Unit 3 2transformer 2 Emf Eq Num 2
Unit 3 2transformer 2 Emf Eq Num 2
on the secondary winding. The net cross sectional area of the core is 200 cm2. If the primary
winding is connected to a 240 V, 50 Hz supply, determine: emf induced in the secondary
side, the maximum value of the flux density in the core
Num: A single-phase transformer has 1000 turns on its primary side and 400 turns on
secondary side. An ac voltage of 1250 V,50 Hz is applied to its primary side, with the
secondary open circuited. Calculate: the secondary emf & maximum value of flux density,
given that the effective cross-sectional area of core is 60 cm2.
Num: A 25 KVA ideal transformer has 500turns on the primary winding and 40 turns on the
secondary winding. The primary is connected to 3kV, 50Hz supply. Calculate:
i. primary and secondary currents on full-load,
ii. secondary emf and
iii. maximum core flux.
Num: A 200/50 V, 50 Hz single phase transformer is connected to a 200V, 50Hz supply with
secondary open. Primary winding has 400 turns.
i) What is the maximum flux through the core?
ii) What is the peak value of flux if primary voltage is 200V, 25Hz?
Num: A 250 kVA, 11000/415 V, 50 Hz single-phase transformer has 80 turns on the
secondary. Calculate:
i. the rated primary and secondary currents
ii. the number of primary turns
iii. the maximum value of flux
iv. voltage induced per turn
Transformer Equivalent Circuit: