This manual describes the installation, operation, and troubleshooting of the Civacon 8130 OPTIC
Loading Rack Monitoring System. It is intended to help operators, maintainers, and specifiers
understand the operation and features of the OPTIC system. This manual should be read before
installation of any equipment.
The OPTIC monitor detects and communicates an overfill condition to the loading rack control
automation equipment. The OPTIC monitor optionally can communicate this "NON-PERMISSIVE"
condition to the loading operator by way of status lights. The OPTIC monitor can also be used in fixed
storage overfill monitoring situations.
An overall loading rack system contains a loading rack control monitor (OPTIC Model 8130), junction
box (Model 7560 Series), and an API optic cord set and plug (Model 7100). A Plug Hanger is also
available. Please consult the factory for the current availability of all optional products. The Optic
signal is compatible with the API 1004 signaling conventions used throughout the industry. The
CIVACON OPTIC loading rack control monitor is designed to provide many years of trouble free
service.
The 8130 has a RED non-permissive and a GREEN permissive indicator. The 8130 system has
BYPASS capability when used with the optional BCU-2 bypass unit.
The purpose of the Civacon OPTIC liquid level sensing system is to detect a liquid point level signal
from a sensor mounted in compartments of a tank truck, or storage tanks. The system provides an
automatic signal to the rack automation equipment to shut-off the flow of liquid, and warn of an
impending overflow condition of a tank truck or storage tank.
The OPTIC system uses self-checking principles to provide a continuous check on all system
components. This is accomplished by the exchange of digital pulses between sensor and rack
monitor. These digital pulses must pass through all active components in the sensor, sensor wiring,
and back to the control monitor to test all the components in the circuit. If at any time the circuit
detects a failure in any of the components, it reverts to a failsafe condition, NON-PERMISSIVE. The
unit must then be repaired before it can return to an operational condition. Sensors cannot be
"jumpered" out of the circuit and have it work.
The monitor will work with any API 5 wire OPTIC sensor. The monitor only uses 4 of the 5 wires,
because the fifth wire is used for onboard monitor diagnostics ONLY. Up to twelve (12) standard optic
sensors may be connected to the monitor.
The monitor is also designed to work with any On Board Monitor's API OPTIC signal format outputs.
The 8130 also incorporates truck-to-load rack Ground Verification. The Ground Verification circuit
detects the presence of a ground on the trailer frame from four possible sources. The primary source
of a ground is through the overfill monitoring systems plugs' sensor ground, which is normally on Pin
10 of the API socket. The other possible sources of a ground are through the loading couplers, the
vapor recovery vent line, or any static grounding ball or clamp connection(s).
CIVACON H52496PA
© 2003 1 JAN 2005
1.1 PRODUCTS
All CIVACON Loading Rack Monitors are suitable for Class I, Division 1, Groups C & D
hazardous locations with intrinsically safe outputs, and housed in an Explosion Proof
Enclosure. All monitors are FM approved. Please consult the factory for the availability of
special models.
OPTIONAL ACCESSORIES
Depending on the model used, two different input voltages are available for installation. The
standard model is rated at 120 VAC, 50/60 Hz., but a 240 VAC, 50/60 Hz., model is available.
Both voltage models provide a relay output with a SPDT set of contacts, rated at 240 VAC, 5
Amps. Determine which voltage model was purchased by the voltage rating on the nameplate;
and wire according to the proper line voltage.
Voltage selection is made at the factory by jumpers on the PCB. Please do not attempt to alter
these settings.
SAFETY FIRST!! POWER MUST BE OFF WHEN INSTALLING OR REMOVING THE PRODUCT
FROM SERVICE. THE WIRES FOR THE POWER TERMINALS FROM THE POWER PANEL MUST
BE KEPT TURNED OFF DURING WIRING, CHECKOUT AND THE BOARD REPLACEMENT !
This is important to maintain safe repair practices.
CIVACON H52496PA
© 2003 2 JAN 2005
2 MOUNTING DIAGRAM
Maximum diameter bolt holes for mounting the enclosure are 7/16 " diameter.
6.750
2.125
CIVACON H52496PA
© 2003 3 JAN 2005
3 WIRING INSTRUCTIONS - POWER
All wiring entering the rack monitor enclosure must enter through the NPT conduit openings provided
by the factory. Use weather tight conduit fittings and thread sealant on pipe threads to keep out
external moisture. Ensure that the proper sealing fittings are installed, and potted (sealed)
appropriately.
