Xyr5000 Honeywell
Xyr5000 Honeywell
User Manual
• This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: 1) this device may not cause harmful interference, and
2) this device must accept any interference received, including interference that
may cause undesired operation.
• This device is for mobile and fixed use only (not portable or body-worn). A
separation distance of 20cm must be maintained at all times between the antenna
and the body of the user and bodies of nearby persons.
• If the Wireless Management Toolkit (RF Server) software is shutdown, the RS-
485 network MUST be physically disconnected from the PC as the serial port is
no longer being controlled by the software and may disrupt communications
between the Base Radio(s) and Analog/Digital Output Module(s).
• This device has been designed to operate with an antenna having a maximum
gain of 9 dBd. Antenna having a higher gain is strictly prohibited per regulations
of Industry Canada. The required antenna impedance is 50 ohms.
• To reduce potential radio interference to other users, the antenna type and its gain
should be so chosen that the equivalent isotropically radiated power (EIRP) is not
more than that required for successful communication.
• The installer of this radio equipment must ensure that the antenna is located or
pointed such that it does not emit RF field in excess of Health Canada limits for
the general population; consult Safety Code 6, obtainable from Health Canada’s
website www.hc-sc.gc.ca/rpb.
! FCC Certification !
• This product is a frequency hopping RF transceiver module for the 900MHz ISM
band, designed to meet FCC 15.247, and is used in industrial control and moni-
toring applications.
Contacts
World Wide Web
The following lists Honeywell’s World Wide Web sites that will be of interest to our industrial automation and control customers.
Corporate http://www.honeywell.com
International http://www.honeywell.com/Business/global.asp
Telephone
Contact us by telephone at the numbers listed below.
Table of Contents
Section 1: Introduction____________________________________1
1.1: Using This Manual 1
1.2: About the Device 2
1.3: Unpacking 2
1.4: Software Compatibility 2
Section 2: In a Hurry? ____________________________________3
Section 3: Installation_____________________________________4
3.1: Mechanical Installation 4
3.1.1: Transmitter Positioning 4
3.1.2: Simple RF Placement Procedure 5
3.2: Electrical Installation 7
3.2.1: Electrical Specifications 7
3.2.2: Wiring the Thermocouple/RTD Input 7
3.2.3: Wiring the Input Switches 8
Section 4: General Configuration __________________________10
4.1: Transmitter Displayed Messages 10
4.1.1: The Read-Only Sequence 10
4.2: Overall Configuration Menu Map 11
4.3: Setting the Transmitter Tag Name 11
4.4: Setting a User Password 12
4.5: Resetting All Transmitter Settings 12
Section 5: Configuring the RF Communications ______________13
5.1: RF Channel Selection 13
5.2: RF Baud Rate Selection 13
5.3: RF Identification Selection 14
Section 6: Configuring the Sampling and Transmission Rates ___15
6.1: Selecting the Normal Transmission Rate 15
6.2: Selecting the Normal Sampling Rate 16
6.3: Selecting the Abnormal Transmission Rate 17
6.4: Selecting the Abnormal Sampling Rate 18
6.5: Setting the Smart Rate Threshold 19
6.6: Selecting the Normal Upper and Lower Values 20
6.7: Selecting Rates, Thresholds, and Deadbands via the Software 21
Section 7: Configuring the Process Variable __________________22
7.1: Selecting the Units of Measure 22
7.2: Selecting the Sensor Type 22
7.3: Setting a Measurement Offset 23
7.4: Trimming the Measurement 23
7.5: Entering a 22-Point Curve 23
Section 8: Maintaining the Transmitter _____________________24
8.1: Changing the Battery 24
Section 9: Technical Specifications _________________________25
Dimensioned Mechanical Drawing 26
Intrinsic Safety Control Drawing 27
Appendix A: Navigating the Menus ________________________28
Appendix B: Displayed Message Definitions _________________29
Appendix C: Transmitter Menu Map _______________________30
Rev. 3 User Manual III
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
Table of Figures
3.1: Example of Incorrect Transmitter Positioning .................................................. 4
3.2: Menu Map to RSSI Mode.................................................................................. 5
3.3: Thermocouple Input Wiring Diagram............................................................... 7
3.4: RTD Input Wiring Diagram.............................................................................. 7
3.5: Input Switch Wiring Diagram........................................................................... 8
3.6: Output Switch Wiring Diagram......................................................................... 9
3.7: Output Switch Configuration with Wireless Management Toolkit................... 9
4.1: Transmitter Power-UP and Operations Sequence ........................................... 10
4.2: The Read-Only Sequence ................................................................................ 10
4.3: Overall Configuration Menu Map ................................................................... 11
4.4: Menu Map to Tag Name Setting ..................................................................... 11
4.5: Menu Map to Password Setting....................................................................... 12
4.6: Password Setting Using Wireless Management Toolkit ................................. 12
5.1: Menu Map to RF Channel Setting................................................................... 13
5.2: Menu Map to Baud Rate Setting ..................................................................... 13
5.3: Menu Map to RF ID Setting............................................................................ 14
6.1: Menu Map to Normal Transmission Rate Setting........................................... 15
6.2: Incorrect Sampling Rate .................................................................................. 16
6.3: Correct Sampling Rate .................................................................................... 16
6.4: Menu Map to Normal Sampling Rate Setting ................................................. 16
6.5: Example of Abnormal Transmission Rate Setting .......................................... 17
6.6: Menu Map to Abnormal Transmission Rate Setting....................................... 17
6.7: Example of Abnormal Sampling Rate Setting ................................................ 18
6.8: Menu Map to Field Abnormal Sampling Rate Setting.................................... 18
6.9: Smart Rate Configuration Using Wireless Management Toolkit.................... 19
6.10: Normal Upper and Lower Value Example.................................................... 20
6.11: Menu Map to Normal Upper and Lower Value Settings .............................. 20
6.12: Condition “Chatter” Without Time Deadband .............................................. 20
6.13: Condition “Chatter” Elimination Due to Time Deadband ............................ 20
6.14: Sampling and Transmission Rate Selection Using the Software .................. 21
6.15: Normal Upper and Lower Value Selection Using the Software ................... 21
7.1: Menu Map to Units Setting ............................................................................. 22
7.2: Menu Map to Sensor Selection Setting ........................................................... 22
7.3: Menu Map to Sensor Offset Setting ................................................................ 23
7.4: Menu Map to Trim Setting.............................................................................. 23
7.5: Setting a 22-Point Curve Using Wireless Management Toolkit ..................... 23
Dimensioned Mechanical Drawing ........................................................................ 26
Intrinsic Safety Control Drawing ........................................................................... 27
Section 1: Introduction
1.1: USING THIS MANUAL This manual is designed to assist in installing, operating, and maintaining
Honeywell Model WT531T and WT531R Temperature Transmitters. The
manual is broken into sections as follows:
Section 2: In a Hurry?
