AVS ControlpanelDanfoss UserManuel ENG04
AVS ControlpanelDanfoss UserManuel ENG04
1. Product Information
AVS is a pump control panel having 4.3“ TFT touch screen, uniquely designed high efficient
variable speed control and relay board. The touch control panel is located on front casing
while relay module is located inside. Other than these, Manual / Auto / Off Selection
Button, Manual Control Buttons and Interlock Switch are available on front casing. AVS
panel provides control and screen up to 6 pumps with the help of EPLC-6 control system,
relays and switching components. System parameters can be changed on touch screen
with user-friendly interface.
AVS Panel can be used on constant pressure booster or differential pressure circulation
systems with the help of receiving data from an analog pressure sensor. The panel
especially is recommended to use with frequency inverted pump applications. Apart from
that, it is also possible to use the panel on constant cycle pump systems.
Manual Control
Buttons
Interlock Switch
2
Thermostatic
Switch For
Cooling Fan Power
Supply
Contactors
Cooling
Fan
Fuses
ETNA Electronic
Thermic Relay Driver
EPLC-6 Relay
Board
Relays
Modbus Swichgear
Connectors
Auto/Man Mod
Selection Button
* The inside image of the panel may differ from the picture above.
4
3. Menus
To reach device menus, tap the symbol on the main screen to reach the password
screen. Once you enter your password, you can make any desired changes in the settings
menu, either when the system is working or after halting it. Changes made to the system
will not be saved unless the symbol on screen is tapped. Simply tap the relevant
symbol for the sub-menu to reach it, and to return to a previous menu, simply tap the
symbol.
The up-down arrow symbol seen in menus is used to increase or decrease the value
in the box to its left. Simply tap the up arrow icon to increase the value, and the down
arrow icon to decrease it. When the symbol is pressed and held, the value will continually
increase or decrease until the allowed limit. For 3-digit numbers, the relevant digit can be
tapped to make changes.
BACK
CIRCULATION
In booster pump mode, the EPLC-6
control unit compares a single data
collected from the 4-20 mA pressure
transmitter to the set value at which SAVE BACK
the device is desired to work. Figure 4: Device Operation Mode
Selection Menu
If the pressure data collected from the transmitter is larger than the set value, the system
stays in standby state. If the pressure data collected from the transmitter is smaller than
the set value, the least used pumps are activated in order. If there is a driver in the system,
the first pump is activated by the driver. In the event that a single pump cannot meet the
demand; if there are other pumps, they are activated in order depending on the demand
and work to bring the system's current pressure up to the set value. When demand
decreases -or as the current pressure value surpasses the set value- the pump with the
driver slows down and attempts to match the reference pressure value. The pumps are
deactivated if they are no longer needed.
5 www.etna.com.tr
If in circulation mode, the EPLC-6 control unit first calculates the difference between two
sets of data collected from the 4-20 mA pressure transmitters (transmitter1-transmitter2,
where transmitter1 is the value gathered from the transmitter at the entrance of the fixture
and transmitter2 is from the transmitter at the exit of the fixture) and then compares
this to the set differential pressure value at which the device is desired to work. When
the system is run, if the difference between the values acquired from the transmitters is
larger than the set value, the system keeps running with a single pump. If there is a driver
in the system, it operates at minimum frequency. If the difference in pressure between
transmitters is smaller than the set value, and if there is a driver in the system, the pump
with the driver accelerates and attempts to match the reference differential pressure. If
necessary, that is to say, if a single pump cannot meet the demand, the other pumps are
activated in order and deactivated if the need is met. If the difference between the two
transmitter values goes above the set value again (if the demand is met), a single pump is
kept in operation. If there is a driver, it operates at minimum frequency.
PARAMETER BOOSTER CIRCULATION
NUMBER OF REPEAT 5 0
SPARE PUMP 0 0
DRIVER SELECTION 1 1
Pump Count: The number of pumps can be determined from the number of pumps field
shown on the screenshot in Figure 5, by touching the icons. Pump number can be
increased up to 6 pumps.
Switch On Time: For systems with multiple pumps (2-6 pumps), the pump activation
period is the time required for other pumps to be activated in order after the 1st one, in
case of need. In driver mode, if the driver has reached maximum frequency and the set
value is higher than the current value, the activation period begins counting down in the
background. If the set pressure value is not reached by the end of the activation period,
a stand-by pump steps in. This process continues for all stand-by pumps until the current
pressure value reaches the set pressure value.
In systems without a driver or in case of an error in the driver;
The activation period shortens by 10 times in booster pump mode. For example, if the
activation period has been set to 30 seconds, it drops to 3 seconds.
