6-Lesson (Fundamentals of Automatic Control)
6-Lesson (Fundamentals of Automatic Control)
1. Fundamentals of control
– terminology
– control laws and algorithms
– control properties
2. Control of hydronic heating systems
3. Control of direct electric heating
4. Valve as a component of control system
5. Particularities of the control of heating/cooling coils
Terminology: disturbances
Changes in direction
Changes in and intensity of Changes in
outdoor solar radiation wind speed
temperature and
and direction
humidity
HVAC systems
Changes in
Changes in
temperature
internal heat
and pressure
loads/gains
of district
heating
network
Terminology: control system
Measured value
Measure-
ment
17ºC
Supply air
5ºC temperature Ta
12ºC [ºC]
Δt = ?
Time [s]
Constant mass flow, Beginning: End:
supply air e0 = 5ºC en = 0 ºC
temperature drops
stepwise by 5ºC
u0 = 40 % un = ?
Solution – I
• Discrete PI-algorithm:
t
un un 1 K p en en 1 en
ti
6 80 %
Perceptions:
• The solution describes ideal 5
70 %
(%)[%]
4
• The procedure results in stable
(C)
50 %
[°C]
signal
Erosuure
control, because proportional
Ohjaus
3 40 %
gain, integral time and sample Offset
Control
30 %
interval are optimal. (In 2
20 %
practice, to find optimal tuning
1
parameters is a challenging 10 %
task.) 0 0%
0 5 10 15 20 25 30 35 40 45 50 55 60
Time
Aika[s]
(s)
Offset
Erosuure Ohjaus
Control signal
Control properties – I
• Slowness: output responds with delay (aka dead time) to changes in set points, input
values and/or control signal
output
set point
63 % measured
value
time
Control properties – II
Example: room
temperature control with
• Hysteresis: behaviour of a system radiator valve
depending on its history (general open
definition).
→ one actuator position refers to
two separate values of the actuator
position
controlled variable
• Requirements for heat distribution
systems: closed
– hysteresis < 1°C
– proportional band: 2…4°C
hysteresis
proportional band (Xp)
Control properties – III
Process tv σ = t v / Xp
Boiler temperature 1…5 min 0.05…0.15 ~20 K
Mixing supply and return
5…20 s 0.2…0.5 20…70 K
water
Room temperature 3…5 min 0.1…0.3 6…10 K
Mixing cold water and hot
0.5…2 s 0.1…0.4 30…60 K
water
DHW heat exchanger
5…30 s 0.1…0.8 30…60 K
Pressure drop, Pa
(heating load is determined) on the Target
basis of calculational design
e.g. flow
temperature (extreme conditions and
duration). 3000 Pa rate
• The heating load varies due to Design
disturbances. flow
• Possible controls: rate
– flow control through valves (throttling)
– burner ON/OFF (boiler plants)
• 2 levels of delivered thermal
power/energy supply management:
1. building level (system level): supply
water temperature control (with
mixing valve) 0.8∙qV0 qV0
2. room level: (”fine tuning”): flow Volumetric flow rate, L/h
control (with radiator valves)
Supply water
temperature control
• Heating load (heat loss) mostly
depends on outdoor temperature
→ Building level control is based on Design conditions
mitoitustilanne
°C °C
changing the set point value of +70
temperature,
supply water temperature +60 Control
according to control curve curve
+50
Menovesi,
• The most common design
temperatures in Finland: 70/40°C +40
(supply/return). normaali-
Operating
+30 tilanne
point
Supply water
• The return water temperature
depends on the heat release of
+20
radiators/convectors/coils. +10
• In contrast with the graph, the
control curve is not always linear, +15 0 –15 –30
since internal and external heat Ulkolämpötila,
Outdoor °C °C
temperature,
gains affect the heating load.
Positioning control curve on the
basis of realized temperatures
temperature, °C
Supply water
Tint
C w (Tsup,0 Tret , 0 ) G (Tint, 0 Text , 0 ) Gr , 0 0 Text .
Cw wc pw qV , w
• Subject to:
Tsup
Conductance of radiator (Note: variable):
p
p p Gr Gr , 0
1 p 0
Gr Gr , 0 Gr Gr , 0 Gr , 0 p Tret
0 0 0
b
Tint Text 1 p Subscript 1 refers to target
Tsup Tret condition (e.g. desired room
Tint temperature at certain Text).