CAUTION:
The control monitor's wiring and terminal strips on one side are intrinsically safe, and are separated
from the AC power wiring by barriers. This separation of wires must be maintained. All sensor wires
must enter the bottom (intrinsically safe side) of the monitor enclosure, and not mix with the AC
power wiring or any other wiring at the top. AC power and control circuit wiring must enter through
the conduit openings in the top of the enclosure. Wires should be cut to length with no excessive wire
coiled inside the enclosure.
The power supply circuit should contain a disconnect switch and an appropriate fuse or circuit breaker
with a minimum current rating of 1 Amp. for proper monitor operation. We strongly suggest the use of
a high quality stranded and tinned copper wire with a minimum thickness of 18 gauge for all electrical
connections. It is recommended that the power be switched off when servicing the electrical system.
See Section 6 for proper monitor fuse replacement values.
Do not apply power to the monitor without reading this manual and thoroughly checking all
connections. If the power wires pass through a Class I, Division 1, Groups C & D area, the conduit and
wire type must be suitable for this use.
ATTENTION:
Be sure to check the local electrical and fire codes for proper installation. Many localities
require an inspection to be performed before circuits are energized.
CIVACON H52496PA
© 2003 4 JAN 2005
Three terminals are provided on the power input terminal strip on the monitor. These are L1 (LINE), L2
(NEUTRAL), and GROUND. The proper power source must be wired to these terminals, including a
GREEN ground wire. In all cases, the appropriate NEC or CEC code should be followed.
Three terminals are provided for the control channel output on the monitor. These are C1 (COMMON
1), NC1 (Normally Closed 1), and NO1 (Normally Open 1), Form C type contacts. The proper control
signal source must be wired to these terminals. It is suggested that the control signal source be wired
into the C1 (COMMON 1) terminal, as it is the fused control terminal. The wire going to the controlled
device should then be connected to the NO1 (or NC1 if applicable) contact of the terminal strip. See
notes for Figure 3 concerning contacts C1, NC1, & NO1.
IMPORTANT:
The control monitor's enclosure has a grounding terminal. Connect a 12 AWG
(minimum conductor size) solid copper wire from the terminal to an earth
ground. The ground connection must be within one (1) ohm of true ground.
There must be only one earth ground for the system to maintain an intrinsically
safe circuit.
CIVACON H52496PA
© 2003 5 JAN 2005
4.1 POWER WIRING
EARTH GROUND
L1 AC INPUT 120VAC/240VAC
L2 AC INPUT 120VAC/240VAC
Additional Notes:
Installation should be in accordance with NEC ANSI/NFPA 70 and ANSI/ISA RP12.6 . In Canada, the
system must be installed in accordance with the Canadian Electrical Code, CEC Part I.
SAFETY FIRST!! POWER MUST BE OFF WHEN INSTALLING OR REMOVING THE PRODUCT
FROM SERVICE. THE WIRES FOR THE POWER TERMINALS FROM THE POWER PANEL MUST
BE KEPT TURNED OFF DURING WIRING, CHECKOUT AND THE BOARD REPLACEMENT !
This is important to maintain safe repair practices.
CIVACON H52496PA
© 2003 6 JAN 2005
4 WIRING INSTRUCTIONS - IS SIGNALS
We strongly suggest the use of a high quality stranded and tinned copper wire with a minimum
thickness of 18 gauge for all electrical connections to the intrinsically safe area connections. For wire
lengths greater than 1000 feet (300 m.), please consult the factory.
WARNING
These recommendations must be followed to limit the inductance and capacitance of the IS field
wiring. Failure to do so will impair the intrinsic safety and approvals of the system.
CAUTION!: Hazardous conditions exist in fixed tank or large open rack installations. For
lightning protection, above ground wiring runs must be in metal conduit, which must be
weather-proof and have grounding rods to earth at each end. Underground wiring runs can be in
non-metal liquid-tight conduit, however, such runs must terminate in a metal weather-proof
junction box upon surface transition. It is suggested that underground wiring runs be run in metal
conduit. This junction box must have a ground rod to earth. Lightning suppression equipment can
be added at each sensor and control monitor. If additional protection is desirable, consult the
factory.
Additional installation information can be obtained from Civacon for the other products used in the IS
wiring portion of this installation. This information is usually shipped with the other products when they
are purchased. If you misplace or lose this information, use the following information for obtaining
replacements.
