3MXS40K - EN - 3P164392-4N - Installation Manuals - English
3MXS40K - EN - 3P164392-4N - Installation Manuals - English
INSTALLATION
MANUAL
R410A Split Series
Installation manual
English
R410A Split series
Installationsanleitung
Deutsch
Split-Baureihe R410A
Manuel d’installation
Français
Série split R410A
Montagehandleiding
Nederlands
R410A Split-systeem
Manual de instalación
Español
Serie Split R410A
Manuale d’installazione
Italiano
Serie Multiambienti R410A
3MXS40K2V1B
3SB64564-17J.fm Page 1 Thursday, October 27, 2011 3:50 PM
DAIKIN.TCF.015 N20/09-2011
Shinri Sada
Manager Quality Control Department
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
, ,
3SB64564-17J
3MXS40K2V1B, 2MXS52E2V1B, 2AMX52E2V1B, 3MXS52E2V1B,
3AMX52E2V1B, 3MKS50E2V1B, 4MKS58E2V1B, 2MXS52E3V1B,
2AMX52E3V1B, 3MXS52E3V1B, 3AMX52E3V1B, 3MKS50E3V1B,
4MKS58E3V1B
3SB65451-5A.fm Page 1 Thursday, October 27, 2011 4:52 PM
Shinri Sada
Manager Quality Control Department
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
, ,
3SB65451-5A
3SB65451-5A.fm Page 2 Thursday, October 27, 2011 4:52 PM
DAIKIN INDUSTRIES, LTD.
DAIKIN.TCF.015 K1/07-2007
Shinri Sada
Manager Quality Control Department
1st. of Dec. 2008
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
3SB64564-1
01_EN_3P164392-4N.fm Page 1 Wednesday, November 2, 2011 5:25 PM
Safety Precautions
• The precautions described herein are classified as WARNING and CAUTION. They both contain important
information regarding safety. Be sure to observe all precautions without fail.
• Meaning of WARNING and CAUTION notices
WARNING..............Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION...............Failure to observe these instructions properly may result in property damage or personal injury,
which may be serious depending on the circumstances.
• The safety marks shown in this manual have the following meanings:
Be sure to follow the instructions. Be sure to establish an earth connection. Never attempt.
• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate
the air conditioner and take care of it with the aid of the operation manual.
WARNING
• Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.
• Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
• Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
• Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
• Electrical work must be performed in accordance with relevant local and national regulations and with instructions
in this installation manual. Be sure to use a dedicated power supply circuit only.
Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire.
• Use a cable of suitable length.
Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals.
• If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
• After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air,
and use only the specified refrigerant (R410A).
The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage and even injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the refrigerant pipes are not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal
pressure in the refrigeration cycle, which may result in equipment damage and even injury.
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed,
causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
• Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.
• Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.
CAUTION
• Do not install the air conditioner at any place where there is a danger of flammable gas leakage.
In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.
• While following the instructions in this installation manual, install drain piping to ensure proper drainage and
insulate piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
• Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
• The temperature of refrigerant circuit will be high, please keep the inter-unit wire away from copper pipes that are not
thermally insulated.
1 ■English
01_EN_3P164392-4N.fm Page 2 Wednesday, November 2, 2011 5:25 PM
Accessories
Accessories supplied with the outdoor unit:
There is on the bottom packing case. There is on the bottom packing case.
(2MXS52*, 2AMX52*, 3MXS52*, 3AMX52*, 4MKS58*)
(D) Screw bag
(E) Refrigerant charge label (For fixing electrical wire anchor bands)
1
1
CAUTION
When operating the air conditioner in a low outdoor ambient temper-
ature, be sure to follow the instructions described below. Construct a large canopy.
1) To prevent exposure to wind, install the outdoor unit with its suc- Construct a pedestal.
tion side facing the wall.
2) Never install the outdoor unit at a site where the suction side may
be exposed directly to wind. Install the unit high enough off the
ground to prevent burying in snow.
3) To prevent exposure to wind, it is recommended to install a baffle
plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the snow will not affect the unit.
■English 2
01_EN_3P164392-4N.fm Page 3 Wednesday, November 2, 2011 5:25 PM
Indoor/Outdoor Unit
Installation Drawings
For installation of the indoor units, refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)
CAUTION
1) Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the
indoor unit in order to add another indoor unit later.
Make sure no dirt or moisture gets into either side of the embedded branch piping.
See “7 Refrigerant piping work” on page 9 for details.
2) Heat pump type: It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
Cooling only type: It is possible to connect the indoor unit for one room only.
25cm from wa
If there is the danger of the unit falling ll
or overturning, fix the unit with
foundation bolts, or with wire or other
means. Allow space for piping
and electrical servicing.
3 ■English
01_EN_3P164392-4N.fm Page 4 Wednesday, November 2, 2011 5:25 PM
Installation
• Install the unit horizontally.
• The unit may be installed directly on a concrete verandah or a solid place if drainage is good.