The activation period gets multiplied in circulation mode. For example, if the activation
period has been set to 30 seconds, it lengthens out to 60 seconds in systems without
drivers or in case of driver errors. Factory setting is 30 seconds.
Switch Off Time: For systems with multiple pumps (2-6 pumps), the pump deactivation
period counts down in the background when there are multiple active pumps and when
the current pressure value is higher than the set value at the same time. If the current
pressure value does not decrease below the set value by the end of the set deactivation
period, pumps deactivate in order.
In systems without a driver, or in case of an error in the driver;
The deactivation period shortens by 10 in booster pump mode. For example, if the
deactivation period has been set to be 30 seconds, it fixture is 0 but to 3 seconds.
The deactivation period gets multiplied by 2 in circulation mode. For example, if the
deactivation period has been set to 30 seconds, it lengthens out to 60 seconds in systems
without drivers or in case of driver errors. Factory setting is 30 seconds.
Wakeup Pressure: Wakeup pressure is the differential pressure between the set system
pressure and the pressure value for pump activation.
In booster pump mode, wakeup pressure is the differential pressure value at which the
wakeup (pump activation) period starts counting, which is identified to prevent the system
from continuously activating and deactivating and which can be adjusted as needed.
7 www.etna.com.tr
p : Wake-up pressure
t1 : Pump start delay time
t2 : Pump stop delay time
P (bar)
Wake up zone t2
t2
Set Pressure
p
Wake-up
pressure
.
t1 t1
t (sn)
Pump on demand
t (sn)
For example, if the set pressure is 8 bars and wakeup pressure is 0.5 bars, a standby pump
will activate after the current system pressure drops below 7.5 bars and the wakeup period
is complete. The factory settings for booster pump mode has been set to 0.5 bars.
However, the concept of wakeup pressure differs in circulation mode. Since a single pump
is always active in circulation systems, the wakeup pressure mentioned in the menu is a
variable that only applies in systems without drivers, or with driver errors. 1. This variable,
applied to the pumps activated after the first one, activates standby pumps after the
activation period is completed and the current differential pressure is less than the set
pressure for the fixture by the wakeup pressure. If the current differential pressure value is
as high as the wakeup pressure value than the set value, the active pumps are deactivated
after the deactivation period is complete. The factory settings for circulation mode has
been set to 0.2 bars.
8
p : Wake-up pressure
t1 : Pump start delay time
t2 : Pump stop delay time
P (bar)
p
Stable Working Zone
.
Set Pressure
p
.
t (sn)
t1 t2 t3 t4 t5 t6
Pump on demand
t (sn)
made from the "Sensor Settings" menu. 16 BAR SEN2 CALIBRATION SENSOR 1
9 www.etna.com.tr
Set Pressure: Set pressure is the pressure value at which the system is expected to work.
In booster pump mode, it is associated with the value read off of pressure transmitters.
In circulation mode, it is associated with the difference between the values read off of
transmitter1 and transmitter2.
Maximum Pressure: Maximum pressure is the pressure value corresponding to the 20 mA
maximum value on pressure transmitters. A standard selection between 10, 16 and 25 bars
can be made on the screen.
Sensor Selection: Sensor1 is selected as the factory setting in booster pump mode. If
the Sensor1 port belonging to the EPLC-6 is damaged, Sensor2 can be selected from the
menu after the pressure transmitter is connected to the Sensor2 port. If a transmitter
is connected to both ports and Automatic is selected, the system continues operating
according to the value read off of Sensor2 without stopping when Sensor1 is damaged.
Sensor1- Sensor2 is selected as the factory setting in circulation mode. Sensor1 or Sensor2
cannot be selected alone in this mode. However, if Sensor2 is not connected or cannot be
reached when Sensor1- Sensor2 is selected, the system will issue a warning and continue
operating according to the Sensor1 value. If Sensor1 is not connected or cannot be reached,
the system is blocked.
Sensor Calibration: Through the sensor calibration settings, any difference between the
pressure value from transmitters and the actual pressure value of the fixture can be fixed. If
the pressure value seen on the main screen is considered to be incorrect, it can be checked
as follows; when the pressure value of the fixture is 0 but the value shown in the
rightmost box is not 0, the symbol can be tapped to set the pressure value in the fixture
to 0. If the pressure of the fixture is not 0, the sensor maximum settings are selected correctly
but the pressure value collected from the manometer is incorrect, the value in
to the right of the symbol can be increased or decreased at the rate of 20% to match the
pressure value of the fixture and the pressure value shown on the main menu. This process
can be done separately for each of the two sensors.
driver frequency settings that are based 0-10V CALIBRATION WAKEUP TIME
Reaction Speed: Reaction speed is a parameter that adjusts the variation in driver speed,
or the reaction speed of the driver, depending on the difference between set pressure
value and the current pressure value in driver mode. Reaction speed can be adjusted
to 3 levels; In the 1st level, the reaction speed on the 1st level is slow and as the level is
increased, the rotation speed in the reference speed relayed by EPLC-6 panel to the driver
also increases. Therefore, the pump rotation speed that works with the driver also varies
in proportion to the reaction speed.
