STRUCTURAL SPECIFICATIONS AND STANDARD DETAILS

1.0 GENERAL 4.0 STRUCTURAL STEEL 8.4. GENERALLY, NO SPLICE SHALL BE PERMITTED ON BEAMS AT POINTS WHERE CRITICAL BENDING STRESSES
OCCUR. LENGTH OF LAP SPLICE, WHERE PERMITTED, SHALL BE AS SHOWN ON TABLE "A" AND "B".
9.5. PROVIDE EXTRA REINFORCEMENT AT CORNER SLAB (TWO ADJACENT DISCONTINUOUS EDGE) AS SHOWN
BELOW.
1.1. MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF THE FOLLOWING 4.1. ALL STRUCTURAL MILL SECTIONS, BUILT UP PLATE SECTIONS SHALL BE DESIGNED IN ACCORDANCE WITH WELDED SPLICES SHALL DEVELOP IN TENSION AT LEAST 125% OF THE SPECIFIED YIELD STRENGTH OF
REFERENCES: AISC'S LATEST "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL THE BAR. NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION SHALL BE ALLOWED TO BE
FOR BUILDINGS." SPLICED THEREIN.
1.1.1. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES 2010, 6TH EDITION MAX. COL. DIMENSIONS
OR 1/6 h WHICH EVER IS
ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES 4.2. DESIGN LOADS FOR BUILDINGS SHALL MEET THE REQUIRED STRUCTURAL DESIGN CRITERIA. GREATER BUT NO LESS 5-10mmØ BARS AT 0.208m.
THAN 0.60m. O.C. BOTTOM BARS

1.1.2. ASEP STEEL HANDBOOK 2004, 3RD EDITION 4.3. STEEL PLATES, SHAPES, BARS AND METAL FABRICATION: ASTM A-36.
ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES 10mm Ø TIES, 5-10mmØ BARS AT 0.914m.
4@ 50mm REST LONG AT 0.208m. O.C.
4.4. STRUCTURAL BOLTS AND NUTS:
@ 100mm. O.C.

0.05

0.05
1.2. IN THE INTERPRETATION OF THE DRAWINGS, INDICATED DIMENSIONS SHALL GOVERN AND DISTANCES OR ASTM A-325M-00, 20mmØ AND BELOW
SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. ASTM A-490M-00, 25mmØ AND ABOVE

1.3. THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECTURAL, ELECTRICAL, MECHANICAL, PLUMBING, 4.5. ELECTRODES FOR WELDING: ASTM A233 E_70XX SERIES; COMPLY WITH AWS D1.1 CODE REQUIREMENTS. 10mm Ø TIES@ 100mm. O.C.

0.05

0.05
SANITARY AND OTHER UTILITY AND EQUIPMENT PLANS FOR THE EXACT SIZE AND LOCATION OF
HOLES THRU FLOOR SLABS AND WALLS. 4.6. FLAME CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITHTHE LATEST "STANDARD CODE FOR
WELDING IN BUILDING CONSTRUCTION" OF THE AMERICAN WELDING SOCIETY.

2.0 CONCRETE 4.7. ALL BUTT WELDS SHALL BE FULL PENETRATION WELDS AND SHALL BE PROPERLY BACK-CHIPPEDOR GOUGED. 10mm Ø TIES,
4@ 50mm REST
9.6. PROVIDE SUPPLEMENTARY REINFORCEMENT AT SMALL UNFRAMED OPENINGS IN FLOOR SLABS AS SHOWN

