0% found this document useful (0 votes)
53 views

MAGNETOM Free - Max EN

Uploaded by

Ali Alkamaly
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views

MAGNETOM Free - Max EN

Uploaded by

Ali Alkamaly
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

MAGNETOM Free.

Max
Basic Planning Information

© Siemens Healthcare GmbH


MAGNETOM Free.Max | Basic Planning Information

Table of contents
Planning Example - Recommended Room Size 3
Planning Example - Minimum Room Size 5
Room Dimensioning 8
Statics and Transport 8
Cooling Water Installation 10
Air-conditioning 11
Electrical Installation 12
Noise Emission Values 12
Fringe Field 13
Siting Requirements 14
RF-Shielding 16
General Information 17

Legend
Motion area / Swivelling range / Minimal room size / Safety distance
Service area Wall mounted
Floor mounted Additional equipment
Ceiling mounted Demolition

Dimensioning
All installation measurements apply to finished wall/floor/ceiling and are to be checked prior to assembling the unit.
cm mm

Orientation point = reference point of the Siemens unit for planning and installation
Please note: The drawing parts in this document are not to scale!

© Siemens Healthcare GmbH 11.01.2022 Page 2 of 19


MAGNETOM Free.Max | Basic Planning Information

Planning Example- Recommended Room Size

385
345
min. 305

Possible additional
iron shielding or
227 restricted area
min. 187
175
min. 165

1.14 1.06

197
B

recommended minimum room length


GPA IDU / EPC

Equipment 1.01
~209

room
1.08

617
577
MREF

1.09 mT
1.11 40 mT
20
1.10 mT B
10 T
1.02 5 mmT
3
Changing Examination room
T
m
1
1.03 T
m
5 T
1.07 1.05 0, m
3
0,
120
1.07 T
1.12 m
1.04 15
0,
1.13 T
200

m
1
0,
Control room

T
m
05
0,
Preparation
Changing

© Siemens Healthcare GmbH 11.01.2022 Page 3 of 19


MAGNETOM Free.Max | Basic Planning Information

Section A-A
Y

Depending on the room height and on


what is located above the magnet,
additional iron shielding maybe required
or arrange for controlled access
T
m
05
0,

T
m
1

T
0,

m
15
0,

0, mT
T
m
3
The RF cabin height is dependent

0,
upon the RF cabin manufacturer

suspended ceiling
m
1

5 mT

suspended ceiling
10 mT
2 mT
3
finished room height)
240 (min. 220 techn.

m T
T
400 m

Preparation

Examination room Control room


Z

Possible additional
iron shielding or 197
restricted area

577
recommended minimum room length

617 200

Depending on what is located below the


magnet additional iron shielding maybe
required or arrange for controlled access

Section B-B
Y

0,0
Depending on the room height and on 5m
T
what is located above the magnet,
additional iron shielding maybe required
or arrange for controlled access
Possible additional
0,1
mT iron shielding or
restricted area
0,1
5m
T
0
0,5,3 m
m T
1m T
The RF cabin height is dependent

T
upon the RF cabin manufacturer

3m
suspended ceiling 15m T
200 mTT
40 mT
finished room height)
240 (min. 220 techn.

mT

Equipment room
X

Examination room

227
min. 187

345
min. 305
385

Depending on what is located below the


magnet additional iron shielding maybe
required or arrange for controlled access

© Siemens Healthcare GmbH 11.01.2022 Page 4 of 19


MAGNETOM Free.Max | Basic Planning Information

Planning Example - Minimum Room Size

Provide for
restricted area
345

305
minimum Fenced
187 area
*1
10

1.15
176.5
156.5

technical minimum finished room lenght


X

1.01
Possible additional
iron shielding or
restricted area
536

mT 576
40 mT
20
D 1.02 mT D
10 T
1.07 5 mmT
3

T
m
120

1.04 Examination room 1 Possible additional


T iron shielding or
m restricted area
5 T
1.03 1.06 0, m
3
0,
1.15
1.07 T
~55

m
GPA IDU / EPC

MREF
1.12 15
1.08 0, 1.14
min. 165

1.13 1.09 Equipment


170

1.10 T
room m Air conditioning cabinet
1
0, Position has to be
Control room 1.11 determined locally

T
m
05
~120 min. 220 0,

Notes Z
Safety distance is not minimum requirement, see text block "Safety
*1 distances". Clear visible markings may be required.

