DATASHEET - PKZM0-20
Motor-protective circuit-breaker, 9 kW, 16 - 20 A, Screw terminals
Part no. PKZM0-20
046988
EL Number 4355148
(Norway)
General specifications
Product name Eaton Moeller® series PKZM0 Motor-protective circuit-breaker
Part no. PKZM0-20
EAN 4015080469889
Product Length/Depth 76 millimetre
Product height 93 millimetre
Product width 45 millimetre
Product weight 0.296 kilogram
Certifications UL Category Control No.: NLRV
IEC/EN 60947
CSA File No.: 165628
CSA
UL File No.: E36332
VDE 0660
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
UL
CE
CSA Class No.: 3211-05
UL 60947-4-1
Product Tradename PKZM0
Product Type Motor-protective circuit-breaker
Product Sub Type None
Features & Functions
Actuator type Turn button
Features Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
Functions Phase failure sensitive
Motor protection
Number of poles Three-pole
General information
Connection Screw terminals
Degree of protection Terminals: IP00
IP20
Explosion safety category for dust ATEX dust-ex-protection, PTB 10, ATEX 3013, Ex II(2) GD
Lifespan, electrical 100,000 operations
Lifespan, mechanical 100,000 Operations
Mounting position Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
Operating frequency 40 Operations/h
Overvoltage category III
Pollution degree 3
Product category Motor protective circuit breaker
Protection Finger and back-of-hand proof, Protection against direct contact when actuated
from front (EN 50274)
Rated impulse withstand voltage (Uimp) 6000 V AC
Shock resistance 25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Suitable for Branch circuit: Manual type E if used with terminal, or suitable for group
installations, (UL/CSA)
Also motors with efficiency class IE3
Temperature compensation -5 - 40 °C to IEC/EN 60947, VDE 0660
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Altitude Max. 2000 m
Ambient operating temperature - min -25 °C
Ambient operating temperature - max 55 °C
08/02/2024 Eaton 046988 ED2023 V1.0 EN 1/4
Ambient operating temperature (enclosed) - min -25 °C
Ambient operating temperature (enclosed) - max 40 °C
Ambient storage temperature - min -40 °C
Ambient storage temperature - max 80 °C
Climatic proofing Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
Terminal capacity (flexible with ferrule) 1 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm², ferrule to DIN 46228
Terminal capacity (solid) 2 x (1 - 6) mm²
1 x (1 - 6) mm²
Terminal capacity (solid/stranded AWG) 18 - 10
Stripping length (main cable) 10 mm
Tightening torque 1.7 Nm, Screw terminals, Main cable
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Rated frequency - min 50 Hz
Rated frequency - max 60 Hz
Rated operational current (Ie) 20 A
Rated operational power at AC-3, 220/230 V, 50 Hz 5.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz 9 kW
Rated operational power at AC-3, 440 V, 50 Hz 11 kW
Rated operational power at AC-3, 500 V, 50 Hz 12.5 kW
Rated operational power at AC-3, 690 V, 50 Hz 15 kW
Rated operational voltage (Ue) - min 690 V
Rated operational voltage (Ue) - max 690 V
Rated uninterrupted current (Iu) 20 A
Short-circuit rating
Rated short-circuit breaking capacity Icu at 400 V AC 50 kA
Rated short-circuit breaking capacity Ics at 400 V AC 38 kA
Rated short-circuit breaking capacity Icu at 440 V AC 10 kA
Rated short-circuit breaking capacity Ics at 440 V AC 3 kA
Rated short-circuit breaking capacity Icu at 500 V AC 3 kA
Rated short-circuit breaking capacity Ics at 500 V AC 3 kA
Rated short-circuit breaking capacity Icu at 690 V AC 3 kA
Rated short-circuit breaking capacity Ics at 690 V AC 1 kA
Short-circuit current 40 kA DC, up to 250 V DC, Main conducting paths
Short-circuit current rating (group protection) 18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse,
SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR
(UL/CSA)
18 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB
with CL, SCCR (UL/CSA)
18 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault,
Fuse with CL, SCCR (UL/CSA)
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR
(UL/CSA)
10 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 150 A, 600 V High Fault, Fuse,
SCCR (UL/CSA)
Short-circuit current rating (type E) Accessories required BK25/3-PKZ0-E
18 kA, 480 Y/277 V, SCCR (UL/CSA)
18 kA, 240 V, SCCR (UL/CSA)
Short-circuit release ± 20% tolerance, Trip blocks
310 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks
Switching capacity
Switching capacity 20 A, AC-3 up to 690 V
20 A (3 contacts in series), DC-5 up to 250V
Motor rating
Assigned motor power at 115/120 V, 60 Hz, 1-phase 1.5 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase 5 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase 3 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase 15 HP
08/02/2024 Eaton 046988 ED2023 V1.0 EN 2/4
Trip blocks
Overload release current setting - min 16 A
Overload release current setting - max 20 A
Tripping characteristic Overload trigger: tripping class 10 A
Design verification
Equipment heat dissipation, current-dependent Pvid 5.82 W
Heat dissipation capacity Pdiss 0W
Heat dissipation per pole, current-dependent Pvid 1.94 W
Rated operational current for specified heat dissipation (In) 20 A
Static heat dissipation, non-current-dependent Pvs 0W
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of assemblies Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 9.0
Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss13-27-37-04-01
[AGZ529021])
Overload release current setting A 16 - 20
Adjustment range undelayed short-circuit release A 310 - 310
With thermal overload protection No
Phase failure sensitive Yes
Switch off technique Thermomagnetic
Rated operating voltage V 690 - 690
Rated permanent current Iu A 20
Rated operation power at AC-3, 230 V kW 5.5
Rated operation power at AC-3, 400 V kW 9
Power loss W 5.82
Type of electrical connection of main circuit Screw connection
Type of control element Turn button
Device construction Built-in device fixed built-in technique
With integrated auxiliary switch No
With integrated under voltage release No
Number of poles 3
Rated short-circuit breaking capacity lcu at 400 V, AC kA 50
08/02/2024 Eaton 046988 ED2023 V1.0 EN 3/4
Degree of protection (IP) IP20
Height mm 93
Width mm 45
Depth mm 76
08/02/2024 Eaton Industries GmbH 4/4
© 04/2023 by Eaton Industries GmbH
Eaton 046988 ED2023 V1.0 EN