Forced Draught Gas Burners: Progressive Two-Stage or Modulating Operation
Forced Draught Gas Burners: Progressive Two-Stage or Modulating Operation
Legnago, 30.05.2012
Burners Division Department
RIELLO S.p.A. Eng. I. Zinna
Manufacturer's Declaration
RIELLO S.p.A. declares that the following products comply with the NOx emis-
sion limits specified by German standard “1. BImSchV release 26.01.2010”.
Product Type Model Power
Forced draught gas burner 866 T1 RS 250/E MZ 600-2650 kW
Legnago, 30.05.2012
Burners Division Department
RIELLO S.p.A. Eng. I. Zinna
6367
1 GB
Contents
Section Page
1 Information and general warnings 3
1.1 Information about the instruction manual 3
1.2 Guarantee and responsibility 3
2 Safety and prevention 4
2.1 Introduction 4
2.2 Personnel training 4
3 Technical description of the burner 5
3.1 Burner designation 5
3.2 Models available 5
3.3 Burner categories- Countries of destination 5
3.4 Technical data 6
3.5 Electrical data 6
3.6 Burner weight 7
3.7 Overall dimensions 7
3.8 Firing rates 8
3.9 Burner components 9
3.10 Burner equipment 9
3.11 Control box for the air/fuel ratio 10
3.12 Servomotors 11
4 Installation 12
4.1 Notes on safety for the installation 12
4.2 Handling 12
4.3 Preliminary checks 12
4.4 Working position 12
4.5 Securing the burner to the boiler 13
4.6 Combustion head adjustment 15
4.7 Assembly of the gas train 17
4.8 Electrical wiring 18
4.9 Calibration of the thermal relay 19
5 Start-up, calibration and operation of the
20
burner
5.1 Notes on safety for the first start-up 20
5.2 Operations before start-up 20
5.3 Burner start-up 21
5.4 Final calibration of the pressure switches 21
5.5 Operator Panel with LCD display 23
5.6 Visualisation and programming modes 24
5.7 Operation sequence of the burner 29
5.8 Start-up procedure 30
5.9 CALC function 32
5.10 Burner adjustment 32
5.11 Steady state operation 33
5.12 Ignition failure 33
5.13 Burner flame goes out during operation 33
5.14 Stopping of the burner 33
5.15 Measuring the ionisation current 33
5.16 Checking the air and gas pressure on the com- 33
bustion head
5.17 Final checks (with the burner working): 33
5.18 List of parameters 34
6 Faults - Possible causes - Solutions 38
6.1 List of error codes 38
7 Maintenance 42
7.1 Notes on safety for the maintenance 42
7.2 Maintenance programme 42
7.3 Opening the burner 43
7.4 Closing the burner 43
A Appendix - Electrical panel layout 44
6367
2 GB
1 Information and general warnings
guarantees its new products from the installation date, in use of the burner with safety devices that are faulty,
accordance with the regulations in force and/or the sales con- incorrectly applied and/or not working;
tract. At the moment of the first start-up, check that the burner is installation of untested supplementary components on the
integral and complete. burner;
powering of the burner with unsuitable fuels;
Failure to observe the information given in this faults in the fuel power supply system;
manual, operating negligence, incorrect installation use of the burner even following an error and/or an
and the carrying out of non authorised modifications irregularity;
WARNING
will result in the annulment by of the repairs and/or overhauls incorrectly carried out;
guarantee that it supplies with the burner. modification of the combustion chamber with inserts that
In particular, the rights to the guarantee and the responsibility prevent the regular development of the structurally
will no longer be valid, in the event of damage to things or injury established flame;
to people, if such damage/injury was due to any of the following insufficient and inappropriate surveillance and care of those
causes: burner components most subject to wear and tear;
incorrect installation, start-up, use and maintenance of the use of non-original components, including spare
burner; parts, kits, accessories and optionals;
improper, incorrect or unreasonable use of the burner; force majeure.
intervention of unqualified personnel;
carrying out of non authorised modifications on the furthermore declines any and every responsibility
equipment; for the failure to observe the contents of this manual.
6367
3 GB
2 Safety and prevention
2.1 Introduction
The user is the person, body or company that has acquired the Personnel must always use the personal protective equip-
machine and intends to use it for the specific purpose. He is re- ment envisaged by legislation and follow the indications given
sponsible for the machine and for the training of the people work- in this manual.
ing around it. Personnel must follow all the danger and caution indications
shown on the machine.
The user:
Personnel must not carry out, on their own initiative, opera-
undertakes to entrust the machine exclusively to suitably
tions or interventions that are not within their province.
trained and qualified personnel; Personnel are obliged to inform their superiors of every prob-
must take all the measures necessary to prevent unauthor- lem or dangerous situation that may arise.
ised people gaining access to the machine; The assembly of parts of other makes, or any modifications,
undertakes to inform his personnel in a suitable way about the can alter the characteristics of the machine and hence com-
application and observance of the safety instructions. With promise operating safety. The Manufacturer therefore de-
that aim, he undertakes to ensure that everyone knows the clines any and every responsibility for any damage that may
use and safety instructions for his own duties; be caused by the use of non-original parts.
must inform the Manufacturer if faults or malfunctioning of the
accident prevention systems are noticed, along with any pre-
sumed danger situation.
6367
4 GB
3 Technical description of the burner
Range : R
Size
Voltage of auxiliaries :
230/50/60 230V/50-60Hz
110/50/60 110V/50-60Hz
6367
5 GB
3 Technical description of the burner
(1) Reference conditions: Room temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m above sea level.
(2) Gas pressure on the pipe coupling test point 21) (Fig. 5) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output.
Motor IE1
Model RS 70/E RS 100/E RS 130/E RS 190/E RS 250/E MZ
Electrical supply 3 ~ 230V / 400V 1N ~ 230V +/-10% 50 Hz (See Ch. 3.2)
Fan motor (rating) rpm 2800 2830 2860 2860 2900
V 230 / 400 230 / 400 230 / 400 230 / 400 230 / 400
kW 1,1 1,5 2,2 4,5 5,5
Operating current A 4,7 - 2,7 6,4 - 3,7 8,5 - 4,9 16 - 9,1 19 - 11
Acceleration current A 33 - 19 48 - 28 68 - 39 126 - 72 144 - 83
V1 - V2 230 V - 1 x 8 kV
Ignition transformer
I1 - I2 1 A - 20 mA
Absorbed electrical power kW max 1,4 1,8 2,6 5,5 6,5
Protection level IP 44
Motor IE2
Model RS 70/E RS 100/E RS 130/E RS 190/E RS 250/E MZ
Electrical supply 3 ~ 230V / 400V 1N ~ 230V +/-10% 50 Hz (See Ch. 3.2)
Fan motor (rating) rpm 2860 2860 2860 2900 2910
V 230 / 400 230 / 400 230 / 400 230 / 400 230 / 400
kW 1,1 1,5 2,2 4,5 5,5
Operating current A 4,1 - 2,4 5,5 - 3,4 7,9 - 4,6 15 - 8,7 18 - 11
Acceleration current A 33 - 19 51 - 30 62 - 36 141 - 81 186 - 107
V1 - V2 230 V - 1 x 8 kV
Ignition transformer
I1 - I2 1 A - 20 mA
Absorbed electrical power kW max 1,4 1,8 2,6 5,5 6,5
Protection level IP 44
6367
6 GB
3.6 Burner weight
The weight of the burner complete with its packaging is shown in table.
