Delta Ia-Plc Dvp-Slim-Dido I Tse 20240223
Delta Ia-Plc Dvp-Slim-Dido I Tse 20240223
20240221
Warning ENGLISH
EN DVP-SLIM is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity,
electric shock and vibration. To prevent non-maintenance staff from operating DVP-SLIM, or to prevent an
accident from damaging DVP-SLIM, the control cabinet in which DVP-SLIM is installed should be equipped with
a safeguard. For example, the control cabinet in which DVP-SLIM is installed can be unlocked with a special tool
or key.
EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring
again before DVP-SLIM is powered up. After DVP-SLIM is disconnected, Do NOT touch any terminals in a
minute. Make sure that the ground terminal on DVP-SLIM is correctly grounded in order to prevent
electromagnetic interference.
FR DVP-SLIM est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.)
saine, dépourvue de poussière, d’humidité, de vibrations et hors d’atteinte des chocs électriques. La protection
doit éviter que les personnes non habilitées à la maintenance puissent accéder à l’appareil (par exemple, une clé
ou un outil doivent être nécessaire pour ouvrir a protection).
FR Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil DVP-SLIM pourra être
endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du DVP-SLIM. Lors de la
déconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien
reliée au connecteur de terre afin d’éviter toute interférence électromagnétique.
Introduction
Thank you for choosing Delta DVP-Slim series programmable logic controller. DVP-Slim digital I/O extension unit offers 6
~ 16 points, and the maximum digital I/O extension points (including the MPU) can reach 256 points. In addition,
maximum 8 additional special modules (AD/DA/PT/TC/XA/PU) can be extended to DVP-Slim series extension unit.
Product Profile & Outline
3.00
3.00
60 60
25.20 25.20
4
P OWE R P OWE R
3 3
L. V L. V
8 8
1 1
●
4
●
●
90.00
90.00
9 9
10 10
DVP-
DVP-
2 2
●
3 7 3 7
3.00
3.00
5 6 8 5 6 8
Model Information
Power Input Output
Model name Dimension (mm) Outline
supply Points Type Points Type
DVP08SP11R 4 4
Relay
DVP16SP11R 8 8
DVP08SP11T 4 DC Type 4 Transistor
DVP16SP11T 24VDC 8 Sink/Source 8 (Sink) 25.2 90 60
DVP08SP11TS 4 4
Transistor (Source)
DVP16SP11TS 8 8
DVP08SM10N 8 100 ~ 120VAC 0 N/A
Power Input Output
Model name Dimension (mm) Outline
supply Points Type Points Type
DVP08SM11N 8 DC Type 0
DVP16SM11N 16 Sink/Source 0
DVP06SN11R 0 6
Relay
DVP08SN11R 0 8
DVP08SN11T 0 8 Transistor
N/A
DVP16SN11T 0 16 (Sink)
DVP08SN11TS 0 8
Transistor (Source)
DVP16SN11TS 0 16
Specifications
Electrical Specifications
Model 08SM11N 08SN11R/T 08SP11R/T 16SN11T
16SM11N 16SP11R/T 16SP11TS 06SN11R
Item 08SM10N /TS /TS /TS
Power supply voltage 24VDC (-15%~20%) (with DC input polarity reverse protection)
Motion specification Within 5ms of the momentary power loss, the device will keep on operating
Power consumption 1W 2W 1.5W 1.5W 2W 2W 1.5W 1W
Insulation resistance > 5MΩ (all I/O point-to-ground: 500VDC)
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Noise immunity Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
The diameter of grounding wire shall not be less than that of L, N terminal of the power. When many PLCs
Earth
are in use at the same time, please make sure every PLC is properly grounded.