This section summarizes what must be done in order to get the device in-
stalled, configured and in operation quickly. However, it does not provide
detailed or how-to information to perform the tasks outlined.
Section 3: Installation
This section explains how to correctly wire the Thermocouple/RTD In-
puts, Input Switches, and ground the Transmitter. Also covered in this
section are mechanical installation considerations; such as Transmitter
placement.
1.2: ABOUT THE DEVICE The Honeywell Temperature Transmitter is a reliable Radio Frequency
(RF) transceiver coupled with an temperature input sensor that can be
used to monitor a variety of processes in hazardous and hard-to-reach ar-
eas. The time and expense of running wires often makes it difficult to
measure parameters that have an economic impact on your plant opera-
tion, but the Temperature Transmitter allows you to quickly and accu-
rately monitor those devices at fraction of the cost, which gives you bigger
and faster returns on your instrumentation investments.
You can use this device for long term monitoring in remote locations, for
short-term data gathering on process conditions, or to quickly test the eco-
nomic viability of a new installation.
The purpose of this manual is to help you install and maintain your Hon-
eywell Temperature Transmitter. BEFORE setting up and installing the
Transmitter please setup and configure the Base Radio.
1.3: UNPACKING Remove the Packing List and check off the actual equipment received. If
you have any questions on your shipment, please call your Honeywell
Representative. Upon receipt of shipment, inspect the container for any
signs of damage in transit. Especially take note of any evidence of rough
handling. Report any apparent damage immediately to the shipping agent.
Please note that sometimes units are assembled with accessories when
shipped. Inspect the shipment carefully if you think that something is
missing. This is rare, as we take considerable care to pack units for ship-
ment, but it does sometimes happen. Please give us a call and we may be
able to resolve this matter quickly over the phone.
NOTE
Please note that the carrier will not honor any claims for damage unless
all shipping materials are saved for their examination. If damage is found
during examining and removal of the contents, save the packing material
and the carton.
1.4: SOFTWARE Software for Honeywell is revised periodically. Internal device software
may contain portions that are not compatible with previous versions of the
COMPATABILITY Wireless Management Toolkit software.
Section 2: In a Hurry?
This section summarizes what must be done in order to get the device in-
stalled, configured and in operation quickly. However, it does not provide
detailed or how-to information to perform the tasks outlined. (Ignore steps
1 thru 6 and 17 if you do not have the split architecture Transmitter).
If the “RF OFF” message is being displayed on the Transmitter LCD, per-
form the following:
! Caution !
If the Base Radio is not energized for more than 30 minutes, the Transmitters should also be
turned off to preserve battery life. Leaving the Transmitters on when the Base Radio is not
energized or out of range will cause the Transmitters to transmit very frequently and drasti-
cally reduces their battery life.
Section 3: Installation
3.1: Mechanical Installation In this section mechanical installation instructions are discussed for the
various setup capabilities of the Temperature Transmitter. The subsections
are as follows:
3.1.1: Transmitter Positioning
3.1.2: A Simple RF Placement Procedure
The Temperature Transmitter is a rugged device, but it provide much bet-
ter performance if installed with careful consideration, as noted in this
manual. It may be utilized in any temperature measurement service so
long as care is exercised to prevent exposing the sensing elements to ex-
cess stress or temperature. Installation practices have a lot to do with
these service parameters and the life that you can expect from your Hon-
! ! eywell Temperature Transmitter. The main considerations for installation
Warning are covered below.
During installation do not apply force to the in-
strument housing or antenna. Use a proper wrench Give careful consideration to the environment where you will be installing
for all installations. Failure to use correct installa-
tion procedures can cause damage to the Base your instrument. Avoid installations that expose the device to excess tem-
Radio. perature, high vibration, considerable shock, or exposure to dripping con-
densate or corrosive materials. Also avoid installing the device in an un-
serviceable location.
Most often these problems can be avoided with some thought at the time
of installation. The practices noted below are generally recommended, but
they can only act as a guideline and cannot cover all possible variations.
The final installation must be made at the discretion and approval of the
user. You must be the judge of the actual installation.
3.1.1: Transmitter Positioning Correct positioning of the Transmitter will ensure the best performance of
the device. When planning the positioning of the Transmitters there are a
few parameters that must be paid attention to:
Because there are so many setup possibilities we cannot cover them all. A
correct setup would make sure that the above warnings are heeded, and
that the Transmitter and Base Radio are capable of communication. The
RF Placement Test section will help you to determine if you have a se-
lected the correct installation points and orientations for your application.