2
Positioning control curve on the
basis of theory – III
Text = const qV ,w const
Relationship between return water and room
temperatures : known target
Tint → Tint,1
1
Tret 21 Tint
b
Tsup = const
Tret → Tret,1
down to 19°C.
2. Known conditions:
– Given (or constant) values:
Tsup Given: linear control curve:
• Text = –10°C 70°C (Tsup,0) → 20°C (Tmin)
• Tint = 22°C
70°C
• G = 21.7 W/K (constant)
– Calculated values:
• Realized thermal input to the room: Tsup = ?
G (Tint Text )
22 10 K 696 W
W
21.7
K
• Supply water temperature (from linearity):
Tsup
Tmin Text C T Tmin C Tmin
Tmin = 20°C
T
min Text,0 C
sup,0
20 10 C 70 20 C 20C 52.6 C Text
–10°C –26°C
20 26 C
20°C
Solution – II
p
1 p 696 W p 0.3
35 K
1 p 10.3
Gr Gr , 0 0 26.5 K
0 G W
28.6
r ,0
K
• Return water temperature:
Tsup Tret
Tint Tret 2 Tint Tsup 2 26.5 22C 52.6C 44.3C
2
• Conductance of radiator:
696 W W
Gr Gr 26.3
26.5 K K
• Auxiliary variables and required change in return water temperature:
a
52.6 44.3C 0.26
Tsup Tret
Tint Text 22 10 C a 1 0.25 1
Tsup 1 Tint 1 22 19 C 5.3C
T T 1 p 22 10C 1 0.3 1.57
b int ext
2 b 2 1.57
26.5C
Solution – III
19 10 K 630 W
W
1 G (Tint,1 Text,1 ) 21.7
K
• Temperature difference between radiator and room:
1
1 1 0.3
1 p p
630 W 0.3
1 1 35 K
1 p 10.3
0 24.5 K
G 28.6 W
r ,0
K
Solution – IV
Note: In the present example, the supply water temperature is reduced by ΔTsup.
Summary table:
Energy utility
measured.
Customer
TIA
2. The set point value is read
from the control curve. TV2 Radiator
3. Supply water temperature is M network
measured. Engine
valve
4. The district heating water flow
rate is decreased/increased TI
Safety valve
Filling, non-return (check)
and drain valves
Supply water temperature
control – air heating
For air heating systems, the supply water
temperature is controlled on the basis of the
recirculated air temperature (which is close to
room temperature). The principle will be
developed further on the course ”EEN-E4003 Temperature control
Ventilation and air-conditioning systems”.
Recirculated
air Fresh air
Fan
Con-
version Heating coil
equip-
ment
Ductwork
Structural example of
mixing valve
Partitioning of
building into zones
Heat
source
Room temperature control
with radiator valves
• Thermostatic valves provide a room
level temperature control.
• The operation is based on a thermal
element that expands due to the rise
of temperature and closes the
spindle. The setpoint value can be
changed according to demand.
• If only room-level control was
implemented (no supply water
temperature control), high supply
water temperature should be (Stem)
maintained all the time
→ significant systemic heat losses
→ no temperature control in spaces
with no valves
→ valve positions would fluctuate a
lot (→ risk of failures)
→ remarkable pressure loss and
noise
Temperature control –
direct electric heating
pv
av
p
pv the pressure drop of valve (fully open)
p the total pressure drop of the water loop (including the valve)
Tw1
Fluid releasing heat qmwc pw
(water)
Tw1
Tw2 qmw = const
Tw2 M
Ta2
qma c pa qmw
Fluid receiving heat
Ta1 (air)
Particularities of the control of
heating/cooling coils – II
• Flow ratio (relative flow rate): • Temperature coefficient:
qmw qV Tw1 Tw2
M a
qmw,max qV ,max Tw1 Ta1
qmw,max = (water) flow rate, when the (temperatures as on the previous slide)
valve is fully open [kg/s] • Load factor:
1
• Control ratio:
d a 1 M
qmw,max 1
S M
qmw,min
Φ = heat exchange rate [W]
qmw,min = (water) flow rate, when the Φd = heat exchange rate in design conditions [W]
valve is fully closed [kg/s]
qmw qmw
The smaller the temperature M M mw
1. Temperature coefficient:
a
Tw1 Tw2
60 40 C
0.23
Equal
0.23
Solution – II