Operation / storage Operation: 0°C ~ 55°C (temperature), 5% ~ 95% (humidity), pollution degree 2
environment Storage: -25°C ~ 70°C (temperature), 5% ~ 95%(humidity)
Shock / vibration
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27 (TEST Ea)
immunity
Weight (g) 162 / 141 146 154 / 146 141 / 136 162 / 154 151 200 70
Operation(X103 )
Operation(X10 )
500
3
24VDC t=7ms
200
300
200
100
100
30VDC
50 Inductive 50
(t=40ms ) 24VDC t=15ms
30
20
0.1 0.2 0.3 0.5 0.7 1 1.5 0 2 4 6
[ Figure 1 ]
Contact Current(A) Contact Current (A) [ Figure 2 ]
C3 ZP 0 UP 1
S /S Y1 0 Y0 Y10
Y3
X1 0
X1 1
X1 2
. C4
Y1 1
Y1 2
Y1 3
Y1
Y2
Y3
Y11
Y12
Y13
Y4
.
X1 3 Y4 Y14
Y1 4
X1 4 Y5 Y15
C5 Y1 5
X1 5 Y6 Y16
Y5 Y1 6
X1 6
X1 7 . Y1 7
ZP 1
Y7
ZP
Y17
ZP
08SP11R
16SP11R 08SP11TS 16SP11TS
08SP11T
S /S S /S
S /S S /S X0
X0
X0 X0
X1 X1
X1 X1 X2 X2
X2 X2 X3
X3
.
X3 X3
X4 .
.
X4
.
.
X5
.
X5
X6
.
X6
X7 .UP
X7
UP
C0 C0 Y0 Y0
Y0 Y0 Y1 Y1
C1 Y1 Y2 Y2
Y1 Y2 Y3
.
Y3
C2 Y3
.
Y4
Y2 Y4
C3
Y3
Y5
Y6
.
.
Y5
Y6
. Y7 ZP
Y7
ZP
Connection
Step 2 Lift the fixing clip by the screwdriver.
Step 1 Screw open the side cover of the extension unit,
and you will see the connection port.
[ Figure 3 ]
[ Figure 4 ]
Step 3 Adjust the positioning hole of the MPU and the Step 4 Fasten the fixing clip on the extension unit to
extension unit. Meet the connection port on the MPU with complete the connection.
the extension unit to tightly connect the two.
[ Figure 5 ] [ Figure 6 ]
Notes
DO NOT install PLC in an environment with
Dust, smoke, metallic debris, corrosive or flammable gas
High temperature, humidity
Direct shock and vibration
During the engineering
1. DO NOT drop tiny metallic conductor into the PLC when screwing and wiring.
2. There should be a margin of more than 50mm between the PLC and other control devices, and the PLC should be
placed away from high voltage wire and power equipment.
Arrangement of I/O Points
No matter the MPU with how many points you are using, the input point No. of the first connected extension unit has to
start from X20 and output point No. from Y20. The MPU is able to connect to maximum 14 digital extension units. The
connection of MPU and extension units is demonstrated in the figure below.
Input Output
PLC Model Input point No. Output point No.
points points
MPU SS/SA/SX/SC 8 4/6 X0 ~ X7, X10, X11 Y0 ~ Y5, X10, X11
EXT1 16SP11T 8 8 X20 ~ X27 Y20 ~ Y27
EXT2 08SM11N 8 0 X30 ~ X37 -
MPU EXT1 EXT2 EXT3 EXT4
EXT3 06SN11R 0 6 - Y30 ~ Y35
EXT4 08SP11R 4 4 X40 ~ X43 Y40 ~ Y43
The 3rd extension module 06SN11R will be regarded as 8-point output. The 2 output points of bigger No. will have no
actual corresponding output points.
The 4th extension module 08SP11R will be regarded as 8-point input/8-point output. The 4 input points and 4 output
points of bigger No. will have no actual corresponding input/output points. Therefore, it is suggested that they placed in
the end of the series connection to make the No. of I/I points continuous.
AC Wiring:
Wiring Loop 110VAC Input Specification
Input voltage 85 ~ 132VAC, 50 ~ 60Hz
85~132VAC Input resistance 19Kohm/50Hz, 16Kohm/60Hz
50/60Hz Prox.
