Protective Relay Unit 2
Protective Relay Unit 2
A relay is automatic device which senses an abnormal condition of electrical circuit and closes its contacts. These contacts in turns close and complete
the circuit breaker trip coil circuit hence make the circuit breaker tripped for disconnecting the faulty portion of the electrical circuit from rest of the
healthy circuit.
Now let’s have a discussion on some terms related to protective relay.
Pickup Level of Actuating Signal:
The value of actuating quantity (voltage or current) which is on threshold above which the relay initiates to be operated.
If the value of actuating quantity is increased, the electromagnetic effect of the relay coil is increased, and above a certain level of actuating quantity, the
moving mechanism of the relay just starts to move.
Reset Level:
The value of current or voltage below which a relay opens its contacts and comes in original position.
Reach of Relay:
A distance relay operates whenever the distance seen by the relay is less than the pre-specified impedance. The actuating impedance in the relay is the
function of distance in a distance protection relay. This impedance or corresponding distance is called the reach of relay.
Power system protection relays can be categorized into different types of relays.
Types of Relays
Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and operation mechanism.
Based on operation mechanism protection relay can be categorized as electromagnetic relay, static relay and mechanical relay. Actually, a relay is
nothing but a combination of one or more open or closed contacts. These all or some specific contacts the relay change their state when actuating
parameters are applied to the relay. That means open contacts become closed and closed contacts become open. In an electromagnetic relay, these closing
and opening of relay contacts are done by the electromagnetic action of a solenoid.
In the mechanical relay, these closing and opening of relay contacts are done by mechanical displacement of different gear level system.
In static relay it is mainly done by semiconductor switches like thyristor. In digital relay on and off state can be referred as 1 and 0 state.
Based on Characteristic the protection relay can be categorized as:
1. Differential.
2. Unbalance.
3. Neutral displacement.
4. Directional.
5. Restricted earth fault.
6. Over fluxing.
7. Distance schemes.
8. Bus bar protection.
9. Reverse power relays.
10. Loss of excitation.
11. Negative phase sequence relays etc.
Based on actuating parameter the protection relay can be categorized as-
1. Current relays.
2. Voltage relays.
3. Frequency relays.
4. Power relays etc.
Based on application the protection relay can be categorized as-
1. Primary relay.
2. Backup relay.
Primary relay or primary protection relay is the first line of power system protection whereas backup relay is operated only when primary relay fails to be
operated during a fault. Hence backup relay is slower in action than primary relay. Any relay may fail to be operated due to any of the following reasons,
1. The protective relay itself is defective.
2. DC Trip voltage supply to the relay is unavailable.
3. Trip lead from relay panel to the circuit breaker is disconnected.
4. The trip coil in the circuit breaker is disconnected or defective.
5. Current or voltage signals from Current Transformers (CTs) or Potential Transformers (PTs) respectively is unavailable.
As because backup relay operates only when primary relay fails, backup protection relay should not have anything common with primary protection
relay.
Some examples of Mechanical Relay are:
1. Thermal
OT trip (Oil Temperature Trip)
WT trip (Winding Temperature Trip)
Bearing temp trip etc.
2. Float type
Buchholz
OSR
PRV
Water level Controls etc.
3. Pressure switches.
4. Mechanical interlocks.
5. Pole discrepancy relay.
List Different Protective Relays are used for Different Power System Equipment Protection
Now let’s have a look on which different protective relays are used in different power system equipment protection schemes.
Differential Relay or
Overall differential Relay
3 nos Non-Directional O/L Overflux Relay
Relay Buchholz Relay
11/132 KV
1 1 no Non-Directional E/L Relay –– OLTC Buchholz Relay
Generator Transformer
and/or standby E/F + REF PRV Relay
Relay OT
Trip Relay
WT Trip Relay
Differential Relay or
Overall differential Relay
13.8/220 KV 3 nos Non-Directional O/L Overflux Relay
15.75/220 KV Relay Buchholz Relay
2 18/400 KV 1 no Non-Directional E/L Relay –– OLTC Buchholz Relay
21/400 KV and/or standby E/F + REF PRV Relay
Generator Transformer Relay OT
Trip Relay
WT Trip Relay
Differential Relay
3 nos Non-Directional O/L Overflux Relay
Relay Buchholz Relay
220 /6.6KV 3 nos Non-Directional O/L
3 1 no Non-Directional E/L Relay OLTC Buchholz Relay
Station Transformer Relay
and/or standby E/F + REF PRV Relay
Relay OT Trip Relay
WT Trip Relay
Differential Relay
Overflux Relay
Buchholz Relay
3 nos Non-Directional O/L 3 nos Non-Directional O/L
4 Gen-volt/6.6KV UAT OLTC Buchholz Relay
Relay Relay
PRV Relay
OT Trip Relay
WT Trip Relay
Buchholz Relay
OLTC Buchholz Relay
3 nos O/L Relay 2 nos O/L Relays
5 132/33/11KV upto 8 MVA PRV Relay
1 no E/L Relay 1 no E/L Relay
OT Trip Relay
WT Trip Relay
Differential Relay
Buchholz Relay
132/33/11KV above 8 MVA & 3 nos O/L Relay 3 nos O/L Relay OLTC Buchholz Relay
6
below 31.5 MVA 1 no Directional E/L Relay 1 no E/L Relay PRV Relay
OT Trip Relay
WT Trip Relay
Differential Relay
Overflux Relay
Buchholz Relay
132/33KV, 31.5 MVA & 3 nos O/L Relay 3 nos O/L Relay
7 OLTC Buchholz Relay
above 1 no Directional E/L Relay 1 no E/L Relay
PRV Relay
OT Trip Relay
WT Trip Relay
Differential Relay
Overflux Relay
220/33 KV, 31.5MVA & Buchholz Relay
3 nos O/L Relay 3 nos O/L Relay
8 50MVA 220/132KV, 100 OLTC Buchholz Relay
1 no Directional E/L Relay 1 no Directional E/L Relay
MVA PRV Relay
OT Trip Relay
WT Trip Relay
9 400/220KV 315MVA 3 nos Directional O/L Relay 3 nos Directional O/L Relay Differential Relay
(with dir.highset) (with dir.highset) Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
1 no Directional E/L relay.
PRV Relay
Restricted E/F relay 1 no Directional E/L relay.
OT Trip Relay
3 nos Directional O/L Relay for Restricted E/F relay
WT Trip Relay
action
Over Load (Alarm)
Relay
Points to be remembered in respect of protection of transformers
1. No Buchholz relay for transformers below 500 KVA capacity.
2. Transformers up to 1500 KVA shall have only Horn gap protection.
3. Transformers above 1500 KVA and upto 8000 KVA of 33/11KV ratio shall have one group control breaker on HV side and individual LV
breakers if there is more than one transformer.
4. Transformers above 8000 KVA shall have individual HV and LV circuit breakers.
5. The relays indicate above shall be provided on HV and LV.
6. LAs to be provided on HV and LV for transformers of all capacities and voltage class.
7. OLTC out of step protection is to be provided where master follower scheme is in operation.
8. Fans failure and pumps failure alarms to be connected.
9. Alarms for O.T., W.T., Buchholz (Main tank AND OLTC) should be connected.