Comments Compliance Sheet For The Calculation Report Ref.6
Comments Compliance Sheet For The Calculation Report Ref.6
Structural Calculation Report - Type 01,02,03 & 04 and Type A, B, C, D Supporting Brackets
1 Clarify the weight of the material considered includes material weight & water weights
Spacing of the supports based on weight to ensure to avoid sagging/ stress concentration.
9
Supports may be designed to accommodate Allow for thermal expansion and contractions
of the pipes to avoid stress.
10
Maximum stress and allowable stress on the support members to be provided in the
schedule
11
Reaction summary (analysis) at the supports, node displacement, utilization ratio etc to be
12
provided.
For example, Type -01, Base plate thickness 16 mm consider in calculation whereas schedule
13 table/ ref: drawing indicatel0mm, to be verified and rectified in the submittals.
Noted
N/A
Noted
Noted
Noted
???????