Model kg
RS 70/E 77 - 79
RS 100/E 80 - 82
RS 130/E 83 - 85
RS 190/E 89 - 91
RS 250/E MZ 124 - 126
D9078
Fig. 1
D731
Fig. 2
mm A B C D E F (1) G H I (1) L M N O
RS 70/E 511 296 215 555 840 250-385 179 430 1161-1296 214 134 221 2”
RS 100/E 527 312 215 555 840 250-385 179 430 1161-1296 214 134 221 2”
RS 130/E 553 338 215 555 840 280-415 189 430 1161-1296 214 134 221 2”
RS 190/E 675 370 305 555 872 372-522 222 436 1328-1478 230 150 223 2”
RS 250/E MZ 732 427 305 555 872 370-520 222 436 1322-1467 230 150 264 2”
6367
7 GB
3 Technical description of the burner
Pressure in combustion
Pressure in combustion
chamber - mbar
chamber - mbar
A A
RS 100/E RS 250/E MZ
Pressure in combustion
Pressure in combustion
chamber - mbar
chamber - mbar
A
A
RS 130/E Fig. 3
Pressure in combustion
gram.
The minimum output must not be lower than the minimum
limit of the diagram.
A
Warning
The firing rate was obtained considering an ambient temper-
ature of 20°C and an atmospheric pressure of 1013 mbar
(approx. 0 m above sea level), with the combustion head ad-
justed as shown in Ch. 4.6.
Example
Output 756 kW (650 Mcal/h):
diameter 60 cm,
length 2 m.
The coupling is ensured when the boiler is
EC type-approved; for boilers or ovens with
combustion chambers of very different
dimensions compared to those shown in
the diagram of Fig. 4, preliminary checks
D715 are recommended.
Fig. 4
6367
8 GB
3 Technical description of the burner
RS 190/E
RS 70-100/E
RS 130/E
RS 250/E MZ
D8038
Fig. 5
6367
9 GB
3 Technical description of the burner
D8266 Fig. 6
6367
10 GB
3 Technical description of the burner
3.12 Servomotors
Introduction
The servomotors that equip the burners of the RS range work directly on
the air damper and the gas butterfly valve, without mechanical lever-
ages but via the interposition of an elastic coupling.
They are commanded by the control box, which constantly checks their
position by means of a return signal from the optic sensor inside the ser-
vomotor.
For this reason it is absolutely forbidden to remove
the cover of the servomotors.
WARNING
The position (in degrees) of the servomotors can be seen on the display
of the Operator Panel. See Ch. 5.18, Parameter 922, index “0” for fuel
servomotor, index “1” for air servomotor.
Fig. 7
Technical Data
Fuel Air
servomotor servomotor
Model SQM33.4.. SQM33.5..
Type of motor Stepping motor
Electrical supply AC/DC 24V
IP IP54
Firing rate 0 - 90°
Opening time 0-90° min: 5 s, max.: 120 s depending on the type of control box
Torque 1.2 Nm 3 Nm
Input power 7.5 W 10 W
Rotation Clockwise/anticlockwise (can be selected from the control box)
6367
11 GB
4 Installation
After carefully cleaning all around the area where the burner will be installed, and arranging the correct lighting of the environment,
proceed with the installation operations.
All the installation, maintenance and disassem- The installation of the burner must be carried out
bly operations must be carried out with the elec- by qualified personnel, as indicated in this man-
tricity supply disconnected. ual and in compliance with the standards and
DANGER WARNING
regulations of the laws in force.
4.2 Handling
The packaging of the burner includes a wooden platform (see Ch. 3.5), so it is possible to move the burner (still packaged) with a
transpallet truck or fork lift truck.
The handling operations for the burner can be highly dangerous if not carried out with the greatest attention: keep any
unauthorised people at a distance; check the integrity and suitableness of the available means of handling.
Check also that the area in which you are working is empty and that there is an adequate escape area (i.e. a free, safe
WARNING area to which you can quickly move if the burner should fall).
During the handling, keep the load at not more than 20-25 cm from the ground.
After positioning the burner near the installation point, correctly dispose of all residual packaging, separating the various
types of material.
Before proceeding with the installation operations, carefully clean all around the area where the burner will be installed.
CAUTION
CAUTION
The packaging elements (wooden cage or cardboard box, nails, clips, plastic bags, etc.) must not be abandoned as they are
potential sources of danger and pollution; they should be collected and disposed of in the appropriate places.
6367
12 GB
4 Installation
9
13 12
11
m 10
0m
10
1 2 5
Fig. 10
mm A B C
8
RS 70/E 185 275-325 M 12
13
RS 100/E 185 275-325 M 12
RS 130/E 195 275-325 M 12
RS 190/E 230 325-368 M 16 3
RS 250/E MZ 230 325-368 M 16 4
15
14
D7950
3 Fig. 11
6367
13 GB
4 Installation
Probe Electrode
D1209
Fig. 12
Separate the combustion head from the rest of the burner, Fig. 11.
To do this, proceed as follows:
loosen the 4 screws 3) and remove the hood 1);
remove the screws 2) from the two guides 5);
disconnect the plug 14), unscrew the grommet 15);
disconnect the socket from the maximum gas pressure switch;
remove the two screws 4);
pull back the burner on the guides 5) by about 100 mm;
disconnect the probe and electrode leads, then unthread the
burner completely from the guides.
D7951
Fig. 13
Once this operation has been carried out, fix the flange 9)(Fig. 11) to the boiler plate, interposing the insulating gasket 8)(Fig. 11) sup-
plied.
Use the 4 screws supplied, with a tightening torque of 35 - 40 Nm, after protecting their thread with anti-seize products.
The seal between burner and boiler must be airtight. After the start-up (see Ch. 5.8), check there is no leakage of flue gases into the
external environment.
6367
14 GB
4 Installation
At this point of the installation, the combustion head is fixed RS 190/E - RS 250/E MZ RS 70-100/E
to the boiler as shown in Fig. 13. It is therefore especially RS 130/E
easy to adjust, and this adjustment depends only on the max- 1
1
imum output of the burner. 2 Fig. 14
Two adjustments of the head are foreseen: 2
the air adjustment;
the gas adjustment.
Important
To facilitate adjustment, loosen the screw 3) 6
(Fig. 15), adjust and then lock.
CAUTION
10
9
No. of Notches
8
RS
RS 190/E
190/ E RS 250/E
RS 250/ E MZ
7
6
5
4
3
2
1
0
1100 1300 1500 1700 1900 2100 2300 2500 Mcal / h
6367
15 GB
4 Installation
Fig. 18 D7975
6367
16 GB
4 Installation
The gas train can enter the burner from the right or left side, depending
on which is the most convenient, see Fig. 19.
The gas train must be connected to the gas attachment 1)(Fig. 19) with
the flange 2), the gasket 3) and the screws 4) supplied with the burner.
Ensure that the maximum pressure necessary for the burner is included
in the calibration field of the pressure adjuster (colour of the spring): gas
D722
train MBC-1900-SE.
The losses of load along the gas supply line are indicated in Appendix C.
6367
17 GB
4 Installation
Fig. 21
6367
18 GB
4 Installation
D8267 Fig. 22
6367
19 GB
5 Start-up, calibration and operation of the burner
The first start-up of the burner must be carried out Check the correct working of the adjustment, com-
by qualified personnel, as indicated in this manual mand and safety devices.
and in compliance with the standards and regula-
WARNING WARNING
tions of the laws in force.
Ensure that the gas supply Company has carried out the supply line vent operations, eliminating air or inert gases from the piping.
Slowly open the manual valves situated upstream of the gas train.
Adjust the minimum gas pressure switch (Fig. 23) to the start of the scale.
Adjust the maximum gas pressure switch (Fig. 24) to the end of the scale.