4 Rev. 3 User Manual
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
3.1.2: A Simple RF Placement Pro- Remember, proper placement of the Transmitter will optimize your RF
communication range and capabilities. Perhaps the best test to perform
cedure before mechanically mounting the unit is a quick hand-held test.
To perform this test you should have a good idea of where the Base Radio
will be placed (for more information see Section 3 of the Base Radio User
Manual). Put the Base Radio in this area and power it up. Make sure that
the Base Radio and Transmitter are on the same RF Channel and Baud
Rate (See Section 5). You may also have to increment the number of
Transmitters with which the Base Radio is communicating (See the Base
Radio User Manual Section 4.3).
Once both the Base Radio and Transmitter are set up to be on the same
network, make sure communication is established by looking at the Trans-
mitter LCD for the ‘RF OK’ message in the Read-Only Sequence (see
Section 4.1.1).
3.1.2.1: Transmitter RSSI Diagnostic The Received Signal Strength Indicator (RSSI), located in the Transmit-
ter’s diagnostic menu, displays the RF signal strength in one of seven
ranges. The signal strength is displayed on the LCD using a combination
of ‘>’ and ‘_’ characters. Full signal strength is displayed as “> > > > > >
>” while minimum signal strength is displayed as “> _ _ _ _ _ _”. If the
Transmitter is not communicating with the Base Radio (i.e. NO RF), all
underscore characters will be displayed (“_ _ _ _ _ _ _”).
The RSSI is measured every time the Transmitter receives a message from
the Base Radio. The signal strength of the received message from the Base
Radio is calculated during this time. The actual signal strength in dBm for
each range is shown below:
To place the Transmitter in RSSI Diagnostic mode follow the menu map
shown on the following page in Figure 3.2. Note that the RSSI menu is
under the DIAGNSE menu and not the CONFIG menu.
3.1.2.1 Continued Now that the Transmitter is in the RSSI mode, bring the Transmitter close
to the equipment you wish to monitor. Look at the LCD; notice the ‘>’
will constantly fluctuate. One should estimate an average value based on
these fluctuations. While the ideal signal integrity is seven arrows, the
suggested fluctuating arrow ranges for the different RF Baud Rate settings
are listed below:
Once you have verified that you are receiving a signal, you should check
to make sure the Transmitter is communicating properly with the Base
Radio. To do so exit the RSSI by pressing ENTER, and then navigate to
the EXIT? of the diagnostic menu and return to the Operations Sequence
shown in Figure 1 on page 8. Once in the Operations Sequence, you will
notice small arrows on the rightmost and leftmost regions of the LCD.
These arrows indicate the sending and receiving of messages between the
Base Radio and the Transmitter. If both arrows are moving up and down,
and you do not see a NO RF message, then the position you have selected
will be suitable for mounting the device.
If only one or neither of the arrows is moving, and you see a NO RF mes-
sage, then you do not have satisfactory RF communication with the Base
NOTE Radio. If your application allows, move the Transmitter to a different posi-
While using slower baud rate increases communi- tion and check again for communications. If your application only allows
cation distance, it also requires more time to com-
plete a communications cycle. This may not be
you to mount at this particular point, you may want to try a slower baud
suitable for your application. rate setting for an increased range (see note).
One final solution is to reposition the Base Radio. However, this may af-
fect communications with previously installed Transmitters, and if so, may
require the use of a second Base Radio for your application. To select a
better spot for the Base Radio, see section 3.1.1 of the Base Radio User
Manual.
3.2: Electrical Installation In this section wiring instructions are discussed for the various setup capa-
bilities of the Temperature Transmitter. This section only applies if you
! Caution ! have ordered the WT531T or WT531R. If the integrated architecture ver-
sion of the Temperature Transmitter has been purchased, then skip the
Remember to turn off all power BEFORE hook-
ing up any wires!
electrical installation section. The subsections are as follows:
3.2.1: Electrical Specifications
3.2.2: Wiring the Thermocouple/RTD Input
3.2.3: Wiring the Input Switches
3.2.1: Wiring the Thermocouple/ To properly wire a thermocouple/RTD to the Temperature Transmitter
follow the wiring diagram provided below. Please note that a thermocou-
RTD Input ple CANNOT be wired to a WI-RT unit, and a RTD CANNOT be wired
to a WI-TC unit.
NOTE
For Dual T/C installations, the inputs share a The diagram shown in Figure 3.3 below refers to the circuit board found at
common ground (-). Use Ungrounded T/C’s or the base of the Transmitter, within the junction box. Before connecting
ensure that both T/C’s are at the same ground wires to the terminal blocks, the input wires should be routed into the back
potential to avoid ground loop effects. of the enclosure and threaded through the center of the circuit board.
Figure 3.3: Thermocouple Input Wiring Diagrams Figure 3.4: RTD Input Wiring Diagrams
NOTE
If using two thermocouples remember to enable
both thermocouple inputs otherwise the measure-
ment of the disabled thermocouple will not be
made.
3.2.2: Wiring the Input Switches To properly wire a switch input device to the Temperature Transmitter
simply follow the wiring diagram provided below. Please note that loop
(Optional) power does NOT need to be supplied as the Transmitter supplies the moni-
toring power. The Temperature Transmitter has the capability of monitor-
ing two input switches.