2.1. ALL CONCRETE MUST BE DEPOSITED, VIBRATED AND CURED IN ACCORDANCE WITH THE LATEST EDITION OF BACK-UP PLATES SHALL BE PROVIDED AS REQUIRED. BELOW.
@ 100mm. O.C.
AMERICAN CONCRETE INSTITUTE (ACI-318-05). TRIMMER MAYBE
4.8. SHOP PAINTING FOR STRUCTURAL STEEL SHALL BE RUST INHIBITIVE PRIMER WITH MINIMUM D.F.T. OF 2.0 MILS.. h = HEIGHT BETWEEN FLOORS OMITTED WHERE
OPENING IS FRAMED
2.2. UNLESS OTHERWISE SPECIFIED, THE MINIMUM 28 - DAYS CYLINDER COMPRESSIVE STRENGTH ARE AS
4.9. TOUCH-UP PAINTING: APPLY PAINT TO EXPOSED AREAS IN MANNER SATISFACTORY TO THE ENGINEER WITH
TYP. TIED COLUMN SPLICE DETAIL BY BEAM
FOLLOWS:
FOOTINGS 20.7 MPa (3,000 PSI) SAME MATERIAL AS SHOP PAINT.
PROPOSED PIPE SLEEVE LOCATIONS
COLUMNS 20.7 MPa (3,000 PSI) 2d (NO PIPE SLEEVE SHALL BE SCH. 40 G.I. PIPE SLEEVE
ALLOWED W/IN THIS ZONE (TYP.))
SUSPENDED SLABS, BEAMS & GIRDERS 20.7 MPa (3,000 PSI) 4.10. COMPLY WITH AISC CODE AND SPECIFICATIONS FOR BEARING, ADEQUACY OF TEMPORARY 2 - EXTRA STIR. EA. SIDE
0 OF SLEEVE
ELEVATOR & STAIRWELL CORES AND R.C. WALLS 20.7 MPa (3,000 PSI) CONNECTIONS AND ALIGNMENT. 2d 50 P. 2d
TY MIN. 1-16mmØ TOP
PARTITIONS AND PARAPET WALLS 20.7 MPa (3,000 PSI) AND BOTTOM FOR
4.11. ALL TRUSSES MUST BE PROVIDED WITH CAMBER AT THE RATE OF 3mm FOR EVERY 3000mm (UNLESS TOP BARS FACE OF SLABS 0.012m. THICK
BEDDED SLABS, CATCH BASINS & SIDEWALK 17.2 MPa (2,500 PSI) SUPPORT AND OVER
OTHERWISE SPECIFIED) EFFECTED BY MEANS OF A PARABOLIC LAYOUT.
2.3. STRIPPING FORMS AND SHORES SHALL BE AS FOLLOWS :

d/5
4.12. CONTRACTOR SHALL FURNISH COMPLETE ERECTION DRAWINGS FOR THE PROPER IDENTIFICATION AND

40 CLR.
FOUNDATIONS 1 Day

MIN.
COLUMNS AND WALLS 7 Days ASSEMBLY OF ALL BUILDING COMPONENTS. THESE DRAWINGS WILL SHOW ANCHOR BOLT SETTING, HOOK SLAB REINF.
Ø 16 EXTRA BARS E.F. OVER TRIMMER BAR
BEAMS AND GIRDERS 14 Days PRIMARY AND SECONDARY ROOF FRAMING, AND NECESSARY INSTALLATION DETAILS. SUBMIT BOT. BARS (TYPICAL)
SUSPENDED SLABS 14 Days SHOP DRAWINGS FOR APPROVAL BEFORE FABRICATION. FACE OF 4d(minimum) STIR. AS SCHED. OPENING
SUPPORT
2.4. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, RE-HANDLING OR LIMIT LOCATION OF PIPE SLEEVE
L/4 L/2 L/4
FLOWING, PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKET OR WHEEL BARROWS. NO
CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONC. FROM HOPPERS TO BUGGIES, WHEEL
5.0. FORMWORKS L 2 - EXTRA STIR. EA.
SIDE OF SLEEVE
BARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED SIX METERS (20 ft.) IN AGGREGATE 5.1. FORMS SHALL BE PROVIDED FOR ALL CONCRETE INDICATED UNLESS SPECIFIES OTHERWISE. FORMS SHALL BE
NOTES: TOP BARS
LENGTH. SET TRUE TO LINE AND GRADE AND MAINTAINED SO AS TO INSURE COMPLETED WORK WITHIN THE
1. MAXIMUM PIPE SLEEVE DIAMETER:
ALLOWABLE TOLERANCES SPECIFIED AND SHALL BE MORTAR TIGHT. Ø 16 EXTRA BARS
A. 51 OF BEAM DEPTH. E.F. (DIAGONALS) 2-16mmØ AT EACH
2.5. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS AUTHORIZED IN B. 100 mm CORNER
5.2. FORMS AND THEIR SUPPORTS SHALL BE DESIGNED SO AS NOT TO DAMAGE PREVIOUSLY PLACED 2. SEEK STRUCTURAL ENGINEER'S APPROVAL FOR PIPE SLEEVES PIPE SLEEVE
WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS WHERE VIBRATIONS IS