Adjust the air pressure switch (Fig. 25) to the start of the scale.
Adjust the pressure switch for the valve leak detection control device (PVP Kit) (Fig. 26), if present, according to the instructions supplied with the Kit itself.
Minimum gas pressure switch Maximum gas pressure switch Air pressure switch Pressure switch PVP Kit
D3854
D3855 D3856 D3855
Bleed the air from the piping of the gas train, con-
necting a plastic tube to the pressure test point
1)(Fig. 27) of the minimum gas pressure switch.
Take the vent tube outside the building so you can
notice the smell of gas.
Connect two lamps or testers to the two gas line so-
lenoids to check the exact moment at which voltage
is supplied.
This operation is unnecessary if each of the two so-
lenoids is equipped with an indicator light that sig-
nals voltage passing through.
1
Before starting up the burner, it is good
practice to adjust the gas train so that D8098
ignition takes place in conditions of
WARNING
maximum safety, i.e. with gas delivery at Fig. 27
the minimum.
6367
20 GB
5 Start-up, calibration and operation of the burner
D7896
Fig. 28
Fig. 29
RS 190-250/E
6367
21 GB
5 Start-up, calibration and operation of the burner
Fig. 30
D3855
Fig. 31
6367
22 GB
5 Start-up, calibration and operation of the burner
Lock-out lamp
Lockout
Flame presence
Valve powered
Ignition transformer powered
Fan motor powered
Pre-heater active
only for burners of fuel oil Fig. 33
Request for heat
D8268
Parameters Mode active
Key to units of measurement
Info Mode active
m3 cubic metre
Service Mode active m3/h cubic metre/hour
l litre
l/h litre/hour
Closure of servomotors D8269 % size as percentage
degree of opening of servomotors
Opening of servomotors Fig. 32
The unit of measurement of the size visualised
Units of measurement is identified by the presence of a dash in the
corresponding unit of measurement.
Description of the keys
Key Function
- Adjustment of the fuel servomotor
6367
23 GB
5 Start-up, calibration and operation of the burner
The Operator Panel, and especially the display visualisation, has 4 working modes:
Normal mode
The information for accessing and operating at the various levels is given below.
Normal Mode
Visualises the operation conditions and allows you to modify the operation point of the burner manually.
It does not require any use of the keys of the Operator Panel.
It allows access to the other visualisation and programming modes.
Some examples in the standard conditions are given below.
P
The burner is in the request for heat waiting mode, or the selector “0-1” of Fig. 28 is at
the “0” position.
D7708
m³ m³/h l l/h %
The display visualises the various phases of the start-up, ignition and switch-off of the
P
burner.
In the example alongside, the display indicates that the burner is in phase 30 (see the
D7710
diagram of Fig. 34) and there are 12 s until the next phase.
m³ m³/h l l/h %
P
The burner is working in the requested load position (in the example alongside, 78.4%).
D7711
m³ m³/h l l/h %
P
D7714
m³ m³/h l l/h % The display visualises alternately the error code (in the example alongside, c: 12) and
the relative diagnostic (in the example d: 0).
The system goes into safety mode and the message shown in the next figure appears.
P
D7715
m³ m³/h l l/h %
P
D7712
m³ m³/h l l/h %
6367
24 GB
5 Start-up, calibration and operation of the burner
D7716
m³ m³/h l l/h %
The display visualises alternately an error code and a diagnostic, which does not take
the system into safety mode.
P
D7717
m³ m³/h l l/h %
Reset procedure
P
D7712
m³ m³/h l l/h % The burner is in lockout when the red indicator light on the Operator Panel is switched on
and the display visualises alternately the lockout code (in the example alongside c: 4) and
the relative diagnostic (in the example d: 3).
P
D7713
m³ m³/h l l/h %
To reset, press the “i/reset” key for 1s: the display will show “rESEt”.
P When the key is released, the lockout signal will disappear and the red indicator light will
switch off.
D7746
If necessary, it is possible to manually block the control box and, consequently, the burner, by pressing the key “i/reset“ simultaneously
with any other key of the Operator Panel.
With the switch 1-0 in Fig. 28 the burner does not stop immediately, but the switch-off phase is activated.
CAUTION
After the adjustment of the burner and the setting of the points on Releasing the key “F”, the
the modulation curve, it is possible to manually check the opera- standard visualisation
tion of the burner along the entire curve. appears, with the current
P load percentage flashing:
Example this means that the burner
D7767
centage: 20%.
m³ m³/h l l/h % Keep the key “F” pressed
P and, with the keys “+” or
Press the key “F” for 1 “–”, increase or decrease
D7768
centage flashes.
m³ m³/h l l/h % To emerge from Manual mode, press simultaneously the keys
“+” and “-” (esc) for 3 seconds: the burner will work in auto-
matic mode and the output will depend on the thermostat/adjust-
ment pressure switch (TR).
6367
25 GB
5 Start-up, calibration and operation of the burner
From Normal Mode, using the keys of the Operator Panel, it is possible to activate one of the three visualisation/programming modes:
Visualises the general system information. Visualises the log of errors and some technical information
The list of the parameters that can be visualised is given in regarding the system.
the table below. The list of the parameters that can be visualised is given in
To access this level, press the key “i/reset” for 1 - 3 s. the table below.
Release the key immediately when the display shows “Info”. To access this level, press the “i/reset” key for more than 3 s.
Release the key immediately when the display shows “SEr”.
P P
D8273
D8273
D7719
D7718
/reset /reset
1..3 s m³ m³/h l l/h % >3s m³ m³/h l l/h %
List of the parameters that can be visualised (in the sequence List of the parameters that can be visualised (in the sequence
in which they are visualised) in which they are visualised)
167 Volumetric delivery of fuel in the unit of measurement 954 Flame intensity (%)
selected 121 Manual setting of output
162 Operation time with flame Not defined = automatic operation
163 Operation time 922 Position of the servomotors (expressed in degrees,
164 No. of resettable ignitions symbol )
166 Total no. of ignitions 0 = fuel
113 Identification code of the burner 1 = air
107 Software version 161 Number of errors
102 Control box test date 701 Log of the errors: 701-725.01, Code
103 Identification code of the control box .
.
104 Identification number of the group of parameters set
.
105 Version of the group of parameters 725
143 Reserved
End
After access to these levels, the display visualises the number of the parameter
(flashing) on the left, and the corresponding value on the right.
If the value is not visualised, press the key “i/reset” for 1 - 3 s.
To return to the Parameters List, press the key “i/reset” for more than 3 s, or press
simultaneously the keys “+” and “-” (esc).
P
To move on to the next parameter, press the key “+” or “i/reset” for less than 1 s. At
the end of the list, the display visualises “End”.
D7720
To move back to the previous parameter, press the key “-”. m³ m³/h l l/h %
To return to the Normal/Standard Visualisation Mode, press the “i/reset” key for
more than 3 s, or press simultaneously keys “+” and “-” (esc). For a moment the
display will show “OPErAte”.
6367
26 GB
5 Start-up, calibration and operation of the burner
Parameters Mode
Visualises and allows you to modify/program the complete list of To access this level, refer to “Access procedure with password”.
parameters, shown in the table on page 34.
Once the access procedure has been carried out, the display will
The factory-set parameters are not visible.
show “PArA” for a few seconds.
The parameters level is subdivided into groups:
100: ParA General parameters P
Information and identification data of the system.
D7722
200: ParA Checks on the Burner
Type of operation, intervention and safety times m³ m³/h l l/h %
of the various phases.