Sensor Input current 9.2mA 110VAC/60Hz
On/Off voltage level 79V 3.8mA/30V 2.5mA
COM X0 X1 X2
Response time 15ms
DVP08SM10N
Circuit isolation/operation instruction By photocoupler / LED On
Relay Output Wiring Circuit (Sink):
DO NOT wire empty terminal
Fuse
C0 Y0 C1 Y1 C2 Y2 Y3 Y4 Y5
1 Reverse current protection diode*1
MC2 MC1
5 2 8
2 Manual exclusive output*2
9 3 7 Emergency stop: by external switch
MC1 MC2 7
5 4
6 Surge absorber*3
Inductive load
10 [ Figure 9 ] Incandescent light (resistive load)
DC power supply
AC power supply
*1: There is no internal protection circuit in the output relay of the PLC; therefore when activating an inductive load,
we suggest you parallely connect a reverse current protection diode to extend the life of the contact.
- The diode has to be able to endure max. 5 ~ 10 times of load voltage.
- The positive current of the diode has to be bigger than load current.
*2: Manual exclusive output uses external circuit and forms an interlock, together with the PLC internal program, to ensure
safety protection in case of any unexpected errors.
*3: There is no internal protection circuit in the output relay of the PLC; therefore when activating an inductive load, we
suggest you parallely connect a surge absorber (0.1uF + “100ohm to 120ohm”) to reduce the noise on AC load and
extend the life of the contact.
Transistor Output Wiring Circuit (Sink):
DO NOT wire empty terminal
C0 Y0 C1 Y1 C2 Y2 Y3 Y4 Y5
MC2 MC1 1 Emergency stop
5 7 8 6 Fuse
MC1 MC2
3 6
4
9 Manual exclusive output*1
2
3
[ Figure 10 ]
DC power supply
5
MC1 MC2 Inductive load
2 6
3 4
9
3
Resistive load
[ Figure 11 ]
Y1, Y3 (refer to other wiring methods)
*1: Manual exclusive output uses external circuit and forms an interlock, together with the PLC internal program, to
ensure safety protection in case of any unexpected errors.
*2: Use a zener diode (39V) in the PLC to protect the transistor output. When activating inductive load, we sugget you
parallely connect a reverse current protection diode.
Transistor Output Wiring Loop (Source):
Y6, Y7 (refer to other wiring methods)
Emergency stop
ZP Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0 UP