The most common application for the switch inputs is to monitor a contact
NOTE closure. However, the input switches must only be attached to simple de-
The RTD Temperature Field Unit (WI-RT-S) has vices. A simple device is one that meets the conditions set forth in the In-
only ONE INPUT SWITCH. trinsic Safety Control Drawing, which can be found in the Technical
Specifications section of this manual.
The diagram shown in Figure 3.4, below, refers to the circuit board found
at the base of the Transmitter, within the junction box. Before connecting
wires to the terminal blocks, the input wires should be routed into the back
of the enclosure and threaded through center of the circuit board.
! Warning !
Wiring the Temperature Transmitter to a non-
simple device (such as an explosion proof device)
voids the intrinsic safety of the Transmitter. A
simple device is one that meets the conditions set
forth in the Intrinsic Safety Control Drawing
found in the Technical Specifications section of
this manual.
3.2.3: Wiring and Configuring the To properly wire an output switch, follow the wiring diagram provided
below. Please note that loop power MUST be supplied.. The Dual Analog
Output Switches (Optional) Input Transmitter has the capability of producing two output switches.
Warning: Wiring the output switch terminal, for any reason, will void the
Intrinsic Safety rating for this Transmitter. If the device is to be used in an
explosive environment or an environment where Intrinsic Safety is a re-
NOTE quirement, then the output switch terminal block should be removed from
The de-energized state of all digital output the device to prevent accidental wiring.
switches is NORMALLY OPEN. Consideration
should be given, as in the event of power loss to The diagram shown in Figure 3.5 below refers to the circuit board found at
the device, all switches will OPEN.
the base of the Transmitter, within the enclosure. Before connecting wires
to the terminal blocks, the wires should be routed into the back of the en-
closure and threaded through the center of the circuit board.
! Warning !
Wiring the output switch terminal, for any reason,
will void the Intrinsic Safety rating for this Trans-
mitter. If the device is to be used in an explosive
environment or an environment where Intrinsic
Safety is a requirement, then the output switch
terminal block should be removed from the device
to prevent accidental wiring.
4.1: Transmitter Displayed To turn the Transmitter on, press both the NEXT and ENTER buttons and
hold them for a few seconds. Upon power up, the Transmitter will display
Messages the Power-Up Sequence, and then go into the Operations Sequence. These
Sequences are shown in Figure 4.1 below:
NOTE
During configuration and testing, keep Transmit-
ters at least one foot apart and away from the Base
Radio to ensure good communications.
4.1.1: The Read-Only Sequence Once the Transmitter is in the Operations Sequence, a user may access the
READ-ONLY Sequence without a password by simply pressing the EN-
TER button at any time. The Read-Only Sequence, as shown in Figure 4.2,
displays extra information about the current settings of the Transmitter
that are not seen during the Operations Sequence, but does not allow any
changes to be made to these settings.
4.2: Overall Configuration A complete Transmitter Menu Map is shown in Appendix B. Below is an
overall view of the configuration menu to aid the user in setting up the
Menu Map Transmitter for proper operation.
NOTE
The user must enter a four digit password to enter
the CONFIG and DIAGNSE. The FACTORY
menu is for factory use only. The default user
password is 0000. For more information on the
password see Section 4.4.
4.3: Setting the Transmitter Each Transmitter also has a user-settable Transmitter Tag Name. This tag
name is displayed upon Transmitter power up, and when the Read Only
Tag Name* Sequence is selected. The Tag Name is a 21-character string that is dis-
played in three separate 7 -character flashes on the Transmitter LCD.
The user may choose from A-Z, 0-9, a dash (“-“), and an underscore (“_”).
The underscore has a special meaning to the software inside the Transmit-
ter. For example, if you have a Tag Name that is only 5 characters long,
then you do not want to wait for the rest of the 16 characters to be dis-
played on the LCD. So if your Tag Name was “TRAP1”, you would want
Figure 4.4: Menu Map to Tag Name to enter the Tag Name like this: “TRAP1 _ _ _ _ _ _ _ _ _ _ _ _ _ _”.
Using Wireless Management Toolkit If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects that
the software is being used (See Appendix A for more details). The tag
name should be entered using the Wireless Management Toolkit software.
To do so, when the software is in the Transmitter view (See Section 8.1 of
the Wireless Management Toolkit User Manual), right-click the Transmit-
ter icon and select Rename, then enter the tag name you wish the Trans-
mitter to have.
This tag name will then be downloaded to the Transmitter and can be dis-
played by pressing the ENTER button when the unit is in the Operations
Sequence (See Section 4.1.1 of this manual)
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
Rev. 3 User Manual 11
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
4.4: Setting a User Password* Each Transmitter has a password that will lock out undesired users from
making changes to the Transmitter. Any user may still view some of the
Base Radio settings by pressing the ENTER key during the Operations
Sequence and viewing the Read-Only Sequence.
The password is a four -digit password. The factory default is 0000. If you
wish to select a different password, follow the Transmitter Menu Map
shown in Figure 4.5 to change it.
If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects that
the software is being used (See Appendix A for more details). The pass-
word should be entered using the Wireless Management Toolkit software.
To do so, enter the configuration menu (See Section 9.2 of the Wireless
Management Toolkit User Manual). Once in the configuration menu click
on the General tab to bring up the general information as shown in Figure
4.6.
The Transmitter password for this device can be set by entering a four-
digit number in the Field Unit Password field. Once a password has been
entered, click OK to save and download the password to the Transmitter.
Please note that the password only protects the Transmitter from unauthor-
ized configuration via the NEXT and ENTER buttons. The Wireless Man-
agement Toolkit requires a user login password to gain access to all con-
figuration parameters. However, user accounts are available and can be set
with different access levels and restrictions (For more information on user
Figure 4.6 : Password Setting Using Wireless accounts see the Wireless Management Toolkit User Manual Section 8.4).