400: Set Air/Fuel modulation curve Select the group of parameters with keys “+“ and “-“, and con-
Setting of Air/Fuel adjustment points firm by pressing the “i/reset” key.
500: ParA Positioning of Servomotors Within the group you have chosen, scroll through the list with the
Choice of positions of the air/fuel servomotors in keys “+“ and “-”. At the end of the list, the display visualises
the various phases. “End“.
600: ParA Servomotors To return to Normal visualisation mode, simultaneously press the
Setting and addressing of the servomotors. keys “+” and “-” (esc) twice.
700: HISt Log of the errors To modify a parameter, refer to “Parameter modification proce-
Choice of different visualisation modes for the dure”.
errors log.
900: dAtA Process information
Visualisation of information for the remote man- All the parameters are checked in the factory.
agement of the burner. Modification/tampering may compromise the good
operation of the burner and cause injury to people
DANGER or damage to things. In any case, modifications
must be carried out by qualified personnel.
D7722
D7736
It is then necessary to
m³ m³/h l l/h % repeat the procedure.
6367
27 GB
5 Start-up, calibration and operation of the burner
Parameter modification procedure Procedure for inserting and adjusting points on the
modulation curve
After accessing the level Nine adjustment/calibration points (P1 - P9) can be inserted in
and group of parameters, the control box for each servomotor, varying their position by de-
the display visualises the grees and, consequently, the quantity of air and fuel introduced.
number of the parameter The ignition point P0 is independent of the minimum modulation
P (flashing) on the left, and value. This means that, in the event of difficulty, it is possible to
the corresponding value on switch on the burner at a value other than the modulation mini-
D7757
the right. mum (P1).
m³ m³/h l l/h % If the value is not visual- To insert or adjust a point, proceed as follows:
ised, press the key “i/
Access the Parameters level (group 400) referring to “Access
reset” for 1 - 3 s.
procedure with password”.
Find below an example of how to modify the parameter relating Using the keys “+” and “-”
to the pre-purging time (No. 225). insert/select the curve
point you want and wait for
Press the key “i/reset“: it to flash: this means that
the value 20 (seconds) will the servomotors are now
P appear. positioned on the values
P
shown on the display and
D7760
D7747
m³ m³/h l l/h % point previously set.
ualised but is understood It is now possible to insert/
m³ m³/h l l/h %
in seconds. modify the position by
Press the key “+“ and degrees.
increase the value to 25 Warning: the set value
P
seconds (flashing). does not require
confirmation.
D7758
D7748
P parameters, press simulta- keys “+” or “-” to increase
neously the keys “+“ and m³ m³/h l l/h % or decrease the value.
D7759
“-“ (esc).
m³ m³/h l l/h % For the air servomotor,
keep the key “A” pressed
P (the position in degrees
flashes) and press the
D7749
6367
28 GB
5 Start-up, calibration and operation of the burner
Signal ON
Operation
Signal OFF
Start-up Switching off Checking of
Any signal is allowed seal
t1 TSA1
Fan motor MV
Ignition transformer TA
OUTPUT SIGNALS
Shutoff valve
Safety valve V1
Adjustment valve V2
Pilot valve VP
Limit lockout
90°
Nominal load
Pos. of post-purging
Ignition load
Low flame
fuel
0°
90°
Nominal load
Pos. of post-purging
Ignition load
air
Low flame
Pos. without load
0°
D7727
Fig. 34
List of the phases
Ph00 Lockout phase Ph44 t44 = interval time 1
Ph01 Safety phase Ph60 Operation
Ph10 t10 = closure in pause Ph62 t62 = max. time to reach the low flame (the burner
Ph12 Standby moves to the switch-off position)
Ph22 t22 = Uphill train of the fan motor (fan motor = ON, Ph70 t13 = post-combustion time
safety valve = ON) Ph72 The burner moves to the post-purging position
Ph24 The burner moves to the pre-purging position Ph74 t8 = post-purging time
Ph30 t1 = pre-purging time Ph80 t80 = emptying time (valve leak detection)
Ph36 The burner moves to the ignition position Ph81 t81 = atmospheric test time (valve leak detection)
Ph38 t3 = pre-ignition time Ph82 t82 = filling time (valve leak detection)
Ph40 TSA1 = safety time 1 (ignition transformer ON) Ph83 t83 = pressure test time (valve leak detection)
Ph42 TSA1 = safety time 1 (ignition transformer OFF), t42 = Ph90 Standby time due to lack of gas
pre-ignition time OFF Ph = Phase
6367
29 GB
5 Start-up, calibration and operation of the burner
P Check that the display of the Operator Panel shows request for heat and “OFF Upr”: this
means it is necessary to set the modulation curve of the burner.
D7734
m³ m³/h l l/h %
m³ m³/h l l/h %
Phase 24:
The burner goes to the pre-purging position, the air servomotor opens the damper at 90°.
Phases 80, 81, 82, 83:
These phases relate to the valve seal test (for the burner RS68/E this function is not inserted
in the factory, as it is optional).
Phase 30:
The count of the pre-purging time pre-set in the factory begins.
Phase 36:
The burner goes to the ignition position, point “P0”, defined in the table on page 31: the
P display visualises the indication “P0” flashing. If the value proposed is suitable, confirm.
Otherwise, modify the ignition point (see “Procedure for inserting and adjusting points on the
D7747
modulation curve”).
m³ m³/h l l/h % Warning: the values shown in the figure alongside are purely for indication
purposes.
DANGER
Confirm with the key “+”.
Phase 38:
The ignition phase begins and the spark goes off.
Phase 40:
P The gas valves open (the count of the safety time begins).
Check the presence of the flame from the special inspection window, and the correctness of
D7712
the combustion parameters; if necessary, vary the degrees of opening/closing of the air and
fuel servomotors.
m³ m³/h l l/h %
If the control box goes into lockout, press the keys “+” and “-” (esc) simultaneously: the
display visualises alternately the lockout code for flame absence (c: 4) and the relative
diagnostic (d: 3).
P Resolve the problem, referring to Ch. 5.12.
D7713
6367
30 GB
5 Start-up, calibration and operation of the burner
After ignition (point “P0”), proceed with the calibration of the modulation curve,
starting from the minimum point “P1”.
Press the key “+”: the display visualises the indication “P1” flashing and proposes
the same settings as for point “P0”. It is possible to modify this value and obtain a
modulation minimum different from the ignition point.
After adjusting point “P1”, press the key “+”: the display shows “CALC” for a few
seconds. The control box will automatically calculate the points from “P2” to “P8”,
distributing them in a straight line, assuming for point “P9” the factory setting (see the
table below). These are theoretical and must be checked.
P Press the key “+” to check if the settings of point “P2” are suitable. If not, modify the
point. Proceed in sequence until point “P9”.
D7763
Important: before moving on from one point to the next, wait for the
m³ m³/h l l/h %
servomotors to reach the position visualised on the display.
WARNING
During the adjustment of each point, work on the air and gas servomotors, without
modifying the position of the gas valve stabiliser.
Halfway through the procedure (i.e. around point P4 or P5), you are advised to
measure gas delivery and check that the output is about 50% of the maximum output.
If this is not the case, work also on the gas valve stabiliser: in this case however, it is
necessary to revise the calibrations of all the points previously set.
Once you have arrived at point “P9”, if the maximum output is not as you wish, work
on the gas valve stabiliser: in this case however, it is necessary to revise the
calibrations of all the points previously set.
P At this point, confirm by pressing simultaneously the keys “+” and “-” (esc): the
parameter “546” will appear.
D7765
If you want to make the burner work on the entire modulation curve, press
m³ m³/h l l/h % simultaneously the keys “+” and “-” (esc): in this way, the parameter “546” will
automatically be assigned the value of 100% and the parameter “545” will have a
value of 20%.