11 www.etna.com.tr
Sleeping Period: Sleeping period is the condition when, in booster pump mode, the
system's current pressure is higher than the set pressure and when pumps stand by ready
to work, without working. In systems with drivers, if the system pressure is above the
set value and if the driver frequency is lower than the deactivation frequency value and
remains that way throughout the sleeping period, the system enters sleep mode.
Wakeup period: In booster pump mode, when the driver is active but the system pumps
are inactive, the wakeup period is the time required to activate the pump operated by
the driver in situations where system pressure is less than the set value by the wakeup
pressure value.
12
Parameter
Parameter Name Set Value
No
0-40 [Hand On] Key on LCP 0=OFF
0-41 [Off / Reset] Key on LCP 2= only Reset active
1-00 Configuration Mode 0= Speed Open Loop (Factory Setting)
1-01 Motor Control Principle 0=U/F
1-20 Motor Power Must be set to value on motor label
1-22 Motor Voltage Must be set to value on motor label
1-23 Motor Frequency Must be set to value on motor label
1-24 Motor Current Must be set to value on motor label
1-25 Motor Nominal Speed Must be set to value on motor label
1-71 Start Delay 1.0 sec.
3-42 Ramp 1 Ramp Down Time Must be set according to the product and motor (ie. 3.00 sec)
0-50: First must be set to 1 and press OK, all the parameters inside the driver are transferred to Keypad
0-50: After must be set to 2 and press OK, all the parameters inside Keypad are transferred to the
driver
0-50: if set to 3 and press OK, all the parameters except Motor power inside Keypad are transferred
to the driver
AI1 Com
Relay Terminals;
12
18
19
20
27
29
33
42
50
53
55
60
Forward Start
01: COM
02: NO
03: NC
0-10 V. input
13 www.etna.com.tr
4.6 Manual Pump Control: MANUAL PUMP CONTROL
Manual pump control is used to PUMP1 DRIVER PUMP1 LINE AUTOMATIC
driver or the network will keep the PUMP5 DRIVER PUMP5 LINE
selected pump active for 3 seconds
PUMP6 DRIVER PUMP6 LINE BACK
through the relevant contactors in
single-driver multiple pump systems. In Figure 10: Manual Pump Control Menu
the meantime, the rotational direction
and the direction specified on the
pump should be checked to make sure
they are the same. While checking
for this issue, the automatic selection
in Figure 10 should be manually
changed and the select button on the
front cover of the panel should be
set to 0. The external start belonging
to the panel must be set to passive.
BACK
14
5.1 Language Settings: LANGUAGE SELECT
A selection between Turkish and
English can be made in the language TURKISH
settings menu.
ENGLISH
SAVE BACK
PARITY, STOP BIT, BAUD RATE and DEVICE TEK 2 bit 9600Kbps
ID adjustments can be made in Modbus CIFT 19200Kbps
communication settings. If more than
38400Kbps
one device will be communicated with
DEVICE ID
the same building automation system
from the DEVICE ID setting, the device- SAVE 001 BACK
specific ID number is determined from
each panel connected to the system. The Figure 14: Modbus Communication
Settings
settings defined for the other features can
be adjusted as can be seen in Figure 14.
(YOK=NONE, TEK=ODD, CIFT=EVEN)
Reading and writing can be done with Modbus RTU protocol. The register table is shared in
Table 3 below. Modbus 06 Write Single Register function allows writing to specified addresses.
The panel must be set to the stop position for the write over Modbus feature to work at the
addresses (W) specified in the table. In order to set the panel to stop position, the automatic-
manual selector button on the panel can be set to manual position or the panel must be
set to stop position by sending 0 value to address 50 with Write Single Register function via
Modbus. After the EPLC6 panel is set to stop position, the Write Single Register function can
be used at the write (W) addresses specified in the table. In order to reset the panel to the start
position via Modbus, a value of 1 must be sent from address 50.