MC2
Fuse
MC1
1 6
Manual exclusive output*1
7
MC1 MC2
6
DC power supply
3 8 4
9 Incandescent light (resistive load)
2
5
3 Reverse current protection diode*2
[ Figure 12 ]
Inductive load
Resistive load
*1: Manual exclusive output uses external circuit and forms an interlock, together with the PLC internal program, to
ensure safety protection in case of any unexpected errors.
*2: Use a zener diode (39V) in the PLC to protect the transistor output. When activating inductive load, we sugget you
parallely connect a reverse current protection diode.
注意事項 繁體中文
請在使用之前,詳細閱讀本使用說明書。
本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊意外之外
殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外衝擊本體,造成危險
及損壞。
交流輸入電源不可連接於直流類型之輸入/出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。
請勿在上電時觸摸任何端子。
產品簡介
謝謝您採用台達 DVP-SLIM 系列可程式控制器。DVP-SLIM 系列 6 ~ 16 點擴充,含主機最大數位輸入/輸出擴充分別可達
256 點。另備特殊模組(AD/DA/PT/TC/XA/PU)擴充功能,最多可擴充 8 台特殊模組。
產品外觀及各部介紹
3.00
3.00
60 60
25.20 25.20
4
P OWE R P OWE R
3 3
L. V L. V
8 8
1 1
●
4
●
●
90.00
90.00
EXTENS ION EXTENS ION
PORT PORT
9 9
10 10
DVP-
DVP-
2 2
●
3 7 3 3.00 7
3.00
5 6 8 5 6 8
電源、低電壓指示燈 擴充機定位孔
機種名稱 銘牌
擴充機固定扣 擴充機固定扣
輸出/入端子 DIN 軌槽 (35mm)
DIN 軌固定扣 擴充機連接口
機種型號
輸入單元 輸出單元
機種 電源 尺寸 (mm) 外形參考
點數 形式 點數 形 式
DVP08SP11R 4 4
繼電器
DVP16SP11R 8 8
DVP08SP11T 4 DC Type 4
電晶體(Sink)
DVP16SP11T 8 Sink/Source 8
DVP08SP11TS 4 4
電晶體(Source)
DVP16SP11TS 8 8
DVP08SM10N 8 100 ~ 120VAC 0
24VDC 25.2 90 60
DVP08SM11N 8 DC Type 0 無
DVP16SM11N 16 Sink/Source 0
DVP06SN11R 0 6
繼電器
DVP08SN11R 0 8
DVP08SN11T 0 無 8
電晶體(Sink)
DVP16SN11T 0 16
DVP08SN11TS 0 8 電晶體(Source)
輸入單元 輸出單元
機種 電源 尺寸 (mm) 外形參考
點數 形式 點數 形 式
DVP16SN11TS 0 16
功能規格
電氣規格
機種 08SM11N 08SN11R/T 08SP11R/T 16SN11T
16SM11N 16SP11R/T 16SP11TS 06SN11R
項目 08SM10N /TS /TS /TS
輸入點規格
輸入點電氣規格
輸入點形式 直流 交流
輸入形式 直流(Sink 或 Source) -
輸入阻抗 - 19Kohm/50Hz 16Kohm/60Hz
85~132VAC 50~60Hz
輸入電壓電流 24VDC 5mA
9.2mA 110VAC/60Hz
Off → On:16.5VDC 以上 79VAC 以上
動作位準
On → Off:8VDC 以下 30VAC 以下
Off On < 15ms
反應時間 約 10ms
On Off < 20ms
電路隔離/操作
光耦合器 / LED On
指示
輸出點電氣規格
輸出點形式 繼電器-R 繼電器-R (*1) 電晶體-T (Sink) 電晶體-T (Source)
55°C 0.1A/1 點、
50°C 0.15A/1 點、
電流規格 1.5A/1 點 (5A/COM) 6A/1 point 55°C 0.3A/1 點 (2A/COM)
45°C 0.2A/1 點、