d/5
BIGGER THAN THE MAXIMUM STIPULATED. EXTEND TRIMMER BAR
EXTREMELY DIFFICULT TO ACCOMPLISH. STRUCTURE.
Ø 16 CROSS ANCHORS 0.61-0.15m. BEYOND SIDE
3. PIPE SLEEVES SHALL BE LOCATED W/IN TENSION ZONES. WELDED TO SLEEVE OF OPENING OR AS FAR
5.3. NO CONSTRUCTION LOAD SHALL BE SUPPORTED ON, NOR ANY SHORING REMOVED FROM ANY PART OF AS POSSIBLE & HOOK
3.0 REINFORCING BARS STRUCTURE UNDER CONSTRUCTION EXCEPT WHEN THAT PORTION OF THE STRUCTURE IN
4. NO PIPE SLEEVE SHALL BE ALLOWED AT TWICE THE BEAM
DEPTH (2d) FROM THE SUPPORT. b
BOT. BARS
PROVIDE EXTRA BARS
3.1. REINFORCING BARS SHALL BE DEFORMED (CONFORMING WITH ASTM A615 - STAMDARD SPECIFICATION COMBINATION WITH THE REMAINING FORMING AND SHORING SYSTEM HAS SUFFICIENT STRENGTH (NOT SHOWN) PARALLEL

FOR DEFORMED AND PLAIN CARBON STEEL BARS FOR CONCRETE REINFORCEMENT) AND GRADED TO SUPPORT SAFELY ITS WEIGHT AND THE ADDITIONAL IMPOSED LOADS. PIPE SLEEVE THRU BEAM DETAIL TO SIDE OF EQUAL AREA
OF INTERRUPTED SLAB
AS FOLLOWS: REINFORCEMENT LESS
5.4. FORMS SHALL BE REMOVED IN SUCH MANNER AS NOT TO IMPAIR SAFETY AND SERVICEABILITY OF THE AREA TRIMMER BARS
STRENGTH
GRADE 60 ( fy = 414 MPa )
FOR COLUMN REINFORCEMENT
28 Ø
FOR ALL OTHER MEMBERS
28 Ø and Larger Bars
STRUCTURE. 9.0 CONCRETE SLAB
GRADE 40 ( fy = 275 MPa ) 12 Ø to 25Ø 12 Ø to 25Ø 9.1. ALL REINFORCEMENT SHALL BE 20MM CLEAR MINIMUM FROM TOP AND BOTTOM OF SLAB.
30 BAR DIA. 30 BAR DIA.
GRADE 33 ( fy = 230 MPa ) 10 Ø 10 Ø
6.0 FOUNDATION 9.2. FOR TWO-WAY SLAB, REINFORCEMENT ALONG THE SHORTER SPAN SHALL BE PLACE BELOW THOSE ALONG
(min.) (min.)

VERIFY DEPRESSION
D=FOR BEAM
3.2. BARS SHALL BE CLEAN OF RUST, GREASE OR OTHER MATERIALS LIKELY TO IMPAIR BOND. ALL REINFORCING 6.1. THE FOUNDATION IS DESIGNED FOR AN ALLOWABLE SOIL BEARING CAPACITY OF _______ kPa (______ ksf). THE LONGER SPAN AT CENTER AND OVER THE LONGER SPAN BARS NEAR THE SUPPORT UNLESS