If you want to make the burner work on a part of the modulation curve, modify the
parameters “546” and “545” according to “Parameter modification procedure”.
Press simultaneously the keys “+” and “-” (esc) twice: the display will visualise the
current load position.
Factory settings
Point of Burner
the curve RS 70/E RS 100/E RS 130/E RS 190/E RS 250/E MZ
air 20° 20° 20° 20° 20°
P0
gas 24° 24° 24° 24° 24°
air 90° 90° 90° 90° 90°
P9
gas 90° 90° 90° 90° 90°
6367
31 GB
5 Start-up, calibration and operation of the burner
90 90
80 80
e l l
70 original Fu 70 Fu
e
curve
Angle (degrees)
Angle (degrees)
60 60
50 CALC+ 50
40 40
30 30
20 CALC- 20
10 10
Recalculation
0 0
P0 P1 P2 P3 P4 P5 P6 P7 P8 P9 P0 P1 P2 P3 P4 P5 P6 P7 P8 P9
6367
32 GB
5 Start-up, calibration and operation of the burner
Burner without modulating operation kit The burner is fitted with an ionisation system to check that a
Once the start-up cycle is completed, the servomotor command flame is present.
moves on to the thermostat/pressure switch TR that controls the The minimum current for control box operation is 4 µA. The
pressure or the temperature in the boiler. Operator Panel visualises “30%” (see Parameters List, parame-
ter no. 954).
If the temperature or the pressure is low (so the thermostat/
The burner provides a much higher current, so controls are not
pressure switch TR is closed), the burner progressively normally required. However, if it is necessary to measure the
increases the output as far as the MAX value (point “P9”). ionisation current, disconnect the plug-socket Ap.37 on the ioni-
If the temperature or the pressure increases as far as the sation probe cable and insert a direct current microammeter with
opening of the thermostat/pressure switch TR, the burner a base scale of 100 µA - see Fig. 37.
progressively reduces the output as far as the MIN value Carefully check the polarities!
(point “P1”). And so on.
The burner switches off when the request for heat is lower
than the heat supplied by the burner at MIN output. The ther-
mostat/pressure switch TL opens and the control box carries
out the switching off phase (see Ch. 5.7). The damper closes
completely to reduce thermal dispersions to a minimum.
6367
33 GB
5 Start-up, calibration and operation of the burner
Reading
102 Control box identification date 1 - 0 255 1 Info Mode
only
Reading
103 Control box identification number 1 - 0 65535 1 Info Mode
only
Reading
104 Identification number of the group of parameters set 1 - 0 255 1 Info Mode
only
Reading
105 Version of the group of parameters set 1 - 0 0xFFFF 1 Info Mode
only
Reading
107 Software version 1 - 0 0xFFFF 1 Info Mode
only
Modifica-
113 Burner identification 1 - 0 99999999 1 Not defined Info Mode
tion
Modifica-
Manual setting of output Service
121 1 - tion / 0% 100 % 0.1 % Not defined
Not defined = automatic operation Mode
zero setting
Modifica- Parameters
126 Brightness of display 1 - 0% 100 % 1% 75 %
tion Mode
Modifica-
143 Reserved - 1 8 1 1 Info Mode
tion
Modifica- Parameters
144 Reserved - 10 s 60 s 1s 30 s
tion Mode
Modifica- Parameters
145 Peripheral address for Modbus - 1 247 1 1
tion Mode
6367
34 GB
5 Start-up, calibration and operation of the burner
Reading Service
161 Total number of errors 1 - 0 65535 1 0
only Mode
162 Hours of operation (that can be reset) 1 h Reset 0h 999999h 1h 0h Info Mode
Reading
163 Total hours of power supply to control box 1 h 0h 999999h 1h 0h Info Mode
only
164 Total number of start-ups (that can be reset) 1 - Reset 0 999999 1 0 Info Mode
Reading
166 Total number of start-ups 1 - 0 999999 1 0 Info Mode
only
Modifica- Parameters
210 Alarm/lockout at start 1 - 0 1 1 0
tion Mode
Modifica- Parameters
211 Uphill train fan motor 1 s 2s 60 s 0.2 s 2s
tion Mode
Modifica- Parameters
212 Maximum time to reach low flame 1 s 0.2 s 10 min 0.2 s 45 s
tion Mode
Modifica- Parameters
215 Maximum repeats of safety circuit 1 - 1 16 1 16
tion Mode
234 Gas: Post-purging time 1 s Modifica- 0.2 s 108 min 0.2 s 0.2 s Parameters
tion Mode
242 Gas: Emptying time (valve leak detection) 1 s Modifica- 0.2 s 3s 0.2 s 3s Parameters
tion Mode
243 Gas: Atmospheric test time (valve leak detection) 1 s Modifica- 0.2 s 60 s 0.2 s 10 s Parameters
tion Mode
6367
35 GB
5 Start-up, calibration and operation of the burner
244 Gas: Filling time (valve leak detection) 1 s Modifica- 0.2 s 3s 0.2 s 3s Parameters
tion Mode
245 Gas: Pressure test time (valve leak detection) 1 s Modifica- 0.2 s 60 s 0.2 s 10 s Parameters
tion Mode
274 Oil: Post-purging time 1 s Modifica- 0.2 s 108 min 0.2 s 0.2 s Parameters
tion Mode
402 Checking air servomotor 13 (°) Modifica- 0° 90° 0.1° 0°; 90°; Parameters
tion 45°; not Mode
defined
502 Position of the air servomotor in absence of flame 3 (°) Modifica- 0° 90° 0.1° 0°; 90°; 45° Parameters
Index 0 = standby position tion Mode
Index 1 = pre-purging position
Index 2 = post-purging position
545 Minimum modulation limit 1 - Modifica- 20 % 100 % 0.1 % Not defined Parameters
tion / Mode
zero setting
546 Maximum modulation limit 1 - Modifica- 20 % 100 % 0.1 % Not defined Parameters
tion / Mode
zero setting
600 Servomotors
645 Analogical exit configuration 1 - Modifica- 0 2 1 0 Parameters
0 = CC 0...10 V tion Mode
1 = CC 2...10 V
2 = CC 0 / 2...10 V
6367
36 GB
5 Start-up, calibration and operation of the burner
922 Position of the servomotors 2 (°) Reading -50° 150° 150° 0° Service
Index 0 = fuel only Mode
Index 1 = air
947 Result of the sampling of the contact (codified in bits) 2 - Reading 0 255 1 0 Parameters
only Mode
6367
37 GB
6 Faults - Possible causes - Solutions
If faults arise in ignition or operations, the burner performs a "safety stop", which is signalled by the red burner lockout LED. The display
visualises alternately the lockout code and the relative diagnostic.
To reset the start-up conditions, refer to “Reset procedure”. When the burner starts up again, the red LED goes out.
6367
38 GB
6 Faults - Possible causes - Solutions
Error Diagnostic
Meaning of the system REC27.100A2 Recommended measures
code code
85 # Reference error of a servomotor
The reference of the fuel servomotor was not successful.
Bit 0 It was not possible to reach the reference point.
Reference error of the fuel servomotor
Valence 1 1. Check if the servomotors have been inverted.
2. Check if the servomotor is blocked or overloaded.
The reference of the air servomotor was not successful.
Bit 1 Reference error of the air servomotor It was not possible to reach the reference point.
Valence 2…3 1. Check if the servomotors have been inverted.
