Seq Param Value Units
0 Alternator L1 Current Adjust 1.000
1 Alternator L2 Current Adjust 1.000
2 Alternator L3 Current Adjust 1.000
3 Alternator L1 Current 0 Amps
4 Alternator L2 Current 0 Amps
5 Alternator L3 Current 0 Amps
Seq Param Value Units
0 Alternator L1 Lead/Lag Status Current Leads Voltage
1 Alternator L2 Lead/Lag Status Current Lags Voltage
2 Alternator L3 Lead/Lag Status Current Lags Voltage
3 Alternator L1 Power Factor Adjust 0.00
4 Alternator L2 Power Factor Adjust 0.00
5 Alternator L3 Power Factor Adjust 0.00
6 Alternator L1 Power Factor 1.000.000
7 Alternator L2 Power Factor 1.000.000
8 Alternator L3 Power Factor 1.000.000
Seq Param Value Units
0 Alternator L1-N Voltage Display Adjust 1.002
1 Alternator L2-N Voltage Display Adjust 1.002
2 Alternator L3-N Voltage Display Adjust 1.002
3 Alternator L1-L2 Voltage 0 Volts
4 Alternator L2-L3 Voltage 0 Volts
5 Alternator L1-L3 Voltage 0 Volts
6 Alternator L1-N Voltage 0 Volts
7 Alternator L2-N Voltage 0 Volts
8 Alternator L3-N Voltage 0 Volts
Seq Param Value Units
0 Voltage Setpoint 0.00 %
1 Voltage Regulator Calibration Adjust 1.000
2 Alternator Nominal Voltage 400 Volts
3 Voltage Adjust 2.004 %
Seq Param Value Units
0 Low AC Voltage Threshold 84.99 %
1 Low AC Voltage Delay 10.00 seconds
2 High AC Voltage Threshold 110.00 %
3 High AC Voltage Delay 10.00 seconds
4 Underfrequency Threshold 6.000 Hz
5 Underfrequency Delay 10.00 seconds
6 Overfrequency Enable Disabled
7 Overfrequency Threshold 6.000 Hz
8 Overfrequency Delay 20.00 seconds
9 High AC Voltage Integral Method Inverse Time
Seq Param Value Units
0 Voltage Adjust 2.004 %
1 AVR Gain Adjust 1.000 gain factor
2 V/Hz Rolloff Table <XYtable>
Hz %#-409.600000#409.587500
0.000 100.000
1.000 100.000
5.313 66.699
9.638 33.288
13.950 0.000
80.000 0.000"
Seq Param Value Units
0 Engine Cold Warning Threshold 65.00 degF
1 LOP Warning Threshold Table <XYtable>
rpm psi#-4096.000000#4095.875000
0.0 0.00
800.0 25.00
1200.0 33.00
1700.0 44.00
1800.0 45.00
2200.0 45.00"
2 LOP Shutdown Threshold Table <XYtable>
rpm psi#-4096.000000#4095.875000
0.0 0.00
800.0 20.00
1200.0 28.00
1700.0 39.00
1800.0 40.00
2200.0 40.00"
3 HOT Warning Threshold 250.00 degF
4 HOT Shutdown Threshold 260.00 degF
5 LCL Warning Threshold 15.0 seconds
6 LCL Shutdown Threshold 15.0 seconds
7 LCL Fault Response Shutdown
8 LCP Warning Threshold Table <XYtable>
rpm psi#-4096.000000#4095.875000
0.0 0.00
1300.0 6.00
1800.0 11.00
2000.0 14.00
2100.0 15.00
3000.0 22.00"
9 LCP Shutdown Threshold Table <XYtable>
rpm psi#-4096.000000#4095.875000
0.0 0.00
1300.0 4.00
1800.0 9.00
2000.0 12.00
2100.0 13.00
3000.0 20.00"
10 LCT Warning Threshold 40.00 degF
11 HCT Warning Threshold 212.00 degF
12 HCT Shutdown Threshold 220.00 degF
13 HBF Warning Threshold Table <XYtable>
degF CFM#-512.000000#511.984375
0.00 14.80
50.00 14.80
100.00 14.80
150.00 14.80
200.00 14.80
250.00 14.80"
14 HBF Shutdown Threshold Table <XYtable>
degF CFM#-512.000000#511.984375
0.00 15.80
50.00 15.80
100.00 15.80
150.00 15.80
200.00 15.80
250.00 15.80"
15 HFT Warning Threshold 150.00 degF
16 HFT Shutdown Threshold 160.00 degF