Management Toolkit
4.5: Resetting All Transmitter To reset all Transmitter settings to their default state, the user must navi-
gate to the DEFAULT menu option in the CONFIG menu via the keypad.
Settings
Once at the default menu option pressing the ENTER button will display
‘RESET?’ on the LCD; which asks if the user is sure he or she wants to
reset the device to its default configuration. The user will then be
prompted with ‘NO’ on the LCD. Pressing the ENTER button while ‘NO’
is being displayed will NOT reset the device. Pressing the NEXT button
will display ‘YES’ on the LCD. If the user presses the ENTER button
while ‘YES’ is being displayed the device will be reset.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
12 Rev. 3 User Manual
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
5.3: RF Identification Selection Each Transmitter is identified by the Base Radio and software according
to the RF Identification (ID) given to that particular unit. Two Transmit-
ters can NOT have the same ID and be on the same RF Channel (if you do
not know the RF Channel see section 5.1). If the Transmitter is in the Op-
erations Sequence, pressing the ENTER button displays the Read-Only
Sequence on the LCD, which displays the ID of that unit like this: ID 3.
All Transmitters in your system are set to a default ID number upon ship-
ment. For example, if you have ordered a Base Radio and three Transmit-
ters, the Transmitters will be configured to ID’s 0, 0 and 0. You must set
these units to three different IDs between 1 and 50. The Transmitters in
this example could be set to RF IDs 1, 2 and 3.
First determine the ID’s you’d like to give each unit. Then follow the
menu map shown in Figure 5.3 to configure the RF ID. The factory de-
fault is RF ID 0, which disables the RF communication of the unit.
Once you have selected the RF ID you wish to use for this particular
Transmitter, save and exit the menus and return to the Operations Se-
quence.
Also notice the two small arrows on either side of the LCD; if they are
fluctuating up and down, that indicates the Transmitter and Base Radio are
successfully communicating. If only one or none of the arrows are moving
then RF communication is unsuccessful.
6.1: Selecting the Normal The Transmitter is in a “sleep” mode to save power during the operations
sequence. This mode turns off most of the electronics on the unit, with the
Transmission Rate* exception of the LCD, in order to preserve battery life. The Transmitter
will then ‘wake up’ every Normal Sampling Period and take the neces-
sary current/voltage readings. The Transmitter will then transmit these
readings to the Base Radio on an interval determined by the Normal
Transmission Rate.
Notice that the fastest update rate of the Normal Transmission Rate is de-
pendent on the baud rate setting you selected earlier (see section 5.2). The
transmission rates cannot update data faster than their communication
speed allows. Thus, if you selected the 19.2K Baud Rate setting, your fast-
est transmission rate will be 5 seconds and no faster. The Transmitter auto-
matically determines these settings and adjusts the menu options accord-
ingly. A complete table of these parameters is shown in the table in the
following section.
In order to properly set the Normal Transmission Rate, you must first de-
termine how often you need updates from the Transmitter when the device
being monitored is operating within what you consider to be normal oper-
ating conditions for that process variable. You have a selectable range of
1-5, 10, 15, 20, 40 seconds and 1 minute. Then, follow the menu map
shown in Figure 6.1 to configure the Normal Transmission Rate. The fac-
tory default is 10 seconds.
Using Wireless Management Toolkit If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects
that the software is being used (See Appendix A for more details). An
explanation of how to select the Normal Transmission Rate using the
Wireless Management Toolkit software can be found in section 6.7.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
Rev. 3 User Manual 15
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
6.2: Selecting the Normal As previously mentioned, the Transmitter is in “sleep” mode to save
power during the operations sequence. This mode turns off most of the
Sampling Rate* electronics on the unit (with the exception of the LCD) in order to preserve
battery life. The Transmitter will then ‘wake up’ for every Normal Sam-
pling Period and take the necessary process readings.
Notice that the minimum speed of the Normal Sampling Rate is dependent
on the Normal Transmission Rate setting you selected earlier (see section
6.1). The Sampling Rates cannot be set to a slower time interval than the
time interval at which the Transmitter is required to transmit updates.
Thus, if you selected the Normal Transmit Rate setting to be 10 Seconds
the Normal Sampling Rate must be set to 10 Seconds or faster. A complete
table of these parameters is shown below.
In order to properly set the Normal Sampling Rate, first determine how
often updates are needed from the Transmitter when the device being
monitored is operating normally. You have a selectable range of 1-30 sec-
onds. Note, however, the more frequently the Transmitter wakes up to
Figure 6.2: Incorrect Sampling Rate check the monitored device, the faster you will use up the battery life of
the Transmitter.
Figure 6.2 is an example of what happens when the Normal Sampling Rate
is too slow for the device being sampled. Notice how the rise in the volt-
age level falls between two normal samples, and thus goes completely
undetected.
Figure 6.3 is an example of what happens when the normal sampling rate
is correctly set for the device that is being monitored. Notice how this set-
ting makes it possible to sample the rise in the voltage level.
Once you have decided on the proper Normal Sampling Rate follow the
Transmitter menu map shown in Figure 6.3 to select this setting. The fac-
tory default is 1 second.
Figure 6.3: Correct Sampling Rate
If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects
that the software is being used (See Appendix A for more details). An
explanation of how to select the Normal Sampling Rate using the Wire-
Figure 6.4: Menu Map to Normal less Management Toolkit software can be found in section 6.7.