2. Check if the servomotor is blocked or overloaded.
Bit 7 The parameterization of an actuator (e.g. the reference position) has been
Reference error owing to parameter modification
Valence 128 modified. This error will be visualised to start up a new reference.
6367
39 GB
6 Faults - Possible causes - Solutions
Error Diagnostic
Meaning of the system REC27.100A2 Recommended measures
code code
98 # Relay supervision error
2 Safety valve
3 Ignition
transformer
The relay does not start up Carry out a reset; if the error arises repeatedly, replace the unit
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
99 - 100 # Relay internal checking error Carry out a reset; if the error arises repeatedly, replace the control box
105 # Contact sampling internal error
0 Min. pressure
switch
1 Max.
pressure
switch
2 Valve
operation test
pressure
switch
3 Air pressure
4 Load
controller open
5 Load Can be caused by capacitive loads or presence of DC voltage on the main power
controller on/ Blocked upon irregularity supply of the control box. The diagnostic code indicates the input in which the problem
off arose
6 Load
controller
closed
7 Safety loop /
Burner flange
8 Safety valve
9 Ignition
transformer
10 Fuel valve 1
11 Fuel valve 2
12 Fuel valve 3
13 Reset
106 - 108 # Contact request internal error Carry out a reset; if the error arises repeatedly, replace the control box
110 # Voltage monitoring test internal error Carry out a reset; if the error arises repeatedly, replace the control box
111 0 Low level of power supply Insufficient mains voltage
Error code for the carrying out of a reset in the event of power supply restoration
112 0 Reset power supply voltage
(absence of error)
113 # Mains voltage supervision internal error Carry out a reset; if the error arises repeatedly, replace the control box
115 # Control box meter internal error
116 0 Life cycle of the control box in the critical interval The envisaged life cycle of the control box has been exceeded. Replace it.
117 0 Life cycle of the control box exceeded The switch-off threshold has been reached.
Too many disturbance impulses on the input of the fuel meter.
120 0 Interruption of fuel limiting meter input
Improve the electromagnetic compatibility.
Carry out a reset, repeat and check the last setting of the parameters. Restore the
121 - 124 # EEPROM access internal error group of parameters. If the error arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
125 # EEPROM reading access internal error
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
126 # EEPROM writing access internal error
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. Restore the
127 # EEPROM access internal error
group of parameters. If the error arises repeatedly, replace the control box.
EEPROM access internal error - synchronisation
128 0 Carry out a reset; If the error arises repeatedly, replace the control box.
during the initialisation
EEPROM access internal error – Carry out a reset, repeat and check the last setting of the parameters. If the error
129 #
command synchronisation arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
130 # EEPROM access internal error - time-out
arises repeatedly, replace the control box.
Carry out a reset, repeat and check the last setting of the parameters. If the error
131 # EEPROM access internal error - page interrupted
arises repeatedly, replace the control box.
132 # EEPROM register initialisation internal error Carry out a reset; If the error arises repeatedly, replace the control box.
EEPROM access internal error – request Carry out a reset, repeat and check the last setting of the parameters. If the error
133 - 135 #
synchronisation arises repeatedly, replace the control box.
136 1 Restoration started The restoration of a backup has been started (no error)
6367
40 GB
6 Faults - Possible causes - Solutions
Error Diagnostic
Meaning of the system REC27.100A2 Recommended measures
code code
137 # Internal error – backup / restoration
Restoration – OK, but backup < compared with set data of Restoration successful, but the backup data installed are fewer than those currently present in
157
current system the system.
242 Backup – the backup carried out is contradictory The backup is irregular and cannot be transferred again
Backup – the data comparison between the internal
243 Repeat the reset and backup
microprocessors is irregular
The backup data are incompatible with the current version of the software; the
244 The backup data are incompatible
restoration is not possible
245 Error in access to the parameter Restore_Complete Repeat the reset and backup
246 Restoration – time-out during logging in EEPROM Repeat the reset and backup
247 The data received are contradictory The series of backup data is not valid; restoration is not possible
248 The restoration cannot currently be carried out Repeat the reset and backup
Restoration – interruption caused by inadequate The backup has an inadequate identification of the burner and must not be transferred
249
identification of the burner to the control box
250 Backup – The CRC of a page is not correct The series of backup data is not valid; restoration is not possible
251 Backup – the identification of the burner is not defined Define the identification of the burner and repeat the backup
252 After restoration, the pages are still in INTERRUPTION Repeat the reset and backup
253 The restoration cannot currently be carried out Repeat the reset and backup
254 Interruption owing to transmission error Repeat the reset and backup
255 Interruption owing to time-out during the restoration Carry out a reset, check the connections and repeat the backup
146 # Time-out of the system automation interface Refer to the Modbus User Documentation (A7541)
1 Modbus time-out
2 Reserved
165 # Internal error
166 0 Watchdog reset internal error
167 # Manual lockout The control box has been manually blocked (no error)
1 Manual lockout from remote reset command
2 Manual lockout from Operator Panel
3 Manual lockout from PC interface
168 - 171 # Internal error management Carry out a reset; if the error arises repeatedly, replace the control box
200 # System free of errors No error
201 # Lockout or error at start Lockout or error due to lack of parameter settings
1 No operation mode selected
2..3 No fuel train defined
4..7 No curve defined
8..15 Standardisation speed not defined
16..31 Backup / restoration impossible
202 # Selection of internal operation mode Redefine the operation mode (parameter 201)
Redefine the operation mode (parameter 201)
203 # Internal error
Carry out a reset; if the error arises repeatedly, replace the control box
Phase
204 Program stop The program stop is active (no error)
number
205 # Internal error Carry out a reset; if the error arises repeatedly, replace the control box
Combination of control box and Operator Panel not
206 0
allowed
207 # Compatibility of control box with Operator Panel
0 Obsolete version of control box
1 Obsolete version of Operator Panel
208-209 # Internal error Carry out a reset; if the error arises repeatedly, replace the control box
240 # Internal error Carry out a reset; if the error arises repeatedly, replace the control box
245 # Internal error Carry out a reset; if the error arises repeatedly, replace the control box
250 # Internal error Carry out a reset; if the error arises repeatedly, replace the control box
6367
41 GB
7 Maintenance
The periodic maintenance is essential for the good operation, Before carrying out any maintenance, cleaning or checking oper-
safety, yield and duration of the burner. ations:
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time. disconnect the electricity supply from the burner by
means of the main switch of the system;
The maintenance interventions and the calibration of
DANGER
the burner must only be carried out by qualified, au-
thorised personnel, in accordance with the contents of close the fuel interception tap;
DANGER this manual and in compliance with the standards and
regulations of current laws.
DANGER
6367
42 GB
7 Maintenance
Disconnect the electrical supply from the burner. Push the burner up to approximately 100 mm from the pipe
Loosen the 4 screws 1) and remove the hood 2). coupling.
Assemble the two extensions supplied on the guides 4) (ver- Reinsert the cables and slide the burner as far as the stop.
sions TL). Connect the plug of the servomotor 7) and tighten the grom-
Disconnect the plug 7) and loosen the cable grommet 8); met 8).
Disconnect the socket from the maximum gas pressure Connect the socket of the maximum gas pressure switch.
switch; Replace the screws 3) and carefully pull the probe and elec-
Remove the screws 3) and pull back the burner on the trode cables outwards until they are slightly taut.
guides 4) by about 100 mm. Disconnect the cables of the Disassemble the two extensions from the guides 4).
probe and electrode, then pull the burner back completely.
At this point it is possible to extract the inner part 5) after having
removed the screw 6).
6
4
5
1
3
8
7
D8272
1
Fig. 39
6367
43 GB
A Appendix - Electrical panel layout
1 Index of layouts
2 Indication of references
2 Indication of references
/1.A1
Sheet no.