17 HAT Warning Threshold 160.00 degF
18 HAT Shutdown Threshold 170.00 degF
19 HIT Warning Threshold 180.00 degF
20 HIT Shutdown Threshold 190.00 degF
21 Overspeed Shutdown Threshold (50Hz) 1725.0 rpm
22 Overspeed Shutdown Threshold (60Hz) 2070.0 rpm
23 Oil Temperature Sensor Enable Disabled
Seq Param Value Units
0 Centinel User Enable Disabled
1 Centinel Enable Status Disabled
Seq Param Value Units
0 Modem Hangup Delay Disabled
1 Modem Disabled
2 Dial Out Attempts 0 retries
3 Modem Configuration String ATE0V0Q0&C1%C0&D0&K0N0\N0$SB9600S0=1S25=25S37=9&W0
4 Dialout Number 1
5 Dialout Number 2
6 Dialout Number 3
7 Dialout Number 4
8 Dial Out Retry Delay 0 minutes
9 Dialout Break Disabled
Seq Param Value Units
0 Genset Exercise Duration 0.5000 hours
Seq Param Value Units
0 Fault Code 135 Override Enable Enabled
1 Fault Code 135 Override Coolant Temp Threshold 150 degF
Seq Param Value Units
0 Time Delay FSO Relay Driver Off Delay 0.0 seconds
Seq Param Value Units
0 kW Overload Warning Threshold 104.99 %
1 kW Overload Warning Delay 60 seconds
2 Application kVA Rating 2000 kVA
3 Power Factor Rating(3-phase) 0.80
Seq Param Value Units
0 Load Dump kW Overload Threshold 104.99 %
1 Load Dump kW Overload Delay 60 seconds
2 Load Dump Underfrequency Offset 3.000 Hz
3 Load Dump Underfrequency Delay 4 seconds
4 Load Dump Activation Method Overload or Underfrequency
Seq Param Value Units
0 12V Low Battery Stopped Threshold 12.000 Volts
1 12V Low Battery Running Threshold 12.000 Volts
2 12V High Battery Threshold 16.000 Volts
3 12V Weak Battery Threshold 8.000 Volts
4 24V Low Battery Stopped Threshold 24.000 Volts
5 24V Low Battery Running Threshold 24.000 Volts
6 24V High Battery Threshold 32.000 Volts
7 24V Weak Battery Threshold 14.391 Volts
8 Low Battery Fault Delay 60 seconds
9 High Battery Fault Delay 60 seconds
10 Weak Battery Fault Delay 2 seconds
Seq Param Value Units
0 Oil Prelube Cycle Enable Disabled
1 Oil Prelube Cycle Time 168 hours
2 Oil Prelube Function Enable Disabled
3 Oil Prelube Oil Pressure Threshold 3.00 psi
4 Oil Prelube Time Limit 10 seconds
Seq Param Value Units
0 Auto Sleep enable Awake in Auto
Seq Param Value Units
0 Power Limiter State STANDBY
1 Power Limiter Enable Disabled
2 Continuous Scale Factor 1.00
Seq Param Value Units
0 Shutdown Override Enable FALSE
Seq Param Value Units
0 Shutdown With Cooldown Advance Notice Time 0 seconds
1 Shutdown With Cooldown Max Ramp Unload0.000
Time seconds
Seq Param Value Units
0 Start Time Delay 0.00 seconds
1 Stop Time Delay 0.00 seconds
2 Idle Warmup Time 150.00 seconds
3 Idle Cooldown Time 2.00 minutes
Seq Param Value Units
0 Number of Phases Three Phase
1 Alternator Nominal Voltage 400 Volts
2 Application kVA Rating 2000 kVA
3 Standby kVA Rating 2200 kVA
4 Connection Type Wye
5 Rating Type Prime
6 Power Factor Rating (3-phase) 0.80
Seq Param Value Units
0 Alternate Frequency Select 50 Hz Only
1 Nominal Frequency 50.000 Hz
2 Frequency Adjust 0.000 Hz
3 Final Target Engine Speed 0.0 rpm
Seq Param Value Units
0 Nominal Frequency 50.000 Hz
1 Nominal Engine Speed 1500.0 rpm