• If the vibration may possibly be transmitted to the building, use a vibration-proof rubber (field supply).
2MXS52∗ 3MXS52∗
Port 3MXS40∗ 3MKS50∗ 4MKS58∗
2AMX52∗ 3AMX52∗
# # #
A 20 , 25 , 35 , 50 15 , 20 , 25 , 35 15 , 20 , 25 , 35 , 42 20 , 25 , 35 , 42 20 , 25 , 35 , 42
# # #
B 20 , 25 , 35 , 50 15 , 20 , 25 , 35 15 , 20 , 25 , 35 , 42 20 , 25 , 35 , 42 20 , 25 , 35 , 42
# # # # # # # # #
C 15 , 20 , 25 , 35 15 , 20 , 25 , 35 , 42 , 50 20 , 25 , 35 , 42 20 , 25 , 35 , 42 , 50
# # # #
D 20 , 25 , 35 , 42 , 50
Precautions on Installation
• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts. (Prepare four sets of M8 or
M10 foundation bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface.
20
■English 4
01_EN_3P164392-4N.fm Page 5 Wednesday, November 2, 2011 5:25 PM
Side view
Top view
Unit: mm
Indoor Unit
Level
Outdoor Unit difference:
15m max.
Level Level
difference: difference: Level
difference: Outdoor Unit
15m max. 7.5m max.
(Heat pump 7.5m max.
unit only) (Heat pump Indoor Unit
unit only)
If the outdoor unit is positioned higher than the If the outdoor unit is positioned otherwise.
indoor units. (If lower than one or more indoor units)
5 ■English
01_EN_3P164392-4N.fm Page 6 Wednesday, November 2, 2011 5:25 PM
2. Drain work
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place Drain-water hole
additional foot bases of at least 30mm in height under the outdoor
unit’s feet. Bottom frame
3) In cold areas, do not use a drain hose with the outdoor unit. While pressing
Drain plug
(Otherwise, drain water may freeze, impairing heating performance.)
Hose (available commercially,
inner dia. 16mm)
3. Refrigerant piping
CAUTION
1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
[Apply oil]
Apply refrigeration oil to
Do not apply refrigeration
the inner surface of the
oil to the outer surface.
flare.
Flare nut
Flare nut tightening torque Valve cap tightening Service port cap
14.2-17.2N • m torque tightening torque
Flare nut for φ6.4
(144-175kgf • cm) Liquid pipe
32.7-39.9N • m 26.5-32.3N • m
Flare nut for φ9.5
(333-407kgf • cm) (270-330kgf • cm) 10.8-14.7N • m
49.5-60.3N • m Gas pipe (110-150kgf • cm)
Flare nut for φ12.7
(505-615kgf • cm) 48.1-59.7N • m
61.8-75.4N • m (490-610kgf • cm)
Flare nut for φ15.9
(630-769kgf • cm)
■English 6
01_EN_3P164392-4N.fm Page 7 Wednesday, November 2, 2011 5:25 PM
WARNING
1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum
pump or the unit.
• If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge
additional refrigerant.
• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.
1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.
2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)
3) Apply vacuum pumping. Check that the compound pressure gauge reads –0.1MPa (–76cmHg).
Evacuation for at least 1 hour is recommended.
4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.
(Leave as is for 4-5 minutes and make sure the coupling meter needle does not go back.
If it does go back, this may indicate the presence of moisture or leaking from connecting parts. After inspecting all the connec-
tion and loosening then retightening the nuts, repeat steps 2-4.)
5) Remove covers from liquid stop valve and gas stop valve.
6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.
After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.
See “3 Refrigerant piping” on page 6 for details.
7 ■English
01_EN_3P164392-4N.fm Page 8 Wednesday, November 2, 2011 5:25 PM
2) Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve
cover).
4
1 factory refrigerant charge of the product: see unit name plate
2 additional refrigerant amount charged in the field
1 (Refer to the above information for the quantity of refrigerant
replenishment.)
2 3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the Kyoto Protocol
3 5 outdoor unit
6 refrigerant cylinder and manifold for charging
6 5
NOTE:
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate
official national language on the unit. Therefor an additional multilingual fluorinated greenhouse gases label is supplied
with the unit.
Sticking instructions are illustrated on the backside of that label.
CAUTION
Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long
period of time.
■English 8
01_EN_3P164392-4N.fm Page 9 Wednesday, November 2, 2011 5:25 PM
Gas pipe insulation I.D.: 12-15mm, I.D.: 16-20mm / Thickness: 13mm min. Gas pipe Liquid pipe
insulation insulation
Liquid pipe insulation I.D.: 8-10mm / Thickness: 10mm min.
Finishing tape Drain hose
O.D.: 6.4mm, 9.5mm / 30mm or more
Minimum bend radius O.D.: 12.7mm / 40mm or more
O.D.: 15.9mm / 50mm or more
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Check
Flare’s inner The pipe end must
surface must be evenly flared in
be flaw-free. a perfect circle.
WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
9 ■English
01_EN_3P164392-4N.fm Page 10 Wednesday, November 2, 2011 5:25 PM
• When using the reducer packing shown above, be careful not to over- Flare nut tightening torque
tighten the nut, or the smaller pipe may be damaged. (about 2/3 - 1 32.7–39.9N·m
the normal torque) Flare nut for φ9.5
(333–407kgf·cm)
• Apply a coat of refrigeration oil to the threaded connection port of the
49.5–60.3N·m
outdoor unit where the flare nut comes in. Flare nut for φ12.7
(505–615kgf·cm)
• Use an appropriate wrench to avoid damaging the connection thread
by overtightening the flare nut. 61.8–75.4N·m
Flare nut for φ15.9
(630–769kgf·cm)
■English 10
01_EN_3P164392-4N.fm Page 11 Wednesday, November 2, 2011 5:25 PM
1. Forced operation
1) Turn the Operation Mode switch (SW2) to “COOL”. (Heat pump only)
2) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to stop
forced cooling.
Service PC-board
11 ■English
01_EN_3P164392-4N.fm Page 12 Wednesday, November 2, 2011 5:25 PM
Wiring
WARNING
1) Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or
fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
3) Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leakage breaker capable handling harmonics in order to
prevent malfunctioning of the earth leakage breaker itself.)
4) Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps.
5) Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
To room D
Indoor unit To room C
H05RN
Room A
To room B
If the length of a connection wire is
10m or more, use φ2.0mm wire.
CAUTION
Good Wrong
Good Wrong
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
■ Earth
This air conditioner must be earthed.
For earthing, follow the applicable local standard for electrical installations.
■English 12
01_EN_3P164392-4N.fm Page 13 Wednesday, November 2, 2011 5:25 PM
Setting procedure
Slide the switch to the ON side for the switch that corresponds to the piping connected to the indoor unit to be set. (In the fig-
ure below, it is room A.)
Once the settings are complete, reset the power.
Be sure to only set one room
13 ■English
01_EN_3P164392-4N.fm Page 14 Wednesday, November 2, 2011 5:25 PM
Setting procedure
Remove the SW5 jumper switch.
Once the settings are complete, reset the power.
Night Quiet Mode
NOTE: setting switch (SW5)
Install the removed jumper switch as described below. This switch will be needed
to later disable this setting.
5<C>3<H>1
5 ! 5 5#
5 PCB
5
5
Allow view
■English 14
01_EN_3P164392-4N.fm Page 15 Wednesday, November 2, 2011 5:25 PM
Wiring error
The service monitor LEDs indicate whether or not correction is check switch
possible, as shown in the table below. For details about how to read the (SW3)
LED display, refer to the service guide.
If self-correction is not possible, check the indoor unit wiring and piping
in the usual manner.
LED 1 2 3 4 Message
All Flashing Automatic correction impossible
Status Flashing One after another Automatic correction completed
(One or more of LEDs 1 to 4 are ON) Abnormal stop [NOTE. 4]
NOTE:
1) For two rooms, LED 3 and 4 are not displayed, and for three rooms, LED 4 is not displayed.
2) If the outside air temperature is 5°C or less , the wiring error check function will not operate.
3) After wiring error check operation is completed, LED indication will continue until ordinary operation starts.
This is normal.
4) Follow the product diagnosis procedures. (Check the nameplate on the underside of the stop valve.)
15 ■English
01_EN_3P164392-4N.fm Page 16 Wednesday, November 2, 2011 5:25 PM
3. Items to check
Check item Consequences of trouble Check
Are the indoor units installed securely? Falling, vibration, noise
Has an inspection been made to check for gas leakage? No cooling, no heating
Has complete thermal insulation been done (gas pipes, liquid
Water leakage
pipes, indoor portions of the drain hose extension)?
Is the drainage secure? Water leakage
Are the ground wire connections secure? Danger in the event of a ground fault
Are the electric wires connected correctly? No cooling, no heating
Is the wiring in accordance with the specifications? Operation failure, burning
Are the inlets/outlets of the indoor and outdoor units free of any
No cooling, no heating
obstructions? Are the stop valves open?
Do the marks match (room A, room B) on the wiring and piping
No cooling, no heating
for each indoor unit?
The priority room setting will not func-
Is the priority room setting set for 2 or more rooms?
tion.
■ ATTENTION
1) Have the customer actually operate the unit while looking at the manual included with the indoor unit. Instruct the customer
how to operate the unit correctly (particularly cleaning of the air filters, operation procedures, and temperature adjustment).
2) Even when the air conditioner is not operating, it consumes some electric power. If the customer is not going to use the unit
soon after it is installed, turn OFF the breaker to avoid wasting electricity.
3) If additional refrigerant has been charged because of long piping, list the amount added on the nameplate on the reverse side
of the stop valve cover.
■English 16
00_CV_3P164392-4N.fm Page 2 Wednesday, November 2, 2011 5:43 PM