40°C 0.3A/1 點 (2A/COM)
電壓規格 250VAC, 30VDC 以下 250VAC, 30VDC 以下 30VDC 30VDC
最大負載 *2 *3 9W 9W
Off → On 15us Off → On 15us
反應時間 約 10ms 約 10ms
On → Off 25us On → Off 25us
*1: 僅適用於 06SN11R 機種
*2: 請參閱英文版[Figure 1]
*3: 請參閱英文版[Figure 2]
安裝及配線
數位 I/O 擴充機之端子配置圖
請參考英文版之端子配置圖。
系統組合
步驟 1 利用螺絲起子將擴充側蓋打開,會出現擴充機連接口。(請參閱英文版[Figure 3])
步驟 2 再利用螺絲起子將擴充機固定扣往上撥。(請參閱英文版[Figure 4])
步驟 3 調整好主機和擴充機的定位孔,並且將主機的擴充機連接口與擴充機接合,此時主機與擴充機之間緊密結合。(請參
閱英文版[Figure 5])
步驟 4 將擴充機固定扣往下扣住,完成與主機之系統組合。(請參閱英文版[Figure 6])
盤內安裝及配線
DVP 系列 PLC 在安裝時,請裝配於封閉式之控制箱內,其周圍應保持一定之空間(如下圖所示),以確保 PLC 散熱功能正
常。
DIN 鋁軌之安裝方法
適合 35mm 之 DIN 鋁軌,主機欲掛於鋁軌時,先將主機(或擴充機)下方之固定塑膠片壓
入,再將主機(或擴充機)由上方掛上再往下壓即可。欲取下主機時,主機背面下之固定
塑膠片,以一字形起子插入凹槽,向上撐開即可,該固定機構塑膠片為保持型,因此該固
定片撐開後便不會彈回去,當所有的固定片撐開後,再將主機往上外方取出。
22-16AWG 配線
1. 輸出/入配線端請使用 22-16AWG (1.5mm) 單蕊祼線或多蕊線,端子規格如左所示。
PLC 端子螺絲扭力為 1.95 kg-cm (1.7 in-lbs)。只能使用 60/75°C 的銅導線。
< 1.5mm
2. 輸入點信號線與輸出點等動力線請勿置於同一線槽內或使用同一多芯之電纜線。
注意事項
請勿將 PLC 裝置於
落塵大、油煙、金屬性粉塵及腐蝕性或可燃性氣體的環境
高溫、結露的環境
有直接振動及衝擊的場所
施工注意
1. 鎖螺絲及配線時請避免微小的金屬導體掉入 PLC 內部。
2. PLC 與其它之控制元件應保持 50mm 以上之間隔,並應遠離高壓線及動力設備。
輸出入點序號排列
無論使用任何點數的主機連接擴充機,所連接的第一台擴充機,輸入點編號由 X20 依序排列,輸出點編號亦由 Y20 開始依
序排列,主機連接數位擴充機最多可連接 14 台,若使用者所連接的系統如下:
系統組合範例:
輸入端配線及規格
輸入點之入力信號共有兩種:為直流電源 DC 輸入及交流電源 AC 輸入。
DC 型式共有兩種接法,SINK (請參閱英文版[Figure 7])及 SOURCE (請參閱英文版[Figure 8])。
AC 型式配線
配線回路 110VAC 輸入規格
輸入電壓 85 ~ 132VAC, 50 ~ 60Hz
電感性負載 電阻性負載 ○
10 Y1,Y3 可參考其它配線方式
请在使用之前,详细阅读本使用说明书。
本机为开放型 (OPEN TYPE) 机壳,因此使用者使用本机时,必须将其安装于具防尘、防潮及免于电击/冲击意外的外
壳配线箱内。另必须具备保护措施(如:特殊的工具或钥匙才可打开)防止非维护人员操作或意外冲击本体,造成危险
及损坏。
交流输入电源不可连接于直流类型的输入/出信号端,否则可能造成严重的损坏,因此请在上电之前再次确认电源配线。
请勿在上电时触摸任何端子。
产品简介
谢谢您采用台达 DVP-SLIM 系列可编程控制器。DVP-SLIM 系列 6 ~ 16 点扩展,含主机最大数字输入/输出扩展分别可达
256 点。另备特殊模块(AD/DA/PT/TC/XA/PU) 扩展功能,最多可扩展 8 台特殊模块。
产品外观及各部介绍
3.00
3.00
60 60
25.20 25.20
4
P OWE R P OWE R
3 3
L. V L. V
8 8
1 1
●
4
●
●
90.00
90.00
EXTENS ION EXTENS ION
PORT PORT
9 9
10 10
DVP-
DVP-
2 2
●
3 7 3 3.00 7
3.00
5 6 8 5 6 8
电源、低电压指示灯 扩展机定位孔
机种名称 铭牌
扩展机固定扣 扩展机固定扣
输出/入端子 DIN 轨槽 (35mm)
DIN 轨固定扣 扩展机连接口
机种型号
输入单元 输出单元 尺寸
机种 电源 外形参考
点数 形式 点数 形 式 mm
DVP08SP11R 4 4
继电器
DVP16SP11R 8 8
DVP08SP11T 4 DC Type 4 晶体管
DVP16SP11T 8 Sink/Source 8 (Sink)
DVP08SP11TS 4 4
晶体管(Source)
DVP16SP11TS 8 8
DVP08SM10N 8 100 ~ 120VAC 0
24VDC 25.2 90 60