2 Final Target Engine Speed 0.0 rpm
3 Governor Gain Adjust 0.730
4 Speed Droop Percentage 0.000 %
Seq Param Value Units
0 Engine Idle Speed 750.0 rpm
1 Idle to Rated Ramp Time 0.000 seconds
2 Rated to Idle Ramp Time 30.000 seconds
3 Starting to Rated Ramp Time 0.000 seconds
Seq Param Value Units
0 Custom Annunciation <DataTable>,17,1
Event Identifier
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0"
Seq Param Value Units
0 Custom Outputs <DataTable>,9,1
Event Identifier
0
0
0
0
0
0
0
0"
Seq Param Value Units
0 Site ID 0
1 Location Location
2 Name Genset
3 LonWorks Software Version 0.00
4 Terminated Unknown
5 Update Interval 2.0 Seconds
6 Test Interval 10.0 Seconds
7 Lonworks Card Disabled
8 Unit ID Site 1
Seq Param Value Units
0 Host 1 Enabled
1 Host 2 Disabled
2 Host 3 Disabled
3 Host 4 Disabled
4 Host 5 Disabled
5 Dialout Retries 10
6 Retry Delay 0.0 Seconds
7 Dialout Break Disabled
8 Connection Time-out 60.0 Seconds
Seq Param Value Units
0 Network Fault #1 Name Network Fault #1
1 Network Fault #2 Name Network Fault #2
2 Network Fault #3 Name Network Fault #3
3 Network Fault #4 Name Network Fault #4
4 Network Fault #1 Status Inactive
5 Network Fault #2 Status Inactive
6 Network Fault #3 Status Inactive
7 Network Fault #4 Status Inactive
8 Battery Charger AC Failure Fault Code 0 event code
9 Utility Circuit Breaker Trip Fault Code 0 event code
Seq Param Value Units
0 Genset Circuit Breaker Fail To Close Standalone
Disabled
Mode Enable
1 CB1 (Genset) Position Enable Enabled
2 CB1 (Genset) Breaker Position Select Hardware
3 CB2 (Utility) Position Enable Enabled
4 CB2 (Utility) Breaker Position Select Hardware
5 Genset CB Open to Close Time Delay 0 msec
6 Utility CB Open to Close Time Delay 0 msec
7 Genset CB Recharge Time 10.00 seconds
8 Utility CB Recharge Time 10.00 seconds
9 Genset CB Fail To Close Time Delay 260 msec
10 Utility CB Fail to Close Time Delay 260 msec
11 Fail to Disconnect Time Delay 200 msec
Seq Param Value Units
0 Bus L1-L2 Voltage 0 Volts
1 Bus L2-L3 Voltage 0 Volts
2 Bus L1-L3 Voltage 0 Volts
3 Bus L1-N Voltage Adjust 1.064
4 Bus L2-N Voltage Adjust 1.070
5 Bus L3-N Voltage Adjust 1.064
6 Bus Nominal Voltage 400 Volts
7 Bus Primary PT Voltage 400 Volts
8 Bus L1-N Voltage 0 Volts
9 Bus L2-N Voltage 0 Volts
10 Bus L3-N Voltage 0 Volts
Seq Param Value Units
0 Load Govern kW Base Load 30.180 %
1 Load Govern kVAR Base Load 60.003 %
2 K2 Gain - Load Govern kW 0.0098 gain factor
3 K3 Gain - Load Govern kW 0.5977 gain factor
4 K4 Gain - Load Govern kW 0.1602 gain factor
5 K2 Gain - Load Govern kVAR 0.1943 gain factor
6 K3 Gain - Load Govern kVAR 0.1758 gain factor
7 K4 Gain - Load Govern kVAR 0.4941 gain factor
8 Load Govern kW Method Analog Input
9 Load Govern kVAR Method Fixed Power Factor
10 Load Govern kW Ramp Load Time 20.000 seconds
11 Load Govern kW Ramp Unload Time 20.000 seconds
12 Load Govern Constant Power Factor 0.85
13 Load Govern kW Gain 10.000 gain factor
14 Load Govern kVAR Gain 10.000 gain factor
15 Load Govern Source Local
16 Load Govern kVAR Ramp Load Time 20.000 seconds
17 Load Govern kVAR Ramp Unload Time 20.000 seconds
