)
Charge Current 3rd Party Certifications
Float charge current limit (A) No limit ISO9001 - Quality Management Systems
Cyclic (or Boost) charge current limit (A) 1.75
Maximum Discharge Current
1 second (A) 210
1 minute (A) 48
Impedance
Measured at 1 kHz (mΩ) 23 Safety
Design Life & Approvals Installation
EUROBAT Classification: Standard Commercial 3 to 5 years Can be installed and operated in orientations up to 90° from
Yuasa design life at 20°C (yrs) up to 5 the upright position.
Handles
Batteries must not be suspended by their handles (where
fitted).
Vent valves
Each cell is fitted with a low pressure release valve to allow
gasses to escape and then reseal.
Gas release
VRLA batteries release hydrogen gas which can form
explosive mixtures in the air. Do not place inside a sealed
container.
Recycling
YUASA’s VRLA batteries must be recycled at the end of life in
accordance with local and national laws and regulations.

Data Sheet generated on 13/10/2024 – E&OE

The world's leading battery manufacturer www.yuasaeurope.com