DVP08SM11N 8 DC Type 0 无
DVP16SM11N 16 Sink/Source 0
DVP06SN11R 0 6
继电器
DVP08SN11R 0 8
DVP08SN11T 0 无 8
晶体管(Sink)
DVP16SN11T 0 16
DVP08SN11TS 0 8 晶体管(Source)
输入单元 输出单元 尺寸
机种 电源 外形参考
点数 形式 点数 形 式 mm
DVP16SN11TS 0 16
功能规格
电气规格
机 种 08SM11N 08SN11R/T 08SP11R/T 16SN11T
16SM11N 16SP11R/T 16SP11TS 06SN11R
项 目 08SM10N /TS /TS /TS
输入点规格
输入点电气规格
输入点形式 直流 交流
输入形式 直 流 (SINK 或 SOURCE) -
输入阻抗 - 19Kohm/50Hz 16Kohm/60Hz
85~132VAC 50~60Hz
输入电压电流 24VDC 5mA
9.2mA 110VAC/60Hz
Off → On:16.5VDC 以上 79VAC 以上
动作位准
On → Off:8VDC 以下 30VAC 以下
Off On < 15ms
反应时间 约 10ms
On Off < 20ms
电路隔离 / 操作指示 光耦合器 / LED On
输出点电气规格
输出点形式 继电器-R 继电器-R (*1) 晶体管-T (Sink) 晶体管-T (Source)
55°C 0.1A/1 点、
50°C 0.15A/1 点、
电流规格 1.5A/1 点 (5A/COM) 6A/1 point 55°C 0.3A/1 点 (2A/COM)
45°C 0.2A/1 点、
40°C 0.3A/1 点 (2A/COM)
电压规格 250VAC, 30VDC 以下 250VAC, 30VDC 以下 30VDC 30VDC
最大负载 *2 *3 9W 9W
*3: 请参考英文版[Figure 2]
安装及配线
数字 I/O 扩展机的端子配置图
请参考英文版之端子配置图。
系统组合
步骤 1 利用螺丝起子将扩展侧盖打开,会出现扩展机连接口。(请参考英文版[Figure 3])
步骤 2 再利用螺丝起子将扩展机固定扣往上拨。(请参考英文版[Figure 4])
步骤 3 调整好主机和扩展机的定位孔,并且将主机的扩展机连接口与扩充机接合,此时主机与扩展机之间紧密结合。(请参
考英文版[Figure 5])
步骤 4 将扩展机固定扣往下扣住,完成与主机之系统组合。(请参考英文版[Figure 6])
盘内安装及配线
DVP 系列 PLC 在安装时,请装配于封闭式的控制箱内,其周围应保持一定的空间(如下图所示)
,以确保 PLC 正常散热。
DIN 铝轨的安装方法
适合 35mm 的 DIN 铝轨,主机欲挂于铝轨时,先将主机(或扩展机)下方的固定塑胶片
压入,再将主机(或扩展机)由上方挂上再往下压即可。欲取下主机时,主机背面下的
固定塑胶片,以一字形起子插入凹槽,向上撑开即可,该固定机构塑胶片为保持型,因
此该固定片撑开后便不会弹回去,当所有的固定片撑开后,再将主机往上外方取出。
22-16AWG
配线
1. 输出/入配线端请使用 22-16AWG (1.5mm) 单蕊祼线或多蕊线,端子规格如左所示。
PLC 端子螺丝扭力为 1.95 kg-cm (1.7 in-lbs)。只能使用 60/75°C 的铜导线。
< 1.5mm 2. 输入点信号线与输出点等动力线请勿置于同一线槽内或使用同一多芯的电缆线。
注意事项
请勿将 PLC 装置于
落尘大、油烟、金属性粉尘及腐蚀性或可燃性气体的环境
高温、结露的环境
有直接振动及冲击的场所
施工注意
1. 锁螺丝及配线时请避免微小的金属导体掉入 PLC 内部。
2. PLC 与其它的控制元件应保持 50mm 以上的间隔,并应远离高压线及动力设备。
输出入点序号排列
无论使用任何点数的主机连接扩展机,所连接的第一台扩展机,输入点编号由 X20 依序排列,输出点编号亦由 Y20 开始依
序排列,主机连接数字扩展机最多可连接 14 台,若使用者所连接的系统如下:
系统组合范例:
PLC 机种 输入点数 输出点数 输入点编号 输出点编号
MPU SS/SA/SX/SC 8 4/6 X0~X7, X10, X11 Y0~Y5, X10, X11
EXT1 16SP11T 8 8 X20~X27 Y20~Y27
MPU EXT1 EXT2 EXT3 EXT4 EXT2 08SM11N 8 0 X30~X37 -
EXT3 06SN11R 0 6 - Y30~Y35
EXT4 08SP11R 4 4 X40~X43 Y40~Y43
输入端配线及规格
输入点的入力信号共有两种:为直流电源 DC 输入及交流电源 AC 输入。
DC 型式共有两种接法,SINK(请参考英文版[Figure 7])及 SOURCE(请参考英文版[Figure 8])。
AC 型式配线
配线回路 110VAC 输入规格
输入电压 85 ~ 132VAC, 50 ~ 60Hz