18 Utility Single Verify Switch Not Verified
19 Load Govern kW Setpoint RC Enable Disabled
20 Load Govern kVAR Setpoint RC Enable Disabled
21 Load Govern kW Base Load Max Limit 100.000 %
Seq Param Value Units
0 Speed Droop Percentage 0.000 %
1 Load Share Speed Control Method Isochronous
2 Load Share Voltage Control Method Constant
3 Voltage Droop Percentage 0 %
4 Load Share Minimum kW -10.988 %
5 Load Share Minimum kVAR -9.986 %
6 Load Share Maximum kW 125.051 %
7 Load Share Maximum kVAR 75.187 %
8 Load Share kW Balance 4.102 %
9 Load Share kVAR Balance 2.734 %
10 Load Share kW Gain 10.000 gain factor
11 Load Share kVAR Gain 10.000 gain factor
12 Load Share Ramp Unload Time 30.000 seconds
13 Load Share Ramp Load Time 30.000 seconds
14 Load Share Ramp kW Unload Level 4.993 %
15 Load Share Ramp State Not in Load Share
Seq Param Value Units
0 Genset Circuit Breaker Fail To Close Standalone
Disabled
Mode Enable
1 Highest Paralleling Level Available UtilMult
2 Paralleling Level UtilMult
3 Utility Single Verify Switch Not Verified
Seq Param Value Units
0 Reverse kW Threshold 10.0 %
1 Reverse kW Time Delay 3.0 sec
2 Reverse kVAR Threshold 20.0 %
3 Reverse kVAR Time Delay 10.0 sec
Seq Param Value Units
0 Paralleling Status Standby
1 Load Share Speed Control Method Isochronous
2 Speed Droop Percentage 0.000 %
3 Speed Droop Status Droop Disabled
4 Customer #1 Switch Off
5 Synchronize Disable INACTIVE
6 Operation Mode Switch Position Off
7 Alternator - Bus Phase Difference -2.8 deg
8 CB1 (Genset) Manual Control No Command
9 CB1 (Genset) Operation Mode Automatic
10 Alternator Line Frequency 0.000 Hz
11 Bus Line Frequency 0.000 Hz
12 Alternator Total kW 0 kW
13 Frequency Adjust 0.000 Hz
Seq Param Value Units
0 Fail to Synchronize Time 120.0 seconds
1 First Start Enable Backup Time 10.0 sec
2 Bus Synchronizer Gain 24.648 gain factor
3 Bus Voltage Window 4.99 %
4 Bus Phase Window 8.0 deg
5 Bus Permissive Window Time 0.50 seconds
6 Bus Phase Difference Calibration 0.0 deg
Seq Param Value Units
0 Paralleling Status Standby
1 Load Share Voltage Control Method Constant
2 Voltage Droop Percentage 0%
3 Voltage Droop Status Droop Disabled
4 Customer #1 Switch Off
5 Synchronize Disable INACTIVE
6 Operation Mode Switch Position Off
7 Alternator - Bus Phase Difference -2.8 deg
8 CB1 (Genset) Manual Control No Command
9 CB1 (Genset) Operation Mode Automatic
10 Alternator L1-L2 Voltage 0 Volts
11 Bus L1-L2 Voltage 0 Volts
12 Alternator Total Power Factor 1.00
13 Alternator Total kVAR 0 kVAR
14 Voltage Adjust 2.004 %
Seq Param Value Units
0 Genset Overvoltage Pick-Up Threshold 0 Volts
1 Genset Overvoltage Drop-Out Threshold 254 Volts
2 Genset Overvoltage Sensor Status Unknown
3 Genset Overvoltage Sensor Enable Enabled
4 Genset Overvoltage Drop-Out Percentage 110 %
5 Genset Overvoltage Drop-Out Delay 3.0 seconds
6 Genset Overvoltage Pick-Up Percentage 95 %
7 Genset Undervoltage Pick-Up Threshold 207 Volts
8 Genset Undervoltage Drop-Out Threshold 0 Volts
9 Genset Undervoltage Sensor Status Unknown
10 Genset Undervoltage Drop-Out Percentage 90 %
