DATAKOM DPR02 Installation Manual
DATAKOM DPR02 Installation Manual
DPR-02 relay is a three-phase (line to neutral) * Electrical equipment should be installed only by
voltage protection relay designed to be used for qualified specialist. No responsibility is assured by
over-voltage, under-voltage and phase rotation the manufacturer or any of its subsidiaries for any
protection in distribution substations, generators, consequences resulting from the non-compliance
motors, transformers and capacitors in to these instructions.
compensation systems. * Check the unit for cracks and damages due to
It offers adjustable over / under voltage limits transportation. Do not install damaged equipment.
together with adjustable trip and reset delays. The * Do not open the unit. There is no serviceable
unit has also phase sequence protection. parts inside.
Both over voltage limit(Max) and under voltage * Fuses of fast type (FF) with a maximum rating of
limit(Min) can be adjusted or disabled via 6A must be connected to phase voltage inputs, in
trimmers on the front panel of the device. Delay close proximity of the unit.
timers are adjusted through related trimmers. * Disconnect all power before working on
equipment.
OPERATION * When the unit is connected to the network do
not touch terminals.
VOLTAGE PROTECTION
* Any electrical parameter applied to the device
If any of phase voltages goes over the set MAX must be in the range specified in the user manual.
limit, the ”U>” led turns on and the adjusted Delay
* Do not try to clean the device with solvent or the
timer starts to count. If the fault condition
like. Only clean with a dump cloth.
disappears before the Delay timer expires, then
the”U>” led turns off. If the fault condition persists * Do not allow water to come inside the unit.
until the expiration of the Delay timer, the relay * Verify correct terminal connections before
output is deactivated and the “OUT” led turns off. applying power.
* Only for DIN rail mounting.
If any of measured voltages goes below the set
MIN limit, the ”U<” led turns on and the adjusted PRE-INSTALLATION
Delay timer starts to count. If the fault condition
disappears before the Delay timer expires, then Before installation:
the”U<” led turns off. If the fault condition persists Read this manual carefully, determine the
until the expiration of the Delay timer, the relay correct connection diagram.
output is deactivated and the “OUT” led turns off. Make sure to use adequate fuses.
When the MAX or MIN Voltage trimmer is Do not subject the unit to water spill.
adjusted to the ”OFF” position, the related voltage Below conditions may damage the device:
protection will be disabled. Incorrect connections.
When all voltages are again within adjusted MIN- Incorrect power supply voltage.
MAX limits, ”U<” and “U>” leds turn off and the Overload or short circuit at relay outputs
adjusted Reset Delay timer starts to count. When
Power supply frequency out of specified limits
the timer is expired, the relay output is activated
and the ”OUT” led turns on. ELECTRICAL INSTALLATION
PHASE FAILURE PROTECTION Do not install the unit close to high
If the voltage of any phase falls below 50% of the electromagnetic noise emitting devices like
nominal value, then ”U<” led turns on and contactors, high current busbars, switchmode
immediately the relay output is deactivated and power supplies and the like. Although the unit
the “OUT” led turns off. is protected against electromagnetic
OVERVOLTAGE PROTECTION disturbances, excessive disturbance can affect
If the any phase voltage goes 50% above the the operation and measurement precision.
nominal value, then ”U>” led turns on and Use adequate cable section, at least 0.75mm 2
immediately the relay output is deactivated and (AWG18).
the “OUT” led turns off.
PHASE SEQUENCE PROTECTION Do not overload relay
If the phase sequence is reversed, both “U<” and outputs. Use extra
“U>” leds flash, the relay output is deactivated contactors if required.
and the “OUT” led turns off.
DIMENSIONS LED INDICATORS
ON: Supply LED (green)
OUT: Relay output LED (yellow)
U<: Under Voltage Warning LED (red)
U>: Over Voltage Warning LED (red)