GST I-9202 Intelligent Manual Call Point Installation and Operation Manual Issue1 06
GST I-9202 Intelligent Manual Call Point Installation and Operation Manual Issue1 06
Features
Electronically addressed. The address can be
modified in field.
Built-in microprocessor processes messages
intelligently.
Alarming by pressing, reset by a special key.
Providing independent normally open output
contact.
Plug-in structure.
Standard: EN 54-11.
Description
548g/02
Connecting to the loop of GST fire alarm system,
I-9202 Intelligent Manual Call Point (the MCP) is Jut
Short Groove
suitable for public places. When there is a fire,
pressing the glass on this MCP can send fire signal to
fire alarm control panel. After receiving the signal, the
control panel will show address information about the
MCP and generate alarm sound.
Connection and Wiring
Terminals on the MCP base are shown as Fig. 1.
62
Screw Hole
Fig. 2
Application
The MCP should be programmed using P-9910B
programmer. Please refer to P-9910B Hand Held
K1 K2 Z1 Z2
Programmer Installation and Operation Manual. Z1,
Z2 in Fig. 3 are pins connecting with the MCP loop for
programming.
Z1
Fig. 1
Z1, Z2: Connecting with loop of the control panel,
polarity-insensitive.
K1, K2: Volt-free normally open terminals. Z2
Others are spare terminals.
Recommended Wiring
0.5mm2 or above fire cable, subject to local codes.
Installation
Hook the juts of the MCP body to the base, and then
press the part below the glass to combine them
Fig. 3
completely. Finally fasten the MCP with tapping
Terminal Z1 and Z2 of MCP base can directly
screws (ST2.9×9.5) .
connect to the loop of control panel. After correct
Note the upward arrow for the mounting direction connection, the control panel should be able to
(Fig.1). register the MCP.
Limited Warranty
GST warrants that the product will be free from defects
in design, materials and workmanship during the
Fig. 4 warranty period. This warranty shall not apply to any
Compatible Equipment product that is found to have been improperly installed
This MCP can be used together with control panels or used in any way not in accordance with the
such as GST100, GST200, GST5000 and GST9000. instructions supplied with the product. Anybody,
Specifications including the agents, distributors or employees, is not
in the position to amend the contents of this warranty.
Operating Voltage 24VDC Please contact your local distributor for products not
Standby Current ≤0.8mA covered by this warranty.
Alarm Current ≤2mA
Red. Flashes every 3s in
Alarm LED polling, and quickly flashes
after alarming.
Normally Open Rated value:60VDC/0.1A
Output Contact Contact resistance≤100mΩ
Type of Initiating Part Reusable
Initiating Mode Pressing the glass manually
Manually resumed by a special
Resuming Mode key
Programming Mode Electronically addressed
Address Range Occupying one address,
selectable within 1~242.
Wiring Polarity-insensitive two-wire
This document is subject to change without notice. Please contact GST for more information or questions.
GST China GST UK GST Dubai
Gulf Security Technology Co., Ltd. Global System Technology PLC Global System Technology PLC
No. 80, Changjiang East Road, Lion Court, Staunton Harold Hall, PO Box 17998 Unit ZA04
QETDZ, Qinhuangdao, Hebei, Melbourne Road, Ashby de la Zouch, JEBEL ALI Free Zone,
P. R. China 066004 Leicestershire, England LE65 1RT Dubai, UAE
Tel: +86 (0) 335 8502528 Tel: +44 1283 225 478 Tel: +971 (0) 4 8833050
Fax: +86 (0) 335 8508942 Fax: +44 1283 220 690 Fax: +971 (0) 4 8833053
[email protected] [email protected] [email protected]
www.gst.com.cn www.gst.uk.com www.gst.uk.com