11 Genset Undervoltage Pick-Up Percentage 90 %
12 Genset Undervoltage Drop-Out Delay 4.0 seconds
13 Genset Voltage Sensor Type Line-Neutral
14 Genset Frequency Lower Pick-Up Threshold 0.0 Hz
15 Genset Frequency Upper Pick-Up Threshold 0.0 Hz
16 Genset Frequency Lower Drop-Out Threshold0.0 Hz
17 Genset Frequency Upper Drop-Out Threshold0.0 Hz
18 Genset Frequency Sensor Status Unknown
19 Genset Frequency Sensor Enable Enabled
20 Genset Center Frequency 50.0 Hz
21 Genset Frequency Pick-Up Percentage 10 %
22 Genset Frequency Drop-Out Percentage 1%
23 Genset Frequency Drop-Out Delay 5.0 seconds
24 Genset CB Tripped Input Enable Disabled
25 Genset Nominal Voltage 400 Volts
26 Genset Connection Type Wye
27 Genset Unloaded Level 5.0 %standbykW
28 Load Govern kW Base Load 30.180 %
29 Load Govern kW Method Analog Input
30 Load Govern kW Ramp Load Time 20.000 seconds
31 Load Govern kW Ramp Unload Time 20.000 seconds
Seq Param Value Units
0 Highest Paralleling Level Available UtilMult
1 Paralleling Level UtilMult
2 Highest Power Transfer Level Available None
3 Fail To Synchronize Open Transition Retransfer
Disabled
Enable
4 Test With Load Disabled
5 Exercise With Load Disabled
Seq Param Value Units
0 Genset Exercise Duration 0.5000 hours
1 Start Time Delay (TDES) 0.00 seconds
2 Stop Time Delay (TDEC) 0.00 seconds
3 Programmed Transition Time Delay (TDPT) 3.0 sec
4 Retransfer Time Delay (TDEN) 600.0 sec
5 Transfer Time Delay (TDNE) 10.0 sec
6 Max Parallel Time (TDMP) 1000.0 sec
Seq Param Value Units
0 Utility L2 Power Factor 0.995178
1 Utility L2 Current 0 Amps
2 Utility L2 Current Adjust 1.000
3 Utility L2 VI Disp Adjust 0.00
4 Utility L2 Lead/Lag Status Current Leads Voltage
Seq Param Value Units
0 Utility Overvoltage Pick-Up Threshold 0 Volts
1 Utility Overvoltage Drop-Out Threshold 254 Volts
2 Utility Overvoltage Sensor Status Unknown
3 Utility Overvoltage Sensor Enable Enabled
4 Utility Overvoltage Drop-Out Percentage 110 %
5 Utility Overvoltage Drop-Out Delay 3.0 seconds
6 Utility Overvoltage Pick-Up Percentage 95 %
7 Utility Undervoltage Pick-Up Threshold 207 Volts
8 Utility Undervoltage Drop-Out Threshold 0 Volts
9 Utility Undervoltage Sensor Status Unknown
10 Utility Undervoltage Drop-Out Percentage 90 %
11 Utility Undervoltage Pick-Up Percentage 90 %
12 Utility Undervoltage Drop-Out Delay 0.5 seconds
13 Utility Voltage Sensor Type Line-Neutral
14 Utility Frequency Lower Pick-Up Threshold 0.0 Hz
15 Utility Frequency Upper Pick-Up Threshold 0.0 Hz
16 Utility Frequency Lower Drop-Out Threshold 0.0 Hz
17 Utility Frequency Upper Drop-Out Threshold 0.0 Hz
18 Utility Frequency Sensor Status Unknown
19 Utility Frequency Sensor Enable Enabled
20 Utility Center Frequency 50.0 Hz
21 Utility Frequency Pick-Up Percentage 10 %
22 Utility Frequency Drop-Out Percentage 1%
23 Utility Frequency Drop-Out Delay 5.0 seconds
24 Utility CB Tripped Input Enable Disabled
25 Utility Primary PT Voltage 400 Volts
26 Utility Nominal Voltage 400 Volts
27 Utility CT Ratio 1
28 Utility Connection Type Wye
29 Utility kW Unloaded Level 15 kW
Seq Param Value Units