Co-ordinates
6367
44 GB
A
6367
!
$"!+++
2 % 2 % %&$
)2$ ;G $,*)) *&$
+ (& + @"(A $$ <+
<+
% 2 % 2
>
>
! $
& $
1
% 2 $
!
1 $
% 2 $
?
C
! B
1
!
<+"
& &
<+"
$
" <+" "
!
*)#
*6= &6= "
# " #!
$
Appendix - Electrical panel layout
"
45 GB
* *(&$ &
!<$ ' + ?2
- .//0 <$ ' +?2 + +
*
*
*
&,$
*
&
# #
<$ ' +?2
<$ !
*
&
*
*
*
$
@ A
+?2 !
<$
@ A
$
<$ '
@ A
+?2
<$ '
1" !
@ A
;
$ 7 $
1 1"
* * * $
1"
3456786 * & 1"
9 B .
64:;7
> 1 1
& *
6367
46 GB
A Appendix - Electrical panel layout
6367
47 GB
A Appendix - Electrical panel layout
6367
48 GB
A Appendix - Electrical panel layout
6367
49 GB
B Appendix - Accessories (on request)
With the modulating operation, the burner continually adapts the power to the request for heat, ensuring great stability for the parameter
controlled: temperature or pressure.
Two components should be ordered:
• the output regulator to install on the burner;
• the probe to install on the heat generator.
Code 3010436
Code 3010437
Gas trains in compliance with standard EN 676 (complete with valves, pressure adjuster and filter)
Gas train - burner adapters
Soundproofing chamber
Reduction of
Burner Kit code Type
noise average
RS 70-100/M
RS 130/M MZ
3010404 C4/5 10 [dB(A)]
RS 190/E
RS 250/M MZ
6367
50 GB
B Appendix - Accessories (on request)
Combustion
Burner Kit code
head
TC
RS 70/E 3010201
TL
TC
RS 100/E 3010202
TL
TC 3010373
RS 130/E
TL 3010374
RS 190/E TC 3010375
TC
RS 250/E MZ -
TL
Combustion
Burner Kit code
head
TC
RS 70/E 3010286
TL
TC
RS 100/E 3010287
TL
TC
RS 130/E 3010288
TL
RS 190/E TC 3010297
TC
RS 250/E MZ -
TL
6367
51 GB
C Appendix - Gas supply pressure
The table show minimum load losses along the gas supply line depending on the maximum burner output operation.
1 2 3
p (mbar) p (mbar) p (mbar)
Model
700 7.4 10.1 0.9 1.1 34.0 45.7 16.4 22.0 12.1 16.4 5.1 6.2 4.2 4.9 - -
750 8.5 11.8 1.0 1.2 37.7 50.3 18.0 24.4 13.4 18.2 5.4 6.7 4.5 5.2 - -
800 9.6 13.4 1.2 1.4 41.5 - 19.9 26.8 14.8 19.9 5.8 7.2 4.6 5.5 - -
850 10.8 15.1 1.3 1.6 45.3 - 21.8 29.3 16.3 21.8 6.2 7.8 4.9 5.8 - -
900 12.1 16.9 1.5 1.8 49.1 - 23.8 31.8 17.7 23.8 6.6 8.4 5.1 6.1 - -
930 12.9 17.9 1.6 1.9 51.4 - 25.0 33.4 18.6 25.1 6.9 8.8 5.2 6.3 - -
700 3.1 4.6 0.7 1.0 - - 16.4 22.0 12.1 16.4 5.1 6.2 4.2 4.9 - -
750 3.7 5.5 0.8 1.1 - - 18.0 24.4 13.4 18.2 5.4 6.7 4.5 5.2 - -
800 4.3 6.4 0.9 1.2 - - 19.9 26.8 14.8 19.9 5.8 7.2 4.6 5.5 - -
850 4.9 7.3 1.0 1.4 - - 21.8 29.3 16.3 21.8 6.2 7.8 4.9 5.8 - -
900 5.5 8.2 1.1 1.6 - - 23.8 31.8 17.7 23.8 6.6 8.4 5.1 6.1 - -
950 6.2 9.0 1.2 1.8 - - 25.8 34.4 19.2 25.9 7.0 9.0 5.3 6.4 - -
RS 100/E
1000 6.8 9.9 1.3 1.9 - - 27.7 37.0 20.6 28.0 7.4 9.6 5.5 6.8 - -
1050 7.3 10.7 1.5 2.1 - - 29.8 39.6 22.2 30.1 7.9 10.3 5.8 7.1 - -
1100 7.9 11.6 1.6 2.4 - - 31.9 42.9 23.9 32.8 8.4 11.2 6.1 7.6 - -
1150 8.4 12.4 1.8 2.6 - - 34.0 46.1 25.6 35.4 8.9 12.2 6.4 8.2 - -
1200 9.1 13.5 1.9 2.8 - - 36.1 49.4 27.2 38.1 9.4 13.1 6.6 8.7 - -
1250 9.9 14.8 2.1 3.0 - - 38.2 52.6 28.9 40.7 9.9 14.0 6.9 9.1 - -
1300 10.8 16.1 2.3 3.3 - - 40.5 55.9 30.9 43.4 10.6 15.0 7.2 9.7 - -
1340 11.4 17.1 2.4 3.5 - - 42.7 58.5 32.6 45.5 11.2 15.7 7.6 10.1 - -
920 4.5 7.0 1.3 2.0 - - 21.5 28.9 14.7 20.2 6.8 8.6 5.2 6.2 3.9 4.4
950 4.7 7.4 1.4 2.1 - - 22.6 30.2 15.5 21.2 7.0 9.0 5.3 6.4 3.9 4.5
1000 5.1 7.9 1.5 2.3 - - 24.4 32.5 16.8 23.0 7.4 9.6 5.5 6.8 4.1 4.6
1050 5.5 8.5 1.7 2.5 - - 26.2 34.9 18.1 24.9 7.9 10.3 5.8 7.1 4.2 4.8
1100 5.9 9.1 1.8 2.8 - - 28.0 37.5 19.5 26.9 8.4 11.1 6.1 7.6 4.3 5.0
1150 6.2 9.6 2.0 3.1 - - 29.9 40.2 20.9 29.1 8.9 12.0 6.4 8.1 4.5 5.2
1200 6.6 10.2 2.2 3.3 - - 31.7 42.9 22.4 31.3 9.4 12.8 6.6 8.6 4.6 5.4
RS 130/E
1250 7.0 10.8 2.4 3.6 - - 33.6 45.7 23.9 33.5 9.9 13.7 6.9 9.1 4.8 5.6
1300 7.4 11.3 2.6 3.9 - - 35.7 48.6 25.5 35.8 10.5 14.7 7.2 9.7 4.9 5.8
1350 7.8 11.9 2.8 4.2 - - 37.8 51.5 27.2 38.2 11.2 15.6 7.6 10.1 5.1 6.0
1400 8.2 12.8 3.0 4.5 - - 40.0 54.5 28.9 40.7 11.9 16.6 8.0 10.7 5.2 6.2
1450 8.6 13.8 3.2 4.9 - - 42.2 57.5 30.7 43.2 12.6 17.6 8.5 11.2 5.3 6.4
1500 9.0 14.7 3.4 5.2 - - 44.5 60.6 32.5 45.8 13.3 18.6 8.9 11.8 5.5 6.6
1550 10.2 15.6 3.6 5.6 - - 46.8 63.8 34.4 48.4 14.1 19.6 9.3 12.4 5.7 6.9
1600 11.4 16.6 3.9 5.9 - - 49.2 67.0 36.3 51.1 14.8 20.7 9.7 13.0 5.8 7.0
1605 11.5 16.7 3.9 6.0 - - 49.4 67.3 36.5 51.4 14.9 20.8 9.8 13.1 5.8 7.0
6367
52 GB
C Appendix - Gas supply pressure
1 2 3
p (mbar) p (mbar) p (mbar)
Model
1700 9.8 14.7 2.4 3.5 - - 61.8 - 48.3 66.3 16.7 23.0 10.7 14.3 6.1 7.6
1800 9.9 14.7 2.7 4.0 - - 67.2 - 52.7 72.9 18.2 25.3 11.5 15.8 6.4 8.2
1900 10.3 15.5 3.0 4.4 - - 72.5 - 57.0 79.5 19.8 27.6 12.4 17.2 6.9 8.8
2000 11.5 17.1 3.3 4.9 - - - - 62.2 - 21.6 29.9 13.5 18.7 7.3 9.3
2100 12.6 18.8 3.6 5.4 - - - - 67.6 - 23.5 32.3 14.6 20.1 7.7 10.0
2200 13.7 20.5 4.0 5.9 - - - - 73.0 - 25.4 35.8 15.8 21.7 8.2 10.7
2290 14.9 22.2 4.3 6.4 - - - - 77.8 - 27.1 38.9 16.8 23.0 8.6 11.4
1250 5.2 7.8 3.0 4.0 - - 38.2 52.6 28.9 40.7 9.9 14.0 6.9 9.1 4.7 5.5
