TGE ch3
TGE ch3
Chapter 3
Relay Description
TECHNICAL GUIDE TG 1.1671
MiCOM P441 & P442 Volume 1
DISTANCE PROTECTION RELAYS Chapter 3
Contents
Page 1 of 1
SECTION 1. RELAY SYSTEM OVERVIEW 1
1.1 Hardware overview 1
1.1.1 Main processor board 1
1.1.2 Co-processor board 1
1.1.3 Input module 1
1.1.4 Power supply module 1
1.1.5 Supplementary input and output boards 1
1.1.6 IRIG-B board (P442 only) 1
1.2 Software overview 2
1.2.1 Real-time operating system 3
1.2.2 System services software 3
1.2.3 Platform software 3
1.2.4 Protection & control software 3
1.2.5 Disturbance Recorder 3
SECTION 2. HARDWARE MODULES 4
2.1 Main processor and co-processor boards 4
2.2 Internal communication buses 4
2.3 Input module 5
2.3.1 Transformer board 5
2.3.2 Input board 5
2.4 Power supply module (including output relays) 7
2.4.1 Power supply board (including RS485 communication interface) 7
2.4.2 Output relay board 8
2.5 IRIG-B board (P442 only) 8
2.6 Mechanical layout 8
SECTION 3. RELAY SOFTWARE 9
3.1 Real-time operating system 9
3.2 System services software 9
3.3 Platform software 10
3.3.1 Record logging 10
3.3.2 Settings database 10
3.3.3 Database interface 10
3.4 Protection and control software 10
3.4.1 Overview - protection and control scheduling 11
3.4.2 Signal processing 11
3.4.3 Programmable scheme logic 12
3.4.4 Event and Fault Recording 12
3.4.5 Disturbance recorder 12
SECTION 4. DISTANCE ALGORITHMS 13
4.1 Distance and Resistance Measurement 13
4.2 "High-Speed" Algorithms 15
4.2.1 Fault Modelling 15
4.2.2 Detecting a Transition 17
4.2.3 Confirmation 18
4.2.4 Defining Direction 18
4.2.5 Phase Selection 19
4.2.6 Summary 19
4.3 "Conventional" Algorithms 20
4.3.1 Convergence Analysis 20
4.3.2 Start-Up 21
4.3.3 Phase Selection 21
4.3.4 Directional Decision 22
4.3.5 Directional Decision during SOTF/TOR 22
4.4 Faulted Zone Decision 23
4.5 Tripping Logic 24
TECHNICAL GUIDE TG 1.1671
MiCOM P441 & P442 Volume 1
DISTANCE PROTECTION RELAYS Chapter 3
Contents
Page 2 of 2
4.6 Fault Locator 24
4.6.1 Selecting the fault location data 25
4.6.2 Processing algorithms 25
4.7 Power swing detection 25
4.7.1 Power swing detection 26
4.7.2 Line in one pole open condition (during single-pole trip) 26
4.7.3 Conditions for isolating lines 27
4.7.4 Tripping logic 27
4.7.5 Fault Detection after Single-phase Tripping (one-pole-open condition) 27
4.8 Double Circuit Lines 28
4.9 DEF Protection Against High Resistance Ground Faults 29
4.9.1 High Resistance Ground Fault Detection 29
4.9.2 Directional determination 29
4.9.3 Phase selection 30
4.9.4 Tripping Logic 30
4.9.5 SBEF – Stand-By earth fault (not communication-aided) 31
SECTION 5. SELF TESTING & DIAGNOSTICS 33
5.1 Start-up self-testing 33
5.1.1 System boot 33
5.1.2 Initialisation software 33
5.1.3 Platform software initialisation & monitoring 34
5.2 Continuous self-testing 34
CPU
Serial data bus
(sample data)
Coprocessor board
Power supply, rear comms,
data, output relay status Parallel data bus Digital input values
Output relays
(x14 or x21)
Up to 5
CT
CT
VT
VT
4
Transformer board
Input board
Up to 5
single
single
single
single
Diffn
Diffn
Diffn
Diffn
to
to
to
to
Anti-alias filters
Up to 5
filter
pass
pass
pass
pass
Low
filter
Low
filter
Low
filter
Low
4
16:1
Multiplexer
isolator
Optical
Noise
filter
Buffer
16-bit
ADC
8 digital inputs
Sample
control
8
8
Calibration
interface
E2 PROM
Serial
Optical
isolator
Noise
filter
board
Trigger from processor
Serial sample
data bus
Parallel bus
Buffer
Parallel bus
Protection
Programmable & task
fixed scheme logic
Platform Software
Fourier signal Protection
Event, fault, Remote
processing algorithms
disturbance, communications
maintenance record interface -
logging IEC60870-5-103
Supervisor task
Protection & control settings
Remote
Settings communications
database interface - Modbus
Sampling function -
copies samples into
2 cycle buffer Control of output contacts and Front panel Local & Remote
programmable LEDs interface - LCD & communications
keypad interface - Courier
Relay hardware
The following describes how to solve the above equation (determination of D fault
distance and R fault resistance). The line model used will be the 3×3 matrix of the
line impedances (resistive and inductive) of the three phases, and mutual values
between phases.