Sampling Rate Setting
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
16 Rev. 3 User Manual
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
6.3: Selecting the Abnormal The Abnormal Transmission Rate is identical to the Normal Transmis-
sion Rate with one exception. The Abnormal Transmission Rate only ap-
Transmission Rate* plies while the Transmitter is in an Abnormal condition (see Setting Nor-
mal Upper and Lower Values section 6.6). This allows you to increase or
decrease the frequency of information you receive depending on the oper-
ating conditions of the device being monitored.
NOTE
In order to properly set the Abnormal Transmission Rate, you must first
If you do not need more or less frequent samples
and updates from a Transmitter for a given appli-
determine how often the Transmitter needs to update its data about the
cation, then there is no need to complete this sec- device being monitored while in an Abnormal condition. You have a se-
tion. Simply set the Normal Transmission and lectable range of 1-10, 15, 20, 40 seconds and 1 minute. Figure 6.5 is an
Sampling Rates to the desired speeds, and make example of how the device switches transmission rates from Normal
sure that the Normal Upper and Lower Values are
configured to Disabled.
Transmission Rate to Abnormal Transmission Rate. Note how the first
abnormal transmission is sent immediately when the Normal Upper Value
set point is exceeded. The next transmission will then follow this immedi-
ate transmission by 10 seconds (or whatever the Abnormal Transmission
Rate is set to). The transmissions will continue at this interval until the
process value drops below the Normal Upper Value set point.
Once the process value drops below this set point, another transmission is
made to the Base Radio. The transmissions will then be made at the Nor-
mal Transmission Rate of one minute (or whatever the Normal Transmis-
sion Rate is set to) from the time of the last abnormal transmission.
The user should also note that the transmission time depends on the sam-
pling rate, and when the process variable is sampled. If the Normal Sam-
pling Rate is 30 seconds, then the process variable may be above the Nor-
mal Upper Value for up to 29 seconds before abnormal condition is de-
tected. This means that the transmission could be as late as 29 seconds
after the process variable exceeded the Normal Upper Value.
Figure 6.5: Example of Abnormal
Transmission Rate Setting Once you have decided the proper time for the Abnormal Transmission
Rate follow the Transmitter menu map shown in Figure 6.6.
Using Wireless Management Toolkit If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects
that the software is being used (See Appendix A for more details). An
explanation of how to select the Abnormal Transmission Rate using the
Wireless Management Toolkit software can be found in section 6.7.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
Rev. 3 User Manual 17
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
6.4: Selecting the Abnormal The Abnormal Sampling Rate is identical to the Normal Sampling Rate
with one exception. The Abnormal Sampling Rate only applies while the
Sampling Rate* Transmitter is in an Abnormal condition (see Setting Normal Upper and
Lower Values section 6.6). This allows you to increase or decrease the
frequency of information you receive depending on the operating condi-
tions of the device being monitored.
NOTE
In order to properly set the Abnormal Sampling Rate, you must first deter-
If you do not need more or less frequent samples
and updates from a Transmitter for a given appli-
mine how often the Transmitter needs to update its data while in an Ab-
cation, then there is no need to complete this sec- normal condition. You have a selectable range of 1-10, 15, 20, 40 seconds
tion. Simply set the Normal Transmission and and 1 minute. Figure 6.7 is an example of how the device switches sam-
Sampling Rates to the desired speeds, and make pling methods from Normal Sampling Rates to Abnormal Sampling Rates.
sure that the Normal Upper and Lower Values are
configured to Disabled.
Note how the first abnormal sample is taken a few seconds after the Nor-
mal Upper Value set point is exceeded. The next sample will then follow
this sample by 5 seconds (or whatever the Abnormal Sampling Rate is set
to). These samples will continue at this interval until the process value
drops below the Normal Upper Value set point.
Once the process value drops below this set point the sampling rate will
return to the Normal Sampling Rate. Also, the Abnormal Sampling must
be equal to or faster than the Abnormal Transmission Rate.
The user should also note that the transmission time depends on the sam-
ple rate, and when the process variable is sampled. If the Normal Sam-
pling Rate is 30 seconds, then the process variable may be above the Nor-
mal Upper Value for up to 29 seconds before abnormal condition is de-
tected. This means that the transmission could be as late as 29 seconds
after the process variable exceeded the Normal Upper Value.
Once you have decided the proper time for the Abnormal Sampling Rate
Figure 6.7: Example of Abnormal Sampling follow the Transmitter menu map shown in Figure 6.8.
Rate Setting
Using Wireless Management Toolkit If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects
that the software is being used (See Appendix A for more details). An
explanation of how to select the Abnormal Sampling Rate using the
Wireless Management Toolkit software can be found in section 6.7.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
18 Rev. 3 User Manual
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
6.5: Setting the Smart Rate The Smart Rate is a feature used to trigger radio transmission of the meas-
ured data sooner than the normal or abnormal rate specified by the user.
Threshold* This feature is used to construct a more accurate graph of the measured
process variable vs. time than is possible with the fixed transmission rates,
while using less battery power.
To configure the Smart Rate Threshold follow the user menu to the
SMART R menu and press the ENTER button. The user is then asked to
enter the amount that the process variable must change since the last data
sample to trigger a new transmission of the process variable.
If the process variable changes by more than the entered Smart Rate
amount within the normal or abnormal sampling rate (whichever is ac-
tive), then the process variable is transmitted immediately. The normal/
abnormal transmit clock is then reset upon this transmission. If no Smart
Rate amount exceeding change takes place in the next normal/abnormal
sample then the next transmission will be the normal/abnormal transmit
rate period.