© Siemens Healthcare GmbH 11.01.2022 Page 5 of 19


MAGNETOM Free.Max | Basic Planning Information

Section C-C Y

Depending on the room height and on


what is located above the magnet,
additional iron shielding maybe required

T
or arrange for controlled access
m
05
0,

T
m
1

T
0,

m
15
0,

0, mT
T
m
3
The RF cabin height is dependent
0,

upon the RF cabin manufacturer


5

T
m
1

5 mT
suspended ceiling

10 mT
2 mT
Provide for

240 (min. 220 techn.

3
finished room height)

m T
restricted area

T
40 0 m
Examination room Equipment room
Z
GPA IDU / EPC
Fenced
area

170
156.5 min. 165

536
technical minimum finished room lenght

576
Depending on what is located below the
magnet additional iron shielding maybe
required or arrange for controlled access

Section D-D

0,0
Depending on the room height and on 5m
T
what is located above the magnet,
additional iron shielding maybe required
or arrange for controlled access
Possible additional
0,1
mT iron shielding or
restricted area
0,1
5m
T
0
0,5,3 m
m T
1m T
The RF cabin height is dependent
upon the RF cabin manufacturer

T
3m
suspended ceiling 15m T
2 0mT
400 mTT
finished room height)
240 (min. 220 techn.

mT

Examination room

Possible additional
iron shielding or
restricted area
187
305

345
Depending on what is located below the
magnet additional iron shielding maybe
required or arrange for controlled access

© Siemens Healthcare GmbH 11.01.2022 Page 6 of 19


MAGNETOM Free.Max | Basic Planning Information

MAGNETOM Free.Max - Equipment Legend


Weight (kg), Heat dissipation to the air (W)

Pos. Description kg W Remark


1.01 Magnet 2970 1000 #1/#2
1.02 Patient table with vertical and horizontal drive 240
1.03 RF-cabin
1.04 RF-door
1.05 RF-window
1.06 RF-System filter plate 63 250 #4
1.07 Magnet stop
1.08 Electronics cabinet GPA / IDU / EPC 970 #1/#3
1.09 MREF - passive cooling 130 #2/#3
1.10 Expansion vessel 9 50 litres
1.11 Power distributor 52 by customer
1.12 Control unit MR AWP with 24" Monitor 9,8 60
1.13 Console node 2
1.14 Air conditioning cabinet by customer
1.15 LCD monitor and camera for patient monitoring 5 75 required
#1 Heat dissipation depending on measuring
#2 Additional water cooling system necessary
#3 Typical heat dissipation of both components to the
environment in the Technical-Room ≤ 1 kW
#4 Installation of non-SIEMENS components prohibited

© Siemens Healthcare GmbH 11.01.2022 Page 7 of 19


MAGNETOM Free.Max | Basic Planning Information

Room Dimensioning

Technical minimum finished room length


Partial Drive, Fixed Patient Table: min. 577 cm

Technical minimum finished room height


Examination room min. 220 cm, Control room min. 210, Equipment room min. 220 cm.

Sky View Option (Floor Bound System Connection)


If you are using the Sky View Option be aware that you might need additional room height!
The minimum technical room height for the Free.Max inside the Examination Room is 220 cm!
The minimum required clear height for the floor bound cabling is 10 cm for the system
connections (without e.g. computer floor like construction; this has to be added if applicable).