0 Utility L1-N Voltage 0 Volts
1 Utility L2-N Voltage 0 Volts
2 Utility L3-N Voltage 0 Volts
3 Utility L1-N Voltage Adjust 1.064
4 Utility L2-N Voltage Adjust 1.070
5 Utility L3-N Voltage Adjust 1.064
6 Utility Nominal Voltage 400 Volts
7 Utility Primary PT Voltage 400 Volts
8 Utility L1-L2 Voltage 0 Volts
9 Utility L2-L3 Voltage 0 Volts
10 Utility L1-L3 Voltage 0 Volts
Seq Param Value Units
0 Cumulative Fuel Consumption 1049194.70 gal
1 Fuel Consumption Since Reset 1049194.70 gal
2 Fuel Consumption Reset Time COT 0.0000 hours
3 Fuel Consumption Reset Time ERT 0.00000 hours
4 Controller On Time (COT) 1.290.248.364 hours
5 Engine Running Time (ERT) 1.846.092.628 hours
Seq Param Value Units
0 Total kWh Delivered 14724444 kWh
1 kWh Since Reset 14724444 kWh
2 kWh Reset Time (COT) 0.0000 hours
3 kWh Reset Time (ERT) 0.00000 hours
4 Controller On Time (COT) 1.290.248.364 hours
5 Engine Running Time (ERT) 1.846.092.628 hours
Seq Param Value Units
0 Total Runs 6299 counts
1 Total Start Attempts 2576 starts
2 Runs Since Reset 6299 counts
3 Start Attempts Since Reset 2576 starts
4 Run Reset Time (COT) 0.0000 hours
5 Run Reset Time (ERT) 0.00000 hours
6 Start Attempts Reset Time (COT) 0.0000 hours
7 Start Attempts Reset Time (ERT) 0.00000 hours
8 Controller On Time (COT) 1.290.248.364 hours
9 Engine Running Time (ERT) 1.846.092.628 hours
Seq Param Value Units
0 Start Time Delay 0.00 seconds
1 Cycle/Continuous Crank Select Cycle
2 Continuous Crank Engage Time 75.00 seconds
3 Cycle Crank Attempts 3 attempts
4 Cycle Crank Engage Time 15.00 seconds
5 Cycle Crank Rest Time 15.00 seconds
Seq Param Value Units
0 Customer #1 Switch Active State Selection Active Closed
1 Customer #4 Switch Active State Selection Active Closed
2 Customer #1 Switch Enable Disabled
3 Customer #4 Switch Enable Disabled
4 High Alternator Temp on Cust Switch 1 Disabled
5 Customer #1 Switch Event Name Customer Input #1
6 Customer #2 Switch Event Name Customer Input #2
7 Customer #3 Switch Event Name Customer Input #3
8 Customer #4 Switch Event Name Customer Input #4
9 Genset CB Tripped on Cust Switch 4 Disabled
10 Customer #1 Switch Off
11 Customer #2 Switch Off
12 Customer #3 Switch Off
13 Customer #4 Switch Off
14 Customer #1 Switch Event Genset Reponse None
15 Customer #2 Switch Event Genset Reponse None
16 Customer #3 Switch Event Genset Reponse None
17 Customer #4 Switch Event Genset Reponse None
Seq Param Value Units
0 Remote Start (H/W) Active State Selection Active Closed
1 Day Tank Low Fuel Switch Enable Enabled
2 Main Tank Low Fuel Switch Enable Enabled
3 Remote Start (H/W) stop
4 Day Tank Low Level Fuel Not Low Fuel
5 Main Tank Low Level Fuel Not Low Fuel
Seq Param Value Units
0 Network Fault #1 Name Network Fault #1
1 Network Fault #2 Name Network Fault #2
2 Network Fault #3 Name Network Fault #3
3 Network Fault #4 Name Network Fault #4
4 Network Fault #1 Status Inactive
5 Network Fault #2 Status Inactive
6 Network Fault #3 Status Inactive
7 Network Fault #4 Status Inactive
8 Battery Charger AC Failure Fault Code 0 event code
9 Utility Circuit Breaker Trip Fault Code 0 event code