The amount entered is in the same units as were selected by the user to be
displayed on the Transmitter. If the measured process variable does not
change by more than the entered Smart Rate mount within the time be-
tween the sampling rate (whichever is active), then the process variable is
transmitted on the next transmit rate.
If changes in the process variable, which exceed the Smart Rate Amount,
continue to occur, the process variable is transmitted repeatedly.
If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects that
the software is being used (See Appendix A for more details). The Smart
Rate should be enabled using the Wireless Management Toolkit software.
To do so, enter the configuration menu (See Section 9.2 of the Wireless
Management Toolkit User Manual). Once in the configuration menu click
on the Sampling Rates tab to bring up the sampling rate information as
shown in Figure 6.9.
To enable the Smart Rate, click the check-box labeled Enable SmartRate
for the correct input. The user will then be allowed to enter a “delta”, or
amount changed, value which will trigger a transmission.
Once a value has been entered, click OK to save and download the con-
figuration changes to the Transmitter.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
Rev. 3 User Manual 19
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
6.6: Selecting the Normal Up- Each Honeywell Temperature Transmitter is equipped with an tempera-
ture level upper and lower value. As the temperature is measured, it is
per and Lower Values* compared to a set threshold value. Depending upon the setting of that
value, whether it is enabled or not, and what the time deadband is, the
Transmitter will enter an Abnormal condition as seen in Figure 6.10.
Figure 6.11: Menu Map to Normal Upper and Lower Value Setting
Figure 6.12: Condition “Chatter” Without
Time Deadband When configuring the Normal Values you will first be prompted to enable
the input. You should only disable an input if it will not be used.
Once an input has been enabled, the user may enter a Normal Upper
Value, Normal Lower Value and the Smart Rate Threshold (see Section
6.5). If, for example, the Normal Upper Value is enabled, the next prompt
you will receive is –XX.XX for the process variable value. Increment this
value to the desired value and press the ENTER button. (The "-" may be
toggled on and off as well).
The final prompt you will receive is the Time Deadband prompt. The
Time Deadband refers to the number of seconds that the measured reading
must stay in a certain condition before, the Transmitter will actually
switch to that condition. To select a proper Time Deadband consider the
example in Figure 6.12. Notice that the Transmitter continues to cycle
Figure 6.13: Condition “Chatter” Elimina- from Normal to Abnormal Conditions due tothe fact that the input value is
tion Due to Time Deadband fluctuating around the 7.5 Volt Normal Upper Value. This is undesired.
The addition of a few second delay before the Transmitter switches condi-
tions will eliminate this “chatter”, as seen in Figure 6.13.
Using Wireless Management Toolkit If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects
that the software is being used (See Appendix A for more details). An
explanation of how to select the Abnormal Sampling Rate using the
Wireless Management Toolkit software can be found in section 6.7.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
20 Rev. 3 User Manual
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
6.7: Selecting Rates, Thresh- If you have the Wireless Management Toolkit software the Normal and
Abnormal Sampling and Transmission menu options will not be accessi-
olds, and Deadbands via ble via the Transmitter once the Transmitter detects that the software is
the Software being used (See Appendix A for more details). These settings should be
entered using the Wireless Management Toolkit software. To do so, enter
the configuration menu (See Section 9.2 of the Wireless Management
Toolkit User Manual). Once in the configuration menu click on the Sam-
pling Rates tab to bring up the sampling rate information, as shown in
Figure 6.10.
To select the Normal Transmission Rate, select one of the time periods
from the drop box. Next, select an Abnormal Transmission Rate in the
same manner. Note that the Normal and Abnormal Transmission Rate can
be the same.
Once the transmission rates have been selected, the user should select the
desired sampling rates. Note that the sampling rate must be equal to or
faster than the associated transmit rate. For example, in Figure 6.10 the
Normal Transmission Rate is set to 10 seconds and the Normal Sampling
Rate is also set to 10 seconds. This is a valid configuration. Another ex-
ample in Figure 6.10 is the Abnormal Transmission Rate being set to 3
seconds and the Abnormal Sampling Rate being set to 1 second.
If the user incorrectly enters the Transmission and Sampling Rates, a mes-
sage will be displayed explaining this to the user. The user will not be
allowed to leave this screen before the setting is corrected.
To set a limit to the normal condition, enable the limit by clicking on the
Use Input X Limit check box. Then enter the value and time deadband
for the limit (for more details see Section 6.6 of this manual).
7.1: Selecting Unit of Measure* The Transmitter can be used in many different types of applications. To
accommodate these various options, there are various engineering units
that can be selected.
Please note that the units selected apply to both Input 1 and Input 2. Each
input may not use different units.
If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects that
the software is being used (See Appendix A for more details). The process
Figure 7.1: Menu Map to Units Setting variable units should be entered using the Wireless Management Toolkit
software. To do so, enter the configuration menu (See Section 9.2 of the
Wireless Management Toolkit User Manual). Once in the configuration
menu click on the General tab to bring up the general information as
shown in Figure 7.2.
To select the units, click the drop down box labeled Input Units. Select
units you wish to use from the available list.
Once a valued has been entered, click OK to save and download the con-
figuration changes to the Transmitter.
7.2: Selecting the Sensor Type Depending on the type of thermocouple or RTD the user intends to em-
ploy for temperature measurement, the sensor setting must be set to the
corresponding sensor type.
To select the sensor type, follow the Transmitter menu map shown in Fig-
ure 7.2.
7.3: Setting a Measurement For various applications, the user may wish to display an offset value
rather than the actual value. To enter an offset, navigate to the OFFSET
Offset command, as shown in Figure 7.3, select the desired input to be offset.
Then enter the offset to be added or subtracted from the actual measured
value.