Statics and Transport

Statics not to scale

Support feet and floor load

58.65 58.65

33.95
Transport weight of the magnet: ~ 3000 kg
Service end
4 3
Installation weight of the magnet: ~ 3000 kg
4 support feet each 14 cm x 24 cm (336 cm²) x
Pos. 1 = 780 kg
Pos. 2 = 580 kg 1 2
33.95

Pos. 3 = 690 kg
Pos. 4 = 945 kg z
Patient end

You have to consider the additional weights of the RF cabin and the possible iron shielding for the static
calculation.
It is only possible to position the magnet on Stop-Chocs if it is installed in a non-magnetic RF cabin and if there is
no iron shielding below the magnet.
Standard configuration is an installation on Sylomer/Sylodamp.

Building vibrations
External vibrations or shocks affecting the magnet may degrade image quality. In the three spatial orientations
the building vibration must not exeed the following specification:
Building vibration specification:
a max = -80 dB(g) in the frequency range from 0 to 100 Hz
The requirement for a max is depending on the frequency.

© Siemens Healthcare GmbH 11.01.2022 Page 8 of 19


MAGNETOM Free.Max | Basic Planning Information

Transport not to scale

Insertion Magnet Standard direction


Minimum transport opening in the ceiling: Transport opening in the wall:
L = 240 cm / W = 185 cm W = 240 cm / H = 210 cm
175

205
229
229

Insertion Magnet
90° rotated
Recommended transport opening in the wall:
W = 185 cm / H = 220 cm

212.4

175

Top cover front & rear


segment has to be removed
The minimum possible transport height
of the magnet is 198.3 cm!
Be aware, that this transport height requires a
198.3

dedicated transport set-up!


Also take in consideration to add height
for e.g. load distribution sheets!
The magnet width is 175 cm.
Dimensions without safety loading.

Transport foot sylomer


has to be removed

The maximum load and the width of doors and openings must be considered for the delivery of system parts
and the later delivery of cryogens.
Largest Parts Length Width Height Weight
Magnet 175 cm 229 cm 205 cm 2970 kg
Patient Table with horizontal drive 245 cm 73 cm 89 cm 180 kg
Patient Table with vertical and horizontal drive 245 cm 73 cm 48 cm - 89 cm 240 kg
Cabinet GPA/IDU/EPC 156 cm 65 cm 198 cm 980 kg
MREF 48.3 cm 53.5 cm 67.7 cm 135 kg
SOU 130.8 cm 155.9 cm 81.4 cm 258 kg
Gradient coil (information for service only) 143 cm Ø 105.2 cm 950 kg
Dimensions without safety loading.

© Siemens Healthcare GmbH 11.01.2022 Page 9 of 19


MAGNETOM Free.Max | Basic Planning Information

Cooling Water Installation

Cooling water (Passive cooling)


Central cooling water supply (e.g.in Hospitals) is alredy avaliable or local chiller is available.
System requires chilled water 24 h a day, 7 days a week - an emergency cooling system is required.

Water quality pH-value : 6 to 8


Primary water Hardness : < 250 ppm CaCO3 , < 14 °dH
Recommendation Chlorine portion : < 200 ppm
Sulfate portion : < 200 ppm
Filtration : 700 µm
Water / antifreeze : 40 % glycol with inhibitors (Glycol N)
Water quality Water to be used : De-ionized water
Secondary water Filtration : 700 µm
Water / antifreeze : n.a.
Additive for secondary
chilled water circuit : NaHCO 3

IDU Heat dissipation to water : 34 kW


Water flow rate : 70 l/min at 6 °C 90 l/min at 14 °C
Primary water temperature : 6 to 14 °C
Primary water pressure : < 6 bar
Pressure loss across IDU : < 1 bar

Cooling water (Active cooling)


No central hospital cooling water or a local chiller is available.
System requires chilled water 24 h a day, 7 days a week - a 2nd SOU is inclueded as Backup.

Water quality Water to be used : De-ionized water


Filtration : 700 µm
Antifreeze concentration : 40 % glycol with inhibitors (Glycol N)

MREF + SOU + SOU Backup Heat dissipation to water : 34 kW


Water flow rate : 59 l / min
Water supply temperature : 22 +-3 °C
Primary water pressure : n.a.

