0% found this document useful (0 votes)
129 views2 pages

24anb6 2W

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
129 views2 pages

24anb6 2W

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

24ANB6

Infinityr Air Conditioner with Puronr Refrigerant


1---1/2 to 5 Nominal Tons (Size 18---60)

Wiring Diagram

Fig. 1 – Wiring Diagram — 24ANB618--60A, 208/230--1


CONNECTION DIAGRAM SCHEMATIC DIAGRAM (LADDER FORM)
BLU CAP BLU L1 CONT COMP L2
R
*SR BRN YEL C CONT
*ST +t
2 1 *SC H YEL 11 21
EQUIP S
5 * SR 23 23
(NOTE #8) BLK C GND
BLK BLU 5 2 *SC
BLK F * CHS CAP
or BLK S +t°
RED BLK
C
* CH 1 H
*CH *CHS COMP R
* ST
RED or BLK CONT C
ECM F
L1 11 21
208/230 1Ø YEL
POWER L2 23 23
SUPPLY C C
EQUIP GND YEL O
BLK YEL
W2

YEL / BLU
BRN / YEL
ECM BRN / YEL BLU R
GRN / YEL LS VS ODFR
YEL VR
YEL/PNK BLU/PNK LLSR
PL4 PL3 PL2 YEL/PNK BLU/PNK Y L
BLU / YEL O
CC HPS LPS VS VR ODF G ODFR
LPS I

OUTPUT
* HPS C

INPUT
1 3 1 2 1 2
* LPS NOTE
4 OCT THIS DEFROST CONTROL OAT
HP 3 1 BRN BOARD CONTAINS A FIVE SEE NOTE #12 LLSR
C 2 DEFROST 2 OCT MINUTE SHORT CYCLE
BRN K4

PL5
RVS TIME 3 PROTECTOR. A FIVE OCT
4 OAT MINUTE DELAY WILL CB
CONT
5 BLK OCCUR BETWEEN
COMM STATUS * HPS K4
OPTIONAL QUIET COMPRESSOR OFF/ON C
BLK CYCLES.
NON-COMMUNICATING AS PROVIDED UTIL SHIFT
CONTROL BY MANUFACTURER

P1
SEE NOTE #13 OAT
SEE NOTE #12 CONDENSING UNIT CHARGING INSTRUCTIONS
A B C R For use with units using R-410A refrigerant
R C Y LS W2 O FORCED COOLING ONLY
REQUIRED LIQUID LINE TEMPERATURE
R C Y LS W2 O
DEFROST CHARGING PROCEDURE
Liquid CB
Required Subcooling 1. Only use subcooling charging method
YEL