Use CIVACON Instruction Sheet or Manual H50457PA for additional information on installing Model
7500 series Junction Boxes.
Use CIVACON Instruction Sheet or Manual H50204PA for additional information on installing Model
7100 or 7300 series Rack Connector Plugs.
CIVACON H52496PA
© 2003 7 JAN 2005
BCU-2
CIVACON H52496PA
© 2003 8 JAN 2005
5 MONITOR INDICATORS
If the cover to the rack monitor is opened, a PERMIT LED may be viewed for operational functions.
FUNCTION TABLE
CAUTION!: DO NOT apply power to this monitor without thoroughly reading this manual and
checking all connections. DO NOT connect a power source other than what's marked on the
label to this monitor, as this may permanently damage it.
CIVACON H52496PA
© 2003 9 JAN 2005
5.1 CHECKOUT PROCEDURE
1. Before applying AC line power to the 8130 Series Rack Monitor, perform a visual
inspection of the power and control wiring according to Figure 3.
2. Apply the proper AC line power to the 8130 Series Rack Monitor. Ensure the rack
monitor's plug(s) is not connected to anything. The RED indicator on the Rack Monitor
should light and FLASH.
3. Connect a Ground Verification signal to the IS connector (pins 1 and 2). The RED lamp
will change from FLASH to continuous ON.
4. Connect the Rack Monitor's Optic plug, 7100, to an appropriate Optic test sensor
source. The RED lamp will go OFF and the GREEN lamp will be ON.
NOTE: Use a known working tank truck with appropriate sensors installed that can
connect through the plug and socket to the Rack Monitor for a permit signal source. A
Civacon Model 1386 Rackcheck-RTM Test Unit may be used if it is available.
5. Testing Bypass (is applicable). If you have purchased the BCU-2 Bypass Control Unit,
make sure to disconnect the Optic equipment in step 4 but leave the Ground
Verification source connected in step 3. Connect the BCU-2 to its connector on the
junction box. The GREEN and RED lights will come on and the relay will activate.
The J3 Intrinsic Safety terminals may be measured for voltage presence. Using a voltmeter set
on a 20 volt DC scale. With the ground (negative) lead of the meter on terminal 2, measure the
DC voltage at pin 3 and it should read between 12 and 14 V with no wiring connected.
CAUTION!: Hazardous conditions exist on the printed circuit board. Only a qualified
technician should be probing around on the circuitry contained within. Please consult the
factory with any questions.
CIVACON H52496PA
© 2003 10 JAN 2005
5.2 REPLACEMENT PARTS
Open the cover to the enclosure; and then remove the two (2) screws holding the safety panel
and remove the safety panel. Remove the four (4) mounting screws that hold the board to the
bottom of the chassis. Separate the two halves of the black connector to disconnect the board
from the pilot lamps. The board can now be removed for replacement.
The following is a list of repair PCBs for the monitors. Replace with the correct version.
CAUTION
The monitor chassis contains NO components that are field replaceable except
for three (3) AC fuses. Any substitution of components may impair the intrinsic
safety and approvals of the system.
The three (3) fuses that are field replaceable are F1, F2 & F5. The following list of
specifications should be followed.
F1 & F2 = 3AG Type, 250V, 1/2 AMP. For AC line input, Li and L2 Inputs.
CIVACON H52496PA
© 2003 11 JAN 2005
6 WARRANTY
All parts and products are thoroughly inspected and tested from the time raw material is received at
our plant, until the product is completed. We guarantee that all products are free from defects in
materials and workmanship for a period of one year from the date of shipment. Any product that may
prove defective within said one year period will, at our option, be promptly repaired, or replaced, or
credit given for future orders. This warranty shall not apply to any product which has been altered in
any way, which has been repaired by any party other than an authorized service representative, or
when such a failure is due to misuse or conditions of use. We shall have no liability for labor costs,
freight costs, or any other cost or charges in excess of the amount of invoice for the products.
WARNING:
CIVACON products should be used in compliance with applicable federal, state, and local
laws and regulations. Product selection should be based on physical specifications and
limitations, compatibility with the environment, and the material to be handled.
CIVACON MAKES NO WARRANTY OF FITNESS
FOR A PARTICULAR USE.
If at any time during the installation a question arises that is not covered in this Installation
Instruction, or with any other applicable documents referenced, feel free to call the CIVACON
ELECTRONICS TECHNICAL ASSISTANCE LINE :
CIVACON H52496PA