Components if no cooling water is available not to scale

MREF SOU SOU


(Helium compressor) Backup

© Siemens Healthcare GmbH 11.01.2022 Page 10 of 19


MAGNETOM Free.Max | Basic Planning Information

Air-conditioning

Environment
In the MR-area must be ensure following conditions (system during operation)
Examination room Room temperature : 18 to 22 °C
Relative humidity : 40 to 60 %
Absolute humidity : < 11 g / kg
Air intake system : ~ 30% - 50% fresh air
Off-take installation height : > 2000 mm
Air pressure: 700-1060 mbar
Technique room Room temperature : 15 to 30 °C
Relative humidity : 40 to 80 %
Absolute humidity : < 11 g / kg
Air pressure: 700-1060 mbar

Control / Evaluation room Room temperature : 15 to 30 °C


Relative humidity : 40 to 60 %
Absolute humidity : < 11 g / kg
Air pressure: 700-1060 mbar

The operating values should be set within these limits and ventilation must conform to local standards and
regulations.
Air filtering In the equipment area: filter classification EU 4 (DIN 24185 / part 2) to filter
out dust particles > 10 µm. For the MR examination room observe the local
regulations.
Typical heat dissipation of the Examination room ≤ 1 kW
MR-components to the Control room ≤ 0.15 kW
environment during an operation. Technique room ≤ 1.5 kW

An Air-conditioning system is required to meet the specified conditions. A separate air conditioning system
for the equipment room is not necessary if an air exchange, e.g. natural air convection, is guaranteed.

rH = 10 % 20 % 30 % 40 % 50 % 60 % 70 % 80 % 90 % 100 %
40

35

30

25
T / [°C]

20

15

10

0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52
x S / [g/kg]

© Siemens Healthcare GmbH 11.01.2022 Page 11 of 19


MAGNETOM Free.Max | Basic Planning Information

Electrical Installation

Power requirements
Mains: TN-S 3/N/PE AC 50/60 Hz ± 1 Hz Connection value
Passive cooling 42 kVA
Line voltage 400 V ± 10 %
Power consumption
Line to line unbalanced max. 2 % for time up to < 3 s 47 kVA

System passive cooling Line impedance ≤ 260 mΩ Connection value


On site circuit breaker 80 A Active cooling 64,2 kVA
(Including SOU & SOU Backup)
System active cooling Line impedance ≤ 180 mΩ Power consumption
On site circuit breaker system 80A for time up to < 3 s: 69,2 kVA
On site circuit breaker SOU 25A
On site circuit breaker SOU Backup 25A
Measurement sequences < 3 s.

The size of the terminals in the EPC are designed for 70 mm². Only copper cables are allowed.

Cable cross section is to be determined by national regulation and calculation.

Room lighting
Ambient lighting in rooms with diagnostics or with workstations must comply with the respective local and national
regulations.
General requirements like the needed intensity of illumination - adjustable, reproducible, flicker-free or a limitation of
dazzlings and reflections etc. have to be observed (EN 12464-1, DIN 5035-7).

Noise Emission Values

Noise emission values


If required, noise reduction should be realized based on the noise emission values as specified.
Average values Examination room Control room Technique room
across 8 hours ≤ 87.7 dB(A) ≤ 55 dB(A) ≤ 65 dB(A)
Noise emission @ 10 m distance: SOU1 60 dB(A), SOU1 + SOU2 63 dB(A)

© Siemens Healthcare GmbH 11.01.2022 Page 12 of 19


MAGNETOM Free.Max | Basic Planning Information

Fringe Field

Requirement for magn. field level warning signs in the control zone ≥ 0.5 mT
Limit for persons with cardiac pacemaker or insulin pump.
If the magnetic flux density in a given area exceeds 0.5 mT, it is necessary to display warning signs and restrict
access in accordance with local regulations.