Raa + Daa Rac + Dac Rac + Dac
Rab + Dab Rbb + Dbb Rbc + Dbc
Rac + Dac Rcc + Dbc Rcc + Dcc
Where: Raa=Rbb=Rcc and Rab=Rbc=Rac
TECHNICAL GUIDE TG 1.1671
MiCOM P441 & P442 Volume 1
DISTANCE PROTECTION RELAYS Chapter 3
Page 14 of 34
The line model is obtained from the positive and zero-sequence impedance. The use
of two different zero-sequence impedance settings is permitted on the relay, as
follows:
· Z01: zero-sequence impedance used to calculate faults in zone 1.
· Z02: zero-sequence impedance used to calculate faults in zones 2, etc.
The solutions "D" and "R" are obtained by solving the system of equations (one
equation per step of the calculation) using the Gauss Seidel method.
Σ(VL x IF) – DN-1 x Σ(ZL x I x IF) Σ(VL x ZL x I) – RF N-1 x Σ(IF x ZL x I)
RN = DN =
Σ (IF)² Σ (ZL x I)²
ZL
Zs i2 ZL
Z Fault
Zs i1 ZL
R / Phase
V3N V2N V1N RFault
kS ZS V1 V2 V3 kL ZL
Location
of DR
Figure 6: Phase-to-earth loop impedance
Zs ZL X/ Phase R Fault/2
i3
ZL
Zs i2 ZL
Z Fault
Zs ZL RFault
i1
R / Phase
V3N V2N V1N V3
Location
of DR
VR IR
R F
ZS ZL ZL ZR
Relay
VF (prefault voltage)
ZS ZL ZL ZR
Relay
RF
VR ' = Voltage at Relay Location
VR IR
R F
ZS ZL ZL ZR
Relay
-V F
Fault Inception
2T
G
G = Current or Voltage
T
G(t)
G(t-2T) G(t-T)
Gp(t)
Time
t-2T t-T t
4.2.3 Confirmation
In order to eliminate the transitions generated by possible operations or by high
frequencies, the transition detected over a succession of three sampled values is
confirmed by checking for at least one loop for which the two following conditions are
met:
∆ V > threshold V, where threshold V = 0.1 Un /√3 = 0.1 Vn
and
∆ I > threshold l, where threshold I= 0.2 In.
The start-up of the high-speed algorithms will be confirmed if ∆U and ∆I are detected
on three consecutive sample.
4.2.4 Defining Direction
The "Delta" detection of the fault direction is determined from the sign of the three-
phase energy for the transition values characterising the fault.
VR
IR
F
ZS ZL ZL ZR
Relay
-V F
Forward Fault
VR
IR
R
ZS ZL ZL ZR
Relay
-V F
Reverse Fault
where no is the instant at which the fault is detected, ni is the instant of the calculation
and S is the calculated transition energy.
· If the fault is in the forward direction, then S<0.
· If the fault is in the reverse direction, then S>0.
The directional criterion is valid if
S >5 x (0.1 Vn x 0.2 In cos 85°)
This sum is calculated on five successive samples.
TECHNICAL GUIDE TG 1.1671
MiCOM P441 & P442 Volume 1
DISTANCE PROTECTION RELAYS Chapter 3
Page 19 of 34
4.2.6 Summary
A transition is detected if ∆I > 20% In or ∆V >10% Vn
Then three tasks are starting in parallel:
• Fault confirmation : ∆I and ∆V (3 consecutive samples)
• Faulty phase selection (4 consecutive samples)
• Fault directional decision (5 consecutive samples)
Confirmation
Phase selection
-D = X4
lim
If a stored voltage does not exist (SOTF) when one or more loops are convergent
within the start-up characteristic, the directional is forced forward and the trip is
instantaneous. If the settable switch on to fault current threshold I>3 is exceeded on
reclosure, the relay instantaneously trips three-phase.