SAVE BACK
15 www.etna.com.tr
MEMORY FUNCTION UNIT COEFFICIENT VALUE DESCRIPTION
ADDRESS (R=Read, W=Write) RANGE
40000 R - - 0-1 Service maintenance alarm (1- alarm, 0- no alarm)
40001 R - - 0-1 Panel start stop information (1- start mode, 0- stop mode)
40007 R - - 0-1 High pressure error (1- high pressure error, 0- no error)
40009 R Seconds - 0 - 65535 Low pressure countdown (Counts down the remaining time if there is a fault.)
40014 R - - 0 - 65535 Pump 1 (11- Pump running, 22- Pump stops, 33- Spare Pump, 44- Thermal fault)
40015 R - - 0 - 65535 Pump 2 (11- Pump running, 22- Pump stops, 33- Spare Pump, 44- Thermal fault)
40016 R - - 0 - 65535 Pump 3 (11- Pump running, 22- Pump stops, 33- Spare Pump, 44- Thermal fault)
40017 R - - 0 - 65535 Pump 4 (11- Pump running, 22- Pump stops, 33- Spare Pump, 44- Thermal fault)
40018 R - - 0 - 65535 Pump 5 (11- Pump running, 22- Pump stops, 33- Spare Pump, 44- Thermal fault)
40019 R - - 0 - 65535 Pump 6 (11- Pump running, 22- Pump stops, 33- Spare Pump, 44- Thermal fault)
40027 R - - 0-1 Low pressure error (1- low pressure error, 0- no error)
16
5.4 History Records: HISTORY RECORD
100 past event records with detailed
26 / 100 BACK
02/06/2017 09:09:05 PUMP 1 HIGH CURRENT FIXED
information on the date, hour and error 02/06/2017 09:09:04 PUMP 2 HIGH CURRENT FIXED
02/06/2017 09:09:04 PUMP 3 HIGH CURRENT FIXED
is shown in the Event Records section. 02/06/2017 09:09:04 PUMP 4 HIGH CURRENT FIXED
02/06/2017 09:08:58 EXTARNAL START OCCURED
The up and down arrows on the right 02/06/2017 09:08:57 PUMP 4 HIGH CURRENT
02/06/2017 09:08:57 PUMP 3 HIGH CURRENT
side of the screen shown in Figure 16 02/06/2017 09:08:57 PUMP 2 HIGH CURRENT
can be moved to display all the errors 02/06/2017
11/05/2017
09:08:57
15:08:19
PUMP 1 HIGH CURRENT
HIGH PRESSURE FIXED
in the event records. 11/05/2017 15:08:16 HIGH PRESSURE
11/05/2017 15:08:08 SENSOR 2 READY
11/05/2017 15:07:00 SENSOR 2 ERROR
17 www.etna.com.tr
7. Dimensions
H: Height
W: Width
L: Length
18
Motor Power 1 Pump Systems 2 Pump Systems 3 Pump Systems
HP KW L (mm) H (mm) W (mm) L (mm) H (mm) W (mm) L (mm) H (mm) W (mm)
0,5 0,37 500 700 260 500 700 260 600 800 260
0,75 0,55 500 700 260 500 700 260 600 800 260
1 0,75 500 700 260 500 700 260 600 800 260
1,5 1,1 500 700 260 500 700 260 600 800 260
2 1,5 500 700 260 500 700 260 600 800 260
3 2,2 500 700 260 500 700 260 600 800 260
4 3 500 700 260 600 800 260 600 800 260
5,5 4 500 700 260 600 800 260 600 800 260
7,5 5,5 500 700 260 600 800 260 600 800 260
10 7,5 500 700 260 600 800 260 600 800 260
15 11 500 700 350 700 900 350 800 1000 350
20 15 500 700 350 700 900 350 800 1000 350
25 18,5 600 800 350 800 1000 350 1000 1200 350
30 22 600 800 350 800 1000 350 1000 1200 350
19 www.etna.com.tr
8. Maintenance
General Information
20
FAULTS and
NO POSSIBLE CAUSE SOLUTION
ALARMS
Setup 1
Motor
Hz
Direction Selected
Status Quick Main Menu
Menu Menu
Menu Menu
Key
50.0
k
Bac
Navigasyon
On OK Keys
Indicator
Warn
Lights
Alarm
130BA605.12
Operation Keys and Leds
DC-link voltage
DC UNDER drops below the • Check driver ramp-up duration.
W8
VOLTAGE voltage warning • Check supply voltage.
limit
Inverter peak
• Check motor power.
W13 OVERCURRENT current
• Check parameter 1-24 current value.
limit is exceeded.
There is an issue
INTERNAL about the elctronic
W38 • Contact local Danfoss supplier.
FAULT companents in
the driver.
23 www.etna.com.tr
Rev. 09/2022