Fringe field distribution MAGNETOM Free.Max


Fringe field Distance in m from the magnetic center in direction of
X axis Y axis Z axis
40 mT 1.3 1.3 1.6
20 mT 1.4 1.4 1.8
10 mT 1.6 1.6 2.1
5 mT 1.7 1.7 2.4
3 mT 1.9 1.9 2.6
1 mT 2.2 2.2 3.4
0.5 mT 2.5 2.5 4.0
0.3 mT 2.6 2.6 4.4
0.15 mT 3.2 3.2 5.3
0.1 mT 3.8 3.8 6.0
0.05 mT 5.0 5.0 7.3

Iron shielding -z-axis


In case of iron shielding behind the magnet, a minimum distance of 200 cm must be kept from iso center to the
shielding.

© Siemens Healthcare GmbH 11.01.2022 Page 13 of 19


MAGNETOM Free.Max | Basic Planning Information

Siting Requirements
Siting requirements for the magnet
The siting of the magnet must be such that during operation neither external influences affect the homogenity of the
magnetic field nor the safety of persons and/or the functioning of sensitive equipment can be affected by the stray
magnetic field.

Disturbing influences on the magnetic field


Static
E.g. steel beams, reinforcements, especially beneath the magnet. Partially correctable by shimming of the magnet
and/or compliance with minimum clearances/maximum weights.
Dynamic
E.g. moving ferromagnetic objects, electrical wiring, transformers. Avoidable when minimum clearances are
observed. Minimum distance depend on moving direction and magnet orientation. If distances are not kept please
contact SIEMENS Healthcare GmbH, Planning Department.
Minimum clearance
Object radial (X/Y) axial (Z) Max. weight
Water cooling system 4,0 m 4,0 m
Wheelchairs, beds 4,9 m 5,8 m
Giudelines
for minimum Carts up to approx. 200 kg 5,3 m 6,5 m
clearances Transformers < 1600 kVA 5,0 m 5,0 m
and
maximum AC cables < 1000A 2,5 m 2,5 m
weights Cars up to approx. 900 kg 5,5 m 7,5 m
Trucks up to approx. 4500 kg, Lifts 6,2 m 9,0 m
Cyclotron 20,0 m 20,0 m
Street cars, trains 40,0 m 40,0 m #1
Angiography systems with
magnetic navigation 30,0 m 30,0 m

Reinforcement distributed > 1.20 m below #2


≤ 100 kg/m²
in thickness of floor slab magnet center
> 1.20 m below #2
Steel beam ≤ 100 kg/m
magnet center

#1 The DC disturbances must not exceed a peak-peak value of 1250 nT (axial) and 2500 nT (radial). Occasionally
these values might be exceeded although the minimum distances to DC sources are kept as stated in the
planning guide. Please contact the planning department of the SIEMENS Healthcare GmbH if the distances to
trains, tramways or subways are smaller than 100 m.
#2 This minimum distance is required for shimming.
Distance for magnetic shielding has to be adjusted according to individual shielding requirements.

© Siemens Healthcare GmbH 11.01.2022 Page 14 of 19


MAGNETOM Free.Max | Basic Planning Information

Minimum distance between MAGNETOM Free.Max


to other MAGNETOM systems in [m] from magnet iso-center
Magnetic field intensity in [T] 0.55 T 3T 1.5 T 0.55 T 7 T

Vida, Lumina, Prisma, Free.Max


System type Free.Max all systems Terra
Skyra, Spectra Trio Tim Free.Star

distance X 4 m 5 m 4 m 4 m 9 m
from magnet
iso-center Z 8 m 9 m 6 m 6 m 14 m
No magnet is ramping during the other runs applications! Shim is only optimized with both magnets ramped up
during the shimming procedure.