Two-phase or three-phase fault
The reference voltage is stored in memory when the fault appears. When the fault is
cleared, the stored voltage value remains valid for 10 seconds. If reclosure occurs
during these 10 seconds, the direction is calculated using the stored voltage value.
If a stored voltage does not exist when one or more loops are convergent within the
start-up characteristic, the forward direction is forced and the trip is instantaneous
when protection starts. If the switch on to fault current threshold I>3 is exceeded on
reclosure, the relay trips instantaneously three-phase.
The distance element trips immediately as soon as one or more loops converge within
the start-up characteristic during SOTF.
Z1
2 1 0
3
4..
R
Zone Time
Z1 T1
Z1X T1
Z2 T2
Zp Tp
Z3 T3
Z4 T4
There are five time delays associated with the six zones present. Zone 1 and
extended zone 1 have the same time delay.
Powerswing Z3
Boundary Stable R
Characteristic Unstable
Swing Swing
Z4
A B C D E F
The P440 provides protection against the effects of this phenomenon by employing
transient blocking. An adjustable timer is available that will block direct and
permissive transfer trip signals from being used in the P440 logic, and will also block
the P440 from sending direct or permissive transfer trip signals. This timer is
designated as “Reverse Guard Timer”.
This provides protection against fault current reversal and will still allow fast tripping
in the event of faults occurring in zone 1, if zone 1 is independent (not used as
overreach zone).
Vr>threshold
Ir fwd threshold
Forward decision & DEF Carrier Send
(DIST if shared
Reverse decision
DEF Timer Block channel)
Ir rev threshold
&
1 pole dead
0
T & Three Phase Trip
Z< starting
& t-AR cycle
Vr>threshold
Ir fwd threshold 0
Forward decision &
Reverse decision t
DEF Timer Block Transmission
time
Ir rev threshold
& Single Phase Trip
&
1 pole dead
0
T & Three Phase Trip
Z< starting
& t-AR cycle
CTS Block
&
IN>x start
& SBEF
Slow VTS
Block
& Directional
Check
Vx > Vs & IDMT/DT Trip
Ix > Is
High-Speed Sbc < Sca < Sab Sca<Sbc < Sab Sab<Sbc<Sca Sbc<Sac<Sab Sac<Sab<Sbc Sab<Sbc<Sca
MiCOM P441 & P442
algorithm phase T x Rab x Rbc x Rca T x Rbc x Rab x Rca T x Rca x Rab x Rbc x Zbc x Zca
selection
High-speed algorithm ni
algorithm directional
determination
I’a + K0I’r I’b + k0’r I’c + k0I’r I’a - I’b I’b - I’c I’c - I’a I’a - I’b
Supervision algorithm U = Va U = Vb U = Vc U = Va - Vb U = Vb - Vc U = Vc - Va U = Va - Vb
V = M2Ia V= M2Ib V = M2Ic V = M x (Ia - Ib) V = M x (Ib - Ic) V = M x (Ic - Ia) V = M x (Ia - Ib)
W = Ia W = Ib W = Ic W = Ia - Ib W = Ib - Ic W = Ic - Ia W = Ia - Ib
Measurement U = Va U = Vb U = Vb U = Va - Vb U = Vb - Vc U = Vc - Va U = Va - Vb
algorithm for zone 1 V = M1Ia V = M1Ib V = M1Ic V = M x (Ia - Ib) V = M x (Ib - Ic) V = M x (Ic - Ia) V = M x (Ia - Ib)
W = Ir W = Ir W = Ir W= Ia - Ib W = Ib - Ic W = Ic - Ia W = Ia - Ib
Measurement U = Va U = Vb U = Vb U = Va - Vb U = Vb - Vc U = Vc - Va U = Va - Vb
algorithm for zones V = M2Ia V = M2Ib V = M2Ic V = M x (Ia - Ib) V = M x (Ib - Ic) V = M x (Ic - Ia) V = M x (Ia - Ib)
2, p, 3 and 4
W = Ir W = Ir W = Ir W = Ia - Ib W = Ia - Ib W = Ic - Ia W = Ia - Ib
M: impedance for multi-phase faults
Volume 1
TG 1.1671
Page 32 of 34
Chapter 3
TECHNICAL GUIDE TG 1.1671
MiCOM P441 & P442 Volume 1
DISTANCE PROTECTION RELAYS Chapter 3
Page 33 of 34