1300 5.6 8.4 3.3 4.3 - - 40.5 55.9 30.9 43.4 10.6 15.0 7.2 9.7 4.9 5.8
1400 6.4 9.6 3.8 5.0 - - 45.9 62.4 35.2 48.7 12.1 16.9 8.2 10.8 5.2 6.2
1500 7.2 10.8 4.4 5.7 - - 51.2 68.9 39.6 54.1 13.6 18.7 9.0 11.8 5.5 6.6
1600 8.0 12.0 5.0 6.5 - - 56.5 75.4 43.9 59.8 15.2 20.7 9.8 13.0 5.8 7.0
1700 8.8 13.2 5.6 7.3 - - 61.8 - 48.3 66.3 16.7 23.0 10.7 14.3 6.1 7.6
1800 9.7 14.5 6.3 8.2 - - 67.2 - 52.7 72.9 18.2 25.3 11.5 15.8 6.4 8.2
RS 250/E MZ
1900 10.5 15.7 7.0 9.2 - - 72.5 - 57.0 79.5 19.8 27.6 12.4 17.2 6.9 8.8
2000 11.3 16.9 7.7 10.1 - - - - 62.2 - 21.6 29.9 13.5 18.7 7.3 9.3
2100 12.4 18.6 8.5 11.2 - - - - 67.6 - 23.5 32.3 14.6 20.1 7.7 10.0
2200 13.6 20.3 9.4 12.3 - - - - 73.0 - 25.4 35.8 15.8 21.7 8.2 10.7
2300 14.7 22.0 10.2 13.4 - - - - 78.3 - 27.3 39.2 17.0 23.2 8.7 11.4
2400 15.8 23.6 11.2 14.6 - - - - 83.7 - 29.1 42.7 18.1 24.8 9.2 12.1
2500 17.0 25.3 12.1 15.8 - - - - - - 31.0 46.1 19.4 26.3 9.6 12.9
2600 18.6 27.7 13.1 17.1 - - - - - - 33.3 49.6 20.6 28.0 10.2 13.5
2650 19.4 28.9 13.6 17.8 - - - - - - 34.8 51.7 21.2 28.8 10.5 13.9
6367
53 GB
C Appendix - Gas supply pressure
NOTE NOTE
To know the approximate output at which the burner is operating To know the required gas pressure at test point 1)(Fig. 40), set
at its maximum: the MAX output required from the burner operation:
- Subtract the combustion chamber pressure from the gas pres- - Find the nearest output value in the table for the burner in
sure measured at test point 1)(Fig. 40). question.
- Find, in the table relating to the burner concerned, column 1, - Read, on the right, column 1, the socket pressure 1)(Fig. 40).
the pressure value closest to the result you want. - Add this value to the estimated pressure in the combustion
- Read off the corresponding output on the left. chamber.
Example with natural gas G 20 - RS 100/E Example with natural gas G 20 - RS 100/E
• Maximum output operation • Required burner maximum output operation: 900 kW
• Ring nut 5)(Fig. 15) adjusted as in the diagram of (Fig. 17) • Ring nut 5)(Fig. 15) adjusted as in the diagram of (Fig. 17)
• Gas pressure at test point 1)(Fig. 39) = 8 mbar • Gas pressure at output of 900 kW = 5.5 mbar
• Pressure in combustion chamber = 2.5 mbar • Pressure in combustion chamber = 2.5 mbar
8 - 2.5 = 5.5 mbar 5.5 + 2.5 = 8 mbar
A pressure of 5.5 mbar, column 1, corresponds in the table to pressure required at test point 1)(Fig. 40).
an output of 900 kW.
This value serves as a rough guide; the effective output must
be measured at the gas meter.
D3734 Fig. 40
6367
54 GB
D Appendix - Firing rate on basis of air density
The firing rate of the burner shown in the manual is valid for a If H3 is greater than H1, as in Fig. 41, the burner can produce the
room temperature of 20 °C and an altitude of 0 m above sea level delivery requested.
(barometric pressure around 1013 mbar). If H3 is less than H1, it is necessary to reduce the output of the
burner. The reduction in output is accompanied by a reduction in
It may be that a burner has to operate with combustive air at a
the combustion chamber pressure:
higher temperature and/or higher altitudes.
Qr = reduced output
The heating of the air and the increase in altitude produce the H1r = reduced pressure
same effect: the expansion of the air volume (i.e. the reduction of
its density).
The delivery of the burner fan remains essentially the same, but
H1r = H1 x ( QrQ )
2
the oxygen per m3 of air, and the thrust (discharge head) of the
Example, 5% reduction in output:
fan are reduced.
Qr = Q x 0.95
It is therefore important to know if the maximum output requested
from the burner at a determinate combustion chamber pressure H1r = H1 x (0.95)2
remains within the firing rate of the burner even with the changed With the new values - Qr and H1r - repeat steps 2 - 5.
temperature and altitude conditions.
To check it, proceed as follows: Warning:
the combustion head should be adjusted in relation to the equiv-
1 -Find the corrective factor F (relating to the air temperature and
alent output Qe.
altitude of the system) in the table alongside.
2 -Divide the output Q required from the burner by F to obtain the
equivalent output Qe:
mbar
mbar
Qe = Q : F (kW)
3 -In the firing rate of the burner, mark the work point identified H2
H3
by:
H1 A
Qe = equivalent output
H1 = pressure in combustion chamber
point A that must remain within the firing rate (Fig. 41). D388
4 -Trace a vertical line from point A, Fig. 41, and find the maxi- Qe
Qe kW
kg/h
mum pressure H2 of the firing rate.
5 -Multiply H2 by F to obtain the maximum lowered pressure H3 Fig. 41
of the firing rate
H3 = H2 x F (mbar)
Average F
Altitude barometric
pressure Air temperature °C
m. above sea
mbar 0 5 10 15 20 25 30 40
level
6367
55 GB
RIELLO S.p.A.
I - 37045 Legnago (VR)
Tel.: +39.0442.630111
http:// www.riello.it
http:// www.rielloburners.com
Subject to modifications