Guidelines for max.Permissible Magnetic Flux Density (mT)


mT radial axial
(X/Y) (Z)
40 1.3 m 1.6 m Servoventilator
20 1.4 m 1.8 m Defibrillator
10 1.6 m 2.1 m RF-filter plate
5 1.7 m 2.4 m MR electronics cabinet (SIEMENS) GPA/EPC, SEP
3 1.9 m 2.6 m Small motors, watches, cameras
1 2.2 m 3.4 m Computers, oscilloscopes
0.5 2.5 m 4.0 m Pacemakers and insulin pumps, X-ray tubes, limit for public access
0.15 3.2 m 5.3 m Colour monitors (CRT)
0.05 5.0 m 7.3 m X-ray image intensifiers, gamma cameras, linear accelerators
The magnetic stray field is present in all three dimensions around the magnet and can be reduced by a
magnetic shielding.
Typical lines of constant magnetic flux density are shown in the drawing.
This represents the ideal field distribution in air, which can be distorted by the presence of steel in the building.
Magnetic field specification depends on manufacturer.

Disturbances caused by the stray magnetic field


All equipment and systems whose functions could be influenced by external magnetic field must be taken into
consideration. The maximum permissible magnetic flux density depends on the sensitivity of each system
component and must be clarified if necessary with equipment manufacturer.

Site inspection
In critical cases the site must be inspected on customer's expense by SIEMENS or one of SIEMENS appointed
representatives to ensure basic suitability on the site.
This inspection is exclusively concerned with the measurement of the magnetic and radio frequency interference
and building vibrations.
This inspection of other construction requirements, in particular the static and air conditioning and also the
performance and supervision of on-site installation preparations and the later compliance with the basic operating
requirements is not our responsibility.

© Siemens Healthcare GmbH 11.01.2022 Page 15 of 19


MAGNETOM Free.Max | Basic Planning Information

RF-Shielding

RF-shielding
An RF-shielding (faraday cage) is required for the MR-examination room. This shielding protects the environment
from RF interference and conversely protects the MR system from external interference.
Required attenuation: >90 dB over the frequency range 15 to 128 MHz (>100 dB at Co-Siting).
These values must be certified by measuring before the MR system is installed.
RF-shielding components (doors, windows, interfaces) and complete modular RF-cabins can be supplied on
request by SIEMENS.

RF-Door
All RF-doors leading into the examination room have to be equipped with a door switch for indicating the
closed / open position of the RF-door! It must be possible to lock the RF-doors from the outside. In
addition to that it must always be possible to open the RF-door without key or additional devices in any
cases from the inside!
The RF-door is an important component for a good image quality and also for safety aspects. The customer/user of
the MR system has to be informed to maintain the maintenance intervals given by the RF-room enclosure
manufacturer. This will guarantee a correct function of the RF-door.

Flooring
An antistatic floor covering is necessary. The floor in the vicinity of the magnet and patient table (2.6 x 4.8 m) must
be levelled to within max. ± 2 mm .
The loading capacity of the flooring must be designed with the weight of the respective system components in mind.

Area of base plate in the RF-cabin (fixed patient table) not to scale

Detail base plate fixed patient table

1342 1275

Floor RF-cabin
(e.g. particle board)
620

Area of the base plate


1000

must be countersunk
Base plate
Base plate
7

1342 1275

Note: The particle board and the base plate will be covered by the floor covering

Cryogens
Liquid helium (He) and also helium gas are required for operation of the superconducting magnet. The transport of
these liquid gases to the examination room requires the use of special vessels. The size and weight of the vessels
should be checked with the local cryogen supplier.
If the magnet can not be filled from the left service side, a long helium transfer line has to be ordered for the refilling
process!

© Siemens Healthcare GmbH 11.01.2022 Page 16 of 19


MAGNETOM Free.Max | Basic Planning Information

General Information

Display screen workstations


For setting up display screen workstations, take account of the guidelines in the Display Screen Workstation
directive as well as any national regulations (e.g. EN ISO 9241-5).

Smart Remote Services (SRS)


Smart Remote Services (SRS) is used for remote diagnostics as well as remote service to provide
highest system availability.
Requirements:
- Broadband connection (minimum 4 MBit/s down- and 768 kBit/s upstream, optimum 30 MBit/s down- and
2 MBit/s upstream) without time or volume limitations
- Router (for exclusive use with SRS)
Data protection and security is defined in the Smart Remote Services security concept.