t=FOR SLAB
BAR BENDS SHALL BE MADE COLD. REINFORCING STEEL OF DIFFERENT GRADES SHALL BE CLEARLY OTHERWISE INDICATED OR SHOWN IN DETAILS THE SPACING OF THE BARS AT THE COLUMN STRIPS
MARKED TO DIFFERENTIATE THEM ON SITE. 6.2. THE CONTRACTOR SHALL REPORT IN WRITING TO THE DESIGNER THE ACTUAL SOIL CONDITION UNCOVERED CAN BE APPROXIMATELY 1-1/2 OF THE MIDDLE STRIP IN NO CASE GREATER THAN 2 TIMES THE SLAB
AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE. THICKNESS.
3.3. IN GENERAL, BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. SPLICES SHALL BE SECURELY
WIRED TOGETHER. STAGGER SPLICES AT LEAST 6OO MM. WHENEVER POSSIBLE IN BEAMS AND SLABS 6.3. NO FOOTING SHALL REST ON UNCOMPACTED FILL. 9.3. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE TENSION FACE AND SHALL NOT BE D=FOR BEAM
2t=FOR SLAB
SPLICE TOP BARS AT MID-SPAN AND BOTTOM BARS NEAR SUPPORT. SPLICE OF REINFORCEMENT LESS THAN 0.0025 B x T.
SHALL BE MADE ONLY AS REQUIRED OR PERMITTED ON DESIGN DRAWINGS OR AS ALLOWED BY 6.4. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75mm CLEAR FOR CONCRETE 30 BAR DIA.
THE ACI-318 CODE OR AS AUTHORIZED BY THE ENGINEER. DEPOSITED AGAINST THE GROUND AND 50mm FOR CONCRETE DEPOSITED AGAINST FORMWORKS. 9.4. UNLESS OTHERWISE NOTED, ALL BEDDED SLAB SHALL BE REINFORCED WITH 10mmØ BAR AT 250mm O.C.E.W. (min.)

AT CENTER OF SLAB. CONSTRUCTION JOINTS FOR SLAB SHALL NOT BE MORE THAN 3.00m APART.
3.4. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL LAP OR EXTEND IN ACCORDANCE WITH TABLE 6.5. IN CASES WHERE REQUIRED FOOTING LEVELS SHOW HONEYCOMBED STRUCTURE CONTAINING LOOSE SUSPENDED SLAB
A AND TABLE B (TABLE OF LENGTH OF EMBEDMENT AND LAP SPLICE). UNLESS OTHERWISE SHOWN MATERIALS, REMOVE LOOSE MATERIALS AND FILL ALL VOIDS WITH 10.3 MPa (1500 psi)LEAN
24d 24d
ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. CONCRETE. USE VIBRATOR TO ASSURE WELL COMPACTED CONCRETE IN ALL VOID PORTIONS.
300mm(MIN.) 300mm(MIN.)
0.10m(min.) COMPACTED 10mmØ (-)TOP BARS
3.5. MINIMUM CONCRETE COVER FOR REINFORCING BARS SHALL BE:
CONCRETE CAST AGAINST EARTH 75 mm 7.0 CONCRETE COLUMNS GRAVEL FILL
@ 150mm O.C.
EXPOSED TO EARTH OR OF WEATHER 50 mm 7.1. FOR ALL TIED COLUMNS, PROVIDE A MINIMUM OF FOUR (4) SETSOF TIES @ 50mm O.C. FOR COLUMN
SLAB, WALLS AND JOISTS 20 mm REINFORCEMENT JUST ABOVE THE FLOOR, JUST BELOW THE GIRDER AND AT BOTH SIDES OF NOTES: 10mmØ TEMP BARS
BEAMS AND COLUMNS 40 mm CONSTRUCTION JOINTS. FOR DOWELS: @ 300mm O.C.
PROVIDE DOWELS OF SAME SIZE
SHELLS FOLDED PLATE MEMBERS 12 mm AND SPACING AS HORIZONTAL
7.2. COLUMN TIES AND SPIRALS SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST OR BENT HORIZONTAL BARS.