RED
GRN

WHT

Pressure when OD ambient is greater than 70ºF


at Service Temperature (ºF)
TO INDOOR UNIT Valve (psig) 6 8 10 12 14 16 and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF,
LEGEND 251 78 76 74 72 70 68 and line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes
259 80 78 76 74 72 70
FACTORY POWER WIRING CONT CONTACTOR 266 82 80 78 76 74 72 before checking the charge.
FACTORY CONTROL WIRING ECM ELECTRONICALLY COMMUTATED MOTOR 274 84 82 80 78 76 74 3. Measure liquid service valve pressure
*HPS HIGH PRESSURE SWITCH 283 86 84 82 80 78 76 by attaching an accurate gauge to the
FIELD CONTROL WIRING service port.
*LPS LOW PRESSURE SWITCH 291 88 86 84 82 80 78
FIELD POWER WIRING 299 90 88 86 84 82 80 4. Measure the liquid line temperature by
LLSR LIQUID LINE SOLENOID RELAY 308 92 90 88 86 84 82 attaching an accurate thermistor type
CONDUCTOR ON CIRCUIT BOARD
OAT OUTDOOR AIR THERMISTOR or electronic thermometer to the
COMPONENT CONNECTION 317 94 92 90 88 86 84
OCT OUTDOOR COIL THERMISTOR 326 96 94 92 90 88 86 liquid line near the outdoor coil.
FIELD SPLICE ODFR OUTDOOR FAN RELAY 335 98 96 94 92 90 88 5. Refer to unit rating plate for required
JUNCTION ODF OUTDOOR FAN 345 100 98 96 94 92 90 subcooling temperature.
*SC 354 102 100 98 96 94 92 6. Find the point where the required
PLUG RECEPTACLE RELAY START CAPACITOR
364 104 102 100 98 96 94 subcooling temperature intersects the
*SR START RELAY measured liquid service valve pressure.
CAP CAPACITOR (DUAL RUN)
*ST START THERMISTOR
374 106 104 102 100 98 96
CIRCUIT BOARD 384 108 106 104 102 100 98 7. To obtain the required sub-cooling
CB
temperature at specific liquid line
*CHS CRANKCASE HEATER SWITCH 395 110 108 106 104 102 100 pressure, add refrigerant if liquid line
COMP COMPRESSOR 406 112 110 108 106 104 102
416 114 112 110 108 106 104 temperature is higher than indicated.
*CH CRANKCASE HEATER 427 116 114 112 110 108 106 When adding refrigerant, charge in
* MAY BE FACTORY OR FIELD INSTALLED liquid form using a flow restricting
439 118 116 114 112 110 108
device into suction service port.
450 120 118 116 114 112 110
462 122 120 118 116 114 112 Recover refrigerant if temperature is
474 124 122 120 118 116 114 lower. Allow a tolerance of +/- 3ºF.
FLASH FAULT DEFINITION FLASH FAULT DEFINITION
CODE CODE
On, No Flash Standby 55 Coil Temp Sensor
1, Pause Normal Operation 56 Thermistor Range Error
16 System Communications Failure 72 Thermal Cutout
31 High Pressure Switch 73 Contactor Shorted
32 Low Pressure Switch 74 No 230V at Compressor
45 Control Fault 82 Thermal lockout
46 Brown out (24V) 83 Low pressure lockout
NOTES: 53 Outside Temp Sensor 84 High pressure lockout
1. Compressor and fan motor furnished with inherent thermal protection.
2. To be wired in accordance with National Electric Code (N.E.C.) and local codes. CAUTION
3. N.E.C. Class 2, 24 V circuit, min. 40 VA required, 60VA on units installed with LLS. 1. Compressor damage may occur if system is over charged.
4. Use copper conductors only from disconnect to units suitable for at least 75ºC (167ºF). 2. This unit is factory charged with R-410A in accordance with the amount shown on
5. Must use thermostat and sub-base as stated in pre-sale literature. the rating plate. The charge is adequate for most systems using matched coils
6. If indoor section has a transformer with a grounded secondary, connect the Grounded and tubing not over 15 feet long. Check refrigerant charge for maximum efficiency.
side to "C" on the circuit board.
7. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
See Product Data Literature for required Indoor air Flow Rates and for use of line
8. Check all electrical connections inside control box for tightness. lengths over 15 feet.
9. Do not attempt to operate unit until service valves have been opened. 3. Relieve pressure and recover all refrigerant before system repair or final disposal.
10. Symbols are electrical representation only. Use all service ports and open all flow-control devices, including solenoid valves.
11. When start relay and start capacitor are installed, start thermistor is not used. 4. Never vent refrigerant to atmosphere.
12. For communicating control only. Use approved recovery equipment.
13. In case of non-communicating Indoor system, disconnect factory provided wires from A, B, C and
R terminals. Using factory provided wires connect to R, C, Y, W2, and O terminals as required by
Installation Instructions. Connect field 24V wires to factory provided wires, cap or remove unused 345081-1 0 1 R E V . A
factory provided wires.

Fig. 1 – Wiring Diagram — 24ANB660B, 208/230--1

Copyright 2019 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 06/19 Catalog No: 24ANB6---2W
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: 24ANB6--- 1W

You might also like