Network Integration
The Siemens components are using TCP/IP Protocol, a 100/1000 Mbit/s switched Ethernet network and
static IP addresses.
The required network cabling (min. CAT 5 TP) has to be provided on site.
Media converters, which are needed for using fibre optic cabling, are not in the scope of Siemens delivery.
To prepare the implementation of the new system into the existing network environment, the availability
of the needed network data at least two weeks before starting the installation is mandatory.
This is the only way to ensure a seamless integration of the new system into the workflow of the department.

Safety distances
Distances from moving parts of the medical device to walls, furniture and other equipment have to be kept to avoid
injuries by crushing in compliance with local regulations, e.g. a minimum distance of 50 cm according to EN 349.
It is the customer's responsibility to ensure the above requirements are followed.
This is to avoid the risk of injury.
If safety distances are not maintained appropriate on-site safety measures have to be put in place.
Clear visible markings according to national guidelines, e.g. crushing warning signs, hazard warning
tape, hazard area cordon, safety mats, may be required.

© Siemens Healthcare GmbH 11.01.2022 Page 17 of 19


MAGNETOM Free.Max | Basic Planning Information

Site readiness guidelines:


The following general conditions are necessary to have the status of "Ready site":
1) Proper power available at SIEMENS Equipment Power Cabinet location and all power outlets functioning.
2) Air conditioning / humidification systems complete, tested and functioning properly according to SIEMENS
specifications.
3) RF enclosure, infastructure of the examination room complete.
4) Plumbing complete except for any final connections to SIEMENS equipment.
5) All cable trays, ducts, conduits correctly sized, located and installed according to the SIEMENS drawings.
6) Room for equipment installation and immediate vicinity is dust-free and is to remain so for the duration of the
installation.
7) Customer approval for SIEMENS Remote Service (SRS) connection and customers IT. Contact information and
IP adress established.

Notes on preparations for installation


Contracts for performing and supervising on-site installation preparations should be concluded with technically
competent companies by the customer. The customer is responsible for timely and proper completion and
supervision of all preparations for installation at the construction site in observance of all applicable legal regulations
(e.g. X-ray regulations, radiation protection regulations) and all applicable general recognized rules of technology
(e.g. VDE regulations, DIN standards).
Execution and supervision of installation preparations at the construction site and later observance of the standard
operating conditions are not included in our duties. The customer is responsible for checking the static calculations
and, where applicable, the air conditioning in the building to be equipped.

© Siemens Healthcare GmbH 11.01.2022 Page 18 of 19


On account of certain regional limitations of sales rights and
service availability, we cannot guarantee that all products
included in this brochure are available through the Siemens sales
organization worldwide. Availability and packaging may vary by
country and are subject to change without prior notice. Some/all
of the features and products described herein may not be available
in the United States.
The information in this document contains general technical
descriptions of specifications and options as well as standard
and optional features which do not always have to be present
in individual cases.
The statements by Siemens’ customers described herein are based
on results that were achieved in the customer’s unique setting.
Since there is no “typical” hospital and many variables exist (e.g,
hospital size, case mix, level of IT adoption), there can be
no guarantee that other customers will achieve the same results.
The customers cited are employed by an institution that might
provide Siemens product reference services, R&D collaboration
or other relationship for compensation pursuant to a written
agreement.
Siemens reserves the right to modify the design, packaging,
specifications, and options described herein without prior notice.
Please contact your local Siemens sales representative for the
most current information.
Note: Any technical data contained in this document may vary
within defined tolerances. Original images always lose a certain
amount of detail when reproduced.
Not all features shown in this brochure are necessarily standard
and available in all countries.

Published by
Siemens Healthcare GmbH
SHS ES FD

Siemens Healthineers Headquarters


Siemens Healthcare GmbH
Henkestr. 127
91052 Erlangen, Germany
Phone: 49 9131 84-0
siemens-healthineers.com

© Siemens Healthcare GmbH

You might also like