D
3.6. WELDING OF REINFORCING STEEL IS NOT PERMITTED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. MONOLITHICALLY WITH THE CORE WITH A MINIMUM THICKNESS OF 38mm AND NOT LESS THAN 1.5
WELDING OF REINFORCING STEEL SHALL CONFORM TO AWS D1.4-92 "STRUCTURAL WELDING CODE TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE.
- REINFORCING STEEL" OF THE AMERICAN WELDING SOCIETY. REINFORCING STEEL WHICH IS O.80mm THK. STEEL DECK
WELDED SHALL CONFORM TO ASTM A-706 "STANDARD SPECIFICATION FOR LOW-ALLOY STEEL 7.3. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENT SHALL BE OFFSET AT A SLOPE OF NOT MORE Fy = 275 MPa
NOTES:
DEFORMED AND PLAIN BARS FOR CONCRETE REINFORCEMENT". REINFORCING STEEL NOT THAN 1 IN 6 AND AN EXTRA 10mm TIES @ 100mm O.C. SHALL BE PROVIDED THROUGHOUT THE (16D BEND 0.30min.) 1. THE BASE METAL QUALITY FOR METAL FLOOR DECK SHALL BE COLD- ROLLED
CONFORMING TO ASTM A-706 MAY BE USED IF MATERIAL PROPERTIES OF THE REINFORCING STEEL OFFSET REGION. STEEL HAVING A MINIMUM YIELD POINT OF 206 MPa, CONFORMING TO THE
SLAB ON GRADE REQUIREMENTS OF JIS G3141 SPCC-8 AND/OR PNS 127 CLASS 1-8.
CONFORM TO AWS D1.4-92.
24d
8.0 BEAMS & GIRDERS
2. DESIGN STRENGTH OF CONCRETE SHALL BE 20.7 MPA (3000 PSI) COMPRESSIVE
30 BAR DIA. STRENGTH @ 7 DAYS WITH 3/4" AGGREGATE.
3.7. WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A-185-01 "STANDARD SPECIFICATION FOR STEEL
(min.)
WELDED WIRE REINFORCEMENT, PLAIN, FOR CONCRETE". WELDED WIRE FABRIC IN SUSPENDED 8.1. CAMBER ALL BEAMS AND GIRDERS AT LEAST 10 MM FOR EVERY 4.00M OF SPAN. 3. YIELD STRENGTH OF STEEL REINFORCEMENT SHALL BE 230 MPA, CONFORMING TO
ASTM 615M.
SLABS SHALL HAVE FY = 60 KSI., LAP 152 MM. MINIMUM OR ONE FULL MESH, WHICHEVER IS GREATER
FOR SLABS ON GRADE. 8.2. FOR TWO OR MORE LAYERS OF REINFORCING BARS, USE SEPARATORS SPACED AT 900 mm O.C. AND IN SLAB ON METAL DECK
NO CASE SHALL BE LESS THAN TWO (2) SEPARATORS.
3.8. SHOP DRAWINGS : THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR REINFORCING STEEL PREPARED
IN ACCORDANCE WITH ACI 318-05. INDICATE BENDING DIAGRAM, ASSEMBLY DIAGRAM, SPLICING 8.3 WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS ON TOP OF GIRDER BARS. REINFORCING BARS SHALL
AND LAPS OF RODS AND SHAPE DIMENSIONS AND DETAILS FOR REINFORCING BARS. BE SYMMETRICAL ABOUT THE CENTERLINE WHEREVER POSSIBLE AND UPPER BARS SHALL BE PLACED
DIRECTLY ABOVE THOSE IN THE BOTTOM LAYER.
3.9. ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS ARE TO BE SECURELY TIED IN PLACE BEFORE
SLAB - ON - FILL
CONCRETE IS POURED.

R.A. 9266, SECTION 33


JUN ERIC R. BANDOY, UAP OWNERSHIP OF PLANS SPECIFICATIONS
AND OTHER CONTRACT DOCUMENTS
REVISIONS: SHEET CONTENTS: SHEET NO:

JE DESIGN and BUILD Drawings and specifications and other contract documents duly
PROPOSED 4-STOREY RESIDENCE Mr. TITO B. MORALES JR. CHECKED BY:
JUN ERIC R. BANDOY, uap signed, stamped or sealed as instruments of service, are the STRUCTURAL SPECIFICATIONS
404 13TH ST. SILVERIO COMPOUND, PARANAQUE CITY intellectual property and documents of the architect, whether the AND STANDARD DETAILS
DATE:
ARCHITECT object for which they are made is executed or not. It shall be ENGINEER
TEL No. ( 02 ) 8478-8470 CEL No. 0919-3455347
CEL No. PRC REG. No: 32271 PTR No: 40101020
unlawful for any person to duplicate or to make copies of the said
documents for use in the repetition of and for other projects or PRC REG. No: PTR No: LOCATION: ADDRESS: APPROVED BY: S-1
E-mail Address : [email protected] IAPOA: 45107 365369 090722 Issued On: Jan 24, 2023 buildings, whether executed partly or in whole, without the written
Issued On: Lot 246 M. Alvero St. Brgy. 2, Romblon, Romblon Lot 246 M. Alvero St. Brgy. 2,
Issued On: September 07,2022 Issued At: Paranaque City consent of the architect or author of said documents.
TIN No:
Romblon, Romblon DATE:
Issued At: Quezon City TIN No: 228 - 311 - 515 Issued At:

You might also like