Exp2 Transformer Regu, Parallel & Param
Exp2 Transformer Regu, Parallel & Param
Transformer Regulation
OBJECTIVE
DISCUSSION
The load on a large power transformer in a sub-station will vary from a very small
value in the early hours of the morning to a very high value during the heavy peaks
of maximum industrial and commercial activity. The transformer secondary voltage
will vary somewhat with the load and, because motors and incandescent lamps and
heating devices are all quite sensitive to voltage changes, transformer regulation is
of considerable importance. The secondary voltage is also dependent upon whether
the power factor of the load is leading, lagging or unity. Therefore, it should be
known how the transformer will behave when it is loaded with a capacitive, an
inductive or a resistive load.
An interesting feature arises with a capacitive load, because partial resonance is set
up between the capacitance and the reactance X so that the secondary voltage E2
may actually tend to rise as the capacitive load value increases.
3-1
Transformer Regulation
Figure 3-1.
EQUIPMENT REQUIRED
PROCEDURE
CAUTION!
Figure 3-2.
3-2
Transformer Regulation
G 2. a. Place all of the Resistive Load switches in their open position for zero
load current.
b. Turn on the power supply and adjust for exactly 240 V ac as indicated
by voltmeter E1.
c. Measure and record in Table 3-1 the input current I1, the output current
I2 and the output voltage E2.
d. Adjust the load resistance ZL to 4800 Ω. Make sure that the input
voltage remains at exactly 240 V ac. Measure and record I 1, I 2 and E 2.
f. Return the voltage to zero and turn off the power supply.
ZL I2 E2 I1
(ohms) (mA ac) (V ac) (mA ac)
4
4800
2400
1600
1200
960
Table 3-1.
= %
b. Does the primary winding VA equal the secondary winding VA for every
value of load resistance in the Table? Explain.
G Yes G No
3-3
Transformer Regulation
ZL I2 E2 I1
(ohms) (mA ac) (V ac) (mA ac)
4
4800
2400
1600
1200
960
Table 3-2.
ZL I2 E2 I1
(ohms) (mA ac) (V ac) (mA ac)
4
4800
2400
1600
1200
960
Table 3-3.
a. Plot your recorded values of E 2 (at each value of I 2 listed in Table 3-1)
on the graph of Figure 3-3.
b. Draw a smooth curve through your plotted points. Label this curve
“resistive load”.
c. Repeat (a) for the inductive (Table 3-2) and capacitive (Table 3-3)
loads. Label these curves “inductive load” and “capacitive load”.
3-4
Transformer Regulation
Figure 3-3.
REVIEW QUESTIONS
1. Explain why the output voltage increases when capacitance loading is used.
3-5
Transformer Regulation
3. Very large transformers are sometimes designed not to have optimum regulation
properties in order for the associated circuit breakers to be within reasonable
size. Explain.
G Yes G No
3-6
Experiment 2(b)
Transformers in Parallel
OBJECTIVE
DISCUSSION
Transformers may be connected in parallel to furnish load currents greater than the
rated current of each transformer. There are two precautions to be observed when
connecting transformers in parallel.
Very large short-circuit currents can be developed if these rules are not followed. In
fact, transformers, circuit breakers and associated circuitry can be severely
damaged, or may even explode, if these short-circuit currents are large enough.
The efficiency of any machine or electrical device is given by the ratio of output
power to input power. (Apparent power and reactive power are not used in
calculating transformer efficiency). The equation for percent efficiency is:
EQUIPMENT REQUIRED
PROCEDURE
CAUTION!
5-1
Transformers in Parallel
circuit shown in Figure 5-1. Note that the two transformers are connected
in parallel. The primary windings (1 to 2) are connected together to the
240 V ac power source. The wattmeter will indicate the input power. Each
secondary winding (3 to 4) is connected in parallel to the load RL. Ammeters
are inserted to measure load current IL and transformer secondary currents
I1 and I2.
5 5
6 6
Figure 5-1.
G 2. Place all the resistance switches in their open positions for zero load
current. Note that the windings are connected for voltage step-up operation
(240 V primary to 415 V secondary).
G 4. a. Turn on the power supply and slowly advance the voltage output
control knob while noting the transformer secondary current meters I1
and I2 and the load current meter IL. If the windings are properly
phased, no load or secondary currents should be flowing.
5-2
Transformers in Parallel
G 5. a. Gradually increase the load RL until the load current IL equals
250 mA ac. Check to see that the input voltage is exactly 240 V ac.
EL = V ac
IL = A ac
I1 = A ac
I2 = A ac
Pin = W
c. Return the voltage to zero and turn off the power supply.
EL x IL = W
Pin ! Pout = W
d. Calculate the power delivered by transformer 1.
I1 x EL = W
e. Calculate the power delivered by transformer 2.
I2 x EL = W
G Yes G No
5-3
Transformers in Parallel
REVIEW QUESTIONS
1. Show how you would parallel connect the transformers to the source and the
load in Figure 5-2. Windings 1 to 2 and 3 to 4 are rated for 1.1 kV ac and
windings 5 to 6 and 7 to 8 are rated for 415 V ac.
Figure 5-2.
5-4
Experiment 2(c)
INTRODUCTION:
The various parameters of this circuit can be determined by open circuit test and short circuit
test. Various performance characteristics (such as regulation, efficiency) can be determined
with the help of this circuit without actually loading the transformer. This experiment is
designed to perform the open circuit and short circuit test. Obtained results will be compared
with those from theoretical calculations.
APPARATUS:
1) One ac voltmeter (0-300V,0-30V)
2) Two ac ammeters (0-5A, 0-1A)
3) One 1- wattmeter
4) One 1- variac
EXPERIMENTAL SETUP:
1 3
2 4
3 1
500
4 2
PROCEDURE:
1) Open Circuit Test: Complete connections as shown in the experimental setup. Apply
rated voltage to secondary (Low Tension side) of the transformer. Note the readings of
the ammeter, voltmeter & wattmeter.
2) Short Circuit Test: Complete connections as shown in the experimental setup. Gradually
apply voltage across the primary (High Tension side) of the transformer until rated
primary current flows through the ammeter. Quickly take the readings of the ammeter,
voltmeter & wattmeter.
DATA:
Name plate data of the transformer:
Data for open circuit test Data for short circuit test
(referred to LT side): (referred to HT side):
CALCULATIONS:
REPORTS:
1. Determine the equivalent circuit parameters of the transformer from the test data.
2. What are the approximations of the short and the open circuit tests?
3. Why open circuit test is performed by keeping the high-tension side open, whereas short
circuit test is performed by keeping the low-tension side shorted?
4. Draw the exact & approximate equivalent circuit of a transformer. Define all the
parameters.
5. Draw the vector diagram of a real transformer for resistive, non-inductive and capacitive
load.