7.4: Trimming the The Transmitter interface allows the user to set a two point correction
curve for the sensor. This process is often called “trimming” because the
Measurement displayed value is trimmed up or down to reflect the actual value being
applied.
To set a trim point take the Transmitter offline and navigate to the TRIM
menu, as shown in Figure 7.4, and select the input to be trimmed. Then
select the point you wish to enter. After selecting the point, you will be
asked if the Transmitter has been taken offline. Press the ENTER button if
this is true. Next, you will be asked to enter a value. This should be a
known reference value. Once you have entered the applied value, you will
be prompted to apply the reference value to the sensor, and then confirm
the value is being applied via a yes/no prompt.
NOTE
If entering a two-point trim via the NEXT and
ENTER buttons, Point 2 MUST be greater than
Point 1 in order for the trim to work properly.
8.1: Changing the Battery The battery will need to be changed within one month of seeing a ‘LOW
BAT’ message on either the Transmitter. This is a simple process:
3. Remove the 4 set screws on the sides of the Transmitter housing with
a standard screw driver.
4. Remove the housing and locate the battery. Warning! When remov-
! Warning ! ing the housing do not twist or bend the green flex cable! Doing so
may cause the tether to improperly seat next to the antenna and
The replacement battery MUST be a TA-
DIRAN™ Lithium Inorganic Battery (non- greatly reduce operable RF distances. Do not allow the housing to
rechargeable). Size C—3.6Volts, #TL2200/S. flop around while hanging by the tether.
Use of a different battery will VOID the intrinsic
safety rating of this device and may result in an 5. Remove the old battery and replace it with the new battery positive
explosion!
end first. (Note that the positive end of the battery clip is the end
with the red wire).
6. Plug the green wire tether back in and replace the housing. Then,
screw the housing back on, and power up the unit by pressing either
of the buttons.
Local Input Switch Characteristics (WT531R/T only) (Simple Device Closure Only) Optional
• Number of Channels: T-2 R-1
• Max External Switch Impedance Applied: 1 KOhm
• Isolation: 110 KOhms (between output (-) and input (-))
• Connector: Wire size 28-16 AWG
• For simple device monitoring only! (i.e., contact closures)
Local Output Switch Characteristics (Both Outputs Share a Common (-) ) Optional
• Number of Channels: 2
• Maximum Current: 1 Amp
• On Voltage: 6-30 VDC
• A/C Frequency: N/A
• On Resistance: 15 mOhms 9 mOhms typical
• Isolation: 110 KOhms (between output (-) and input (-))
• Connector: Wire size 14 AWG MAX
Any Field Unit Containing Output Switches Are Classified As ORDINARY LOCATION ONLY.
RF Characteristics
• 902 MHz – 928 MHz Frequency Hopping Spread Spectrum, FCC certified ISM license-free band
• Up to 3000’ range from Base Radio with clear line of sight;
Physical Characteristics
• Aluminum junction box
• GE Lexan® cover. V-0 rating and UV stable
Industrial Certification
• Rated for industrial use -40 °F to 185 °F(-40 °C to 85 °C)
• FM NEMA 4X(Integrated) or 4 (Split) weather-proof housing
• FM rated intrinsically safe for Class I/II/III, Division 1, Groups A,B,C,D,E,F&G; Class I/II/III, Di-
vision 2, Groups A,B,C,D,F&G
Rev. 3 User Manual 25
11/04
Honeywell Industrial Wireless Wireless Temperature Transmitter
Split Architecture
WT531R and WT531T
Integrated Architecture
WT532R and WT532T
Pressing the NEXT button at any time while the Transmitter is cycling
through the normal messages causes the Transmitter to enter the setup
mode. The NEXT button is then used to step through menu options, and
the ENTER button is used to enter a sub menu of what is displayed on the
LCD at that time. If no button is pressed within a 30 second period the unit
goes back to the normal display mode.
If you enter a sub menu that requires a numerical input, such as 001, the
left most 0 will be blinking. This indicates that pressing the NEXT button
will increment this value with each press from 0 to 9 and back to 0 again.
Pressing the ENTER button will move to the next available value. If the
last value is blinking, pressing ENTER will save the entered values and
return from the sub menu.
If both the NEXT and ENTER buttons are depressed at once, a message
on the LCD displaying OFF? will appear. If both buttons are released
upon appearance of this message the user will be returned to the scrolling
main screen. If both buttons are not released for the duration of the OFF?
message the unit will power down and turn off. Note: If the unit is turned
off while entering values in a sub menu, those values will NOT be saved.
* As shown throughout the document, this mark indicates that these menu
options will automatically turn off if the Wireless Management Toolkit
Software is used. All changes to these Transmitter menu options should be
made through software instead. This is to prevent simultaneous changes
from taking place. If you wish to discontinue use of the software and want
these menus re-instated, you must contact your Honeywell Sales Repre-
sentative.
Operations Sequence
• RF Link Status
⇒ RF OK – Transmitter and Base Radio are communicating
properly
⇒ RF SYNC - Transmitter and Base Radio are attempting to
synchronize communications.
⇒ RF OFF - Transmitter’s RF Channel is set to RF OFF
⇒ NO RF - Transmitter and Base Radio have no communica-
tions
• Temperature Input Level
⇒ –XX.XX – Currently measured Temperature Input level
Error Messages
There are few types of error messages, warning and fatal. Warning mes-
sages are displayed as part of the normal cycling message sequence. These
are:
Fatal error messages will replace the normal cycling message sequence
and will flash. A fatal message indicates the Transmitter is no longer oper-
ating normally and requires repair. These are: